User Manual ControlLogix 5580
User Manual ControlLogix 5580
Original Instructions
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ControlLogix 5580 Controllers Overview . . . . . . . . . . . . . . . . . . . . . . . . 7
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
ControlLogix System and Minimum Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Controllers ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Configuration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Design a ControlLogix System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
ControlLogix 5580 Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . 15
System, Communication, and Programming Features. . . . . . . . . 15
Direct connection to an EtherNet/IP Network . . . . . . . . . . . . . . 15
Secure Digital (SD) Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 2
Configure Communication Drivers Configure the Ethernet Communication Driver . . . . . . . . . . . . . . . . . 18
on Your Workstation Configure the USB Communication Driver . . . . . . . . . . . . . . . . . . . . . 20
Chapter 3
Start Using the Controller Connect to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Connect to an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . 24
Connect a USB Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Update Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Determine Required Controller Firmware . . . . . . . . . . . . . . . . . . . 30
Obtain Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Use ControlFLASH Software to Update Firmware. . . . . . . . . . . 31
Use AutoFlash to Update Firmware. . . . . . . . . . . . . . . . . . . . . . . . . 34
Create a Logix Designer Application Project. . . . . . . . . . . . . . . . . . . . . 36
Go Online with the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Use a Recent Communications Path . . . . . . . . . . . . . . . . . . . . . . . . 38
Download to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Use the Who Active Dialog Box to Download . . . . . . . . . . . . . . . 39
Use the Controller Status Menu to Download . . . . . . . . . . . . . . . 40
Upload from the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Use the Who Active Dialog Box to Upload . . . . . . . . . . . . . . . . . . 40
Use the Controller Status Menu to Upload . . . . . . . . . . . . . . . . . . 41
Choose the Controller Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . 43
Change the Operation Mode: Mode Switch . . . . . . . . . . . . . . . . . 43
Change the Operation Mode: Logix Designer Application . . . . 45
Load or Store to the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Store to the Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 4
Communication Networks Networks Available. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
EtherNet/IP Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . 58
ControlLogix EtherNet/IP Network Features . . . . . . . . . . . . . . . 58
EtherNet/IP Network Communication Rates . . . . . . . . . . . . . . . 59
ControlLogix EtherNet/IP Communication Modules . . . . . . . . 62
Software for EtherNet/IP Networks . . . . . . . . . . . . . . . . . . . . . . . . 63
Double Data Rate (DDR) Backplane Communication . . . . . . . 63
ControlNet Network Communication . . . . . . . . . . . . . . . . . . . . . . . . . 64
ControlLogix ControlNet Module Features . . . . . . . . . . . . . . . . . 65
ControlLogix ControlNet Modules . . . . . . . . . . . . . . . . . . . . . . . . . 65
Software for ControlNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . 65
DeviceNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . 66
ControlLogix DeviceNet Module Features . . . . . . . . . . . . . . . . . . 66
ControlLogix DeviceNet Bridge Module and Linking Devices 67
Software for DeviceNet Networks . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Connections Over DeviceNet Networks . . . . . . . . . . . . . . . . . . . . 67
ControlLogix DeviceNet Module Memory . . . . . . . . . . . . . . . . . . 67
Data Highway Plus (DH+) Network Communication . . . . . . . . . . . 68
Communicate Over a DH+ Network . . . . . . . . . . . . . . . . . . . . . . . 69
Universal Remote I/O (RIO) Communication . . . . . . . . . . . . . . . . . . 70
Communicate Over a Universal Remote I/O Network . . . . . . . 71
Foundation Fieldbus Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 72
HART Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Chapter 5
Manage Controller Connection Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Communication Nodes on an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Devices Included in the Node Count. . . . . . . . . . . . . . . . . . . . . . . . 76
Devices Excluded from the Node Count. . . . . . . . . . . . . . . . . . . . . 77
Controller Communication Interaction with Control Data. . . . . . . 78
Produce and Consume (Interlock) Data. . . . . . . . . . . . . . . . . . . . . . . . . 79
Requested Packet Interval (RPI) of Multicast Tags . . . . . . . . . . . 80
Send and Receive Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Determine Whether to Cache Message Connections . . . . . . . . . 82
Socket Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 6
I/O Modules Selecting ControlLogix
I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Electronic Keying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Add Local I/O to the I/O Configuration . . . . . . . . . . . . . . . . . . . . 85
Remote I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Add Remote I/O to the Ethernet Port on the Controller . . . . . 88
Add Remote I/0 to a Local Communication Module . . . . . . . . . 90
Add to the I/O Configuration While Online . . . . . . . . . . . . . . . . . . . . 94
Modules and Devices that Can be Added While Online . . . . . . 94
Determine When Data is Updated. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Input Data Update Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Output Data Update Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Chapter 7
Develop Applications Elements of a Control Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Task Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Scheduled and Unscheduled Programs . . . . . . . . . . . . . . . . . . . . . 103
Routines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Parameters and Local Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Programming Languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Add-On Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Extended Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Access the Module Object from an Add-On Instruction . . . . . . . . . 109
Create the Add-On Instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Monitoring Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Monitoring I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Determine if I/O Communication Has Timed Out . . . . . . . . . 111
Determine if I/O Communication to a Specific I/O Module has
Timed Out. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Automatic Handling of I/O Module Connection Faults . . . . . 112
Sample Controller Projects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Chapter 8
Develop Motion Applications Motion Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Motion Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Program Motion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Obtain Axis Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Chapter 9
Troubleshoot the Controller Controller Diagnostics with Logix Designer . . . . . . . . . . . . . . . . . . . . 119
Warning Symbol and Controller State Indicators . . . . . . . . . . . 119
I/O Module Properties Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Notification in the Tag Editor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Enable Major Fault on Controller. . . . . . . . . . . . . . . . . . . . . . . . . . 121
Port Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Advanced Time Sync . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Controller Diagnostics with RSLinx Software . . . . . . . . . . . . . . . . . . 126
General Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Port Diagnostics Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Connection Manager Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
USB Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Controller Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Tasks Webpage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Browse Chassis Webpage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Appendix A
Status Indicators 4-Character Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
General Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Major Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
I/O Fault Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Controller Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
RUN Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
SD Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
OK Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
EtherNet/IP Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Thermal Monitoring and Thermal Fault Behavior . . . . . . . . . . . . . . 146
Appendix B
Security Options Disable the Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Disable the 4-character Status Display. . . . . . . . . . . . . . . . . . . . . . . . . . 149
Disable the 4-character Display Entirely . . . . . . . . . . . . . . . . . . . . 150
Disable a Subset of the 4-character Display Information . . . . . 152
Disable the Controller Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Summary of Changes This manual contains new and updated information as indicated in the
following table.
Topic Page
Updated tables with new maximum number of EtherNet/IP nodes supported in Version 30 or later. 15, 76
Added the 1756-IF16IH module to the list of supported HART devices. 73
ControlLogix 5580 This manual explains how to use standard ControlLogix 5580 controllers.
Controllers Overview Table 1 - ControlLogix Catalog Numbers
Cat. No.(1)
1756-L81E, 1756-L82E, 1756-L83E, 1756-L84E, 1756-L85E
(1) Catalog numbers followed by a K indicate a conformal coating option.
Before You Begin Before you begin using your ControlLogix controller, verify that you have the
applications that are required to configure and program the controller.
Required Software
Use Table 2 to identify the minimum software versions that are required to use
your ControlLogix controller.
Table 2 - Required Software for Controller Use
Cat. No. Studio 5000 Logix Designer RSLinx Classic ControlFLASH
1756-L81E Version 29.00.00 or later Version 3.80 or later Version 13.00.00 or later
1756-L82E Version 29.00.00 or later Version 3.80 or later Version 13.00.00 or later
1756-L83E Version 28.00.00 or later Version 3.80 or later Version 13.00.00 or later
1756-L84E Version 29.00.00 or later Version 3.80 or later Version 13.00.00 or later
1756-L85E Version 28.00.00 or later Version 3.80 or later Version 13.00.00 or later
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Notes:
This chapter describes features and functions that are associated with the
ControlLogix 5580 controllers.
Topic Page
Minimum Requirements 11
ControlLogix System 11
Design a ControlLogix System 14
ControlLogix 5580 Controller Features 15
ControlLogix System The ControlLogix system is chassis-based, which provides options for
configuring a variety of communications and I/O capabilities. The controller
supports multiple programming languages that enable sequential, process,
motion, and drive control.
Configuration Options
This section describes some of the many system configuration options that are
available with ControlLogix controllers.
Logix5585 TM
DC INPUT DC INPUT AC OUTPUT
SAFETY ON
NET
0000 LINK
RUN FORCE SD OK
For some applications, you can use multiple controllers in one ControlLogix
chassis. The following example shows a ControlLogix 5580 controller
connecting directly to the EtherNet/IP Network, and a ControlLogix 5570
controller connecting to the network through a 1756-EN2TR module.
LINK LINK
REM REM
5069-AEN2TR
RUN PROG RUN PROG
1
5069 Compact I/O
PanelView Plus 7 2
COMPACT I/O
Stratix 5410
100 Mbps 1 Gbps 1 2 3 4 5
13 14 15 16 17 18 19 20 21 22 23 24 27 28
6 7 8 9 10 11 12 25 26
Disp.
Mode
1 4 5 10/100/1000 PoE+ 8 9 12
IN
OUT
IN
OUT
TOD
EIP Mod
EIP Net
Setup
GPS
TimeCD
1
2
Out
2
Speed
Duplex
PRP
DLR
PoE
Stratix 5700
At Reference
6 0 . 00 Hz
PowerFlex 755
480V 4.2A
AUTO
F
STS
ENET
LINK
100 Mbps
20G . . . B4P2
00
Mod Mod Mod
ESC REF PAR# TEXT Net Net Net
5700 5700 5700
8
7 9
4 5 6
1 3
2
0
755
Kinetix 5700
CAUTION
HOT surfaces can cause severe burns
002 1734-AENTR
POINT I O
Module
Status
Network
Activity
PowerFlex 755
Network
Status
Point Bus
Link 1 Status
Activity/
Status System
Power
Field
Power
IP ADDRESS
1734-AENTR
Link 2
Activity/
Status
1734 POINT I/O
1756-EN2TR
1756-CN2R
1756-EN2T
1756-IF8H
1756-L85E
1756-DNB
HART
DeviceNet
PowerFlex Drive
ControlNet
Ethernet Device-level
Ring Network
POINT I/O
Design a ControlLogix System When you design a ControlLogix system, there are several system components
to consider for your application:
I/O devices
Motion control axes and drives
Communication modules
Controllers
Chassis
Power supplies
Studio 5000 Logix Designer Application
For more information to design and select components for your ControlLogix
system, see:
1756 ControlLogix Controllers Technical Data,
publication 1756-TD001
1756 ControlLogix I/O Specifications Technical Data,
publication 1756-TD002
5069 I/O Modules Specifications Technical Data,
publication 5069-TD001
See the Additional Resources section in the preface for more information if
you are designing your ControlLogix System for any of the following
applications:
Motion with Integrated Motion on the EtherNet/IP network
Motion with the use of a coordinate system
ControlLogix 5580 Controller The ControlLogix 5580 controllers are part of the Logix5000 family of
controllers. The sections that follow describe these features of the controllers.
