Dry Type Traformer 1mva

The document is a test report for a 630 KVA transformer. It provides details of the transformer such as manufacturer, ratings, test results, and remarks. Key findings from the tests include: insulation resistance met standards, voltage ratios matched specifications within 1%, and winding resistances were measured to be correct. The conclusion was that the transformer is fit for commissioning.

Uploaded by

idris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
465 views4 pages

Dry Type Traformer 1mva

The document is a test report for a 630 KVA transformer. It provides details of the transformer such as manufacturer, ratings, test results, and remarks. Key findings from the tests include: insulation resistance met standards, voltage ratios matched specifications within 1%, and winding resistances were measured to be correct. The conclusion was that the transformer is fit for commissioning.

Uploaded by

idris
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

TEST REPORT FOR TRASFORMER

VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.


CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 1 of 4

1. Equipment Details :

Make : VOLTAMP

Type of Cooling : AN

Rating : 630 KVA

HV Volts : 11000V

LV Volts : 433V

Impedance voltage % : 4.57

Vector Group : Dyn11

HV Rated Current : 33.07A

LV Rated Current : 840.02 A

Sl. No. : 10992/32

Mfg Year : 2009

No of Taps : 5

Normal Taps : 3

Type : dry type

Insulation class : F

No load loss : 1.908 KW

Full load loss : 6.729 KW

HV
Tap position volts LV volts Actual ratio
1 11550 26.67
2 11275 26.03
3 11000 433 25.40
4 10725 24.76
5 10450 24.13

Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 2 of 4

2. Location : Zone-1 (CSS-5)

3. Insulation Resistance Test : (Value in Giga Ohms) (Using 5 KV Megger)

REFERANCE 15sec 60sec PI VALUE


HV to Earth 0.585 0.765 1.307
HV to LV 0.300 - -
LV to Earth 0.987

4. Ratio Test:

Tap Applied voltage in Measured voltage in secondary(v)


position primary(v)
1U1V 1V1W 1W1U 2U2V 2V2W 2W2U
1 400 400 404 15.05 15.06 15.10
2 390 393 398 15.00 15.01 15.35
3 404 402 402 15.90 15.80 15.80
4 394.5 396.3 396 15.80 15.96 15.98
5 394 390 389 16.20 16.00 16.10

Tap Actual Measured Ratio


position ratio
1U1V 1V1W 1W1U
1 26.67 26.57 26.56 26.75
2 26.03 26.00 26.18 25.92
3 25.40 25.40 25.44 25.44
4 24.76 24.96 24.83 24.78
5 24.13 24.32 24.37 24.16
5. Magnetizing Current Test:

Tap No Applied voltage in Measured Current in secondary


primary(V) (m A)
1U1V 1V1W 1W1U 1U 1V 1W
3 399 400 399 10.3 7.6 7.4

Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 3 of 4

6. Magnetic Balance Test: (Using Equipment Details)

Tap Applied voltage in Measured voltage in primary(v)


position primary(v)
1U1V 1V1W 1W1U 1U1V 1V1W 1W1U
Normal 396 - - - 295 103
tap - 404 - 198 - 205
- - 401 95 305 -

7. Vector Group Test: (Using Equipment Details)

a. Dyn11 (1U & 2U short d )

1. 1U1V=1U2N+1V2N

399 = 7.2 + 391

2. 1V2W = 1V2V

388 = 389

3. 1W2N > 1W2W

397 > 389

4. 1U2W = 1U2V

15.8 = 15.9

Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 4 of 4

8. Winding Resistance Measurement:

HV Side: ()

Tap 1U1V 1V1W 1W1U


Position
1 2.44 2.45 2.44
2 2.38 2.39 2.37
3 2.32 2.32 2.31
4 2.25 2.25 2.24
5 2.18 2.19 2.19

LV-Side:(m )

Tap 2U2V 2V2W 2W2U


Position
3 1.431 1.427 1.439

Tap 2U2N 2V2N 2W2N


Position
3 0.693 0.712 0.724

9. Remarks: Transformer is fit for commissioning

Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date