Industrial Protocols Users Guide 6e
Industrial Protocols Users Guide 6e
www.moxa.com/product
The software described in this manual is furnished under a license agreement and may be used only in accordance
with the terms of that agreement.
Copyright Notice
Trademarks
Disclaimer
Information in this document is subject to change without notice and does not represent a commitment on the part of
Moxa.
Moxa provides this document as is, without warranty of any kind, either expressed or implied, including, but not
limited to, its particular purpose. Moxa reserves the right to make improvements and/or changes to this manual, or to
the products and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate and reliable. However, Moxa assumes no responsibility
for its use, or for any infringements on the rights of third parties that may result from its use.
This product might include unintentional technical or typographical errors. Changes are periodically made to the
information herein to correct such errors, and these changes are incorporated into new editions of the publication.
www.moxa.com/support
Moxa Americas Moxa China (Shanghai office)
Toll-free: 1-888-669-2872 Toll-free: 800-820-5036
Tel: +1-714-528-6777 Tel: +86-21-5258-9955
Fax: +1-714-528-6778 Fax: +86-21-5258-5505
Moxa Europe Moxa Asia-Pacific
Tel: +49-89-3 70 03 99-0 Tel: +886-2-8919-1230
Fax: +49-89-3 70 03 99-99 Fax: +886-2-8919-1231
Table of Contents
Introduction
MODBUS TCP is a protocol commonly used for the integration of a SCADA system. It is also a vendor-
neutral communication protocol used to monitor and control industrial automation equipment such as PLCs,
sensors, and meters. In order to be fully integrated into industrial systems, Moxas switches support
Modbus TCP/IP protocol for real-time monitoring in a SCADA system.
Moxa switches support Function Code 4 with 16-bit (2-word) data access for read-only information.
Select the checkbox and click Activate to enable the Modbus TCP.
Industrial Protocols MODBUS/TCP MAP
Modbus TCP is enabled by default. To disable Modbus TCP, uncheck Enable Modbus TCP then click Apply.
1-2
Industrial Protocols MODBUS/TCP MAP
1-3
Industrial Protocols MODBUS/TCP MAP
1-4
Industrial Protocols MODBUS/TCP MAP
1-5
Industrial Protocols MODBUS/TCP MAP
1-6
Industrial Protocols MODBUS/TCP MAP
1-7
2
2. EtherNet/IP
Introduction
EtherNet/IP is an Industrial Ethernet Protocol defined by the ODVA association. The protocol is open to the
public and vendors can implement EtherNet/IP into their industrial devices without incurring a license fee.
Many vendors have adopted this protocol as the standard communication protocol between devices. For
example, Rockwell Automation uses EtherNet/IP as the standard protocol for their Logix controllers over
Ethernet networks.
To allow complete integration with a Rockwell system, Moxa switches not only provide a full-functioning of
industrial network infrastructure, but also enable the SCADA system to monitor the status of the switches
as well as that of the PLCs, .making the switches part of a Rockwell system.
Messaging Types
EtherNet/IP supports two types of communication methods for EtherNet/IP devices: Explicit Messaging and
Implicit Messaging. Explicit Messaging is unscheduled and is used for a request/response communication
procedure (or client/server procedure). Explicit Messaging uses TCP/IP over Ethernet. Implicit Messaging is
scheduled and is used for a producer/consumer communication with UDP over Ethernet. Implicit Messaging
is also called I/O Messaging.
Check the Enable checkbox to enable EtherNet/IP. With EtherNet/IP enabled, IGMP Snooping and IGMP
Query functions will be enabled automatically to be properly integrated in Rockwell systems for multicast
Implicit (I/O) Messaging.
Industrial Protocols EtherNet/IP
Identity Object
TCP/IP Interface Object
Ethernet Link Object
Assembly Object
Message Router Object
Connection Manager Object
Port Object
Moxa Networking Object (Vendor Specific)
The supported attributes and services of the above objects are introduced in the table below, including the
access rules for each attribute. To understand the details of each attribute of the standard objects, refer to
the official documents of CIP introduction (Vol. 1) and the EtherNet/IP Adaptation of CIP (Vol. 2).
Identity Object
The Class code of Identity object is 0x01 (Defined in CIP Vol1, 5-2).
There is one instance of this object in our product. It stores the information of the production and the
device. The following tables summarize the class attributes and the instance attributes.
