Line Protection
Line Protection
Serge Beauzile
Chair IEEE FWCS
Ch i Power
Chair P &EEnergy SSociety
i t
[email protected]
June, 10,
June 10 2014
8:30 -12:30
Company Philosophy
Protection engineer preference
System requirements
If eachh device
d i that
th t sensedd a fault
f lt operated
t d
simultaneously, large portions of the system
g
would be de-energized everyy time a fault needed
to be cleared. This is unacceptable.
1
A is the slowest.
.25
25 sec A
0.1 B
For a given current
C
value, the operating
ti
time can be
b found.
f d
D
0.01
10
100
1000
10,000
100,000
3 kA
Current in Amperes
Device B is clearly
0.1
faster for high
A
(>1000 A) fault
B currents,
t but
b t iin the
th
0.01
700-1000 A region,
10
100
1000
10,000
100,000
g is uncertain.
timing
1
Current in Amperes
Minimum Melt
Average Melt + tolerance
10
Time in Seconds
1 Total Clear
100
1000
10,000
00,000
10
Current in Amperes
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 8
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
1 (protected) fuse.
100
1000
10,,000
100,,000
1
Current in Amperes
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 9
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
1. Tolerances.
Time in Seconds
1 2. Ambient
temperature.
p
0.1
3. Preloading effects.
4. Predamage effects.
0.01
10
100
1000
0,000
0,000
1
10
100
Current in Amperes
Consideration of these
four factors can be
10 quite involved.
100
1000
10,000
100,000
1
Current in Amperes
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 11
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
1
protecting link at 5 kA is
0.22 seconds.
0.1
0.22 < 0.3 75% = 0.225,
so coordination is
assured for current
0.01
magnitudes 5 kA.
10
100
1000
0,000
0,000
10
100
Current in Amperes
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 12
Utility
y Distribution Feeders
Multiple Feeder Segments
A optimum
An ti point
i t mustt b
be sought
ht tto d
determine
t i ththe
best segment size.
1. Maximum Sensitivity.
2. Maximum Speed.
3. Maximum Security.
4. Maximum Selectivity.
4
4. Determine
D t i remaining
i i
overcurrent device
characteristics starting
from the load and moving g to
the source.
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 17
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 18
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 19
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 20
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 21
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 22
Fuse Peak Load Capability
Fuse Save
Minimizes customer interruption time by attempting to
open the breaker or recloser faster than it takes to melt the
fuse.
fuse
This saves the fuse and allows a simple momentary
interruption.
FUSE is BLOWN
Lateral experiences
sustained interruption
30
Fuse Blow
Used primarily to minimize momentary
interruptions (reduces MAIFI)
Increases interruption duration (SAIDI)
Very successful in high short circuit areas
More suitable for industrial type
customers having very sensitive loads
FUSE is SAVED
Protection Features:
P f
Performs att lleastt 18 different
diff t protection
t ti functions.
f ti
Protection Features:
B U
Bus Undervoltage
d lt (27)
Phase Overvoltage (59P)
G
Ground
d Overvoltage
O lt (59G)
Sequence Overvoltage (59Q)
O
Overfrequency
f (81O)
Underfrequency (81U)
Ph
Phase Di
Directional
ti l Overcurrent
O t (67P)
Ground Directional Overcurrent (67G)
S
Sequence Di
Directional
ti l Overcurrent
O t (67Q)
Instantaneous Phase Overcurrent (50P)
I t t
Instantaneous Ground
G d Overcurrent
O t (50G)
Instantaneous Sequence Overcurrent
(50Q)
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 40
SEL-351S
Protection and Breaker Control Relay
Ti
Time Ph
Phase Overcurrent
O t (51P)
Time Ground Overcurrent (51G)
Ti
Time S
Sequence Overcurrent
O t (51Q)
Directional Neutral Overcurrent (67N)
I t t
Instantaneous N t l Overcurrent
Neutral O t (50N)
Time Neutral Overcurrent (51N)
S
Synchronism
h i Ch
Check
k (25)
Automatic Circuit Reclosing (79)
TRIP/CLOSE Pushbuttons
Enable/Disable Reclosing
Enable/Disable Supervisory Control
Other Features:
E
Event
t Reporting
R ti and
dRRecording
di
Breaker Wear Monitor
St ti Battery
Station B tt M
Monitor
it
High-Accuracy Metering
F lt Locator
Fault L t
TAGGING
NORMAL mode 2 reclosing
g attempts
p
WORK mode HOT LINE TAG
COLD mode
10
S
e
c Moderately Inverse
o 1
Inverse
n
d Very Inverse
s Extremely Inverse
0.1
0.01
0.1 1 10 100
Multiple of Pick Up
In this example
p
Multiple of Pickup = 3.