Features
Topic Page
System, Communication, and Programming Features 15
Direct connection to an EtherNet/IP Network 15
Secure Digital (SD) Card 16
We recommend that you use the SD card available from Rockwell Automation
(catalog number 1784-SD2). While other SD cards can be used with the
controller, Rockwell Automation has not tested the use of those cards with the
controller and you could experience data corruption or loss.
SD cards that are not provided by Rockwell Automation can have different
industrial, environmental, and certification ratings as those cards that are
available from Rockwell Automation. These cards can have difficulty with
survival in the same industrial environments as the industrially rated versions
available from Rockwell Automation.
Before you can connect to the controller through the EtherNet/IP or USB
port, you must configure the EtherNet/IP or USB driver in RSLinx software
on your workstation.
Topic Page
Configure the Ethernet Communication Driver 18
Configure the USB Communication Driver 20
Configure the Ethernet Before you add a driver, confirm that these conditions exist:
Communication Driver The workstation is properly connected to the Ethernet network.
TIP To view devices on another subnet or VLAN from the workstation running
RSLinx software, click Browse Remote Subnet.
Configure the USB To configure RSLinx software to use a USB port, you must first configure a
USB driver.
Communication Driver
To configure a USB driver, perform this procedure.
2. Click any of the Windows Update connection options and click Next.
TIP If the software for the USB driver is not found and the installation is canceled, verify
that you have installed RSLinx Classic software, version 3.80 or later.
Your controller appears under two drivers, a virtual chassis and the USB port.
You can use either driver to browse to your controller.
Notes:
Topic Page
Connect to the Controller 23
Update Controller Firmware 30
Create a Logix Designer Application Project 36
Go Online with the Controller 37
Download to the Controller 39
Upload from the Controller 40
Choose the Controller Operation Mode 43
Load or Store to the Memory Card 46
Reset Button 52
Disable the Ethernet Port 55
Connect to the Controller Before you can begin using your controller, you must make a connection to the
controller. Make sure you have already configured the EtherNet/IP or
USB communication drivers (see Configure Communication Drivers on Your
Workstation on page 17)
The controller has an Ethernet port that supports 10 Mbps, 100 Mbps,
or 1 Gbps. See Connect to an EtherNet/IP Network on page 24.
The controller has a USB port that uses a Type B receptacle. The port is
USB 2.0 compatible and runs at 12 Mbps. See Connect a USB Cable on
page 29.
For information on how to select the proper cable, see Guidance for Selecting
Cables for EtherNet/IP Networks, publication ENET-WP007-EN-P.
If you use DNS addressing, or reference the controller via host name in MSG
instructions, define these parameters.
Table 2 - EtherNet/IP Network Parameters for DNS Addressing
EtherNet/IP Network Parameter Description
Host name A host name is part of a text address that identifies the host for a module. The full text address of a module is
host_name.domain_name.
Domain name A domain name is part of a text address that identifies the domain in which the module resides. The full text address of a module is
host_name.domain_name. The domain name has a 48-character limit.
If you specify a DNS server, you must type a domain name. Also, if you send email from the module, some mail relay servers require a
domain name during the initial handshake of the SMTP session.
Primary DNS server address An address that an identifies any DNS servers that are used in the network. You must have a DNS server if you specified a domain name
or a host name in the module configuration. The DNS server converts the domain name or host name to an IP address that is used by the
Secondary DNS server address network.
For more information on DNS addressing, see page 28.
The BOOTP/DHCP server is a standalone server that you can use to set an IP
address. When used, the BOOTP/DHCP server sets an IP address and other
Transport Control Protocol (TCP) parameters.
IMPORTANT Before you start the BOOTP/DHCP server, make sure that you have the
module hardware (MAC) address. The hardware address is on a label on the
side of the controller, and uses an address in a format similar to the
following:
00-00-BC-14-55-35
6. Click OK.
7. To assign this configuration to the module, wait for the module to
appear in the Relation List panel and select it.
8. Click Disable BOOTP/DHCP.
The module now uses the assigned configuration and does not issue a
BOOTP or DHCP request.
IMPORTANT If you do not click Disable BOOTP/DHCP, then on a power cycle the host clears
the current IP configuration and begins sending DHCP requests again.
The controller verifies that its IP address does not match any other network
device IP address when you perform either of these tasks:
If the controller IP address matches that of another device on the network, the
controller EtherNet/IP port transitions to Conflict mode. In Conflict mode,
these conditions exist:
When two devices on a network have IP addresses that conflict, the resolution
depends on the conditions in which the duplication is detected. This table
describes how duplicate IP addresses are resolved.
DNS Addressing
You can also use DNS addressing to specify a host name for a controller, a
domain name, and DNS servers. DNS addressing makes it possible to
configure similar network structures and IP address sequences under different
domains.
DNS addressing is necessary only if you refer to the controller by host name,
such as in path descriptions in MSG instructions.
In the DNS server, the host name must match the IP address of the
controller.
4. In the Logix Designer application, add the controller to the I/O
configuration tree.
IMPORTANT If a child module resides in the same domain as its parent module, type the
host name. If the domain of the child module differs from the domain of its
parent module, type the host name and the domain name
(hostname.domainname)
IMPORTANT You can also use DNS addressing in a module profile in the I/O configuration
tree or in a message path. If the domain name of the destination module
differs from the domain name of the source module, then use a fully qualified
DNS name (hostname.domainname). For example, to send a message from
EN2T1.location1.companyA to EN2T1.location2.companyA, the host names
match, but the domains differ. Without the entry of a fully qualified DNS
name, the module adds the default domain name to the specified host name.
To use the USB port of the controller, you must have RSLinx software
installed on your workstation. Use a USB cable to connect your workstation to
the USB port. With this connection, you can update firmware and download
programs to the controller directly from your workstation.
Logix5
585
0000 NET
LINK
RUN FORC
E SD OK
REM
RUN
PROG
Update Controller Firmware To update controller firmware, use one of these tools:
ControlFLASH software
AutoFlash feature of the Logix Designer application
IMPORTANT The controller must be in Remote Program or Program mode and all major
recoverable faults must be cleared to accept updates.
The firmware major revision level must match the software major version level.
For example, if the controller firmware revision is 28.xxx, you must use the
Logix Designer application, version 28.
IMPORTANT The firmware that is packaged with the software installation is the initial
release of the controller firmware. Subsequent firmware revisions to address
anomalies may be released during a products life.
We recommend that you check the Product Compatibility and Download
Center (PCDC) to determine if later revisions of the controller firmware are
available. For more information, see the next bullet.
ATTENTION: If the Secure Digital Card is locked and set to load on power-up,
then this update may be overwritten by firmware on the SD card.
1. Verify that the network connection is made and the network driver has
been configured in RSLinx software.
2. From the Windows Start Menu, click FLASH Programming Tools >
ControlFLASH.
3. Click Next.
TIP If you experience a Script File Error after selecting the firmware revision number (see the following
example), there is likely a problem with your firmware files.
The progress dialog box indicates the progress of the firmware update.
ControlLogix 5580 controllers indicate progress in updates and blocks.
WARNING: Allow the firmware update to complete before you cycle power
or otherwise interrupt the update.
When the update is complete, the Update Status dialog box indicates
that the update is complete.
To update your controller firmware with the AutoFlash feature, complete these
steps.
ATTENTION: If the Secure Digital Card is locked and set to load on power-up,
then this update may be overwritten by firmware on the SD card.
1. Verify that the network connection is made and your network driver is
configured in RSLinx software.
2. Use the Logix Designer application to create a controller project.
See Create a Logix Designer Application Project on page 36.
3. On the Path bar, click Who Active.
4. On the Who Active dialog box, select your controller under the
communication driver you want to use, and click Update Firmware.
.
Create a Logix Designer To create a Logix Designer application project, follow these steps.
Application Project 1. Start the application.
7. Click Finish.
Go Online with the Controller To go online with the controller, you must first specify a communication path
in the Logix Designer application.
TIP For this section, the USB port was chosen as the communication path. Other paths
through the embedded Ethernet port or via the backplane are also possible.
4. If you want to store the path in the project file, click Set Project Path.
If you store the project path in the project, then you do not have to
choose the path each time you go online.
5. After choosing the communication path, click Go Online in the
Who Active dialog box.
Go Online will use the highlighted node in the Who Active tree,
regardless of the setting for Path in Project. For more information on the
Who Active dialog box, see the Logix Designer Online Help.
You can also select a recent communications path and go online or apply it to
your project.
For more information on the Select Recent Communications Path dialog box,
see the Logix Designer Online Help.
Once you have established a communication path, then you can choose Go
Online from the Controller Status menu when you are working in the project.
Download to the Controller When you download a project to the controller, it copies the project from the
Logix Designer application onto the controller. You can download a project in
two ways:
Use the Who Active Dialog Box to Download on page 39
Use the Controller Status Menu to Download on page 40
You can use the features of the Who Active dialog box to download to your
controller after you have set the communication path. Complete these steps to
download to the controller.
After you choose a communication path in the Logix Designer application, you
can use the Controller Status menu to download to the controller. To
download, from the Controller Status menu, choose Download.
TIP After the download completes, the project name appears on the scrolling status
display.
Upload from the Controller When you upload a project from the controller, it copies the project from the
controller to the Logix Designer application. To upload a project, use one of
these methods:
Use the Who Active Dialog Box to Upload, page 40
Use the Controller Status Menu to Upload, page 41
You can use the features of the Who Active dialog box to upload from your
controller after you have set the communication path. Complete these steps to
upload from the controller.
2. On the Connected to Upload dialog box, verify that the project is the
one you want to upload.
3. Click Upload.
For more information on the Connected To upload dialog box, see the Logix
Designer Online Help.
2. On the Connected to Upload dialog box, verify that the project is the
one you want to upload.
3. Click Upload.
For more information on the Connected To upload dialog box, see the Logix
Designer Online Help.
Choose the Controller Use Table 3 as a reference when determining your controller operation mode.
