TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 1 of 4
1. Equipment Details :
Make : VOLTAMP
Type of Cooling : AN
Rating : 630 KVA
HV Volts : 11000V
LV Volts : 433V
Impedance voltage % : 4.57
Vector Group : Dyn11
HV Rated Current : 33.07A
LV Rated Current : 840.02 A
Sl. No. : 10992/32
Mfg Year : 2009
No of Taps : 5
Normal Taps : 3
Type : dry type
Insulation class : F
No load loss : 1.908 KW
Full load loss : 6.729 KW
HV
Tap position volts LV volts Actual ratio
1 11550 26.67
2 11275 26.03
3 11000 433 25.40
4 10725 24.76
5 10450 24.13
Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 2 of 4
2. Location : Zone-1 (CSS-5)
3. Insulation Resistance Test : (Value in Giga Ohms) (Using 5 KV Megger)
REFERANCE 15sec 60sec PI VALUE
HV to Earth 0.585 0.765 1.307
HV to LV 0.300 - -
LV to Earth 0.987
4. Ratio Test:
Tap Applied voltage in Measured voltage in secondary(v)
position primary(v)
1U1V 1V1W 1W1U 2U2V 2V2W 2W2U
1 400 400 404 15.05 15.06 15.10
2 390 393 398 15.00 15.01 15.35
3 404 402 402 15.90 15.80 15.80
4 394.5 396.3 396 15.80 15.96 15.98
5 394 390 389 16.20 16.00 16.10
Tap Actual Measured Ratio
position ratio
1U1V 1V1W 1W1U
1 26.67 26.57 26.56 26.75
2 26.03 26.00 26.18 25.92
3 25.40 25.40 25.44 25.44
4 24.76 24.96 24.83 24.78
5 24.13 24.32 24.37 24.16
5. Magnetizing Current Test:
Tap No Applied voltage in Measured Current in secondary
primary(V) (m A)
1U1V 1V1W 1W1U 1U 1V 1W
3 399 400 399 10.3 7.6 7.4
Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 3 of 4
6. Magnetic Balance Test: (Using Equipment Details)
Tap Applied voltage in Measured voltage in primary(v)
position primary(v)
1U1V 1V1W 1W1U 1U1V 1V1W 1W1U
Normal 396 - - - 295 103
tap - 404 - 198 - 205
- - 401 95 305 -
7. Vector Group Test: (Using Equipment Details)
a. Dyn11 (1U & 2U short d )
1. 1U1V=1U2N+1V2N
399 = 7.2 + 391
2. 1V2W = 1V2V
388 = 389
3. 1W2N > 1W2W
397 > 389
4. 1U2W = 1U2V
15.8 = 15.9
Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date
TEST REPORT FOR TRASFORMER
VOLTECH ENGINEERS PVT. LTD. DATE :07.06.2010 Page No.
CLIENT : M/S. BSP A/C ABB LTD
PROJECT : ELECTRICAL ENABLING WORK (PKG-113) Sheet No 4 of 4
8. Winding Resistance Measurement:
HV Side: ()
Tap 1U1V 1V1W 1W1U
Position
1 2.44 2.45 2.44
2 2.38 2.39 2.37
3 2.32 2.32 2.31
4 2.25 2.25 2.24
5 2.18 2.19 2.19
LV-Side:(m )
Tap 2U2V 2V2W 2W2U
Position
3 1.431 1.427 1.439
Tap 2U2N 2V2N 2W2N
Position
3 0.693 0.712 0.724
9. Remarks: Transformer is fit for commissioning
Test Performed by: VEPL Witnessed by: ABB LTD Witnessed by: BSP
Name : R.Vinod kumar Name : Mr. Abhay Medpalliwar Name : Mr. S.C.Soni
Designation : T & Comm Engineer Designation : Site In-charge Designation : Jr.manager
Signature & Signature & Signature &
Date Date Date