API 653 Qbank
API 653 Qbank
INTRODUCTION
This material is to help prepare you for the API 653 Certification
Examination. Your degree of proficiency in this material will be tested
throughout the course.
The below listed references are indicated as the source of the answers
next to each question. To best prepare for the course and the
examination, you should strive to memorize these questions and answers.
REFERENCE INDEX
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 1
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (c)
ANS : (b)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 2
[email protected] www.gotoITC.com
Professional Training and Consultation
5) An external floating roof shall be provided with atleast one manhole having
a minimum inside diameter of __________ inches.
ANS : (c)
ANS : (a)
ANS : (a)
ANS : (b)
ANS : (a)
ANS : (b)
11) A liquid penetrant examiner must have vision to enable him to read Jagger
Type 2 standard chart at a distance of not less than 12 inches and is
capable of distinguishing and differentiating contrast between colours
used. Examiners shall be checked __________ to ensure that they meet
these requirements :-
ANS : (c)
REF : IX QW-200.2
ANS : (d)
13) A radiograph is made using an X-ray source and two films in each film
holder. For composite viewing, each film of the composite shall have a
minimum density of :-
ANS : (b)
14) A reconstructed tank with a total height of 25' has been determined to
have an out-of-plumbness of 2-3/4". This is :-
ANS : (a)
15) A riveted tank shell with a butt joint has 3 rows. What is the joint
efficiency ?
ANS : (b)
ANS : (b)
ANS : (b)
(a) made with atleast 2 passed; (b) may be made with 1 pass
(c) shall be atleast 3 / 16" (d) both (a) and (c) above
ANS : (a)
19) A single film technique was used to make a radiograph using a Cobalt-60
source. The minimum permitted density in the area of interest is :
ANS : (c)
ANS : (b)
21) A tank bottom depression is 9.125" deep, radius of depression is 22.5 feet.
What is the maximum depth of depression ?
ANS : (d)
22) A tank bottom lining with a measured thickness of 15 mils should be tested
with :-
ANS : (b)
ANS : (b)
(a) 25; (b) 30; (c) 35; (d) Both (a) and (b) are
responsible;
ANS : (a)
25) A welder may deviate from the parameters specified in WPS if they are
nonessential variables :-
ANS : (c)
REF : IX QW-461.9
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 7
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (b)
(a) One foot; (b) One and a half feet; (c) Two feet; (d) Three
feet.
ANS : (d)
29) A welding procedure qualified on inch thick plate can be used to weld
groove welds in materials from to :-
REF : QW-451.1
ANS : (d)
30) A welding procedure qualified on 3/8" thick plate can be used to weld
groove welds in materials :-
REF : IX QW-451.1
ANS : (b)
31) A welding procedure qualified under the 1965 ASME Code Section IX :
(a) Is obsolete;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 8
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (c)
33) Acceptance standards for MT examination shall be per :-
ANS : (c)
34) All tanks shall be given a formal visual external inspection by an inspector
atleast :-
REF : API-653-4.3.2.1
ANS : (b)
ANS : (b)
ANS : (b)
ANS : (d)
38) At what design metal temperature must impact tests be made for all weld
metal and procedures to be used ?
(a) Below 32oF; (b) Below 20oF; (c) Below 15oF; (d) Below
10oF.
ANS : (b)
39) At what level is the atmosphere considered oxygen-deficient ?
ANS : (a)
40) Base metals are grouped into groupings according to their welding
characteristics :-
REF : IX QW-421
ANS : (d)
ANS : (d)
ANS : (c)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 11
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
ANS : (b)
46) Bottoms exceeding 100' diameter in tanks operating above 200 oF shall
have :-
ANS : (a)
ANS : (b)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 12
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d).
ANS : (c)
(a) clean the part, apply the developer, apply the penetrant, remove
excess penetrant, inspect the part, clean the part;
(b) clean the part, apply the penetrant, remove excess penetrant, apply the
developer, inspect the part, clean the part;
(c) clean the part, apply the developer, apply the penetrant, inspect the
part, remove excess penetrant, clean the part;
(d) clean the part, apply the developer, apply the penetrant, inspect the
part, clean the part.
