Distributed I/O
SIMATIC ET 200
5/2 ET 200S
5/2 IM 151-3PN interface module
5/6 Digital electronic modules
5/15 SIPLUS digital electronic modules
(extended temperature range)
5/16 Analog electronic modules
5/29 ET 200S Software
5/29 Motor Starter ES
5/31 ET 200pro
5/31 IM 154-8 PN/DP CPU interface module
5/35 RFID Systems
5/35 SIMATIC RF180C
5/38 Motor Starters
and Frequency Converters
5/38 ET 200pro motor starters
Standard and High-Feature
5/43 ET 200pro isolator modules
5/45 Safety modules
5/48 Accessories for ET 200pro motor starters
5/51 ET 200pro FC Frequency Converter
5/55 ET 200M
5/55 IM 153-4 PN
Overview
Interface module for linking the ET 200S to PROFINET
Handles all data exchange with the PROFIBUS I/O Controller
3 versions:
- IM 151-3 PN STANDARD
- IM 151-3 PN HIGH FEATURE and IM 151-3 PN FO :
supports, in contrast to the STANDARD version, the opera-
tion of PROFIsafe F modules
with integrated 2-port switch for line topology
Note:
Micro Memory Card required for operation.
Technical specifications
5 6ES7 151-3AA22-0AB0 6ES7 151-3BA22-0AB0 6ES7 151-3BB22-0AB0
Supply voltages
Supply voltage of electronics 1L+
Rated value (DC) 24 V 24 V 24 V
reverse polarity protection Yes Yes Yes
Voltages and currents
Mains/voltage failure jumpering, 20 ms 20 ms 20 ms
min.
Current consumption
from supply voltage 1L+, max. 250 mA 250 mA 200 mA
Power loss, typ. 2.5 W 2.5 W 3W
Address area
Adressing volume
Outputs 256 Byte 256 Byte 256 Byte
Inputs 256 Byte 256 Byte 256 Byte
Connection point
RJ45 Yes Yes No
Protocols
PROFINET IO Yes Yes Yes
PROFINET IO
Transmission speed, max. 100 Mbit/s 100 Mbit/s 100 Mbit/s
automatic detection of transmission Yes Yes Yes
speed
Isochronous mode
Isochronouos mode No No No
Overview
2, 4 and 8-channel
ET 200S
digital inputs and outputs for the
Design
5 Possible combinations of the TM-E terminal modules and digital modules
Electronic modules TM-E terminal modules for electronic modules
Screw-type terminal 15S26-A1 15S24-A1 15S24-01 15S23-01 15S24-AT 30S44-01 30S46-A1
Order No. 6ES7 193 4CA40-0AA0 4CA20-0AA0 4CB20-0AA0 4CB00-0AA0 4CL20-0AA0 4CG20-0AA0 4CF40-0AA0
Spring-loaded terminal 15C26-A1 15C24-A1 15C24-01 15C23-01 15C24-AT 30C44-01 30C46-A1
Order No. 6ES7 193 4CA50-0AA0 4CA30-0AA0 4CB30-0AA0 4CB10-0AA0 4CL30-0AA0 4CG30-0AA0 4CF50-0AA0
FastConnect 15N26-A1 15N24-A1 15N24-01 15N23-01
Order No. 6ES7 193 4CA80-0AA0 4CA70-0AA0 4CB70-0AA0 4CB60-0AA0
2DI 24 V DC ST
2DI 24 V DC HF
4DI 24 V DC ST
4DI 24 V DC HF
4DI 24 V DC /SRC ST
4DI 24 to 48 V UC HF
4 DI NAMUR
8 DI 24 V DC, ST
2 DI 120 V AC ST
2 DI 230 V AC ST
2 DO 24 V DC/0.5 A ST
2 DO 24 V DC/0.5 A HF
4 DO 24 V DC/0.5 A ST
8 DO 24 V DC/0.5 A ST
2 DO 24 V DC/2 A ST
2 DO 24 V DC/2 A HF
4 DO 24 V DC/2 A ST
2 DO 24 230 V AC/2 A
2RO NO
24 to 120 V DC/5 A
24 to 230 V AC/5 A
2RO NO/NC
24 to 48 V DC/5 A
24 to 230 V AC/5 A
Technical specifications
6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131- 6ES7 131-
4BB01-0AA0 4BB01-0AB0 4BD01-0AA0 4BD01-0AB0 4BD51-0AA0 4BF00-0AA0
Supply voltages
Rated value
DC 24 V Yes; from power Yes; from power Yes; from power Yes; from power Yes; from power Yes
module module module module module
Reverse polarity protection Yes Yes Yes Yes Yes Yes
Current consumption
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA 10 mA
from supply voltage L+, max. dependent on
encoder
Power loss, typ. 0.4 W 0.4 W 0.7 W 0.7 W 0.7 W 1.2 W
Address area
Address space per module
with packing 2 Bit 2 Bit 4 Bit 4 Bit 4 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes;
TWE = 3000 s 5
Digital inputs
Number of digital inputs 2 2 4 4 4 8
Number of simultanneously 8
controllable inputs
Cable length
cable length, shielded, max. 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m 1,000 m
Cable length unshielded, max. 600 m 600 m 600 m 600 m 600 m 600 m
Input characteristic curve Yes Yes Yes Yes Yes Yes; 2-wire sen-
to IEC 1131, Typ 1 sors connectable
Input voltage
Rated value, DC 24 V 24 V 24 V 24 V 24 V 24 V
