Appendix C Fault Level Calculation Rev 0
Appendix C Fault Level Calculation Rev 0
Base kV (kVb) = 33 kV
1.1.1 Equivalent circuit for 1 ph Fault level at 33kV Bus at North Awqad-II Primary Substation
(Considering the worse case i.e two 125MVA trafo with Solid Earthing of EAT neutral
in parallel and two cable lines in parallel)
Z0EAT = 12.50 ohm
= 1.435 pu = 0 + j1.435 pu
Reference Bus
Source
ZT1 Zc1
U0=1 pu
ZT2 Zc2
Z0EAT
Zc0
ZS0
Z0EAT Zc0
Total Impedance Zt = Z1 + Z2 + Z0
= (0.0204025 +j 0.128135) + (0.0204025 +j 0.128135) +
(0.241475 +j 0.749525)
= 0.28228 +j 1.005795
= 1.045 pu
Z (ohms) = 9.10 ohm [=Zt*Zb]
33kV Earth Fault current is determined for Solid Earthing of EAT neutral with both feeders
operating in parallel at 33kV Bus of NA PSS. = 3 * (33/sqrt(3))/Zt)
= 6.28 kA