ANS : (b)
52) Determine the exact interval for ultrasonic thickness measurements for a
tank with 17 mils of the original 25 mils corrosion allowance still remaining
after 15 years ?
(a) 5 years; (b) 15 years; (c) 23.875 years; (d) 31.875 years.
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 13
[email protected] www.gotoITC.com
Professional Training and Consultation
53) Determine the maximum allowable height for a 90 foot diameter tank
based on a maximum shell plate thickness of 0.5 inch and maximum
allowable stress of 21,000 psi, with a joint efficiency of 0.85, and no
corrosion allowance :-
ANS : (c)
(a) potential floating roof hang up; (b) lack of circularity at the top;
(c) oval shape at the top; (d) all of the above.
ANS : (d)
ANS : (c)
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 14
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
REF : IX QW-432
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 15
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (c)
(a) 1/2 inch; (b) 1/4 inch; (c) 3/16 inch; (d) 5/8 inch.
ANS : (b)
(a) fluid static head, internal and external pressure, wind loads, settlement
and business needs;
(b) wind loads, settlement, fluid static head, internal and external pressure
and nozzle loads;
(c) internal and external pressure, wind loads, fluid static head, settlement
and if it convenient.
(d) only (a) and (b) above.
ANS : (b)
ANS : (c)
65) Find the capacity of a small tank, with a joint efficiency of 0.85,
specific gravity = 1.0, no corrosion allowance, diameter is 40 feet, height
is 30 feet with 5 completed 72" courses.
ANS : (c)
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 17
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
68) For a 30 inch shell manhole, 0.5 inches thick shell and reinforcing
plate, what minimum neck thickness is required ?
ANS : (d)
69) For an existing 150 foot diameter storage tank, which has been in
service for 28 years, known joint efficiency is 1.0, contents have been the
same, with a specific gravity of 1.0, material yield of plate is 30,000 and
tensile strength is 55,000, liquid fill level is 50 feet, calculate the miimum
allowable thickness for the second course :-
ANS : (d)
70) For butt-welded joints in which the thinner shell plate is 3/8 inch or
less, how many spot radiographs shall be taken in the first 10 feet of
completed vertical joint of each type and thickness welded by each
welder or welding operator ?
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 18
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
71) For dome roofs that are flanged, the radius of curvature is limited
by the deptch of the roof, including the crown and knuckle depth. What is t
he maximum roof deptch for a shop assembled cone roof 10 feet in
diameter ?
ANS : (c)
72) For impact testing materials, what is the minimum transverse value
of Group IV materials, 1.5" thick ?
ANS : (c)
73) For impact testing materials, what is the minimum longitudinal value
for a 1.8" thick A-516-70 as rolled material for a WPS ?
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 19
[email protected] www.gotoITC.com
Professional Training and Consultation
74) For new or repaired shell horizontal joints, how many radiographs
shall be taken for each 50 feet of horizontal joint, not including those
required at intersections of vertical and horizontal joints ?
ANS : (a)
75) For welds that attach nozzles, manholes, cleanout openings and
permanent attachments, undercut shall not exceed ______ inch.
ANS : (d)
77) From what type of material should shims be fabricated when they
are to be used to radiograph welds ?
(a) Malleable materials capable of being drilled;
(b) From the same heat number as the material being inspected;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 20
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
78) Generally, tank bottom linings cover the entire tank bottom and
extend ____ inches up the shell of the tank :-
ANS : (c)
(a) on the roof of a tank or within the gas / vapour space of a tank;
(b) where heat of welding may cause environmental cracking;
(c) hot (a) and (b);
(d) (a) only.
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 21
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
81) How does the calculation of minimum thickness for a riveted tank
shell differ from that of a welded tank shell :-
(a) The formula for the calculation of minimum thickness of a riveted tank
shell is the same as for a welded tank shell except that the maximum
allowable stress (S) is 21,000 lbs / sq. inch and the efficiency equals 1 for
the shell plate 6 inches away from rivets;
(b) The formula for the calculation of minimum thickness of a riveted tank
shell is exactly the same for a welded tank;
(c) The formula for the calculation of minimum thickness of a riveted tank
shell is the same as for a welded tank shell except the minimum allowable
stress (S) is
21,000 lbs /s q. inch and the efficiency equals 0.85 for the shell plate 6
inches away from the rivets.