for signal "0" -30 to 5 V -30 to 5 V -30 to 5 V -30 to 5 V 30 to -5 V -30 to 5 V
for signal "1" 15 to 30 V 11 to 30 V 15 to 30 V 11 to 30 V -15 to -30 V 15 to 30 V
Input current
for signal "1", typ. 7 mA; at 24 V 8 mA 7 mA; at 24 V 8 mA 7 mA; at 24 V 5 mA
Input delay
(for rated value of input voltage)
for standard inputs
- programmable No Yes; 0.1 / 0.5 / 3 / No Yes; 0.1 / 0.5 / 3 / No No
15 ms 15 ms
- at " to "1", min. 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 2 ms
typically 3 ms 14.85 typically 3 ms 14.85 typically 3 ms
- at "0" to "1", max. 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 4.5 ms
15.15 15.15
- at "1" to "0", min. 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 0.05 / 0.4 / 2.7 / 2 ms; 2 ms
typically 3 ms 14.85 typically 3 ms 14.85 typically 3 ms
- at "1" to "0", max. 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 0.15 / 0.6 / 3.3 / 4.5 ms 4.5 ms
15.15 15.15
Encoder supply
Number of outputs 0; no encoder
supply
Output voltage min. L+ (-0.5 V), min. L+ (-0.5 V), min. L+ (-0.5 V), min. L+ (-0.5 V), max. M + 0.5 V,
under load under load under load under load under load
Output current, rated value 500 mA 500 mA 500 mA 500 mA 500 mA
Output current, permissible range 0 to 500 mA 0 to 500 mA 0 to 500 mA 0 to 500 mA 0 to 500 mA
Short-circuit protection Yes; electronic Yes; electronic
Encoder
Connectable encoders
2-wire BEROS Yes Yes Yes Yes Yes Yes
permissible quiescent current 1.5 mA 1.5 mA 1.5 mA 1.5 mA 1.5 mA 1.5 mA
(2-wire BEROS), max.
6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132- 6ES7 132-
4BB01-0AB0 4BB01-0AA0 4BB31-0AB0 4BB31-0AA0 4BD01-0AA0 4BF00-0AA0
Voltages and currents
Reverse voltage protection Yes; when using Yes; when using Yes; when using Yes; when using Yes; when using Yes
the same load the same load the same load the same load the same load
voltage as on the voltage as on the voltage as on the voltage as on the voltage as on the
power module power module power module power module power module
Load voltage L+
Rated value (DC) 24 V; From 24 V; From 24 V; From 24 V; From 24 V; From 24 V
power module power module power module power module power module
reverse polarity protection Yes; polarity Yes; polarity Yes; polarity Yes; polarity Yes; polarity Yes
reversal can lead reversal can lead reversal can lead reversal can lead reversal can lead
to the digital out- to the digital out- to the digital out- to the digital out- to the digital out-
puts being con- puts being con- puts being con- puts being con- puts being con-
nected through nected through nected through nected through nected through
Current consumption
from load voltage L+ (without load), 5 mA; 5 mA; 5 mA; 5 mA; 5 mA; 5 mA;
max. Per channel per module per channel Per channel Per channel Per channel
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA 10 mA 10 mA;
max. 15 mA at
Power loss, typ. 0.4 W 0.4 W 1.4 W 1.4 W 0.8 W 1.5 W
Address area
Address space per module
with packing 2 Bit 2 Bit 2 Bit 2 Bit 4 Bit
without packing 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte 1 Byte
Isochronous mode
Isochronouos mode Yes No Yes No Yes Yes; jitter incum-
bered < 100 s
5 Isolation
Isolation, digital outputs
between the channels No No No No No No
between the channels and the Yes Yes Yes Yes Yes Yes
backplane bus
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 40 g 40 g 40 g 40 g 40 g
Overview
2, 4 and 8-channel digital inputs and outputs for the
ET 200S
Can be plugged onto TM-E terminal modules with automatic
coding.
High-feature versions for enhanced plant availability, additio-
nal functions and comprehensive diagnostics
Hot swapping of modules possible
Overview
Analog inputs and outputs for the ET 200S
Can be plugged onto TM-E terminal modules with automatic
coding
High-feature versions with enhanced performance, precision
and resolution
Hot swapping of modules possible
Note:
Consult the configuring guide for selection of the appropriate
TM-E terminal modules.