2-2
Industrial Protocols EtherNet/IP
The Identity Object Instance supports the following CIP Common services:
2-3
Industrial Protocols EtherNet/IP
2-4
Industrial Protocols EtherNet/IP
The TCP/IP Object Instance supports the following CIP Common services:
2-5
Industrial Protocols EtherNet/IP
The following tables summarize the attributes of the Ethernet Link object.
There are some vendor specific attributes in the table (Starting from attribute Id 100).
2-6
Industrial Protocols EtherNet/IP
2-7
Industrial Protocols EtherNet/IP
Interface Flags
Bit(s) Called Definition
0 Link Status 0 indicates an inactive link;
1 indicates an active link.
1 Half/Full Duplex 0 indicates half duplex;
1 indicates full duplex.
2-4 Negotiation Status Indicates the status of link auto-negotiation
0 = Auto-negotiation in progress.
1 = Auto-negotiation and speed detection failed. Using default values
for speed and duplex. Default values are product-dependent;
recommended defaults are 10Mbps and half duplex.
2 = Auto negotiation failed but detected speed. Duplex was defaulted.
Default value is product-dependent; recommended default is half
duplex.
3 = Successfully negotiated speed and duplex.
4 = Auto-negotiation not attempted. Forced speed and duplex.
5 Manual Setting Requires 0 indicates the interface can activate changes to link parameters
Reset (auto-negotiate, duplex mode, interface speed) automatically. 1
indicates the device requires a Reset service be issued to its Identity
Object in order for the changes to take effect.
6 Local Hardware 0 indicates the interface detects no local hardware fault; 1 indicates a
Fault local hardware fault is detected. The meaning of this is product-
specific. For example, an AUI/MII interface might detect no
transceiver attached, or a radio modem might detect no antenna
attached. In contrast to the soft, possibly self-correcting nature of the
Link Status being inactive, this is assumed a hard-fault requiring user
intervention.
7~31 Reserved. Shall be set to zero
The Ethernet Link Object Instance supports the following CIP common services:
Assembly Object
The Moxa switch support static assembly object for CIP I/O messaging.
2-8
Industrial Protocols EtherNet/IP
For the definition of the I/O messaging, see the following table for details.
Explicit Messaging
Unconnected Messaging
Implicit messaging
When using the UCMM to establish an explicit messaging connection, the target application object is the
Message Router object (Class Code 2).
2-9
Industrial Protocols EtherNet/IP
Port Object
The port object represents the underlying interface of CIP which is EtherNet/IP.
2-10
Industrial Protocols EtherNet/IP
It can also be used to do the device diagnostic & configuration through explicit messaging.
2-11
Industrial Protocols EtherNet/IP
2-12
Industrial Protocols EtherNet/IP
The list includes the sections which are described in our EDS file.
[File]
[Device]
[Device Classification]
[Port]
Our AOI would provide logic of Moxa switch configuration and monitoring by using EtherNet/IP in explicit
messaging and implicit messaging. The AOI also provides some tags for RSLogix 5000/SCADA
programming.
AOI Installation
To install the AOI, you must use Rockwell RSLogix 5000 version 18 or later and Moxa managed Ethernet
switches with firmware version 3.0 or later.
In order to import the AOI, the first step is to create a new Ethernet Module in RSLogix 5000.
2-13
Industrial Protocols EtherNet/IP
2-14
Industrial Protocols EtherNet/IP
3. Under the Communications group, select Generic Ethernet Module to represent Moxa Ethernet
switches
4. Configure the Ethernet module with the correct name, description, IP address and connection parameters
and click OK.
5. After finishing configuration, the new Ethernet module representing the Moxa Ethernet switch will appear
under the I/O Configuration list in the controller organizer window.
2-15
Industrial Protocols EtherNet/IP
1. In the controller organizer window, right click the Add-On Instructions folder, select Import Add-On
Instructions and select the correct AOI file (xxx.L5X) to import.
NOTE The AOI file is available from the Moxa website or in the software CD. Please make sure to use the latest
switch firmware and AOI for programming.
2. After importing, the controller organizer window shows all AOI for Moxa Ethernet switches under the
Add-On Instructions folder.
2-16
Industrial Protocols EtherNet/IP
1. Double click the MainRoutine in the Controller Organizer to start the ladder programming. Add the AOI
for the specific Moxa Ethernet switch to create a new rung.