(d) API does not set minimum thickness.
ANS : (a)
82) How many equally spaced measurement are required for the
thickness averaging technique ?
ANS : (b)
83) How many impact specimens must be broken for an average value
for P1, Group 1, 2, 3 material ?
ANS : (b)
84) How many inches must project beyond the outside edge of the weld
attaching t he bottom sketch plate to the shell plate ?
(a) atleast 1/2 inch; (b) atleast 2 inches; (c) atleast 9/16 inch; (d)
atleast 1.0 inch
ANS : (d)
85) How many settlement measurement points are required for a tank
that measures 200 ft. in diameter ?
ANS : (c)
86) How many specimens and impact tests must be performed from a
single test coupon or test location ?
ANS : (c)
87) How many specimens must be broken for an average value for P1,
Group 1, 2, 3 material ?
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 23
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (b)
ANS : (c)
90) If penetrameters are not placed adjacent to the welds, what rules
apply ?
(a) The penetrameter should be placed on the source side of the material
being radiographed.
(b) The penetrameter may be placed on the film side of the material being
radiographed.
(c) Lead letter "F" atleast as high as the identification number is placed
adjacent to the film side penetrameter;
(d) All of the above.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 24
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
ANS : (a)
92) In a riveted tank shell, a butt joint has 3 rows. What is the joint
efficiency ?
ANS : (b)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 25
[email protected] www.gotoITC.com
Professional Training and Consultation
94) In general, if shell thickness does not exceed ____ inch, it does not
require further assessment for brittle fracture :-
ANS : (d)
(a) Floor thickness; (b) The radius of an inscribed circle in the area;
(c) tank diameter; (d) Tank height.
ANS : (b)
REF : AI 653,
ANS : (d)
ANS : (a)
ANS : (d)
ANS : (d)
ANS : (b)
ANS : (d)
ANS : (d)
(a) roof; (b) upper shell; (c) bottom; (d) lower shell.
ANS : (c)
ANS : (d)
ANS : (a)
ANS : (c)
107) Letters and numerals on nameplates shall not be less than inch
high.
ANS : (a)
ANS : (b)
109) Magnetic particle examination shall be performed in accordance
with a written procedure that is in compliance with the requirements of :-
ANS : (a)
ANS : (b).
ANS : (b)
112) Minimum thickness calculation for shells of tanks 200 ft. or less in
diameter shall be done using ____ :-
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 31
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
114) Of the following welding processes, which one is not permitted for
welding on above ground storage tanks :-
ANS : (c)
115) On plates more than 3/16 inch thick, the fillet weld thickness shall
not be less than 1/3 the thickness of the thinner plat at the joint and shall
be atleast :-
(a) 1/2 inch; (b) 1/4 inch; (c) 3/16 inch; (d) 9/32 inch.
ANS : (c)
116) On the drawing that the manufacturer shall furnish the purchase,
you would expect to see which of the following information :-
(a) The required shell thickness for both the design condition (including
corrosino allowance) and the hydrostatic test condition;
(b) The nominal thickness used;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 32
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
(a) 1.0 inch; (b) 1.5 inch; (c) 2.0 inch; (d) 2.5 inch.
ANS : (c)
ANS : (c)
119) Per API 650, calculation of shell thickness by the 1-foot method
cannot be used for tanks :-
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 33
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
(a) grinding and out area; (b) penning over affected area;
(c) applying additional weld bead over area; (d) mechanical caulking.
ANS : (c)
ANS : (d)
ANS : (c)
123) Plates found to be thinner than those in the course above it are :-
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 34
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
ANS : (d)
ANS : (d)
ANS : (d)
ANS : (a)
ANS : (b)
ANS : (b)
(a) < 500; (b) 500 1000; (c) 1000 2000; (d) < 10,000
ANS : (a)
131) Rewelding vertical joints requires cutting horizontal welds back from
the joint a minimum of ____ inches :-
ANS : (d)
(a) semi-annually;
(b) annually;
(c) at intervals determined by experience locally;
(d) every 5 years.