Design
5 Possible combinations of the TM-E terminal modules and analog modules
Electronic modules Terminal modules TM-E for electronic modules
Screw-type terminal 15S26-A1 15S24-A1 15S24-01 15S23-01 15S24-AT 30S44-01 30S46-A1
Order No. 6ES7 193- 4CA40-0AA0 4CA20-0AA0 4CB20-0AA0 4CB00-0AA0 4CL20-0AA0 4CG20-0AA0 4CF40-0AA0
Spring-loaded terminal 15C26-A1 15C24-A1 15C24-01 15C23-01 15C24-AT 30C44-01 30C46-A1
Order No. 6ES7 193- 4CA50-0AA0 4CA30-0AA0 4CB30-0AA0 4CB10-0AA0 4CL30-0AA0 4CG30-0AA0 4CF50-0AA0
FastConnect 15N26-A1 15N24-A1 15N24-01 15N23-01 - - -
Order No. 6ES7 193- 4CA80-0AA0 4CA70-0AA0 4CB70-0AA0 4CB60-0AA0
2AI U ST
2AI U HF
2AI I 2WIRE ST
2AI I 2WIRE HS
4 AI I 2WIRE ST
2AI I 2/4WIRE HF
2 AI I 4WIRE ST
2AI RTD ST
2AI RTD HF
2 AI TC ST
2 AI TC HF
2AO U ST
2AO U HF
2AO U HS
2 AO I ST
2AO I HF
4 IQ-SENSE
Technical specifications
6ES7 134- 6ES7 134- 6ES7 134- 6ES7 134-
4FB01-0AB0 4LB02-0AB0 4GB01-0AB0 4GB52-0AB0
Voltages and currents
Load voltage L+
Rated value (DC) 24 V; 24 V 24 V; 24 V
From the power module From the power module
Short-circuit protection Yes
reverse polarity protection Yes Yes Yes; Yes
Destruction limit 35 mA
per channel
Voltage supply to the transducers
present No Yes
short-circuit proof Yes
Current consumption
from load voltage L+ (without load), 30 mA 55 mA 80 mA 225 mA
max.
from backplane bus 3.3 V DC, max. 10 mA 10 mA 10 mA 10 mA
Power loss, typ. 0.6 W 0.85 W 0.6 W 2.5 W 5
Address area
Address space per module
Address space per module, max. 4 Byte 4 Byte 4 Byte 4 Byte
Isochronous mode
Isochronouos mode No Yes No Yes
Analog inputs
Number of analog inputs 2 2 2 2
cable length, shielded, max. 200 m 200 m 200 m 200 m
permissible input frequency for volt- 35 V; 35 V permanent, 75 35 V; 35 V continuous, 75
age input (destruction limit), max. V for max. 1 ms (pulse V for max. 1 ms
duty factor 1:20)
permissible input current for current 40 mA
input (destruction limit), max.
Cycle time (all channels), max. Number of active chan- 0.5 ms; Number of active chan- 0.25 ms
nels per module x conver- 0.5ms for 2 channels nels per module x conver-
sion time without interference sion time
suppression 18/21 ms
per channel with interf.
Input ranges (rated values),
voltages
Voltage Yes Yes
1 to 5 V Yes Yes
Input resistance (1 to 5 V) 800 k
-10 V to +10 V Yes Yes
Input resistance (-10 V to +10 V) 800 k
-5 V to +5 V Yes Yes
Input resistance (-5 V to +5 V) 800 k
Input ranges (rated values), currents
Current Yes
0 to 20 mA Yes
Input resistance (0 to 20 mA) 106
4 to 20 mA Yes; on 50 ohms Yes
Operational limit
in overall temperature range
Current, relative to input area +/- 0,6 % +/- 0,1 %; 0.2% without interefence +/- 0,4 %
freqency suppression
Basic error limit
(operational limit at 25 C)
Current, relative to input area +/- 0,4 % +/- 0,05 %; 0.1% without intefer- +/- 0,3 %
ence frequency suppression
5 Analog outputs
Number of analg outputs 2 2 2 2 2
cable length, shielded, max. 200 m 200 m 200 m; 200 m 200 m;
100m if Twa < 2ms 100m if Twa < 2ms
Voltage output, Yes Yes Yes
Short-circuit protection
Voltage output, 25 mA 25 mA 25 mA
short-circuit current, max..
Current output, 18 V 18 V
no-load voltage, max.
Cycle time (all channels) max. 1.5 ms 0.25 ms 0.5 ms; 1.5 ms 0.5 ms
at max. 0.5F
Output ranges, voltage
1 to 5 V Yes Yes Yes; -5 to +5V also
implemented
-10 to +10 V Yes Yes Yes
Output ranges, current
-20 to +20 mA Yes Yes
4 to 20 mA Yes Yes
Connection of actuators
for voltage output 2-conductor Yes; Yes Yes
connection without compen-
sation of the line
resistances
for voltage output Yes Yes Yes
4-conductor connection
for current output Yes Yes
2-conductor connection
for current output No No
4-conductor connection
Load impedance
(in rated range of output)
with voltage outputs, min. 1 k 1 k 1 k
with voltage outputs, capacitive 1 F 1 F 0.5 F
load, max.
with current outputs, max. 500 500
with current outputs, inductive 1 mH 1 mH
load, max.