Operation Mode Table 3 - Controller Operation Modes and Meanings
Mode Switch Setting(1) Run Remote Program
Mode set with the Logix Designer application Run Test Program
while online, and the Mode Switch set to
Remote
If you want to: Select one of these modes:
Turn outputs to the state commanded by the logic X X
of the project
Turn outputs to their configured state for Program X X X
mode
Execute (scan) tasks X X X
Change the mode of the controller via the Logix X X X
Designer application
Download a project X X
Schedule a ControlNet network X X
While online, edit the project X X X X
Send messages X X X
Send and receive data in response to a message X X X X X
from another controller
Produce and consume tags X X X X X
(1) Moving the mode switch from Run to Remote leaves the controller in the Remote Run mode, while moving the switch from
Program to Remote leaves the controller in the Remote Program mode. You cannot choose Remote Test mode by the mode
switch alone, it is only available via the Logix Designer application.
To change the operation mode, use the mode switch. The controller mode
switch provides a mechanical means to enhance controller and control system
security. You must physically move the mode switch on the controller to
change its operating mode from RUN, to REM, or to PROG. When the mode
switch on the controller is set to RUN mode, features like online editing,
program downloads, and firmware updates are prohibited. See Table 3 for a
complete list of prohibited features.
IMPORTANT During runtime, we recommend that you place the controller mode switch in
RUN mode and remove the key (if applicable) from the switch. This can help
discourage unauthorized access to the controller or potential tampering
with the program of the controller, configuration, or device firmware. Place
the mode switch in REM or PROG mode during controller commissioning and
maintenance and whenever temporary access is necessary to change the
program, configuration, or firmware of the product.
The mode switch on the front of the controller can be used to change the
controller to one of these modes:
Run (RUN)
Remote (REM)
Program (PROG)
Mode Switch
RUN Run modeThe controller is actively controlling the process/machine. Projects cannot Run mode is used only when all conditions are safe.
be edited in the Logix Designer application when in Run mode.
REM Remote Run modeThis mode is identical to Run mode except you can edit the You are able to modify a project file online in Remote Run
project online, and change the controller mode through the Logix Designer application. mode.
Be sure to control outputs with care to avoid injury to
personnel and damage to equipment.
Remote Program modeThis mode functions like Program mode, except you can Outputs are commanded to their Program mode state,
change the controller mode through the Logix Designer application. which can cause a dangerous situation.
Remote Test modeThis controller mode executes code, but I/O is not controlled. You
can edit the project online, and change the controller mode through the Logix Designer
application.
Output modules are commanded to their Program mode state (on, off, or hold).
PROG Program modeThis controller mode does not execute code or control I/O, but Do not use Program mode as an emergency stop (E-stop).
editing operations are available. Program mode is not a safety device.
Output modules are commanded to their Program mode state (On, Off, or Hold). Outputs are commanded to their Program mode state,
In this position, controller modes cannot be changed through the Logix Designer which can cause a dangerous situation.
application.
When you are online with the controller, and the controller mode switch is set
to Remote (REM or the center position), then you can use Logix Designer to
change the operation mode.
The Controller Status menu in the upper-left corner of the application window
lets you specify these operation modes:
Remote Program
Remote Run
Remote Test
TIP For this example, the controller mode switch is set to Remote mode. If your
controller mode switch is set to Run or Program modes, the menu options change.
Load or Store to the The memory card that is compatible with your ControlLogix controller is used
to load or store the contents of user memory for the controller.
Memory Card
After you are online with the controller and have changed the controller to
Program or Remote Program mode, complete these steps to store a project to
the memory card.
The following table describes the Load Image options that you can
choose for the project.
If you want the image (project) to load when Then choose Menu Items
Power to the controller is applied or cycled On Power Up
The controller has lost the project and power has been cycled or applied On Uninitialized Memory
Initiated via the Logix Designer application User Initiated
IMPORTANT If the SD card is locked and the Load Image option of the project is set to On
Power Up, then the controller firmware is not updated as a result of a firmware
update. The previously stored firmware and project are loaded instead.
This table shows what happens at power up when you insert an SD card
that contains an image into a ControlLogix 5580 controller.
Image Setting Controller is in out-of-box condition Firmware > 1.x and internal non-volatile Firmware > 1.x and internal non-volatile
(v1.x firmware) memory is not valid(2) memory is valid(2)
User Initiated Loads Firmware Only(1) Does Nothing Does Nothing
On Power Up Loads both Firmware and Application Loads Firmware if there is a revision mismatch Loads Firmware if there is a revision mismatch
Loads Application Loads Application
On Uninitialized Memory Loads both Firmware and Application(1) Loads Firmware if there is a revision mismatch Does Nothing
Loads Application
(1) Indicates change in behavior from ControlLogix 5570 and older controllers.
(2) Valid includes th No Project condition.
This table describes the Load Mode options that you can choose for the
project.
If you want the controller to go to this mode after loading Then choose Menu Items
Program Program (remote only)
Run Run (remote only)
This table describes the Automatic Firmware Update options that you
can choose for the project.
Enable and Store Files to Image Enables automatic firmware updates for I/O devices in the configuration tree of
the controller. Saves I/O device firmware and controller firmware to the image.
I/O devices must be configured to use Exact Match Keying.(1)
Disable and Delete Files to Image Disables automatic firmware updates for I/O devices in the configuration tree of
the controller. Removes I/O device firmware from the image, but does not
remove controller firmware from image.This item only appears in the menu on
subsequent saves of the image.
(1) The devices that are used with this option must support the revision of firmware being updated to.
7. Click Store.
8. Click Yes in the confirmation dialog box that appears.
IMPORTANT Allow the store to complete without interruption. If you interrupt the store,
data corruption or loss can occur.
After you have set the communication path, are online with the controller, and
have changed the controller to Program mode, you can load a project to the
controller from the memory card.
This table shows what happens at power up when you insert an SD card
that contains an image into a ControlLogix 5580 controller.
Image Setting Controller is in out-of-box condition Firmware > 1.x and internal non-volatile Firmware > 1.x and internal non-volatile
(v1.x firmware) memory is not valid(2) memory is valid(2)
User Initiated Loads Firmware Only(1) Does Nothing Does Nothing
On Power Up Loads both Firmware and Application Loads Firmware if there is a revision mismatch Loads Firmware if there is a revision mismatch
Loads Application Loads Application
On Uninitialized Memory Loads both Firmware and Application(1) Loads Firmware if there is a revision mismatch Does Nothing
Loads Application
(1) Indicates change in behavior from ControlLogix 5570 and older controllers.
(2) Valid includes th No Project condition.
To load a project to the controller from the memory card, complete these steps.
1. Open the Controller Properties and click the Nonvolatile Memory tab.
2. On the Nonvolatile Memory tab, verify that the project listed next to
Name: is the project that you want to load.
TIP If no project is stored on the memory card, a message in the lower-left corner of
the Nonvolatile Memory tab indicates that an image (or project) is not available
as shown here.
TIP For information on how to change the project that is available to load from
nonvolatile memory, see the Logix5000 Controllers Nonvolatile Memory
Programming Manual, publication 1756-PM017.
3. Click Load/Store.
4. Click Load.
IMPORTANT Allow the load to complete without interruption. If you interrupt the load,
data corruption or loss can occur.
Other tasks that you can complete by using the memory cards of the controller
include the following:
Change the image that is loaded from the card
Check for a load that was completed
Clear an image from the memory card
Store an empty image
Change load parameters
Read/write application data to the card
For more information to complete any of these tasks, see the Logix5000
Controllers Memory Card Programming Manual, publication 1756-PM017.
Reset Button You can reset the controller with the reset button. The controller reset button
is only read during a controller power-up or restart. If you press the reset button
at another time, it has no effect.
IMPORTANT Since port enable/disable status is associated with the application program,
the Ethernet port becomes enabled after a Stage 1 or Stage 2 reset.
WARNING: When you press the reset button while power is on, an Electric
Arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
0000
Reset Button
Stage 1 Reset
If you release the reset button before Project Cleared scrolls across the display,
then the controller continues with powerup and does not reset.
Stage 2 Reset
Disable the Ethernet Port You can disable the embedded Ethernet port on the controller.
If you are offline, then the change takes effect when you download
the program to the controller.
5. On the Port Configuration tab, click OK.
Notes:
Communication Networks
Topic Page
Networks Available 57
EtherNet/IP Network Communication 58
ControlNet Network Communication 64
DeviceNet Network Communication 66
Data Highway Plus (DH+) Network Communication 68
Universal Remote I/O (RIO) Communication 70
Foundation Fieldbus Communication 72
HART Communication 73
Networks Available Table 4 describes typical application features that are used with ControlLogix
systems, and lists the networks available to support such application features.
Table 4 - Applications and Supported Networks
Application Features Supported Networks
Integrated Motion EtherNet/IP
Time synchronization EtherNet/IP
Control of distributed I/O EtherNet/IP
ControlNet
DeviceNet
Foundation Fieldbus
HART
Universal remote I/O
Produce/consume data between controllers EtherNet/IP
ControlNet
Messaging to and from other devices, including access to EtherNet/IP
the controller via Logix Designer application ControlNet
DeviceNet (only to devices)
Data Highway Plus (DH+)
DH-485
EtherNet/IP Network The EtherNet/IP network offers a full suite of control, configuration, and data
collection services by layering the Common Industrial Protocol (CIP) over the
Communication standard Internet protocols, such as TCP/IP and UDP. This combination of
well-accepted standards provides the capability that is required to support
information data exchange and control applications.
When you design a ControlLogix 5580 system and consider using the 1 Gbps
rate on the controller, remember the following:
You can use the 1 Gbps network communication rate on the controller
port when all network devices support 1 Gbps, for example,
5069-AEN2TR adapters with 5069 Compact I/O modules.
When you use the 1 Gbps network communication rate, configure the
controller ports to use Auto Negotiate.
NET
0000 LINK
RUN FORCE SD OK
5069-AEN2TR Adapter
1 Gbps 5069 Compact I/O Modules
5069-AEN2TR Adapter
5069 Compact I/O Modules
1 Gbps
1 Gbps
1 Gbps
You can use the 1 Gbps network communication rate on the controller
port when some network devices support a maximum network
communication rate of 100 Mbps. However, in this case, the controller
must be connected to those devices through a managed switch.
1 Gbps
1 Gbps
100 Mbps
PanelView Plus 7
Terminal 100 Mbps
5069-AEN2TR Adapter
5069 Compact I/O Modules
IMPORTANT Do not use different network communication rates on device ports in the
same EtherNet/IP network without a managed switch.