1. Right click on the ? in the field of each tag, select New Tag and input a Name for each new tag.
2-17
Industrial Protocols EtherNet/IP
For Switch_Input and Switch_Output, use the scrollbar to select the tag name
2-18
Industrial Protocols EtherNet/IP
Click the Communication tab and set up the communication path to the Moxa Ethernet switch for
Get_AllMessage
4. Click the square button to the right of the Set_Message tag and configure all parameters as follows:
(Service Code: 10; Class: f6; Instance: 1; Attribute: 1; Source Ethernet: MOXA_SetData)
2-19
Industrial Protocols EtherNet/IP
Click the Communication tab and set up the communication path to the Moxa Ethernet switch for
Set_Message
5. Click the square button to the right of the Get_SingMessage tag and configure all parameters as
follows:
(Service Code: e; Class: f6; Instance: 1; Attribute: 1; Destination: MOXA_Singlestorage[0])
Click the Communication tab and set up the communication path to the Moxa Ethernet switch for
Get_SingMessage
2-20
Industrial Protocols EtherNet/IP
1. Click the Network Icon, select the Rockwell PLC connected to the Moxa switch and click Download to
install the AOI configuration to the PLC.
2. After finishing configuration, go to the controller organizer window, right click Controller Tags and
select Monitor Tags to check if each tag can display the correct value transferred from the Ethernet
device.
2-21
Industrial Protocols EtherNet/IP
NOTE Only Moxa pre-configured tags will display the correct values. Refer to the CIP Tags section below for
detailed information.
For easier AOI installation, Moxa has also provided a sample AOI project, in which all the parameters are
configured with default values. The sample project is a (.ACD) file, which is available for download from the
Moxa website or software CD. You may import the sample project in RSLogix 5000, and directly download
this AOI to the PLC with minimal installation steps. But to use the sample project, you still must change or
set up the parameters below.
NOTE The sample AOI project only supports RSLogix 5000 version 18.
CIP Tags
There are tags for each CIP object. The tags correspond to the objects attributes.
2-22
Industrial Protocols EtherNet/IP
2-23
Industrial Protocols EtherNet/IP
Rate
Tx Multicast Packet DINT Total number of TX multicast packets
Rx Multicast Packet DINT Total number of RX multicast packets
Tx Broadcast Packet DINT Total number of TX multicast packets
Rx Broadcast Packet DINT Total number of RX broadcast packets
Redundant Port Status DINT Bit 0 = Disable,
Bit 1 = Not Redundant port,
Bit 2 = Link down,
Bit 3 = Blocking,
Bit 4 = Learning,
Bit 5 = Forwarding
2-24
Industrial Protocols EtherNet/IP
The Moxa AOI supports all the CIP tags listed in the tables above. But in the AOI, we only pre-configure
logic links between selected tags and Moxa switches. To monitor the non-configured tags, PLC
programmers need to create the links manually. Otherwise, in RSLogix 5000, the value column of these
tags will display as 0. If you experience problems creating new links, please contact Moxa technical
support for assistance.
NOTE For pre-configured tags, Moxa has already created the logic links between the CIP tags and Moxa Ethernet
switches so RSLogix 5000 can get/set the switch information correctly.
The table below specifies all the pre-configured tags in Moxa AOI with a m a rk .
2-25
Industrial Protocols EtherNet/IP
Interface Lable
Interface Description
Interface Port Description
Broadcast Storm Protection
Interface Utizatiion
Utilization Alarm Upper Threshold
Utilization Alarm Lower Threshold
Port Link Alarm
Port Traffic-Overload Alarm
Tx Unicast Packet Rate
Rx Unicast Packet Rate
Tx Multicast Packet Rate
Rx Multicast Packet Rate
Tx Broadcast Packet Rate
Rx Broadcast Packet Rate
Tx Multicast Packet
Rx Multicast Packet
Tx Broadcast Packet
Rx Broadcast Packet
Redundant port status
Port Object (0xf4)
Port Type
Port Number
Link Object
Port Name
Port Type Name
Port Description
Node Address
Port Key
MOXA Networking Object (0x404)
Firmware Version
System Fault Status
Switch Port Number
Port Exist
Port Enable
Port Link Status
IGMP Snooping Enable
Query Interval
IGMP Enhanced Mode
Relay1
Relay2
Power 1 relay waring
Power 2 relay waring
DI 1(off) relay warning
DI 1(on) relay warning
DI 2(off) relay warngin
DI 2(on) relay warngin
Turbo Ring Break relay warning
CPU usage
Device Up Time
Reset MIB Counts
Redundant device mode
reset device
I/O message Object
Switch Fault Status
Port Exist
Port Link Status
Port Enable
NOTE Only Moxa pre-configured tags will display the correct values. Refer to the CIP Tags section above for
detailed information.