10
TD = 0.5
05 Time = 0.3s
0 3s
TD = 2 Time = 1.1s
SECONDS
1
TD=0.5
TD = 6 Time = 3.4s
TD=2
TD=6
TD 6
TD = 15 Time = 7.0s
TD=15
0.1
0.01
0.1 1 10 100
Multiples Of Pick Up
Pickup
Pi k = 600 A A.
Fault Current = 1800 A.
10
T = 0.5
TD Time = 0.29s
0. 9s
TD = 2 Time = 1.16s
SECONDS
Backup Primary
Single
g Phase to Ground Fault
IMU<IPU<I MIN Fault
IMU = Maximum Unbalance
CTR = 600.0
INSTANTANEOUS ENABLED ONLY AFTER FIRST RECLOSE ATTEMPT
50P2P = 2.5 (1500 AMPS PRIMARY)
50G2P = 1.6
1 6 (960 AMPS PRIMARY)
Sample output:
IaIb
OP
IaIb IaIb
R R
OP
IbIc IbIc IbIIc
R R
Power System Protection -64- Ralph Fehr, Ph.D., P.E. October 28, 2013
DistanceRelays
y
ProtectionFeatures
Fourzonesof distanceprotection
Pilotschemes
Phase/Neutral/GroundTOCs
Phase/Neutral/GroundIOCs
Phase/Neutral/Ground IOCs
Power System Protection -65- Ralph Fehr, Ph.D., P.E. October 28, 2013
DistanceRelays
y
ProtectionFeatures continued
NegativesequenceTOC
NegativesequenceIOC
PhasedirectionalOCs
NeutraldirectionalOC
NegativesequencedirectionalOC
Phaseunder andovervoltage
Powerswingblocking
Outofsteptripping
Power System Protection -66- Ralph Fehr, Ph.D., P.E. October 28, 2013
DistanceRelays
Control Features
ControlFeatures
BreakerFailure(phase/neutralamps)
B k F il ( h / t l )
Synchrocheck
Autoreclosing
Power System Protection -67- Ralph Fehr, Ph.D., P.E. October 28, 2013
DistanceRelays
Metering Features
MeteringFeatures
FaultLocator
F lt L t
Oscillography
EventRecorder
DataLogger
Phasors/trueRMS/active,reactive
and apparent power, power factor
andapparentpower,powerfactor
Power System Protection -68- Ralph Fehr, Ph.D., P.E. October 28, 2013
DistanceRelays
ZonesofProtection Zone 2
Zone2
X
3 Zone1
Line Impedance (Line A)
LineImpedance(LineA) 2 1
Zone2 A1 LineA A2
1 Z
Zone3
3 4 3
Bus1 Bus2
Zone1
2 NormalLoad
Normal Load
R
DistanceRelay
atBus1 Zone1 fastest(80%ofline)
toprotectLineA Zone2 slower(120%ofline)
4 Zone3(backwardsUseinPilot
Zone3 Protectionforcurrent
Reversallogic)
Power System Protection -69- Ralph Fehr, Ph.D., P.E. October 28, 2013
Zone of Protection Zone 3
Zone 2 t Zone 2
t
Zone 1 t Zone 1
1 2 3 4
Zone 1 Zone 1
Zone 2 Zone 2
Zone 3
Zone 1: Under reaches the remote line end Typically 0.7 Z1L to 0.9 Z1L
With no intentional time delay.
Zone 2:
Z 2 Over
O reaches
h the
th remote
t line
li end
d Typically
T i ll 1.21 2 Z1L
with definite time delay.
Zone 2
t
Zone 1
Zone 1 Reach = 0.8 * (35.11 83.97) primary Zone 1 Reach = 28.09 83.97) primary
Z
Zone 2R
Reach
h=1
1.2
2 * (35.11
35 11 83.97)
83 97) primary
i Z
Zone 2R
Reach
h = 42.13
42 13 83.97)
83 97) primary
i
Check Zone 2 reach does not overreach = Circuit 2 Impedance + (Zone 1 of Circuit 3) or (Zone 1of Circuit 6).
General rule = p
protected Circuit Impedance
p + Zone 1 of the Shortest Circuit p
past the p
protected circuit.
Zone 4 Reach = (35.11 83.97) + (17.56 83.72) ( primary) Zone 4 Reach = 52.55 83.35) primary
IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 74
Primary / Secondary Impedance
Relay Input
75
Relay Input
1) Find the lowest fault seen by relay 3 Set above (maximum load) and 60% of min fault.
for a remote end bus (4
(4, 10
10, 5
5, 11)
11).
IT =0.5 A
ZT =1
Actual Impedance from L to the Fault is 3
Apparent Impedance = EL
IL