Workstation
1756-L85E
1756 I/O
Remote I/O
1756-EN2T
CompactLogix
100 Mbps
Table 6 lists software that is used with the EtherNet/IP networks and modules.
.
The ControlLogix 5580 controller provides double data rate capabilities across
the ControlLogix backplane.
The following communication modules support DDR when used with the
ControlLogix 5580 controller. Minimum series are indicated as follows:
1756-EN2T/C
1756-EN2TR/B
1756-EN2TF/B
1756-EN2TXT/C
1756-EN3TR/A
For efficient DDR communication, make sure that all modules in the
communication path are DDR modules.
If the chassis has a mix of DDR and non-DDR modules, then the DDR
communication occurs between the modules that support it. Communication
between the non-DDR modules in the chassis occurs at the non-DDR rate.
When multicast communication is used within a chassis that has a mix of DDR
and non-DDR modules, then the transmission rate is limited to the slowest
moduleor at the non-DDR rate.
ControlNet Network The ControlNet network is a real-time control network that provides high-
speed transport of time-critical I/O and interlocking data and messaging data.
Communication This includes the upload and download of program and configuration data on
one physical-media link.
In the example in Figure 10, these actions occur via the ControlNet network:
The controllers produce and consume tags.
The controllers initiate MSG instructions that do the following:
Send and receive data.
Configure devices.
The workstation is used to do the following:
Configure the ControlNet devices and the ControlNet network.
Download and upload projects from the controllers.
Workstation
Logix5585
SAFETY ON
TM
DC INPUT DC INPUT AC OUTPUT
1756-L85E
1756-CN2
NET
0000 LINK
RUN FORCE SD OK
1756 I/O
ControlNet
1794-ACN15
1794 I/O
PanelView
1734-ACNR
1734 I/O
Table 8 lists software that is used with the ControlNet networks and modules.
DeviceNet Network The DeviceNet network uses the Common Industrial Protocol (CIP) to
provide the control, configuration, and data collection capabilities for
Communication industrial devices. The DeviceNet network uses the proven Controller Area
Network (CAN) technology, which lowers installation costs and decreases
installation time and costly downtime.
Logix5585 TM
DC INPUT DC INPUT AC OUTPUT
SAFETY ON
Logix5585 TM
DC INPUT DC INPUT AC OUTPUT
NET
0000 SAFETY ON
LINK
NET
0000
RUN FORCE SD OK
LINK
1756-L85E
RUN FORCE SD OK
EtherNet/IP Network
CompactLogix
FLEX I/O 1788-EN2DNR
DeviceNet Network
Personal Computer
Sensor
Motor Push Button
Starter Cluster
Input/output Devices
Barcode
Indicator Scanner
PowerFlex Lights
For more information about using DeviceNet modules and devices, see
DeviceNet Modules in Logix5000 Control Systems User Manual, publication
DNET-UM004.
Table 9 lists the available ControlLogix DeviceNet bridge and linking devices
that can be used with the DeviceNet network.
Table 10 lists software that is used with the DeviceNet networks and modules.
Data Highway Plus (DH+) For DH+ network communication, you have two module options for use in
the ControlLogix chassis. Table 11 lists the DH+ modules and capabilities.
Network Communication
Table 11 - DH+ Modules and Capabilities
RIO Module Is used to
1756-DHRIO Function as a remote I/O (RIO) scanner.
Support 32 logical rack connections or 16 block transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.
1756-DHRIOXT Performs the same functions as a1756-DHRIO module.
Operates in extreme environments with -2570 C (-13158 F) temperatures.
EtherNet/IP Network
ControlLogix ControlLogix
For more information to configure and use a DH+ network via the
1756-DHRIO or 1756-DHRIOXT module, see the Data Highway Plus-
Remote I/O Communication Interface Module User Manual, publication
1756-UM514.
Universal Remote I/O (RIO) For universal remote I/O communication, you have three module options for
use in the ControlLogix chassis. Table 12 lists the RIO modules and
Communication capabilities.
Table 12 - RIO Modules and Capabilities
RIO Module Is used to
1756-RIO Function as an RIO scanner and adapter.
Support connections to 32 racks in any combination of rack size or block transfers.
Update data to the ControlLogix controller by using scheduled connections.
1756-DHRIO Function as an RIO scanner.
Support 32 logical rack connections or 16 block transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.
1756-DHRIOXT Performs the same functions as a1756-DHRIO module.
Operates in extreme environments with -25+70 C (-13+158 F) temperatures.
Logix5585
0000
SAFETY ON
TM
NET
LINK
DC INPUT DC INPUT
1771-ASB
RUN FORCE SD OK
1756-L85E
1746-ASB
1756-RIO
PLC-5
1794-ASB
Foundation Fieldbus Foundation Fieldbus is an open interoperable fieldbus that is designed for
process control instrumentation. The Foundation Fieldbus devices that are
Communication described in Table 13 can be connected to the ControlLogix controller via
another network as shown in the following example.
Table 13 - Foundation Fieldbus Devices and Capabilities
Fieldbus Device Is used to
1788-EN2FFR Bridge an EtherNet/IP network to Foundation Fieldbus.
Connect via a low-speed serial (H1) and high-speed Ethernet (HSE) network
connections.
Access devices directly via an OPC server.
1788-CN2FFR Connect via low-speed serial (H1) connections.
Bridge a ControlNet network to a Foundation Fieldbus.
Support redundant ControlNet media.
RSFieldbus Software
1756-L85E
SAFETY ON
NET
0000 LINK
RUN FORCE SD OK
24V DC
1788-EN2FFR Linking Device Power
Supply
Power
Conditioner
For more information about using the Foundation Fieldbus devices available
from Rockwell Automation, see these publications:
HART Communication HART (Highway Addressable Remote Transducer) is an open protocol that is
designed for process control instrumentation.
Device Is used to
1756 analog HART I/O modules: Act as HART master to allow communication with HART field devices.
1756-IF8H Interface directly with field devices (through built-in HART modems), which
1756-IF8IH eliminates the need for external hardware and more wiring.
Provide access to more field device data, including voltage and current
1756-IF16H measurements.
1756-IF16IH Directly connect asset management software to HART devices.
1756-OF8H Support differential wiring for environments where improved noise
1756-OF8IH immunity is needed (input modules).
ProSoft interface Acquire data or control applications with slow update requirements, such as a
MVI56-HART tank farm.
Does not require external hardware to access HART signal.
Does not provide a direct connection to asset management software.
The HART protocol combines digital signals with analog signals to ready the
digital signal for the Process Variable (PV). The HART protocol also provides
diagnostic data from the transmitter.
1756-L85E
NET
0000 LINK
RUN FORCE SD OK
1756-IF8H or
1756-OF8H
For more information about using the HART I/O modules, see the
ControlLogix HART Analog I/O Modules User Manual, publication
1756-UM533.
For more information about the ProSoft HART interface, see the
ProSoft Technologies website at http://www.prosoft-technology.com.
Notes:
Topic Page
Connection Overview 75
Nodes on an EtherNet/IP Network 76
Controller Communication Interaction with Control Data 78
Produce and Consume (Interlock) Data 79
Send and Receive Messages 81
Socket Interface 82
Connections are used when the system contains the following conditions or
activities:
I/O modules, communication modules, and adapter modules are
present in the I/O configuration of the user project.
Produced or Consumed tags are configured in the user project.
Connected Messages are executed in the user application.
External devices, programming terminals, or HMIs communicate with
the controller.
Nodes on an EtherNet/IP When configuring your ControlLogix 5580 control system, you must account
for the number of EtherNet/IP nodes you include in the I/O configuration
Network tree in your project. Table 14 shows the maximum number of EtherNet/IP
nodes supported for the ControlLogix 5580 controllers.
With firmware revision 29 and later, the Ethernet Nodes field on the
Controllers Properties Capacity tab keeps a running count as you add
EtherNet/IP nodes to the I/O configuration tree. See Figure 16 on page 77.
Table 14 - ControlLogix 5580 Controller Maximum Number of Ethernet/IP Nodes Supported
Cat. No. Version 28 Version 29 Version 30 or later
1756-L81E 60 100
1756-L82E 80 175
1756-L83E 100 100 250
1756-L84E 150 250
1756-L85E 300 300 300
IMPORTANT EtherNet/IP communication modules in the local chassis with the controller
do not count as nodes, but EtherNet/IP devices connected to the
communication modules do count as nodes. See Figure 16 on page 77.
Any EtherNet/IP devices that you add to the I/O configuration section are
counted toward the controller node limits. The following are examples of
devices that must be counted:
Remote communication adapters
Remote controllers.
Devices with an embedded EtherNet/IP port, such as I/O modules,
drives, and linking devices
EtherNet/IP devices connected to a communication module in the local
chassis, even though the communication module in the local chassis
does not count as a node. See Figure 16 on page 77.
HMI devices that are included in the I/O configuration section, for
example, PanelView Plus terminals.
Third-party devices that are directly connected to the EtherNet/IP
network.
The following devices are not added to the I/O configuration section in your
project and are not counted among the total number of nodes:
Computer
Communication modules in the local chassis.
HMIs that are not added to the I/O configuration section.
Devices that are the target of MSG Instructions
Standard Ethernet devices with which the controller communicates via a
socket interface
Node
Node
Node
Node
Controller Communication The ControlLogix 5580 controller runs the communications task separately
from the application code. Because the controller runs communications
Interaction with Control Data asynchronously to the application, it is important to make sure
communications delivered to the controller are complete before the
application executes on the newly delivered data. This applies to both data
coming into the controller as well as data going out.
For example, if the HMI is writing a large block of recipe data down to the
controller, it is possible that application code could start executing on that
recipe data before the data is completely written. This action results in half of
the current recipe and half of the last recipe in the application space.
Since the controllers have 32 bit data integrity, this only applies to data
structures larger than 32 bits.
Good programming practice dictates the use of two unique words placed at the
beginning and end of data and validated by the controller to assure the entire
structure has data integrity. This handshake data should change and be
validated by application code every transaction before it is acted on by either
the application code of the controller, or any higher level system reading data
from the controller.
Table 16 shows two data elements added to a structure for data integrity
checking, Start Data, and End Data. Before the controller acts on My_Recipe1
it should validate that the values of Start Data and End Data match. If they do
not, it is likely communications is still in the process of filling the structure.
The same applies to higher level systems that are receiving data from the
controller.
Table 16 - Data Elements
Structure My_Recipe1 My_Recipe2 My_Recipe3
Start Data 101 102 103
Sugar 3 4 8
Flour 4 3 9
Chocolate 2 2 4
Oil 6 7 2
End Data 101 102 103
It is recommended that you perform this test on a buffered copy of the data and
not the actual data element being written to by the communications core.