2-26
Industrial Protocols EtherNet/IP
Click moxa_param Switch_Identity and expand the list to check the values for Identity tags.
Click moxa_param Switch_TCPIP and expand the list to check the values for TCPIP tags.
2-27
Industrial Protocols EtherNet/IP
Click moxa_param Switch_Ethernet_Link and expand the list to check the values for per port Ethernet
Link tags.
2-28
Industrial Protocols EtherNet/IP
Click moxa_param Switch_Vendor and expand the list to check the values for Moxa custom tags.
2-29
Industrial Protocols EtherNet/IP
1. Start the FactoryTalk View Studio software and select Site Edition (Local).
2. Add a new Site Edition (Local) and enter the Application name.
2-30
Industrial Protocols EtherNet/IP
2-31
Industrial Protocols EtherNet/IP
1. Right click Display in the FactoryTalk View Explorer window, select Import and Export and choose
Import graphic information into displays.
NOTE Moxa provides sample graphics files for selected switches, which are available for download at the Moxa
website or from the software CD.
2-32
Industrial Protocols EtherNet/IP
4. After import, these objects will appear under Displays in the Explorer window.
1. Right click Local Message in the FactoryTalk View Explorer window, select Add Component Into
Application and import all the local message files (.loc)
NOTE Moxa provides sample local message files for selected switches, which are available for download at the
Moxa website or from the software CD..
2-33
Industrial Protocols EtherNet/IP
2. After import, these objects will appear under Local Message in the Explorer window.
1. Right click Images in the FactoryTalk View Explorer window, select Add Component Into
Application and import all the image files (.bmp)
NOTE Moxa provides sample image files for selected switches, which are available for download at the Moxa
website or from the software CD.
2-34
Industrial Protocols EtherNet/IP
2-35
Industrial Protocols EtherNet/IP
1. Right click Parameters in the FactoryTalk View Explorer window, and select New
In the parameter definition, the shortcut PLC was created earlier. (Refer to Create a FactoryTalk
View Shortcut to PLC)
Another important piece is moxa_param, which is the name of the Switch_Parameters tag created for
the MOXA_SWITCH_AOI in your RSLogix project. (Refer to Create and configure tags for the AOI)
2-36
Industrial Protocols EtherNet/IP
1. Right click all parameter tabs under Displays in the FactoryTalk View Explorer window, and select
Display Setting.
2-37
Industrial Protocols EtherNet/IP
For easier FactoryTalk View Faceplate installation, Moxa also provides a sample project, in which all the
parameters are configured with default values. The sample project is a (.APA) file, which is available for
download from the Moxa website or software CD. You may import the sample project in FactoryTalk View
Faceplate Site Edition (SE).
2-38
Industrial Protocols EtherNet/IP
5. Configure the FactoryTalk View SE Client Components and set Initial Display to
MOXA_Device_Info
2-39
Industrial Protocols EtherNet/IP
6. Configure the FactoryTalk View SE Window Properties and input Title bar text with the text you
would like to appear in the title bar.
2-40
Industrial Protocols EtherNet/IP
Device Information
The device information display shows general switch information and power and link status.
2-41
Industrial Protocols EtherNet/IP
Port Status
The port status display shows information for a selected switch port. Use the right/left buttons to select a
switch port.
2-42
Industrial Protocols EtherNet/IP
Port Setting
The Port Setting allows some switch port settings to be changed. Use the right/left buttons to select a
switch port and click the Activate button to save the change.
2-43
3
3. PROFINET I/O
Introduction
This section is supported only with EDS-400A-PN, EDS-510E, and EDS-G500E series devices.
PROFINET is a communication standard for automation of PROFIBUS & PROFINET International (PI). It is
100% Ethernet-compatible as defined in IEEE standards. With PROFINET, applications can be implemented
for production and process automation, safety applications, and the entire range of drive technology. With
its integrated Ethernet-based communication, PROFINET satisfies a wide range of requirements, from data-
intensive parameter assignment to extremely fast I/O data transmission.
PROFINET I/O is used for data exchange between I/O controllers (PLC, etc.) and I/O devices (field devices).