Destruction limits against externally
applied voltages and currents
Voltages at the outputs towards 15 V; max. 15 V 15 V 15 V; 15 V; max. 15 V
MANA continuous, as required continuous,
75 V for max. 1 s 75 V for max. 1 s
(pulse duty ratio (pulse duty ratio
1:20) 1:20)
Current, max. 50 mA; DC 30 mA 50 mA; DC 50 mA
5 Isolation
Isolation, analog outputs
Galvanic isolation, analog outputs Yes
between the channels No No No No No
between the channels and Yes Yes Yes Yes Yes
the backplane bus
between the channels and Yes Yes Yes Yes Yes
the load voltage L+
Permissible potential difference
between MANA and M internally 75 V DC / 60 V AC 75V DC / 60V AC 75 V DC / 60 V AC 75 V DC / 60 V AC
(UISO)
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm
Height 81 mm 81 mm 81 mm 81 mm 81 mm
Depth 52 mm 52 mm 52 mm 52 mm 52 mm
Weights
Weight, approx. 40 g 40 g 40 g 40 g 40 g
Overview
Using Motor Starter ES, the communication-capable motor starters
are easily parameterized during start-up, monitored during nor-
mal operation and successfully diagnosed for service purposes.
Preventative maintenance is supported by a function for reading
out diverse statistical data (e.g. operating hours, operating cycles,
cut-off currents, etc.). The user is supported during these proce-
dures with comprehensive Help functions and plain text displays.
Motor Starter ES can either be used as a stand-alone program or
it can be integrated into STEP 7 V5.1 SP3 upwards using an
object manager.
The following components are required for a serial connection:
ET 200S motor starters, High-Feature:
Control module 2DI DC 24 V COM
3RK1 903-0CH10
LOGO! PC cable
6ED1 057-1AA00-0BA0
ET 200pro motor starters:
Motor Starter ES for parameterization, monitoring, diagnostics and RS 232 interface cable
testing of motor starters 3RK1 922-2BP00 5
ECOFAST High-Feature motor starters (interface cable):
Motor Starter ES is used for start-up, parameterization,
diagnostics, documentation and the preventative maintenance PC cable
of the High-Feature motor starters of the SIMATIC ET 200S, 3RK1 911-0BN20.
ET 200pro and ECOFAST product families.
Interfacing is performed
Either through the serial device interface
(applies for ET 200S/ET 200pro/ECOFAST) or
With PROFIBUS DP-V1 capable motor starters
from any point in PROFIBUS
(applies for ET 200pro/ECOFAST)
Overview
PROFINET IO Controller to operate distributed I/Os on
PROFINET
Component Based Automation (CBA) on PROFINET
PROFINET proxy for intelligent devices on PROFIBUS DP in
Component Based Automation (CBA)
CPU with PLC functionality equivalent to S7-315-2 PN/DP,
provides distributed intelligence for preprocessing
Interface module to exchange preprocessed I/O data from
ET 200pro with a higher-level master through PROFIBUS DP
Fast, simple and end-to-end programming of a system with
modular programs via STEP 7
Micro Memory Card required for operation of CPU.
Technical specifications
6ES7 154-8AB00-0AB0 6ES7 154-8AB00-0AB0
5
Revision level Nesting depth
Associated programming package STEP 7 V5.4 SP1 Per priority class 8
with hardware update Additionally within an error OB 4
Supply voltages CPU/ Processing times
Rated value For bit operations, min. 0.1 s
24 V DC Yes
For word operations, min. 0.2 s
Permissible range, lower limit (DC) 20.4 V
For fixed point arithmetic, min. 2 s
Permissible range, upper limit (DC) 28.8 V
For floating point arithmetic, min. 3 s
Voltages and currents
External protection for supply lines 24 V DC circuit breaker / 16 A Timers/counters and
(recommended) with tripping characteristic type B their retentivity
and C (see ET 200pro Manual) S7 counters
Current consumption Number 256
Starting current, type 2 A; typical Of which retentive without battery
It 0.04 As; typical - Adjustable Yes
Current consumption 350 mA; typical - Lower limit 0
(nominal value) - Upper limit 255
Power loss, typ. 8.5 As; typical Retentivity
Memory - Adjustable Yes
Memory type - Lower limit 0
- Upper limit 255
Work memory
- Integrated 256 KB Counting range
- Expandable No - Adjustable Yes
- Lower limit 0
Load memory
- Upper limit 999
- Plug-in (MMC) Yes
- Plug-in (MMC), max. 8 MB IEC counter
Available Yes
Buffer
Type SFB
Available Yes
Without battery Yes S7 times
Number 256
CPU/ Chips
DB Retentivity
Number, max. 1,023; Number range: 1 to 1023 - Adjustable Yes
Size, max. 16 KB - Lower limit 0
- Upper limit 128
FB
- Pre-selected No retentivity
Number, max. 1,024; number range: 0 to 2047
Size, max. 16 KB Time range
- Lower limit 10 ms
FC
- Upper limit 9,990 s
Number, max. 1,024; number range: 0 to 2047
Size, max. 16 KB IEC timers
Available Yes
OB
Type SFB
Size, max. 16 KB
5 Of which distributed
- Inputs 2,048 bytes
Of which are Status Variable, max. 30
Of which are Modify Variable, max. 14
- Outputs 2,048 bytes Forcing
Process image Forcing Yes
Inputs, adjustable 2,048 bytes Forcing, variables I/O
Outputs, adjustable 2,048 bytes Number of variables, max. 10
Inputs, pre-selected 128 bytes Status Block Yes
Outputs, pre-selected 128 bytes Single step Yes
Process image partition Number of breakpoints 2
Number of partial process image, 1 Diagnostic buffer
max.
