1. The document discusses terminology related to overload and short-circuit protection settings for circuit breakers. 2. It defines terms for long time protection against overloads including adjustable coarse and fine settings, and fixed or adjustable time delays. 3. It also defines terms for short circuit protection including fixed or adjustable thresholds and time delays, as well as load shedding thresholds. 4. Earth fault protection settings include insulation fault thresholds and time delays.

Uploaded by

Adhyartha Keraf
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
282 views

Protection Curve PDF

1. The document discusses terminology related to overload and short-circuit protection settings for circuit breakers. 2. It defines terms for long time protection against overloads including adjustable coarse and fine settings, and fixed or adjustable time delays. 3. It also defines terms for short circuit protection including fixed or adjustable thresholds and time delays, as well as load shedding thresholds. 4. Earth fault protection settings include insulation fault thresholds and time delays.

Uploaded by

Adhyartha Keraf
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

terminology of the overload and short-circuit protection settings

E31303

Io x Ir 1 adjustable for all modeles

tr 2 fixed for : TM16D to 250D


STR22SE / 22GE / 22ME, STR23SE, STR25DE, STR35SE / GE / ME
Ic2 Ic1
6 6 adjustable for : STR43ME, STR53UE, STR45AE / BE, STR55UE

Im 3 fixed for : TM16D 160 / TM16G to TM63G, STR22ME

adjustable for all other models

fixed for: TM16D to 250D


STR22SE / GE / ME, STR23SE, STR25DE / GE

adjustable for : STR45AE / BE


ON tm 4 STR35SE / GE, STR43ME, STR53UE, STR55UE

OFF

7 Ih
5 fixed for : STR22SE / GE / ME,
ON th STR23SE / GE,
STR35SE / GE / ME,
OFF I STR43ME

8 adjustable for : STR53UE, STR55UE

Long time protection against


overloads 4 tm = short circuit time delay
1 Io = coarse adjustment fixed or adjustable,
Earth fault protection
(function of In) Instantaneous protection
Ir = fine adjustment 7 Ih = insulation fault threshold,
5 I = instantaneous threshold, I2t curve in position ON or
2 fixed or adjustable depending OFF
tr = long time delay on the trip unit
fixed or adjustable depending
on the trip unit
8 th = earth fault time delay

Short circuit protection


6 Ic1 = adjustable load shedding
threshold for STR45, STR53
3 Im = short circuit threshold, and STR55
I2t curve in position ON or Ic2 = adjustable load shedding
OFF (depending on the trip threshold for STR45 and
unit) STR55
Merlin Gerin 13