Using buffered data prevents the risk of data being changed by the
communications core after you have passed the data valid test.
Produce and Consume ControlLogix controllers let you produce (transmit) and consume (receive)
controller-scoped tags. ControlLogix 5580 controllers produce the same
(Interlock) Data standard tag through both the Ethernet port and the backplane, and consumer
counts apply to the total consumers from both ports.
Controller_3
Consumed Tag
Controller_4
Consumed Tag
Tag Definition
Produced tag A tag that a controller makes available for use by other controllers. Multiple controllers
can simultaneously consume (receive) the data. A produced tag sends its data to one or
more consumed tags (consumers) without using logic.
Consumed tag A tag that receives the data of a produced tag. The data type of the consumed tag must
match the data type (including any array dimensions) of the produced tag. The RPI of
the consumed tag determines the period at which the data updates.
For two controllers to share produced or consumed tags, the controllers must
be attached to the same network. You cannot bridge produced and consumed
tags over two networks.
Produced and consumed tags use connections of the controller and the
communication modules being used.
Send and Receive Messages Messages transfer data to other devices, such as other controllers or operator
interfaces. The MSG instruction is a ladder logic output instruction that
asynchronously reads or writes a block of data to or from another module over
the backplane or a network. The size of the instruction depends on the data
types and message command that you program.
Messages use connection resources to send or receive data. Messages can leave
the connection open (cached) or can close the connection when the message is
done transmitting.
Each message uses one connection out of the controller, regardless of how
many devices are in the message path.
Table 19 - Message Types
Message Type Communication Connected Message Message Can Be Cached
Method
CIP data table read or write N/A Configurable Yes(2)
PLC-2, PLC-3, PLC-5, or SLC CIP No No
(all types)
CIP with Source ID No No
DH+ Yes Yes(2)
CIP generic N/A Optional (1) Yes(2)
Block-transfer read or write N/A Yes Yes(2)
(1) You can connect CIP generic messages. However, for most applications we recommend that you leave CIP generic messages
unconnected.
(2) Connected messages that occur more frequently than once every 60 seconds should be cached if possible.
For more information about using messages, see the Logix5000 Controllers
Messages Programming Manual, publication 1756-PM012.
When you configure a MSG instruction, you can choose whether to cache the
connection. Use Table 20 to determine options for caching connections
.
TIP Cached connections transfer data faster than uncached connections. The
ControlLogix 5580 controller can cache 256 messages and trigger 256 messages
simultaneously.
Socket Interface The controller can use socket interfaces to communicate with Ethernet devices
that do not support the EtherNet/IP application protocol. The socket
interface is implemented via the Socket Object. The controller communicates
with the Socket Object via MSG instructions. MSG instructions that
configure and operate the socket interface must be configured as Unconnected,
and use the Message to Self path. To communicate with another device, you
must understand the application protocol of the other device.
I/O Modules
Topic Page
Selecting ControlLogix I/O Modules 83
Local I/O Modules 85
Remote I/O Modules 87
Add to the I/O Configuration While Online 94
Determine When Data is Updated 95
Selecting ControlLogix Rockwell Automation offers many I/O modules for use in ControlLogix 5580
controller systems. For a list of all I/O product lines that are compatible with
I/O Modules the ControlLogix 5580 controllers, see the 1756 ControlLogix Controllers
Technical Data, publication 1756-TD001.
Electronic Keying
Electronic Keying reduces the possibility that you use the wrong device in a
control system. It compares the device that is defined in your project to the
installed device. If keying fails, a fault occurs. These attributes are compared.
Attribute Description
Vendor The device manufacturer.
Device Type The general type of the product, for example, digital I/O module.
Product Code The specific type of the product. The Product Code maps to a catalog number.
Major Revision A number that represents the functional capabilities of a device.
Minor Revision A number that represents behavior changes in the device.
Carefully consider the implications of each keying option when selecting one.
IMPORTANT When you change Electronic Keying parameters online, it interrupts connections to
the device and any devices that are connected through the device. Connections
from other controllers can also be broken.
If an I/O connection to a device is interrupted, the result can be a loss of data.
More Information
Local I/O Modules The ControlLogix chassis that you choose affects how many local I/O modules
you can use. Several ControlLogix chassis sizes are available to suit your
configuration requirements. You can fill the slots of your chassis with any
combination of controllers, communication modules, and I/O modules.
Table 21 lists the available ControlLogix chassis and the number of slots
available with each.
If you have empty slots in your chassis, use the 1756-N2 or 1756-N2XT slot-
filler module.
If you are adding local I/O, add the I/O module to the backplane with the
controller. To add an I/O module to the local chassis, complete these steps.
2. Select the I/O module that you want to add and click OK.
Remote I/O Modules Remote I/O refers to I/O that is not in the local chassis and connects to the
controller via a communication network. There are several families of I/O that
are remote from the controller:
5069 Compact I/O in a remote bank using a 5069-AEN2TR or similar
adapter
1756 I/O in a remote chassis via a Network Bridge Module
Distributed I/O families such as Point or Block I/O
On-machine I/O families such as ArmorPoint or ArmorBlock I/O
The ControlLogix controller supports the use of remote I/O via these
networks:
EtherNet/IP
ControlNet
DeviceNet
Universal remote I/O
For more information about the network configurations that can be used to
connect remote I/O, see Communication Networks on page 57.
Figure 18 - ControlLogix 5580 Controller and Remote I/O on a 1 Gbps EtherNet/IP Network
1756-L85E
1756 I/O
5069-AEN2TR
5069 Compact I/O
5069-AEN2TR
5069 Compact I/O
If you are adding remote I/O, you can add the I/O modules to the Ethernet
port of the controller. To add remote I/O to the I/O Configuration folder in
the Logix Designer application, complete these steps.
7. Select the I/O module that you want to add and click OK.
11. Add any other I/O modules that you are using in the remote chassis.
12. Complete steps 111 until your remote I/O network and I/O modules
are configured.
If you are using local communication modules that are connected to the
controller, then add the I/O modules to the backplane of the communication
module. To add remote I/O to the I/O Configuration tree in the Logix
Designer application, complete these steps.
1. Right-click the backplane of the local chassis, and choose New Module.
3. Click Create.
5. Click OK.
6. Click Close on the Select Module Type dialog box.
7. Right-click the communication network under the communication
module, and choose New Module.
8. Select the communication adapter for the I/O platform that you are
using.
9. Click Create.
10. Specify the module and connection properties according to your
network configuration.
14. Select the I/O module that you want to add, and click Create.
16. Add any other I/O modules that you are using in this bus.
17. Complete steps 116 until your remote I/O network and I/O modules
are configured.
Add to the I/O Configuration With Studio 5000 software version 28 or later, you can add I/O and other
devices to the controller configuration while you are online, and the mode
While Online switch is in either the REM or PROG positions.
The modules and devices you can add while online depends on the version of
the software you are using. Later versions have more modules and devices that
can be added while online.
You can add modules and devices to the local or remote chassis via an
EtherNet/IP network, or via the unscheduled portion of a ControlNet
network.
For information on the number of nodes you can have for an EtherNet/IP
network, see Nodes on an EtherNet/IP Network on page 76.
For more information about adding to the I/O Configuration while online, see
the these publications:
Runtime/On-line Addition of ControlLogix (1756) I/O over
ControlNet and EtherNet/IP White Paper,
publication LOGIX-WP006
Logix5000 Controllers Design Considerations Reference Manual,
publication 1756-RM094
You can add these modules and devices to the ControlLogix 5580 controller
I/O configuration while online with Logix Designer, version 28.00.00 or later.
1756 controllers
1756 ControlNet modules
1756 DeviceNet bridges
1756 EtherNet/IP modules
5069 EtherNet/IP adapters
5069 Compact I/O modules
1756 I/O and specialty modules
1756-DHRIO
1756-DHRIOXT
Determine When Data is ControlLogix controllers update data asynchronously with the execution of
logic. See these flowcharts to determine when a controller, input module, or
Updated bridge sends data:
Input Data Update Flowchart on this page
Output Data Update Flowchart on page 96
Method of Input Data Production Produced tag with data state change events
RTS RPI? No
Yes
Data is sent by the module at the RTS. Data is sent by the module
at the RTS and RPI.
New data can appear in Input tags at any point in the program scan. If
the control logic reads input tag values in multiple locations, do not
assume the data will be unchanged throughout the scan of the logic.
Automatic output
processing of each task.
Method of Output Data Production Type of local module
Data is sent by the Data is sent by the Data is sent by the controller No data sent by automatic Data is sent by the controller
controller triggered controller triggered to the ControlNet module output processing (data sent triggered by the end of task.
by the RPI. by the user program. (sent out on ControlNet at the at RPI).
next scheduled interval).
Develop Applications
Topic Page
Elements of a Control Application 97
Tasks 98
Programs 101
Routines 104
Parameters and Local Tags 105
Programming Languages 106
Add-On Instructions 107
Extended Properties 108
Access the Module Object from an Add-On Instruction 109
Monitoring Controller Status 110
Monitoring I/O Connections 110
Elements of a A control application consists of several elements that require planning for
efficient application execution. Application elements include the following:
Control Application
Tasks
Programs
Routines
Parameters and Local Tags
Add-On Instructions
Task 32
Task 1
Configuration
Status
Fault Routine
Other Routines
Add-On Instruction
Controller (global) Tags I/O Data System-shared Data
Definition
Tasks A Logix5000 controller lets you use multiple tasks to schedule and prioritize
the execution of your programs based on criteria. This multitasking allocates
the processing time of the controller among the operations in your application:
The controller executes only one task at a time.
One task can interrupt the execution of another and take control based
on its priority.
In any given task, multiple programs can be used. However, only one
program executes at a time.
You can display tasks in the Controller or Logical Organizer views, as
necessary.
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Figure 21 - Tasks
Controller Organizer Logical Organizer
Main Task
(continuous)
Main Task
(continuous)
Task 2
(periodic)
Task 2
(periodic)
A task provides scheduling and priority information for a set of one or more
programs. Configure tasks as continuous, periodic, or event by using the Task
Properties dialog box.
A task can have up to 1000 programs, each with its own executable routines
and program-scoped tags. Once a task is triggered (activated), the programs
that are assigned to the task execute in the order in which they are grouped.
Programs can appear only once in the Controller Organizer and multiple tasks
cannot share them.
Task Priority
Each task in the controller has a priority level. The operating system uses the
priority level to determine which task to execute when multiple tasks are
triggered. A higher priority task interrupts any lower priority task. The
continuous task has the lowest priority, and a periodic or event task interrupts
it.