Available Yes
Digital channels Number of entries, max. 500
Inputs 16.384 Adjustable No
Outputs 16.384
Communication functions
Inputs, of which central 128
PG/OP communication Yes
Outputs, of which central 64
Routing Yes
Analog channels
Inputs 1.024 Shared data communication
Outputs 1.024 Supported Yes
Inputs, of which central 64 GD package size, max. 22 bytes
Outputs, of which central 64 S7 basic communication
Hardware configuration Supported Yes
Module rack, max. 1 S7 communication
Modules per rack, max. 16; Expansion width, max. 1m Supported Yes
Overview Application
The PROFINET communication module SIMATIC RF180C has
been specially designed for a wide range of applications in
industrial automation and logistics. Due to the high degree of
protection IP67, SIMATIC RF180C can be installed in the pro-
cess outside the control cabinet.
Main applications for SIMATIC RF180C:
Machine manufacturing, automation systems, conveyor
systems
Ancilliary assembly lines in the automotive industry / suppliers
Small assembly lines
Design
PROFINET IO
master module
e.g. S7-400 with CP 443-1
Benefits
Two parallel MOBY channels ensure real-time operation of the
dynamic read points
Reader connection with an 8-pole M12 connector for rapid
assembly of all components PROFINET
Easy changeover from PROFIBUS applications to PROFINET
with SIMATIC RF180C thanks to software compatibility
24 V for
The integrated switch allows several PROFINET modules to be RF180C and Reader
installed in star or bus topology. Each application can then be
built up quickly and inexpensively
to other
Powerful hardware ensures rapid data communication with PROFINET IO
the reader (SLG). So that the data are available to the applica- participants
tion more quickly
Simple firmware downloading in the case of function expan-
2. Reader 1. Reader
sions and error rectification ensures high availability of the
G_FS10_XX_00228
RFID system
Adjustable and parameterizable RFID-specific diagnostics
facilitate commissioning and troubleshooting
A broad selection of pre-assembled connecting cables can Tag / MDS
be ordered for connecting PROFINET and readers to SIMATIC
RF180C. This saves time and money during installation and
increases the quality
The hardware configuration with a base unit and connection
block ensures that SIMATIC RF180C is prepared for other con-
nection techniques, such as fiber-optic cables
SIMATIC RF180C has two reader interfaces from which the read- 1 reader connected 1.0 A
ers are also supplied with voltage. There is a solid-state fuse in Ambient temperature
SIMATIC RF180C for the reader power supply. The maximum
During operation -0 ... 60 C
current permitted for the readers per SIMATIC RF180C is 1 A. It
is not important here whether the current is drawn by 1 or 2 read- During storage -40 ... +70 C, 20 K/h
ers. Shock load during operation 30 g
The application accesses the tag via FB45. FB45 accesses the acc. to IEC 61131-2
tag via absolute addresses. For large volumes of data and com- Vibratory load during operation 0.75 mm (10 Hz to 58 Hz)
plex tag operations, the FB45 can process chained commands. acc. to IEC 61131-2 10 g (58 Hz to 150 Hz)
Data is exchanged between SIMATIC RF180C and the applica- Housing
tion by means of acyclic data records. This ensures that a large
Material Thermoplastic
quantity of data can be transferred from/to SIMATIC RF180C (fiberglass reinforced)
without loading the bus cycle. This is advantageous when large
volumes of data are being transferred. SIMATIC RF180C can Color IP Basic 714
also process chained tag commands in this mode extremely Degree of protection IP67
quickly.
Dimensions (W x H x D) in mm
SIMATIC RF180C 60 x 210 x 30
without connection block
SIMATIC RF180C 60 x 210 x 54
with connection block
Weight
Base module only 210 g
Connection block only 230 g
Application
With the ET 200pro motor starters, any three-phase loads can be As the result of the protection concept with solid-state overload
protected and switched. They are an integral part of ET 200pro evaluation and the use of SIRIUS controls size S00, additional
and have the high degree of protection IP65. This makes them advantages are realized on the standard and High-Feature motor
ideal for operation in modular, distributed peripherals without starters advantages which soon make themselves positively
control cabinets or control enclosures. felt particularly in manufacturing processes with high plant
The ET 200pro motor starters are available both with mechanical stoppage costs:
as well as electronic contacts. Configuration is made easier by the fine modular structure.
When using the ET 200pro motor starters, the list of parts per
The ET 200pro electromechanical starters are offered as direct load feeder is reduced to two main units: the bus module and
(DSe/DSe) and reversing starters (RSe/RSe) in the High-Feature the motor starter. This makes the ET 200pro ideal for modular
version with the following features: machine concepts or solutions for conveying systems and in
4 digital inputs machine-tool building.