ANS : (c)
ANS : (c)
ANS : (c)
(a) the lesser of every 5 years of 1/2 corrosion rate of the shell life;
(b) the lesser of every 5 years or 1/4 corrosion rate of the shell life;
(c) the lesser of every 10 years or 1/2 corrosion rate of the shell life;
(d) the lesser of every 10 years or 1/4 corrosion rate of the shell life.
ANS : (c)
(a) between the outer periphery of the roof and the tank shell;
(b) around columns, ladders and gauge pipes that penetrate the deck;
(c) the seal shall be flexible;
(d) all of the above.
ANS : (d)
ANS : (d)
ANS : (d)
ANS : (b)
ANS : (a)
ANS : (a)
142) Tests for leaks in reinforcing plate welds require ____ psig :-
(a) upto 2.5; (b) upto 15; (c) upto 21; (d) upto 30.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 40
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
143) The "critical zone" for tank bottom repairs is the area within the
annular plate ring, within inches of the shell or within inches of the inside
edge of the annular plate ring:-
ANS : (c)
144) The "L" in actual thickness determination for each shell course :
ANS : (c)
REF : IX QW-120
ANS : (a)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 41
[email protected] www.gotoITC.com
Professional Training and Consultation
146) The API 653 standard covers the maintenance inspection, repairs,
alteration, relocation and reconstruction of tanks constructed to which one
of the following standards :-
(a) ASME; (b) API 651; (c) API 65; (d) API 650.
ANS : (d)
ANS : (c)
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 42
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
150) The determining factor for intervals between internal and external
inspections :-
ANS : (b)
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 43
[email protected] www.gotoITC.com
Professional Training and Consultation
(a) (b) and (d) below; (b) cleaned, gas freed and safe for entry;
(c) hammer test the roof; (d) complete isolation.
ANS : (a)
ANS : (b)
154) The formula for maximum bulge or depression of a tank bottom is :-
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 44
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
(a) that portion of the base metal which has not been melted;
(b) whose mechanical properties or micro structures have been altered by
the heat of welding;
(c) is least likely to contain discontinuities;
(d) both (a) and (b) above.
ANS : (d)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 45
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
ANS : (b)
ANS : (a)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 46
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
ANS : (d)
ANS : (b)
(a) On plate 3/16 inch thick, the weld shall be a full-fillet weld, and on
plates more than 3/16 inch thick, the weld thickness shall not be less than
1/3 the thickness of the thinner plate at the joint and shall be atleast 3/16
inch.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 47
[email protected] www.gotoITC.com
Professional Training and Consultation
(b) On plate 5/16 inch thick, the weld shall be a full-fillet weld, and on
plates more than 5/16 inch thick, the weld thickness shall not be less than
1/3 the thickness of the thinner plate at hte joint and shall be atleast 3/16
inch.
(c) On plate 3/16 inch thick, the weld shall be a full-fillet weld, and on
plates more than 5/16 inch thick, the weld thickness shall not be less than
1/3 the thickness of the thinner plate at the joint and shall be atleast 5/16
inch.
(d) On plate 1/4 inch thick, the weld thickness shall not be less than 1/3
the thickness of the thinner plate at the joint and shall be atleast 1/4 inch.
ANS : (a)
ANS : (a)
167) The permissible exposure limit (PEL) is the maximum ____ time-
weighed average of any airborne contaminant to which an employee may
be exposed :-
ANS : (a)
168) The proper method for dismantling tank bottoms that are to be
reused shall be cut by:-
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 48
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
169) The purchaser has not specified the use of 1-foot method for
calculating thickness and L/H 2, therefore, what is the shell plate
thickness for the first course for the following tank design ?
