Appendix C Fault Level Calculation Rev 0

This document contains calculations to determine the earth fault current at the 33kV bus of the North Awqad-II Primary Substation. It provides details of the system voltage, fault current, impedances of the transmission lines, transformers and earth. An equivalent circuit is presented considering the worst case scenario of two parallel transformers and two parallel cable lines. The total impedance is calculated and used to determine the 33kV earth fault current to be 6.28kA.

Uploaded by

Vikram Singh
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
400 views

Appendix C Fault Level Calculation Rev 0

This document contains calculations to determine the earth fault current at the 33kV bus of the North Awqad-II Primary Substation. It provides details of the system voltage, fault current, impedances of the transmission lines, transformers and earth. An equivalent circuit is presented considering the worst case scenario of two parallel transformers and two parallel cable lines. The total impedance is calculated and used to determine the 33kV earth fault current to be 6.28kA.

Uploaded by

Vikram Singh
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

CALCULATION SHEETS Appendix-C

Fault Level Calculations for 33/11 kV North Awqad-II Primary Substation

System Voltage at = 132 kV


3 Phase bolted fault current at 132kV bus Ikr = 31.50 kA (Maximum Design Fault Level
at 132kV end)

Base MVA (MVAb) = 125 MVA


(132/33kV, Transformer MVA is considered as Base MVA)

Base kV (kVb) = 33 kV

Source Fault MVA = Sqrt(3) *132* 31.5


= 7201.87

Source Impedance, Zs Zs = Base MVA


Fault MVA
= 0.017 pu =0 + j0.017 pu

Single 125 MVA Trafo. impedance = 16.65 % (Refer Appendix - E)


ZT1 = 0.167 pu = 0 + j0.167 pu
ZT2 = 0.167 pu = 0 + j0.167 pu

1.1 Earth fault current at North Awqad-II Primary Substation

Source positive sequence impedance Zs1 = 0.00 + j 0.017 pu


Source negative sequence impedance Zs2 = 0.00 + j 0.017 pu
Transformer impedance ZT = 0.00 + j 0.167 pu
Base Impedance Zb = 8.712 ohm (kVb2/MVAb)
EAT zero sequence impedance Z0EAT = 12.50 ohm (As per Past project data)
= 1.435 pu (Z0EAT / Zb)
= 0 + j 1.435 pu
Cable Data
3C x 300 Sq.mm, 33kV, Cu/XLPE/SWA/PVC cable is used
Approximate cable length = 4.5 km (Refer Appendix - E)
Cable positive sequence impedance/km = 0.079 +j 0.107 ohm/km (Refer Appendix - E)
Cable positive sequence impedance Zc 1 = 0.35550 +j 0.48150 ohm
= 0.04081 +j 0.05527 pu [=Zc1/Zb]
Cable negative sequence impedance Zc2 = 0.04081 +j 0.05527 pu

Cable zero sequence impedance/km = 0.935 +j 0.124 ohm/km (Refer Appendix - E)


Cable zero sequence impedance ZC0 = 4.20750 +j 0.55800 ohm
= 0.48295 +j 0.06405 pu [=Zc0/Zb]
EAT zero sequence impedance Z0EAT = 12.50 ohm (As per Past project data)
= 1.435 pu
= 0.000 +j 1.435 pu

352221897.xls Page C1+1 of C3


CALCULATION SHEETS Appendix-C

1.1.1 Equivalent circuit for 1 ph Fault level at 33kV Bus at North Awqad-II Primary Substation
(Considering the worse case i.e two 125MVA trafo with Solid Earthing of EAT neutral
in parallel and two cable lines in parallel)
Z0EAT = 12.50 ohm
= 1.435 pu = 0 + j1.435 pu
Reference Bus

Source
ZT1 Zc1
U0=1 pu

ZS1 ZT1 Zc1

ZT2 Zc2

ZS2 ZT2 Zc2

Z0EAT
Zc0
ZS0
Z0EAT Zc0

1.1.2 Symmetrical Ground Fault Current Calculations


Z1 = ZS1 + ((ZT1//ZT1) + (Zc1 // Zc1))
= [(0+ j 0.017) + {(0+ j 0.167) // (0+ j 0.167)} +
{(0.040805+j0.05527) // (0.040805+j0.05527)}]
= [(0+ j 0.017) + (0+ j 0.0835) + (0.0204025+j0.027635)]
= 0.0204025 +j 0.128135 pu
Z2 = 0.0204025 +j 0.128135 pu
Z0 = (Z0EAT1//Z0EAT2) + (Zc0//Zc0)
= [{(0+j1.435) // (0+j1.435)} + {(0.48295+j0.06405) //
(0.48295+j0.06405)}]
= [(0+j0.7175) + (0.241475 +j 0.032025)]
= 0.241475 +j 0.749525 pu

Total Impedance Zt = Z1 + Z2 + Z0
= (0.0204025 +j 0.128135) + (0.0204025 +j 0.128135) +
(0.241475 +j 0.749525)
= 0.28228 +j 1.005795
= 1.045 pu
Z (ohms) = 9.10 ohm [=Zt*Zb]
33kV Earth Fault current is determined for Solid Earthing of EAT neutral with both feeders
operating in parallel at 33kV Bus of NA PSS. = 3 * (33/sqrt(3))/Zt)
= 6.28 kA

352221897.xls Page C2+1 of C3