You can configure periodic and event tasks to execute from the lowest priority
of 15 up to the highest priority of 1. Configure the task priority by using the
Task Properties dialog box.
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Program 1
Program Tags
Main Routine and Program
Parameters
Fault Routine
Other Routines
Add-On Instruction
Controller (global) Tags I/O Data System-shared Data
Definition
Figure 25 - Programs
Controller Organizer Logical Organizer
The scheduled programs within a task execute to completion from first to last.
Programs that are not attached to any task show up as unscheduled programs.
Unscheduled programs within a task are downloaded to the controller with the
entire project. The controller verifies unscheduled programs but does not
execute them.
You must schedule a program within a task before the controller can scan the
program. To schedule an unscheduled program, use the
Program/Phase Schedule tab of the Task Properties dialog box.
Each program has a main routine. The main is the first routine to execute when
the controller triggers the associated task and calls the associated program. Use
logic, such as the Jump to Subroutine ( JSR) instruction, to call other routines.
You can also specify an optional program fault routine. The controller executes
this routine if it encounters an instruction-execution fault within any of the
routines in the associated program.
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Program 1
Program Tags
and Program
Main Routine
Parameters
Fault Routine
Other Routines
Figure 28 - Routines
Controller Designer Logical Designer
Routine
Routine
Routine Routine
Parameters and Local Tags With a Logix5000 controller, you use a tag (alphanumeric name) to address
data (variables). In Logix5000 controllers, there is no fixed, numeric format.
The tag name identifies the data and lets you do the following:
Organize your data to mirror your machinery.
Document your application as you develop it.
This example shows data tags that are created within the scope of the Main
Program of the controller.
Integer Value
Storage Bit
Counter
Timer
Digital I/O Device
There are several guidelines for creating and configuring parameters and local
tags for optimal task and program execution. For more information, see the
Logix5000 Controllers and I/O Tag Data Programming Manual, publication
1756-PM004.
Programming Languages The Studio 5000 Logix Designer application supports these programming
languages.
Table 23 - ControlLogix Controller Programming Languages
Language Is best used in programs with
Ladder Diagram (LD) Continuous or parallel execution of multiple operations (not sequenced)
Boolean or bit-based operations
Complex logical operations
Message and communication processing
Machine interlocking
Operations that service or maintenance personnel have to interpret to
troubleshoot the machine or process
Function Block Diagram (FBD) Continuous process and drive control
Loop control
Calculations in circuit flow
Sequential Function Chart (SFC) High-level management of multiple operations
Repetitive sequence of operations
Batch process
Motion control that uses structured text
State machine operations
Structured Text (ST) Complex mathematical operations
Specialized array or table loop processing
ASCII string handling or protocol processing
Add-On Instructions With the Logix Designer application, you can design and configure sets of
commonly used instructions to increase project consistency. Similar to the
built-in instructions that are contained in Logix5000 controllers, these
instructions you create are called Add-On Instructions. Add-On Instructions
reuse common control algorithms. With them, you can do the following:
Ease maintenance by creating logic for one instance.
Apply source protection to help protect intellectual property.
Reduce documentation development time.
You can use Add-On Instructions across multiple projects. You can define your
instructions, obtain them from somebody else, or copy them from another
project.
Instruction Toolbar
Extended Properties The Extended Properties feature lets you define more information, such as
limits, engineering units, or state identifiers for various components within
your controller project.
Use the .@Min and .@Max syntax to define tags that have limits, as there is no
indication in the tag browser that limit extended properties are defined for a
tag. If you try to use extended properties that have not been defined for a tag,
the editors show a visual indication and the routine does not verify. Visual
indicators include:
A rung error in Ladder Logic.
A verification error X in Function Block Diagrams.
The error underlined in Structured Text.
You can access limit extended properties that are defined on tags by using the
.@Min and .@Max syntax. However, you cannot write to extended properties
values in logic.
Access the Module Object The MODULE object provides status information about a module. To select a
particular module object, set the Object Name operand of the GSV/SSV
from an Add-On Instruction instruction to the module name. The specified module must be present in the
I/O Configuration section of the controller organizer and must have a device
name.
With the Logix Designer application, you can access a MODULE object
directly from an Add-On Instruction.
You must create a Module Reference parameter when you define the Add-On
Instruction to access the MODULE object data. A Module Reference
parameter is an InOut parameter of the MODULE data type that points to the
MODULE Object of a hardware module. You can use module reference
parameters in both Add-On Instruction logic and program logic.
For more information on the Module Reference parameter, see the Logix
Designer application online help and the Logix5000 Controllers Add-On
Instructions Programming Manual, publication 1756-PM010.
Monitoring Controller Status The ControlLogix controller uses Get System Value (GSV) and Set System
Value (SSV) instructions to get and set (change) controller data. The controller
stores system data in objects. There is no status file, as in the PLC-5 processor.
The GSV instruction retrieves the specified information and places it in the
destination. The SSV instruction sets the specified attribute with data from the
source. Both instructions are available from the Input/Output tab of the
Instruction toolbar.
Figure 31 - GSV and SSV Instructions for Monitoring and Setting Attributes
When you add a GSV/SSV instruction to the program, the object classes,
object names, and attribute names for the instruction are shown. For the GSV
instruction, you can get values for the available attributes. For the SSV
instruction, only the attributes you can set are shown.
Some object types appear repeatedly, so you have to specify the object name.
For example, there can be several tasks in your application. Each task has its
own Task object that you access by the task name.
The GSV and SSV instructions monitor and set many objects and attributes.
See the online help for the GSV and SSV instructions.
Monitoring I/O Connections If communication with a device in the I/O configuration of the controller does
not occur in an application-specific period, the communication times out and
the controller produces warnings.
For more information on how to determine the time for your application,
search the Rockwell Automation Knowledgebase for answer ID 38535. The
document is available at http://www.rockwellautomation.com/
knowledgebase.
I/O Fault status information scrolls across the 4-character status display
of the controller.
A shows over the I/O configuration folder and over the devices
that have timed out.
A module fault code is produced, which you can access via the
following:
The Module Properties dialog box
A GSV instruction
For more information about I/O faults, see the Logix5000 Controllers Major,
Minor, and I/O Faults Programming Manual, publication 1756-PM014.
The GSV instruction gets the status of the I/O status indicator (via the
LEDStatus attribute of the Module object) and stores it in the
IO_LED tag.
IO_LED is a DINT tag that stores the status of the I/O status indicator
or status display on the front of the controller.
If IO_LED equals 2, then at least one I/O connection has been lost and
the Fault_Alert is set.
If responding to a failed I/O module connection can wait until the next
program scan, put the logic in a normal routine and use the GSV technique
that is described on page 111 to call the logic.
First, develop a routine in the Controller Fault Handler that can respond to
I/O connection faults. Then, in the Module Properties dialog box of the I/O
module or parent communication module, check Major Fault On Controller If
Connection Fails While in Run Mode.
TIP Detecting the I/O connection loss takes at least 100 milliseconds, even if the Controller
Fault Handler is used.
For more information about programming the Controller Fault Handler, see
the Logix5000 Major, Minor, and I/O Faults Programming Manual,
publication 1756-PM014.
Logix Designer includes sample projects that you can copy and modify to fit
your application. To access the sample projects, choose Open Sample Project in
the Studio 5000 interface and navigate to
Samples > ENU > vXX > Rockwell Automation.
Notes:
Topic Page
Motion Overview 115
Motion Applications 116
Obtain Axis Information 118
Program Motion Control 116
Motion Overview The ControlLogix 5580 controllers support up to 256 axes of integrated
motion. The 256 axes can be any combination of CIP, Virtual, and Consumed
axes. You can add all axes to one Motion Group, and you can assign any
combination of axes to different axis update schedules.
The ControlLogix 5580 controllers do not support Analog or SERCOS
motion.
TIP Rockwell Automation recommends using the built-in EtherNet/IP port for
high-performance motion applications.
You can associate Integrated Motion axes to any appropriate drive, regardless of
whether the communications path to the drive is via the embedded Ethernet
port, or over the 1756 backplane (through an Ethernet bridge such as a
1756-EN2T).
Motion Applications The configuration process varies, depending on your application and your
drive selection.
These are general steps to configure a motion application. See the Integrated
Motion on the Ethernet I/P Network Configuration and Startup User
Manual, publication MOTION-UM003 for more information.
Program Motion Control The controller provides a set of motion control instructions for your axes:
The controller uses these instructions just like the rest of the Logix5000
instructions.
Each motion instruction works on one or more axes.
Each motion instruction needs a motion control tag. The tag uses a
MOTION_INSTRUCTION data type and stores the information
status of the instruction.
You can program by using motion control instructions in these
programming languages:
Ladder Diagram (LD)
Structured Text (ST)
Sequential Function Chart (SFC)
ATTENTION: Use each motion control tag in only one motion instruction.
Unintended operation can result if you reuse the same motion control tag in
other motion instructions, or if you write to any of the motion control tag
elements.
Example
In this example, a simple ladder diagram that homes, jogs, and moves an axis.
If Initialize_Pushbutton = on and the axis = off (My_Axis_X.ServoActionStatus = off) then the MSO instruction turns on the axis.
If Home_Pushbutton = on and the axis hasnt been homed (My_Axis_X.AxisHomedStatus = off) then the MAH instruction homes the axis.
If Jog_Pushbutton = on and the axis = on (My_Axis_X.ServoActionStatus = on) then the MAJ instruction jogs the axis forward at 8 units/second.
If Jog_Pushbutton = off then the MAS instruction stops the axis at 100 units/.second. Make sure that Change Decel is Yes. Otherwise, the axis
decelerates at its maximum speed.
If Move_Command = on and the axis = on (My_Axis_X.ServoActionStatus = on) then the MAM instruction moves the axis. The axis moves to the
position of 10 units at 1 unit/second.
Obtain Axis Information You can obtain axis information by using these methods:
Double-click the axis to open the Axis Properties dialog box.
Use a Get System Value (GSV) or Set System Value (SSV) instruction to
read or change the configuration at runtime.
View the QuickView pane to see the state and faults of an axis.
Use an axis tag for status and faults.
Topic Page
Controller Diagnostics with Logix Designer 119
Controller Diagnostics with RSLinx Software 126
Controller Web Pages 131
Controller Diagnostics with You can use the Controller Properties in Logix Designer to view fault
conditions.
Logix Designer
Warning Symbol and Controller State Indicators
A warning symbol appears in the controller organizer next to the I/O module.