Height = 40 feet
Diameter = 260 feet
Stress @ test condition = 30,000 psi
Specific gravity = 1.0
Course Length = 8 feet
Corrosion Allowance = 0
Joint Efficiency = .0
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 49
[email protected] www.gotoITC.com
2.6 D (h 1) G
Professional Training and Consultation
SE
ANS : (c)
171) The root opening for square grooves for butt-welded bottom plate
shall not be less than :-
(a) 1/2 inch; (b) 1/4 inch; (c) 3/16 inch; (d) 9/32 inch.
ANS : (b)
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 50
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
ANS : (a)
175) The thickness to be used for each shell course when checking the
tank design after reconstruction shall be based on measurements taken
within ____ days prior to relocation :-
ANS : (c)
(a) non-refrigerated;
(b) vertical, cylindrical, above ground closed and open top;
(c) built to API 650 and 12 C;
(d) All of the above.
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 51
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
178) The variable design point method shall be used for tanks greater
than ____ in diameter :-
ANS : (d)
ANS : (a)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 52
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
ANS : (c)
ANS : (b)
(a) 12" or greater NPS nozzles; (b) greater than 12" NPS nozzles;
(c) greater than 2" NPS nozzles; (d) greater than 10" NPS nozzles.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 53
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (c)
ANS : (d)
ANS : (b)
187) Top decks of external floating roofs (double deck or pontoon type)
which are designed with are designed with a permanent slope for
drainage shall have a minimum slope of ____ inch in 12 inches :-
ANS : (a)
188) Underun on plate not more than inch from the computed design
thickness or minimum permitted thickness is acceptable :-
ANS : (a)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 55
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
ANS : (a)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 56
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
193) Welded joints that have experienced metal loss due to corrosion :-
ANS : (b)
ANS : (d)
(a) 9 feet;
(b) 6 feet;
(c) 3 feet;
(d) As identified on the approved welding procedure specification.
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 57
[email protected] www.gotoITC.com
Professional Training and Consultation
REF : IX QW-322
ANS : (a)
197) Welding filler metals are grouped into groupings based on their
AWS classification:-
REF : IX QW-432
ANS : (b)
ANS : (d)
199) Welding procedures are qualified in accordance with ____
REF : IX Article 2
ANS : (c)
ANS : (a)
201) What are the two general approaches for determining minimum
thicknesses of tank bottom plate and briefly describe their differences :-
ANS : (a)
202) What are the two methods of guided-bend tests permitted by ASME
Section IX ?
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 59
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
203) What diameter bolt circle is required and how many bolts for a 24
inch roof mahole ?
ANS : (d)
REF : QW-432
ANS : (d)
ANS : (c)
(a) An examination of a welded joint that will disclose surface and sub-
surface discontinuities without physical harm to the welded joint;
(b) An examination of a bolted joint;
(c) An examination of a welded joint that will disclose surface and sub-
surface discontinuities that may cause physical harm to the welded joint.
(d) An examination of a welded joint that will disclose only surface
discontinuities without physical harm to the welded joint.
ANS : (a)
REF : 2.4.7.1
ANS : (a)
208) What is the 42 gallon barrel capacity of a tank 110 feet in diameter,
24 feet high, joint efficiency is 0.85, specific gravity = 1.0, corrosion
allowance = 0.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 61
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
209) What is the allowable stress at root of anchor bolt threads for a tank
with a design pressure upto 2.5 psig ? Uplift is based on tank design
pressure and wind.
ANS : (b)
210) What is the capacity of a tank 110 feet in diameter, 24 feet high,
joint efficiency is 0.85, specific gravity is 1.0, corrosion allowance = 0 ?
ANS : (d)
211) What is the distance from the centre pipe to shell for a 3 inch
nominal pipe size, 36 diameter drawoff sump, which is 18 inched deep ?
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 62
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
212) What is the distance in inches, that both a roof plate or a shell
bottom must be cut from the weld when dismantling a shell tank :-
ANS : (b)
213) What is the expected service life for a properly applied tank bottom
lining ?
ANS : (c)
ANS : (d)
(a) 1/4 inch; (b) 1/8 inch; (c) 9/32 inch; (d) 1/64 inch.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 63
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
(a) 1/4 inch; (b) 1/8 inch; (c) 1/32 inch; (d) 1/64 inch.