Device versions with or without control for externally fed Expansions are easily possible through the subsequent adding
brakes with 400 V AC of modules. The innovative plug-in technology also does away
With expanded parameterization capabilities. with the wiring needed up to now. Through the hot swapping
function (disconnection and connection during operation) a
The ET 200pro electronic starters are offered as direct motor starter can be replaced within seconds if necessary,
(DSe/DSe) and reversing starters (RSe/RSe) in the High-Feature without having to shut down the ET 200pro station and with it
version with the following features: the process in the plant. The motor starters are therefore
4 digital inputs recommendable in particular for applications with special
With soft-starting and soft ramp-down function
With deactivated smooth start function as an electronic starter
demands on availability. Storage costs are optimized in
addition by the low level of variance (2 units up to 5.5 kW). 5
for applications with a high level of switching frequency The ordering option for motor starters with a 400 V AC brake
output provides the possibility of controlling motors with
Device versions with or without control for externally fed 400 V AC brakes. With four locally acting inputs available on the
brakes with 400 V AC High-Feature motor starter it is possible to realize autonomous
With expanded parameterization capabilities special functions which work independently of the bus and the
higher-level control system, e.g. as a quick stop on gate valve
controls or limit position disconnectors. In parallel with this, the
states of these inputs are signaled to the control system.
When using the optional isolator module with switch disconnec-
tor and group fusing function for the ET 200pro, the 400 V supply
of the motor starters can be switched on and off directly in the
field, i.e. locally.
Technical specifications
Motor starters, Motor starters, High-Feature
Standard
DSe, RSe DSe, RSe sDSSte, sDSte,
sRSSte, sRSte
General data
Motor starters that can be connected to ET 200pro or modules Max. 8
with a width of 110 mm
Mounting dimensions (W x H x D) in mm
Direct-on-line starter and reversing starter 110 x 230 x 150 110 x 230 x 160
Permissible ambient temperature
During operation -25 ... +55 C, from +40 C with derating
During storage -40 ... +70 C
Permissible mounting positions Vertical, horizontal
Vibration resistance according to IEC 60068, Part 2-6 2g
Shock resistance according to IEC 60068, Part 2-27 Half-sine 15 g/11 ms
Power consumption 24 V DC
From auxiliary circuit L+/M (U1) Approx. 40 mA
DSe standard
High-Feature motor starters, mechanical 1)
Motor protection: thermal model
DSe direct-on-line starters
Without brake output and with 4 inputs 3RK1 304-5 7 S40-2AA0
3RK1 304-0HS00-6AA0
Safety local isolator modules 2) 3)
Rated operational current 16 A 3RK1 304-0HS00-7AA0
5
3RK1 304-0HS00-7AA0
1) Only functions when used together with the corresponding backplane bus module 110 mm and the wide module rack.
The backplane bus module and the wide module rack must be ordered separately
(see Accessories for ET 200pro motor starters).
2) The Safety local isolator module only functions when used together with the 400 V disconnecting module.
3) Only in combination with the special backplane bus module for the Safety local isolator module
(see Accessories for ET 200pro motor starter).
Overview Application
Safety local isolator modules
The Safety local isolator module features the same functions as
a standard isolator module with an additional local safety function.
The Safety local isolator module contains a 3TK28 41 module
and is equipped with M12 terminals for the connection of external
safety components.
Terminals 1 and 2 can be used to connect either 1-channel or
2-channel EMERGENCY-STOP circuits or protective door
circuits (IN 1, IN 2).
For monitored starts, an external START switch can be connected
to terminal 3.
The required safety functions can be set using 2 slide switches
located under the left M12 opening.
In the event of an EMERGENCY-STOP, the Safety local isolator
module trips the downstream 400 V disconnecting module. This
safely isolates the 400 V circuit up to Cat. 4/SIL 3.
Safety local isolator modules In combination with the 400 V disconnecting module, the
Technical specifications
Safety local 400 V disconnecting modules
isolator modules
General data
Mounting dimensions (W x H x D) in mm
Direct-on-line starter and reversing 110 x 230 x 170 mm 110 x 230 x 150 mm
starter
Permissible ambient temperature
During operation -25 ... +55 C
During storage -40 ... +70 C
Permissible mounting positions Any
Vibration resistance according to 2g
IEC 60068, Part 2-6
Shock resistance according to Half-sine 15 g/11 ms
IEC 60068,
Part 2-27
Power consumption
From auxiliary circuit L+/M (U1) Approx. 20 mA
5 From auxiliary circuit A1/A2 (U2) --
Rated operational current for 25 A
power bus Ie
Rated operational voltage Ue 400 V
Approval according to DIN VDE 0106, Up to 500 V
Part 101
CSA and UL approval Up to 600 V
Conductor cross-sections
Incoming energy supply max. 6 x 4 mm2
Degree of protection IP65
Touch protection Touch protection
Degree of pollution 3, IEC 60664 (IEC 61131)
Rated impulse withstand 6 kV
voltage Uimp
Rated insulation voltage Ui 400 V
Rated operational current
for starters Ie
AC-1/2/3 at 40 C
- At 400 V 16 A 25 A
- At 500 V 16 A 25 A
Rated short-circuit breaking capacity 50 at 400 V
Type of coordination according to 2
IEC 60947-4-1
Safe isolation between main and 400 V, according to DIN VDE 0106, Part 101
auxiliary circuits
Operating times at 0.85 ... 1.1 x Ue
Closing delay -- 25 ... 100 ms
Opening delay -- 7 ... 10 ms
Device functions
Group diagnostics Yes, parameterizable
Device indications
Group fault SF LED (red)
3RK1 304-0HS00-7AA0
400 V disconnecting modules
Rated operational current 25 A 3RK1 304-0HS00-8AA0
The 400 V disconnecting module only functions when used together with the
Safety local isolator module.
