The document discusses low flow, low temperature HVAC systems and their benefits for energy efficiency. These EarthWise systems reduce energy usage in chillers, cooling towers, pumps and other equipment by lowering water flow rates and temperatures. Specific examples are provided that show energy savings from reducing cooling tower, pump and chiller loads through the use of low flow, low temperature systems.

Uploaded by

dimchien
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
186 views37 pages

EarthWise System en

The document discusses low flow, low temperature HVAC systems and their benefits for energy efficiency. These EarthWise systems reduce energy usage in chillers, cooling towers, pumps and other equipment by lowering water flow rates and temperatures. Specific examples are provided that show energy savings from reducing cooling tower, pump and chiller loads through the use of low flow, low temperature systems.

Uploaded by

dimchien
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

EarthWise System

HOANG LAC VIET


System Application & Control Sales
TRANE VIETNAM HANOI OFFICE

s u s t a i n a b I l I t y
average commercial building
Energy Consumption

Others
15%

Lifts/escalators Air-conditioning
11% 55%
Lighting
19%

s u s t a i n a b I l I t y
EarthWise Systems?

Energy
Efficiency

Emissions

s u s t a i n a b I l I t y
EarthWise Systems
Chiller system:
Low flow, low temperature
high efficiency systems
What do they do?
How do they do it?
Why use them?

s u s t a i n a b I l I t y
Low Flow, Low Temperature,
High Efficiency Systems

+/-$ ~/$
air handlers ductwork

+/-$

controls

+/-$

~/$
piping +/-$
chillers
s u s t a i n a b I l I t y
How?
Supply temperature Flow rates Fans

Ductwork

Temperature differential Pump

Piping

s u s t a i n a b I l I t y
Why Use LLH Systems?
Good for business: Offers the potential to
lower first cost and/or operating cost while
enhancing comfort, IAQ, and acoustics
Environmentally responsible: Reduced utility
generated greenhouse gas emissions and
uses less natural resources
Ideal for use in health care, institutional,
governmental, office building, education, and
other markets where VAV systems are used

s u s t a i n a b I l I t y
EarthWise Systems

s u s t a i n a b I l I t y
EarthWise Systems
100

95

90
LEED
% of HVAC energy consumption

85

80
EAc1
75

70

65

60
Conventional System Trane EarthWise System
Atlanta 100% 83%
Minneapolis 100% 93%
Los Angeles 100% 70%
Denver 100% 83%
Philadelphia 100% 89%
Portland 100% 80%

s u s t a i n a b I l I t y
EarthWise Systems
1970s 2007

18%
9% 31%

73%
17% 51%

Chiller
Cooling tower
Water pumps
s u s t a i n a b I l I t y
History of Chiller Performance

8.0 Centrifugal
Chiller efficiency, COP

>600 tons
Screw
6.0 150-300 tons
Scroll
<100 tons
4.0
Reciprocating
<150 tons

2.0

0.0
1977 1980 1989 1999 best
available
ASHRAE Standard 90.1

s u s t a i n a b I l I t y
Cool More or Pump More?
Pump efficiency 70%
COP 0.7
Chiller COP 7.0
Chiller COP 10x the pump COP
Conclusion work your most efficient
equipment harder

s u s t a i n a b I l I t y
Old Rule (ARI Standard)

Evaporator flow Condenser flow Standard


Chiller Type
Compressor
Piston 2.4 gpm/ton 3.0 gpm/ton ARI
Scroll [0.043 L/s/kW] [0.054 L/s/kW] 550/5901998
Screw
Centrifugal

6.7C - Supply water temp.


5.5C - Evaporator T
5.5C - Condenser T

s u s t a i n a b I l I t y
Earthwise Systems
Earthwise reduces energy for circulation
Basic Equation:

Q = cp x G x DT
Btuh = 500 x gpm x DT(0F)
Watts = 4184 x lps x DT(0C)

Saves
energy
s u s t a i n a b I l I t y
New Rule ( EarthWise System)

Evaporator flow Condenser flow


Chiller Type
Compressor
Piston EarthWise
1.5 gpm/ton 2.0 gpm/ton
Scroll System
Screw [0.027 L/s/kW] [0.036 L/s/kW]
Centrifugal

5C - Supply water temp.


