Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System
Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System
2,2006,3237
UniversitiTeknologiMalaysia ELEKTRIKA
Faculty of Electrical Engineering, Universiti Teknologi Malaysia, 81310 UTM Skudai, Johor, Malaysia.
*
Corresponding author: [email protected] (Alias Mohd Yusof), Tel: 607-5535240, Fax: 607-5566272.
Abstract: This paper highlights voltage sag as one of a power quality issue and Dynamic Voltage Restorer (DVR) is using
for mitigation of voltage sag. Voltage sag is short reduction voltage from nominal voltage, occurs in a short time which can
cause damage and loss of production especially in industrial sector. Voltage sag always related with short circuit events and
starting motor which draw very high lagging current. Since voltage sag is creating worse effects, the researchers almost keen
to find the solutions for this problem. Nowadays, a lot of devices have been developed to mitigate voltage sag such as
Dynamic Voltage Restorer (DVR), Distribution Static Compensator (D-Statcom) and Uninterruptible Power Supply (UPS).
In this paper, focus is given only on DVR system which will be simulated by using PSCAD software in order to mitigate
voltage sag. Mathematics model for calculation of voltage sag and voltage injection by DVR System also described.
32
SHAIRULWIZMARWAHAB,ALIASMOHDYUSOF/ELEKTRIKA,8(2),2006,3237
3. DVR SYSTEM
Dynamic voltage restorer (DVR) is a series compensator Figure 4. DVR system in power system
which is able to protect a sensitive load from the
distortion in the supply side during fault or overloaded in
power system. The basic principle of a series 4. THE PRINCIPLE OPERATION OF DVR
compensator is simple, by inserting a voltage of required SYSTEM
magnitude and frequency, the series compensator can In normal situation without short circuit in power system,
restore the load side voltage to the desired amplitude and a capacitor between rectifier and inverter (Figure 3) will
waveform even when the source voltage is unbalanced or be charging. When voltage sag happened, this capacitor
distorted [3].This DVR device employs gate turn off will discharge to maintain load voltage supply. Nominal
thyristor (GTO) solid state power electronic switches in a voltage will be compared with voltage sag in order to get
pulse width modulated (PWM) inverter structure. The a difference voltage that will be injected by DVR system
DVR can generate or absorb independently controllable to maintain load voltage supply. PWM technique is using
real and reactive power at the load side. The DVR also is to control this variable voltage. In order to maintain load
made of a solid state dc to ac switching power converter voltage supply, reactive power must be injected by DVR
that injects a set of three phase ac output voltages in system. Practically, the capability of injection voltage by
series and synchronism with the distribution feeder DVR system is 50% of nominal voltage. It is sufficient
voltages [3]. The amplitude and phase angle of the for mitigation voltage sag because from statistic shown
injected voltages are variable thereby allowing control of that many voltage sag cases in power system involving
the real and reactive power exchange between the DVR less than 0.5 p.u. voltage drop.
and the distribution system [3]. The dc input terminal of a
DVR is connected to an energy source or an energy 5. MATHEMATICS MODEL FOR VOLTAGE SAG
storage device of appropriate capacity. The reactive CALCULATION
power exchange between the DVR and the distribution Considered Figure 5, in a normal condition (no fault),
system is internally generated by the DVR without ac current through load A and load B is equal (balance
passive reactive components. The real power exchanged load).When theres fault on feeder 1, a high current (short
at the DVR output ac terminals is provided by the DVR circuit current) will flow to feeder 1. So, based on
input dc terminal by an external energy source or energy Kirchhoffs Law, currents flow to feeder 2 will be
storage system. reduced. Consequently, voltage will also drop in feeder
DVR structure comprises rectifier, inverter, filter and 2.This voltage drop will be defined as voltage sags.
coupling transformer (Figure 3). Besides, pulse width Assume
modulated (PWM) technique is using to control variable Load A = ZLOAD_A
voltage. Filter is using for elimination harmonic Load B = ZLOAD_B B
33
SHAIRULWIZMARWAHAB,ALIASMOHDYUSOF/ELEKTRIKA,8(2),2006,3237
I=
V2
+
V2
(1) Here , and are the angle of VDVR, Zth and Vth,
x 2 + ZLOAD _ B x1 + ZLOAD _ A respectively and is the load power factor angle with
QL
When a fault happened (see Figure 5) in feeder 1, because = tan 1 .
PL
of short circuit, a high current will flow through feeder 1
as well as source current I. During this time, voltage in
The power injection of the DVR can be written as
feeder 2 decreased due to increasing of voltage drop
across source reactance xs, this makes sag happened.