Only functions when used together with the backplane bus module and the wide
module rack. The backplane bus module and the wide module rack must be
ordered separately (see Accessories for ET 200pro motor starter).
5
3RK1 304-0HS00-8AA0
F-Switch PROFIsafe N
24 V DC, 6ES7 148-4FS00-0AB0
incl. bus module
Connection module to be ordered separately
6ES7 148-1FS00-0AB0
Connection modules for F-Switch N
24 V DC 6ES7 194-4DA00-0AA0
Overview
Infeed on
isolator module
1
RSM
MS MS MS MS
NSA0_00467
NSA0_00465
3 4 7
5 2 9
5 / 6
Legend:
Infeed on $ Power feeder plug, see Seite 49
Motorstarter ET 200pro
% Power connection plug, see Seite 49
& Power jumper plug, see Seite 49
( Motor connection plug, see Seite 49
MS MS ) Motor plug, see page 49
* Motor plug with EMC suppressor circuit, see page 49
+ Power loop-through plug, see page 49
, Power connection cable, see page 49
NSA0_00466
10
8
3RK1 922-3BA00
Crimping tools for male contacts and sockets up to 4.0 mm2 (HAN Q8/0) 3RK1 902-0CT00
Dismantling tools for male contacts and sockets (HAN Q8/0) 3RK1 902-0AJ00
M12 sealing caps N
For sealing unused input and output sockets
3RX9 802-0AA00
Overview Benefits
The frequency converter is completely integrated into the
ET 200pro system and offers all the system advantages such
as cabinet-free installation, easy mounting on the module car-
rier, reduction of the wiring overhead due to self-assembling
communication and supply rails in the backplane bus, com-
prehensive diagnostic mechanisms and high availability
thanks to replaceability without affecting other modules in the
ET 200pro station.
The load voltage is routed to downstream frequency convert-
ers or motor starters with minimal installation costs through
pre-assembled jumper plugs. The maximum current carrying
capacity of the jumper plugs is 25 A.
Easy combination and expansion of converter functionality
using I/O modules or RSM isolator modules within the distrib-
uted station.
Input for PTC/KTY encoder for comprehensive motor protec-
tion
The integral 180 V DC brake control makes the rectifier in the
motor terminal box superfluous
Slot for optional memory card (MMC) to save the parameter
settings for fast replacement of modules with automatic repa-
rameterization
5
Available control modes: Frequency control, sensorless
vector control or torque control
STARTER, the graphical parameterization tool for Siemens
drives, is used to set the parameters either over the connected
fieldbus or over a point-to-point connection
Note: Access to the frequency converter over the bus is not
possible using STARTER when a CPU is located between the
PC and a frequency converter. This also applies to the
IM154-8 CPU.
Active and dynamic braking of the motor is possible without
incurring any additional costs. The generated braking energy
is fed back into the power supply, so there is no need for
braking choppers and pulse resistors.
The fail-safe version of the frequency converter offers auto-
nomous, certified safety functions that ensure that persons
and machines are protected from the dangerous movement of
machines. Integration of the safety system into the drive also
simplifies the machine architecture and supports system-wide
diagnostics.
Minimum reaction time of the fail-safe frequency converter to
signals of safe sensors thanks to local activation through the
Safety Local Isolator Module F-RSM or via field bus with the
PROFIsafe F-Switch module.
Application Design
The frequency converter controls the speed of asynchronous
motors steplessly
The modular, service-friendly concept of the frequency con-
verter is ideally suited to manufacturing processes with high
plant standstill costs
Optimal solutions can be created using several frequency
converters combined in one distributed station when drives
are operated in the same area or for the same purposes.
The frequency converter handles frequency control for simple
applications as well as vector control for more complex drive
tasks. It also handles the optimal control of a motor brake,
if used.