ANS : (c)
ANS : (d)
218) What is the maximum depth of edge settlement if the distance from
the inside of the shell to the bend point of the depression is 7 feet ?
ANS : (a)
ANS : (b)
220) What is the maximum out-of-plumbness of a new tank from the top
of shell relative to the bottom of the shell ?
(a) 1/100 of the total tank height; (b) 1/50 of the total tank height;
(c) 1/60 of the total tank height; (d) 1/200 of the total tank height.
ANS : (d)
ANS : (b)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 65
[email protected] www.gotoITC.com
Professional Training and Consultation
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 66
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
224) What is the minimum acceptable shell plate thickness for a tank
shell made of A 283 grade C material, 70 feet in diameter and 50 feet high
? Specific gravity of contents is 0.8. Original joint efficiency was 100 %.
ANS : (d)
225) What is the minimum allowable density through the image of the
penetrameter for radiographs made with a 2000 kv tube ?
(a) 1.8 4.0; (b) 1.3 2.8; (c) 2.0 4.0; (d) 1.3 1.8;
ANS : (b) 2.0 4.0 (for any gamma source anything besides a tube)
ANS : (d)
227) What is the minimum nominal shell thickness required when the
normal tank diameter is less than 50 feet ?
ANS : (a)
228) What is the minimum nominal thickness for bottom plates, exclusive
of any corrosion allowance ?
(a) 3/16 inch; (b) 1/4 inch; (c) 5/16 inch; (d) 7/16 inch.
ANS : (b)
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 68
[email protected] www.gotoITC.com
Professional Training and Consultation
(a) + 8; (b) 0;
(c) 4; (d) All Material must be impact tested.
ANS : (c)
REF : V-T282.1
ANS : (a)
ANS : (c)
233) What is the minimum thickness of bolting flange and cover plate for
a 24 24 size flush-type cleanout to be installed in a tank having
maximum h eight of 53 feet :-
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 69
[email protected] www.gotoITC.com
Professional Training and Consultation
234) What is the calculated minimum thickness of shell plates from the
stress on vertical joints for a field-erected small capacity tank, which has a
diameter of 30 feet, height of 36 feet, joint efficiency is 0.85, specific
gravity is 1.0, with a corrosion allowance of 0.125 ?
ANS : (c)
ANS : (b)
ANS : (a)
237) What is the nominal shell thickness required when the nominal tank
diameter is less than 50 feet ?
(a) 3/16 inch; (b) 1/4 inch; (c) 5/16 inch; (d) 3/8 inch.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 70
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
238) What is the radii tolerance measured at 1 foot above the shell to
bottom for a reconstructed 125 foot diameter tank ?
(a) +/- 1/2; (b) +/- 3/4; (c) +/- 1; (d) +/- 1 1/4.
ANS : (b)
(a) "Guide for Controlling the Lead Hazard Associated with Tank Entry and
Cleaning."
(b) "Cleaning Open-Top and Covered Floating-Roof Tanks"
(c) "Guidelines for Confined Space Work in the Petroleum Industry"
(d) "Welded Steel Tanks for Oil Storage"
ANS : (a)
240) What must be done to the tank prior to dismantling to insure proper
alignment after the tank is reconstructed ?
(a) Atleast four sets of matching centre punch marks should be placed at
the top and bottom edges of each shell plate.
(b) Atleast two sets of matching centre punch marks shall be placed at the
top and bottom edges of each shell plate.
(c) Atleast three alignment tabs shall be tack welded to the top and
bottom edges of the each shell plate.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 71
[email protected] www.gotoITC.com
Professional Training and Consultation
(d) Atleast two sets of matching centre punch marks may be placed at the
top and side edges of each shell plate.
ANS : (b)
241) What are NDE methods and to what extent shall they be used for
the examination of repairs to butt welds ?
ANS : (d)
242) What of the following are not principal causes of shell distortion :-
ANS : (a)
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 72
[email protected] www.gotoITC.com
Professional Training and Consultation
244) What size diameter cover plate is required for a 20 inch roof
manhole ?