This occurs when there are faults or other conditions in the I/O module, or if
the connection to the I/O module fails while in run mode.
If you have set an I/O module to fault the controller when the
connection fails, then the controller state indicates Faulted and the
controller status displays Controller Fault and is lit solid red. I/O Not
Responding blinks green.
If you have set an I/O module to not fault the controller when the
connection fails, then the controller status displays Controller OK and
is lit solid green. I/O Not Responding blinks green.
Controller Status
I/O Module set to fault controller I/O Module set to not fault controller
The Connection tab shows the module fault. This example shows a
communications fault.
On the Module Info tab, the Status section lists the Major and Minor
Faults along with the Internal State of the module.
The Module Info tab requires successful communications. If
communication to the I/O module is OK, but the module itself is
faulted, then the Module Info tab helps in troubleshooting the fault. If
there is a communication fault, then the Connection Tab would be of
more use.
When you click on the Module Info Tab, a dialog box appears that
shows the module reported general error status and the fault code.
General module faults are also reported in the Tag Editor. Diagnostic faults are
reported only in the tag editor.
To display recent I/O fault information in the Major Faults tab of the
Controller Properties screen, you must first check the Major Fault on
Controller option on the I/O Properties Connection tab.
Port Diagnostics
When your project is online, you can view the status of the embedded Ethernet
port on the controller.
The Port Diagnostics page, displays information for the port. See Table 25 on
page 123 for parameter descriptions.
The Advanced Time Sync dialog displays information that is related to CIP
Sync time synchronization. The information appears only if the project is
online, and Time Synchronization is enabled on the Date/Time tab.
The Advanced Time Sync dialog box opens. See Table 26 on page 125
for parameter descriptions.
Controller Diagnostics with You can also view diagnostic information in RSLinx software.
RSLinx Software 1. From the Communications menu, choose RSWho.
General Tab
The General tab shows device information, and any faults on the controller.
The Port Diagnostics tab shows information for the port. See Table 27 on
page 128 for parameter descriptions.
USB Tab
The USB tab provides the following information about the adapter USB port.
Table 31 - Media Counters provide diagnostic information in the USB driver layer.
Counter Name Description
Rx Byte Counter Total number of bytes received.
Rx Dropped Counter Total number of received bytes dropped.
Tx Byte Counter Total number of bytes sent.
Tx Dropped Bytes Total number of transmit bytes dropped.
FIFO Overflow Total number of FIFO (First in First Out) overflows.
Controller Web Pages The controller provides diagnostic web pages that track controller
performance, network performance, and backplane performance.
To access the diagnostic web pages, open the Diagnostics folder in the left-most
navigation bar, and click the link for each diagnostic web page you need to
monitor.
The Diagnostics web pages provide communications and messaging data for
the controller.
The Advanced diagnostics web pages provide data about the TCP/IP Network
and Precision Time Protocol.
Also see:
Tasks Webpage on page 132
Browse Chassis Webpage on page 133
Tasks Webpage
On the Tasks webpage, the pie chart shows the percentage of the control core's
CPU consumed by the tasks that are on that core. The gauges show the CPU
utilization of the control and communications cores. The table shows the tasks
that are running on the control core (all system tasks are summarized as one
task).
Browse Chassis lets you view module information, backplane statistics, and
connection statistics for modules in the local chassis.
Notes:
Status Indicators
The ControlLogix 5580 controllers have six status indicators and one
four-character scrolling status display.
Topic Page
4-Character Status Display 136
Controller Status Indicators 144
EtherNet/IP Indicators 145
Thermal Monitoring and Thermal Fault Behavior 146
This figure shows the location of the 4-Character status display and status
indicators.
4-Character Scrolling Status Display, see page 136 EtherNet/IP Status Indicators, see page 145
Status Indicators, see page 144
32511-M
4-Character Status Display The ControlLogix 5580 controller 4-character status display scrolls messages
that provide information about the firmware revision, energy storage status,
project status, Ethernet port status, and major faults of the controller.
The messages that are described in Table 32 are typically indicated upon
powerup, powerdown, and while the controller is running to show the status of
the controller.
Table 32 - General Status Messages
Message Interpretation
No message is The controller is Off.
indicated Check the OK indicator to determine if the controller is powered and determine the state
of the controller.
TEST The controller is conducting power-up tests.
CHRG The embedded energy storage circuit is charging.
PASS Power-up tests have been successfully completed.
SavingDo Not The controller is about to save an image to the SD card.
Remove SD Card
SAVE A project is being saved to the SD card. You can also view the SD Indicator (see page 144)
for more status information.
Allow the save to complete before:
Removing the SD card.
Disconnecting the power.
IMPORTANT: Do not remove the SD card while the controller is saving to the SD card.
Allow the save to complete without interruption. If you interrupt the save, data corruption
or loss can occur.
LOAD A project is being loaded from the SD card. You can also view the SD Indicator (see
page 144) for more status information.
Allow the load to complete before doing the following:
Removing the SD card
Disconnecting the power
IMPORTANT: Do not remove the SD card while the controller is loading from the SD card.
Allow the load to complete without interruption. If you interrupt the load, data corruption
or loss can occur.
UPDT A firmware update is being conducted from the SD card upon powerup. You can also view
the SD Indicator (see page 144) for more status information.
If you do not want the firmware to update upon powerup, change the Load Image
property of the controller.
Rev XX.xxx The major and minor revision of the firmware of the controller.
1756-L8XX The controller catalog number and series.
Link Down Message appears when the EtherNet/IP port does not have a connection. Message scrolls
continuously during operation.
Link Disabled Message appears when you have disabled the EtherNet/IP port. Message scrolls
continuously during operation.
DHCP- Message appears when the controller is set for DHCP, but not configured on a network.
00:00:XX:XX:XX:XX The message shows the MAC address of the controller. Message scrolls continuously
during operation if no IP address is set.
Ethernet Port Rate/ The current port rate and duplex state when the EtherNet/IP port has a connection.
Duplex State Message scrolls continuously during operation.
Fault Messages
If the controller displays a fault, these messages can appear on the status display.
Table 33 - Fault Messages
Message Interpretation
Major Fault TXX:CXX message A major fault of Type XX and Code XX has been detected.
For example, if the status display indicates Major Fault T04:C42 Invalid
JMP Target, a JMP instruction is programmed to jump to an invalid LBL
instruction.
For details about major recoverable faults, see the Logix5000 Major,
Minor, and I/O Fault Codes Programming Manual, publication
1756-PM014.
I/O Fault Local:X #XXXX message An I/O fault has occurred on a module in the local chassis. The slot
number and fault code are indicated along with a brief description.
For example, I/O Fault Local:3 #0107 Connection Not Found indicates
that a connection to the local I/O module in slot three is not open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor,
and I/O Fault Codes Programming Manual, publication 1756-PM014.
I/O Fault ModuleName #XXXX message An I/O fault has occurred on a module in a remote chassis. The name of
the faulted module is indicated with the fault code and brief description
of the fault.
For example, I/O Fault My_Module #0107 Connection Not Found
indicates that a connection to the module named My_Module is not
open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor,
and I/O Fault Codes Programming Manual, publication 1756-PM014.
I/O Fault ModuleParent:X #XXXX message An I/O fault has occurred on a module in a remote chassis. The parent
name of the module is indicated because no module name is configured
in the I/O Configuration tree of Logix Designer application. In addition,
the fault code is indicated with a brief description of the fault.
For example, I/O Fault My_CNet:3 #0107 Connection Not Found
indicates that a connection to a module in slot 3 of the chassis with the
communication module named My_CNet is not open.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor,
and I/O Fault Codes Programming Manual, publication 1756-PM014.
X I/O Faults I/O faults are present and X = the number of I/O faults present.
If there are multiple I/O faults, the controller indicates the first fault
reported. As each I/O fault is resolved, the number of indicated faults
decreases and the I/O Fault message indicates the next reported fault.
Take corrective action specific to the type of fault indicated.
For details about each I/O fault code, see the Logix5000 Major, Minor,
and I/O Fault Codes Programming Manual, publication 1756-PM014.
The Major Fault TXX:CXX message on the controller status display indicates
major faults. Table 34 lists fault types, codes, and the associated messages as
they are shown on the status display.
For detailed descriptions and suggested recovery methods for major faults, see
the Logix5000 Major, Minor, and I/O Fault Codes Programming Manual,
publication 1756-PM014.
Table 34 - Major Fault Status Messages
Type Code Message
1 1 Run Mode Powerup
1 60 Nonrecoverable
1 61 Nonrecoverable Diagnostics Saved on SD Card
1 62 Nonrecoverable Diagnostics and Program Saved on SD card
3 16 I/O Connection Failure
3 20 Chassis Failure
3 21
3 23 Connection Failure
4 16 Unknown Instruction
4 20 Invalid Array Subscript
4 21 Control Structure LEN or POS < 0
4 31 Invalid JSR Parameter
4 34 Timer Failure
4 42 Invalid JMP Target
4 82 SFC Jump Back Failure
4 83 Value Out of Range
4 84 Stack Overflow
4 89 Invalid Target Step
4 90 Invalid Instruction
4 91 Invalid Context
4 92 Invalid Action
4 990 User-defined
4 991
4 992
4 993
4 994
4 995
4 996
4 997
4 998
4 999
6 1 Task Watchdog Expired
The first part of the format is used to indicate the location of the module with
a fault. How the location is indicated depends on your I/O configuration and
the properties of the module that are specified in Logix Designer application.
The latter part of the format, #XXXX message, can be used to diagnose the
type of I/O fault and potential corrective actions. For details about each I/O
fault code, see the Logix5000 Major, Minor, and I/O Fault Codes
Programming Manual, publication 1756-PM014.
Table 35 - I/O Fault Messages
Code Message
#0001 Connection Failure
#0002 Insufficient Resource
#0003 Invalid Value
#0004 IOI Syntax
#0005 Destination Unknown
#0006 Partial Data Transferred
#0007 Connection Lost
#0008 Service Unsupported
#0009 Invalid Attribute Value
#000A Attribute List Error
#000B State Already Exists
#000C Object Mode Conflict
#000D Object Already Exists
#000E Attribute Not Settable
#000F Permission Denied
#0010 Device State Conflict
#0011 Reply Too Large
Controller Status Indicators The status indicators are below the status display on the controller. They
indicate the state of the controller as described in these tables.
RUN Indicator
The RUN indicator shows the current mode of the controller. To change the
controller mode, you can use the keyswitch on the front of the controller or the
Controller Status menu in the Logix Designer application.
FORCE Indicator
The Force indicator shows if I/O forces are enabled on the controller.