The converter also supports torque control, for example, for Installation of an ET 200pro station with 2 ET 200pro FC frequency
applications with mechanically coupled drives converters with integral safety functions
The advantages of line-commutated power regeneration are
primarily evident in continuous regenerative operation. The ET 200pro FC consists of the following components:
Examples include unwinding units, lowering of loads, or ET 200pro FC Standard frequency converter or converter with
dynamic braking of large centrifugal masses. integral safety functions
The integral safety functions significantly reduce the overhead Special backplane bus module to hold the frequency
5 for drive solutions in plant sections where there is a hazard
potential. Additional savings can be made thanks to sensor-
converter
Technical specifications
ET 200pro frequency converter ET 200pro frequency converter
with integral safety functions with integral safety functions
Selection features Functions
Integral safety functions according Safe Torque Off (STO) Open-loop/closed-loop V/f control linear (M~n)
to Category 3 of EN 954-1 and Safely Limited Speed (SLS)1) control procedure with/without flux current control
according to SIL 2 of IEC 61508 Safe Stop 1 (SS1) 1) (FCC), quadratic (M~n 2) or pa-
Activation of the integral safety rameterizable
functions through Safety Local Vector closed-loop control with-
Isolator Module F-RSM or out encoder
through PROFIsafe F-Switch Closed-loop torque control
Electrical data Operating functions Jogging mode, free function
blocks (FFB), positioning deceler-
Line voltage 3 AC 380 V to 480 V +10% / -10% ation ramp, automatic restart fol-
Output 1.1 kW lowing interruption due to power
(at 0 C to 55 C ambient tempera- failure, bumpless connection of
ture) converter to rotating motor
Rated input current 2.0 A Braking functions Regenerative braking operation
(at 0 C to 55 C ambient tempera- without brake chopper and pulse
ture) resistor
Contol of an electromagnetic
Rated output current 3.5 A holding brake
(at 0 C to 55 C ambient tempera-
ture)
Protective functions Undervoltage, overvoltage,
ground faults, short circuits, stall
5
Output 1.5 kW prevention, thermal motor
(at 0 C to 45 C ambient tempera- protection I2t, or sensor), con-
ture) verter overtemperature, motor
blocking protection
Rated input current 2.5 A
(at 0 C to 45 C ambient tempera- Connectable motors Low-voltage asynchronous mo-
ture) tors
Motor cable lengths: max. 15 m
Rated output current 3.9 A (shielded)
(at 0 C to 45 C ambient tempera-
ture) Mechanical data
Line frequency 47 Hz to 63 Hz Degree of protection IP65
Overload capability Overload current 1.5 x rated out- Operating temperature 0 C to +55 C
put current (i.e. 150% overload) Increased output
for 60 s, cycle time 300 s at 0 C to +45 C
Overload current 2 x rated out-
put current (i.e. 200% overload) Mounting position Vertical wall mounting (vertical
for 3 s, cycle time 300 s alignment of the cooling fins)
Skipped frequency range 1, programmable Compliance with standards UL, cUL ,CE, c-tick, Low Voltage
Directive 73/23/EEC, EMC Direc-
Converter efficiency 96% tive 89/336/EEC
Interfaces Connection to PROFIBUS
(PROFINET available soon) over
the ET 200pro backplane bus
Optical interface with USS proto-
col for optical RS232 connecting
cable
Slot for an optional memory card
(MMC) for uploading or down-
loading parameter settings
PTC/KTY84 interface for motor
temperature monitoring
1) The safety functions "Safely limited speed" and "Safe stop 1" are
certified for asynchronous motors without encoders - these safety
functions are not permitted for pull-through loads as in the case of
lifting gear and winders.
2) Valid for industrial control cabinet installation according to NEC Article
409 / UL 508A. Additional information is available in the Internet under:
http://support.automation.siemens.com/ww/view/en/23995621
Ordering data
Order No.
ET 200pro FC frequency converter with integral safety functions 6SL3235-0TE21-1SB0
380 V 480 V 3 AC +10/-10%
47 Hz 63 Hz
Overload:
150% 60 s
200% 3 s
Output:
5 1.1 kW (0 55 C)
1.5 kW (0 45 C)
Dimensional drawings
Grounding point
Clearance required
50
Mounting rail
24
36
279.5
230
Frequency
Converter
Grounding point
62 155
248
ET 200pro FC frequency converter with backplane bus module and mounting rail
5 To accommodate up to 5 bus
modules for
displacement contacts for con-
necting Industrial Ethernet FC
installation cables;
Length 483 mm 6ES7 195-1GA00-0XA0 with 90 cable outlet
Length 530 mm 6ES7 195-1GF30-0XA0 1 unit 6GK1 901-1BB20-2AA0
SIMATIC S7-300 DIN rail 10 units 6GK1 901-1BB20-2AB0
Length 160 mm 6ES7 390-1AB60-0AA0 50 units 6GK1 901-1BB20-2AE0
Length 480 mm 6ES7 390-1AE80-0AA0 Industrial Ethernet
FastConnect
Length 530 mm 6ES7 390-1AF30-0AA0 installation cables
Length 830 mm 6ES7 390-1AJ30-0AA0 FastConnect standard cable 6XV1 840-2AH10
Length 2,000 mm 6ES7 390-1BC00-0AA0 FastConnect trailing cable 6XV1 840-3AH10
FastConnect marine cable 6XV1 840-4AH10
Industrial Ethernet 6GK1 901-1GA00
Fast Connect Stripping Tool
1) To operate the IM153-4, an MMC is required with at least 64 KB
memory. Cards with higher memory capacity may also be used.
7