9C - Evaporator T
8C - Condenser T

s u s t a i n a b I l I t y
Basic Rule
Fan :
Velocity1 / Velocity2 = Airflow1 / Airflow2
SP1 / SP2 = (Airflow1 / Airflow2 )2
Power1 / Power2 = (Airflow1 / Airflow2 )3

Pump :
Velocity1 / Velocity2 = Flow1 / Flow2
Pressure1 / Pressure2 = (Flow1 / Flow2 )2
Power1 / Power2 = (Flow1 / Flow2 )3

SP: Static Pressure


s u s t a i n a b I l I t y
Basic Rule

Meaning:

40% reduce in flow Power


consumption remaining:

[(0.6) X (0.6) X (0.6)] = 0.21

or reduce 80% in power consumption.

s u s t a i n a b I l I t y
Show Me the Impact
Cooling towers
Cooling coils
Pumps
Chillers
Air handlers
Controls

s u s t a i n a b I l I t y
waterside example
Cooling Tower Performance
(800 tons)

37/32/28 C 39/31/28 C
2400 GPM(151 l/s) 1600 GPM(100 l/s)

5C range 8C range
4C approach 3C approach
32 kW 32 kW

s u s t a i n a b I l I t y
waterside example
Cooling Tower: Size?, Cost?

37/32/28 C 39/31/28 C 39/32/28 C


2400 GPM 1600 GPM 1600 GPM
(151 l/s) (100 l/s) (100 l/s)
5C range 8C range 7C range
4C approach 3C approach 4C approach
32 kW 32 kW 24 kW

Same Tower Smaller Tower

s u s t a i n a b I l I t y
lessons learned
Cooling Tower Performance

!Tower water
should be hot!
Towers should use
inverters!

s u s t a i n a b I l I t y
Cooling Coil
MBH 504 504

WTR 5.5C 9C

GPM/Ton 2.4 1.5

EWT 6.5C 5C

LWT 12C 14C

GPM 101 63.0


GPM reduction of 37.5%

s u s t a i n a b I l I t y
Chilled Water Pump (800 tons)

Lu lng 1920 gpm 1200 gpm


121 l/s 75.6 l/s
Ct p 33.5 Hm 15 Hm
Hiu sut bm 80 % 80 %
Hiu sut motor 95 % 95 %
CS in 52 kW 16 kW

In this installation:
a 37.5% reduction in flow =
nearly 70% reduction in chilled water
pumping energy consumption
s u s t a i n a b I l I t y
lessons learned:
Cooling Cool Performance

!Chilled water
should be cold!

s u s t a i n a b I l I t y
waterside example
Chiller Energy (800 tons)
Capacity 800 tons

LWT 7C
Power 464 kW

LWT 5C
Power 490 kW

s u s t a i n a b I l I t y
waterside example
System Power (Chilled Water)

Low Low
delta T flow

Chiller 464 kW 490 kW +26 kW

CHW pump 52 kW 16 kW - 36 kW

Total 516 kW 506 kW - 10 kW

s u s t a i n a b I l I t y
lessons learned
Chiller Performance

!Chillers should be
efficient!

Factory witness tested

s u s t a i n a b I l I t y
Airside: What is different?
Common Low air
practice temp.system

Supply air 14C 8 9C


Room setpoint 24C 25C
Airside delta T 10C 17C

Lowers the required air flow by 30-40%

s u s t a i n a b I l I t y
air handler options
Fan Room Floor Area

10x

s u s t a i n a b I l I t y
CDQ OA OA

EarthWise
airside system EA
OA CA EA
for floor-by-floor applications

RA
SA
to EA
occupied
space

MA

RA
SA
to EA
occupied
space

MA
Yeah, but.
Cold downdrafts
Condensation

s u s t a i n a b I l I t y
Eliminating Cold Downdrafts

Parallel fan-powered units


on the perimeter
Using linear slot diffusers...

s u s t a i n a b I l I t y
What about Condensation?
Cold surfaces must be kept inside the
humidity controlled envelope
Positive building pressure is critical for
no condensation and IAQ
Install a vapor barrier with reasonable
construction
Design the P traps and pitch the condensate
drains correctly

s u s t a i n a b I l I t y
EarthWise Systems

Energy
Efficiency

Emissions

s u s t a i n a b I l I t y
s u s t a i n a b I l I t y
Projects designed with
EarthWise system in Vit Nam
- Nh My Intel Viet Nam HCM: 2350RT x 4 = 9800 Tons
- Financial Tower ( Bitexco) 68 tng HCM: 1100RT x 6=6600RT
- Nh My in T Hoya Hanoi: 2100 Tons
- Nh My Canon Hanoi: 2930 Tons
- Nh My in t Panasonic Hanoi: 2100 Tons
- Nh My Thy Sn Nam Vit An Giang: 750 Tons
- Khch sn Sheraton Nha Trang: 700RT x 3 = 2100 Tons
- VINCOM + EDEN Tower- HCM: 1000RT x 8 = 8000 Tons
- Linh m Project- Hanoi: 4 x 600RT = 2400 Tons
- Crown Plaza Hanoi: 4 x 750 RT = 3000 Tons
s u s t a i n a b I l I t y
- The End -

Thanks for your consideration !

s u s t a i n a b I l I t y