Hence
V2 = Vs Ixs (3)
34
SHAIRULWIZMARWAHAB,ALIASMOHDYUSOF/ELEKTRIKA,8(2),2006,3237
Figure 7. Modelling for variable voltage of supply 7.2 Applying Voltage Sags in Power System with DVR
Three phase fault is created on the network system
(Figure 10). Time duration for fault is (0.3-0.5)s and
breaker will isolate the unhealthy feeder at 0.5s. The
length between the feeders will determine the severity of
dropped voltage. For short distance between these
feeders, if fault occurred at one feeder, the other feeder
will face high severity for dropped voltage. For long
distance between these feeders, the severity for dropped
voltage is not too high. So, a variable length is set in this
simulation to show the severity of dropped voltage during
voltage sag phenomenon. Table 2 shows the data taken
from the simulation.
From previous section that has been discussed
(Variable Voltage of Supply), DVR can only provide
sufficient voltage for the 48% severity from nominal
voltage. As the conclusion for this simulation, the lengths
between these feeders determine the severity of drop
voltage and DVR will mitigate voltage sag phenomenon.
Mitigation voltage sag for this simulation can be observed
in Figure 11 and Figure 12.
35
SHAIRULWIZMARWAHAB,ALIASMOHDYUSOF/ELEKTRIKA,8(2),2006,3237
Table 2. Variable length for voltage sag Figure 13. Increasing performance of DVR system
Length (km) Ea (p.u) Eb (p.u)
10 0.95812 0.998482
Table 3: Data for increasing performance of DVR
3 0.896826 0.993272
Voltage(kV) Ea(p.u) Eb(p.u)
1 0.763966 0.966975
11 0.97835 0.993059
0.75 0.71729 0.95369
5 0.445864 0.936014
0.5 0.651827 0.920331
4.8 0.428068 0.910269
0.1 0.547569 0.870387
4.7 0.419155 0.896031
7.3 Increasing Performance of DVR System 4 0.35688 0.788454
There are two main factors relating to the capability and
performance of DVR working against voltage sags in a
certain power system: the sag severity level and the Total 8. CONCLUSION
Harmonic Distortion (THD). Both of these in turn are In this paper, a complete simulated DVR system has been
mainly decided by the DC source [4]. developed by using the PSCAD software. Its
Based on previous discussion (Variable Voltage of characteristic and performance when applied to a
Supply), the DC voltage is coming from the transformer simulated power system has been studied. It is shown that
that the setting parameter is 1MVA and secondary the simulated DVR developed, works successfully
voltage is 2kV.Besides that, the secondary filter at without lacks in its performance when applied to a
coupling transformer is 50uF. The result shows DVR simulated power system network. By introducing DVR
only can compensate voltage for severity 48% from in the power network, it can help to improve power
nominal value. It means DVR can inject sufficient quality. It is important to have a good delivery power
voltage when the drop voltage is at least 0.62 p.u. quality in electrical power systems especially to the
There are two ways for increasing DC voltage in critical areas, such as in the industrial sectors, in order
DVR system. One of them is increasing secondary to ensure the smoothness of the daily operations.
voltage value and another one is increasing rating MVA Hopefully this paper could be a beneficial reference to
transformer. Increasing rating MVA transformer will others who are keen on voltage sag study.
draw small dropped voltage from primary to secondary
voltage. For better and higher DC result for this
simulation, both of this parameter is increased.
36
SHAIRULWIZMARWAHAB,ALIASMOHDYUSOF/ELEKTRIKA,8(2),2006,3237
REFERENCES
[1] M. F. Faisal, Power quality management program:
TNBs Experience, Distribution Engineering
Department, TNB, 2005.
[2] A. Felce, G. Matas, Y. D. Silva, Voltage sag
analysis and solution for an industrial plant with
embedded induction motors, Inelectra S.A.C.A.
Caracas, Venezuela, 2004.
[3] A. Ghosh and G. Ledwich, Power Quality
Enhancement Using Custom Power Devices, Kluwer
Academic Publishers, 2002.
[4] P. T. Nguyen and T. K. Saha (2004), DVR against
balanced and unbalanced voltage sags: Modeling and
simulation, IEEE-School of Information
Technology and Electrical Engineering, University
of Queesland, Australia, 2004.
[5] Pirjo Heine, Matti Lehtonen, Voltage sag
distributions caused by power system faults, IEEE
Transactions on Power Systems, Vol. 18, No. 4,
November 2003.
37