ANS : (c)
ANS : (a)
ANS : (c)
(a) is removed;
(b) is covered by the new name plated;
(c) is located next to the new name plate;
(d) is left for the owner / user to keep on file
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 73
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
248) When alternative inspection intervals are selected, the owner / user
:-
(a) shall document the procedure and make it part of the permanent
record;
(b) alternatives are not allowed;
(c) alternative method shall include method for determining bottom plate
thickness;
(d) both (a) and (c) above.
ANS : (d)
249) When calculating the maximum liquid level for reconstructed tanks,
the required corrosion allowance shall be :-
(a) deducted from the actual thickness before calculating maximum liquid
level;
(b) added to actual thickness before calculating maximum liquid level;
(c) not be considered when calculating maximum liquid level;
(d) deducted from the original design thickness.
ANS : (a)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 74
[email protected] www.gotoITC.com
Professional Training and Consultation
REF : IX QW-200.1
ANS : (a)
251) When concrete ringwalls are provided under the shell, the top of the
ringwall shall be level with ______ inch in the total circumference
measured from the average elevation :-
ANS : (a)
ANS : (b)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 75
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
254) When is pitting an important factor in determining tank shell
acceptability ?
ANS : (c)
ANS : (a)
256) When preparing the surface for lining, the abrasive blasting should
not be performed if the temperature of the steel surface is less than ____
above the dew point or if the relative humidity is greater than ____ %.
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 76
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (a)
ANS : (b)
ANS : (b)
260) When reusing the entire bottom in the intact condition, the shell cut
shall be a minimum of ____ inch(es) above the top of the bottom plate :-
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 77
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
ANS : (b)
262) When the corrosion rate is not known or determinable from similar
service experience, actual bottom plate thickness shall be determined by
inspection within the next ____ years of operation :-
ANS : (a)
263) When the tank is out of service, additional bottom plate examination
includes :-
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 78
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (a)
264) When two (2) welders weld opposite sides of the same butt joint :-
ANS : (d)
265) When two or more tanks are installed concurrently in the same
location for the same purchase :-
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 79
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
ANS : (c)
ANS : (a)
269) Which below best describes how surfaces shall be prepared for
Ultrasonic examination :-
(a) The finished contact surfaces shall be free from weld splatter and any
roughness that would interfere with free movement of the search unit or
impair the transmission of ultrasonic vibrations;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 80
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
270) Which below option Thin-Film lining system shall be used for the
following service conditions; Temperature 200 degrees F, product
contents are distillates,
ANS : (b)
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 81
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (c)
ANS : (d)
ANS : (d)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 82
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
(a) Attack by frost; (b) Rusting; (c) Wind load; (d) Floods.
ANS : (a)
ANS : (c)
(a) Stresses placed on the bottom plates by roof support loads and shell
settlement;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 83
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
ANS : (b)
ANS : (a)
(a) Edition and revision number; (b) Shell material for shell course;
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 84
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
ANS : (d)
ANS : (a)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 85
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (d)
285) Which thin-film lining system shall be used for the following service
conditions : Temperature 200 degrees F, product contents are distillates :-
ANS : (b)
ANS : (b)
REF : IX QW-200.1
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 86
[email protected] www.gotoITC.com
Professional Training and Consultation
ANS : (b)
REF : IX QW-103.1
ANS : (b)
289) Who is responsible for stating the design metal temperature (based
on ambient temperatures), the design specific gravity, the corrosion
allowance (if any), and the design wind velocity ?
ANS : (a)
290) Widely scattered pits may be ignored provided that the sum of their
dimensions along any vertical line does not exceed 2 inch in an 8 inch
length and no pit depth results in a shell thickness of less than of the
minimum thickness exclusive of corrosion allowance :-
ANS : (c)
P.O. Box No. 7274, Dammam 31462, Saudi Arabia TEL (966) 3 857 0006 FAX (966) 3 857 5255 87
[email protected] www.gotoITC.com
Professional Training and Consultation