SD Indicator
OK Indicator
EtherNet/IP Indicators The EtherNet/IP indicators show the state of the EtherNet/IP port and
communications activity.
Thermal Monitoring and The ControlLogix 5580 controllers can monitor internal module
temperatures. The controllers take actions as the temperature increases, as in
Thermal Fault Behavior this graphic.
IMPORTANT If you follow the recommended limits for ambient (inlet) temperature and apply the required clearances
around the chassis, the controller should not reach the initial warning (minor fault) temperature.
See the 1756 ControlLogix Controllers Technical Data, publication 1756-TD001.
IMPORTANT The presence of any temperature warning indicates that measures need be taken to reduce the ambient temperature of
the module.
Instructions for using relay ladder logic to check for a minor fault can be found in the Logix5000 Controllers Major,
Minor, and I/O Faults Programming Manual, publication 1756-PM014.
A GSV instruction can be used to read the MinorFaultBits attribute of the FaultLog class name. If the Diagnostics minor
fault bit (Bit 17) is set, then a temperature minor fault can be present. Check the Minor Faults tab of the Controller
Properties dialog box in Logix Designer to see if the minor fault is a temperature warning.
Security Options
Topic Page
Disable the Ethernet Port 147
Disable the 4-character Status Display 149
Disable the Controller Web Pages 154
Disable the Ethernet Port You can disable the controller Ethernet port with the Studio 5000 Logix
Designer application, version 28.00.00 or later.
Ethernet ports return to the default setting after one of these actions occur on
the controller:
Stage 1 reset
Stage 2 reset
New project is downloaded - In this case, the settings in the new project
take effect.
Program is cleared from the controller - These examples clear the
program from a controller:
Major non-recoverable fault occurs.
Firmware update occurs.
You must reconfigure the settings to disable an Ethernet port after the port
returns to its default settings.
IMPORTANT You cannot add a MSG instruction to your program if the controller
is in Run mode or if the FactoryTalk Security settings deny this
editing option.
IMPORTANT These values are stored to NVS memory in such a way that the MSG
instruction is not required to be executed each time the controller
powers up.
4. Before you enable the MSG instruction, make sure that the Source
Element tag value is 2.
Disable the 4-character With the Studio 5000 Logix Designer application, version 29.00.00 or later,
you can disable the 4-character status display in these ways:
Status Display
Disable the 4-character Display Entirely
Disable a Subset of the 4-character Display Information
The 4-character status display returns to the default setting after one of these
actions occur on the controller:
Stage 1 reset
Stage 2 reset
New project is downloaded - In this case, the settings in the new project
take effect.
Program is cleared from the controller - these examples can clear the
program from a controller:
Major non-recoverable fault occurs.
Firmware update occurs.
You must reconfigure the settings to disable the controller web page after it
returns to its default settings.
When you disable the 4-character display entirely, this information is no longer
shown:
Project name
Link status
Port status
IP address
4. Before you enable the MSG instruction, make sure that the Source
Element tag value is 1.
You can disable a subset of the information that scrolls across the
ControlLogix 5580 controller. You can disable these subsets:
Project name and link status
Port status and IP address
4. Before you enable the MSG instruction, make sure that the Source
Element uses one of the following tag values, based on what information
that you want to disable:
Project name and link status - Bit 0 of the Source Element = 1
Port status and IP address - Bit 1 of the Source Element = 1
IMPORTANT You can re-enable the subsets of information on the 4-character display
after they are disabled.
To re-enable the subsets, complete the steps that are described in this
section. Before you enable the MSG instructions, however, make sure the
appropriate bit in the Source Element tag value is 0.
Disable the Controller You can disable the ControlLogix 5580 controller web pages with the
Studio 5000 Logix Designer application, version 28.00.00 or later.
Web Pages
Controller web pages return to the default setting after the following occur on
the controller:
Stage 1 reset
Stage 2 reset
New project is downloaded - In this case, the settings in the new project
take effect.
Program is cleared from the controller - The following are examples of
what clears the program from a controller:
Major non-recoverable fault occurs.
Firmware update occurs.
You must reconfigure the settings to disable the controller web page after it
returns to its default settings.
IMPORTANT You cannot add a MSG instruction to your program if the controller
is in Run mode or if the FactoryTalk Security settings deny this
editing option.
Source Length - 5
To enable the controller web page, the last element in the SINT array
for the Source Element must be 1.
Notes:
Numerics A
10/100/1000 23 add
1756-CN2 local I/O 85
uses 65 remote I/O 88, 90
1756-CN2R Add-On Instructions
uses 65 in project 107
1756-CN2RXT application
uses 65 elements 97
1756-CNB networks and 57
uses 65 AutoFlash
1756-CNBR update 34
uses 65 axes
1756-DHRIO 68 consumed 115
communication via 69 virtual 115
uses axis
remote I/O 70 obtain information 118
1756-DHRIOXT
uses 68, 70
1756-DNB B
uses 67 behavior
1756-EN2F thermal fault 146
uses 62 BOOTP/DHCP server
1756-EN2T setting IP network address 25 - 26
uses 62
1756-EN2TR
uses 62 C
1756-EN2TRXT cache
uses 62 message options 82
1756-EN2TSC messages
uses 62 about 81
1756-EN2TXT chassis
uses 62 ControlLogix
1756-EN3TR list 85
uses 62 communication
1756-ENBT allow 78
uses 62 block 78
1756-EWEB Data Highway Plus 68, 69
Foundation Fieldbus 72
uses 62 HART 73
1756-IF8H network options 15
uses 73 path
1756-N2 85 set 37
1756-N2XT 85 universal remote I/O 70
1756-RIO Communication Drivers 17
uses 70 configure
1784-SD1 DHCP server 26
load from 49 motion 115
store to 46 connection
1784-SD2 DeviceNet
load from 49 network 67
store to 46 EtherNet/IP 76
1788-CN2DN message, required 81
uses 67 scheduled
1788-CN2FFR ControlNet 80
unscheduled
uses 72 ControlNet 80
1788-EN2DNR consume
uses 67 data 79
1788-EN2FFR continuous task 100
uses 72 control data 78
F indicator 144
fault FORCE 144
OK 145
cpu temperature 146 SD 144
hardware preservation 146 instruction
recoverable 146
fault code motion 116
integrated motion
use GSV to get 112
fault handler on the EtherNet/IP network 15
IP addresses
execute at I/O fault 112
definition 24
fault messages 138
DHCP server 26
I/O 141 duplicate address detection 27
features 15 duplicate address resolution 27
controller
communication 15
programming 15 L
filler slot
load
slot filler 85
firmware from memory card 49
local
controller 30
I/O
obtain 30
required 30 add 85
remote I/O 85
security certificate, error 32
Logix controller 75
update with AutoFlash, use 34
update with ControlFlash 31 Logix Designer
FORCE indicator 144 change controller operation mode 45
Foundation Fieldbus 72 Logix Designer application
Add-On Instructions 107
program 101
G routine 104
tags 105
gateway 24 tasks 98
general status messages 136
GSV
fault code 112 M
monitor memory
connection 111 DeviceNet module 67
memory card 46
H load from 49
other tasks 51
handshake 78 store project to card 46
HART. See Highway Addressable Remote store to 46
Transducer. message
Highway Addressable Remote Transducer 73 about 81
cache 82
host name 24 determine if 82
fault 138
status display 136
I minimum requirements 11
I/O mode switch 43
connection error 112 change controller operation mode 43
ControlLogix position 44
remote 87 module
selection 83 ControlNet 65
determine data update 95 EtherNet/IP 58
fault codes 141 motion
remote 87
I/O configuration about 115
application 115
add instructions 116
local I/O 85 program 116
remote I/O 88, 90 MVI56-HART
while online 94
uses 73
N project
network Add-On Instructions 107
download 39
application and 57 elements 97
controller options 15 go online 37
ControlNet 64 program 101
Data Highway Plus 69 routine 104
DeviceNet 66 tags 105
DH+. See Data Highway Plus. tasks 98
EtherNet/IP 58 upload 40
Foundation Fieldbus 72
HART 73
universal remote I/O 70 R
network address
receive
DNS addressing 28
network communication rates messages 81
remote
EtherNet/IP 59
on an EtherNet/IP network 59 I/O 87
network parameters remote I/O 68
DNS addressing 24 add 88, 90
domain name 24 ControlLogix
gateway 24 local 85
host name 24 universal 70
IP addresses 24 required
subnet mask 24 connections
nodes on an EtherNet/IP network 76 messages 81
reset button 52
stage 1 reset 53
O stage 2 reset 54
RIO. See universal remote I/O
obtain
routine
axis information 118
firmware 30 in project 104
OK indicator 145 RSLinx software
online controller diagnostics 126
RSWho
add
to I/O configuration 94 set
go 37 path 37
optimize EtherNet/IP network performance
59 S
scheduled
P program 103
script file
path
error 32
set SD card 16
communication 37
periodic task 100 other tasks 51
store to 46
port diagnostics 122
SD indicator 144
with RSLinx software 127
priority Secure Digital (SD) card 16, 46
task 101 load from 49
store project to card 46
produce
security certificate
data 79
produce/consume error 32
security options 147
data 79
program disable the 4-character status display 149
disable the controller web pages 154
in project 101 disable the Ethernet port 147
scheduled 103 selection
unscheduled 103
programming languages 106 I/O 83
send
programming practices 78 messages 81
sercos 115
T
tag
consume 79
in project 105
produce 79
task
continuous 100
event 100
in project 98
periodic 100
priority 101
temperature
limit 146
warning 146
U
universal remote I/O 70
communicate via 71
unscheduled
program 103
update
determine frequency 95
update firmware
AutoFlash, use 34
upload
project 40
USB
communication driver 17, 20
connect cable 29
software required 29
Notes:
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User https://rockwellautomation.custhelp.com/
Forums, and Product Notification Updates.
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Find the Direct Dial Code for your product. Use the code to
Direct Dial Codes route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, ArmorBlock, ArmorPOINT, Block I/O, Compact I/O, CompactLogix, ControlFLASH, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, DriveGuard, FactoryTalk, FLEX, Flex I/O, Integrated Architecture, Kinetix,
Logix5000, Logix Designer, PanelView, PLC-5, POINT I/O, PowerFlex, QuickView, RediSTATION, Rockwell Automation, Rockwell Software, RSFieldbus, RSLinx, RSNetWorx, RSView, Series 9000, SLC, SLC 500, Stratix, Stratix 5400,
Stratix 5700, Studio 5000, Studio 5000 Automation & Engineering Design Environment, and Studio 5000 Logix Designer are trademarks of Rockwell Automation.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400