This specification defines a protocol and an application interface for exchanging I/O data, alarms, and
diagnostics. And its real-time (RT) solution allows response time in the range of 5 ms, which corresponds to
todays PROFIBUS DP applications.
There are 3 major character types defined by PROFINET I/O, including I/O controller, I/O supervisor, and
I/O devices. Switches are considered I/O devices.
I/O Controller
This is typically the programmable logic controller (PLC) on which the automation program runs. The I/O
controller provides output data to the configured I/O-devices in its role as provider and is the consumer of
input data of I/O devices.
Industrial Protocols PROFINET I/O
I/O Supervisor
This can be a programming device, personal computer (PC), or human machine interface (HMI) device for
commissioning or diagnostic purposes.
I/O Device
An I/O device is a distributed I/O field device that is connected to one or more I/O controllers via PROFINET
I/O. The I/O device is the provider of input data and the consumer of output data.
PROFINET Protocols
DCP
In PROFNET I/O, each field device has a symbolic name that uniquely identifies the field device within a
PROFINET I/O system. This name is used for assigning the IP address and the MAC address. The DCP
protocol (Dynamic Configuration Protocol) integrated in every I/O device is used for this purpose.
DHCP
Because DHCP (Dynamic Host Configuration Protocol) is in widespread use internationally, PROFINET has
provided for optional address setting via DHCP or via manufacturer-specific mechanisms.
Automation systems can be configured flexibly in a line, star, or tree structure. To compare the specified
and actual topologies, to determine which field devices are connected to which switch port, and to identify
the respective port neighbor, LLDP according to IEEE 802.1AB was applied in PROFINET I/O.
PROFINET filed bus exchange existing addressing information with connected neighbour devices via each
switch port. The neighbor devices are thereby unambiguously identified and their physical location is
determined.
Device descriptions
GSD file
The GSD files (General Station Description) of the field devices to be configured are required for system
engineering. This XML-based GSD describes the properties and functions of the PROFINET I/O field devices. It
contains all data relevant for engineering as well as for data exchange with the device.
Find your field device GSD file in the CD or download the GSD file from the MOXA web site.
3-2
Industrial Protocols PROFINET I/O
Type 1
Select the Enable option and click Activate to enable PROFINET I/O. With PROFINET I/O enabled, PROFINET
type LLDP will be enabled automatically.
Select the Disable option and click Activate to disable PROFINET I/O, the switch will disable PROFINET type
LLDP and use standard LLDP.
PROFINET special model is enabled by default on the EDS-400A-PN series switches.
The default PROFINET I/O setting of EDS E series is disabled. To enable the PROFINET I/O support, check the
Enable PROFINET I/O and click Apply.
NOTE: Enabling PROFINET will prevent MXview (2.2 and earlier versions) from performing auto-detection of
network topology. Auto-detection of network topology is only supported by versions of MXview 2.3 and later.
To use auto-detection in earlier versions of MXview (2.2 and earlier), you should first disable PROFINET I/O,
perform MXview auto-detection of network topology, and then enable PROFINET I/O.
CLI
The CLI (command line interface) can be used to enable or disable PROFINET for the switch.
Command List:
3-3
Industrial Protocols PROFINET I/O
Manufacturer Information
Each PROFINET device is addressed based on a MAC address. This address is unique worldwide. The
company code (bits 47 to 24) can be obtained from the IEEE Standards Department free of charge. This
part is called the OUI (organizationally unique identifier).
0 0 0 2 2 9 x x x x x x
PROFINET Attributes
The PROFINET I/O connection can be configured for both cyclic I/O data and I/O parameters. I/O
parameters are acyclic I/O data. These are major setup and monitor attributes in PROFINET.
3-4
Industrial Protocols PROFINET I/O
NOTE: The default transfer frequency of PROFINET Cyclic I/O data is 128 ms. There are 3 options available
in SIMATIC STEP 7: 128/256/512 ms.
You can monitor these attributes in SIMATIC STEP 7. Operation steps are in the Chapter Monitoring the
Switch
3-5
Industrial Protocols PROFINET I/O
communication in the network. You can use the SIMATIC STEP 7 tool or engineering deployment software
to edit it. There are 3 categories of parameters, including Device Parameters, Device Status and Port
Parameters. The following tables provide parameter information:
Device parameters
These parameters control PROFINET Alarm functions. PROFINET Alarm is a message which sends from
switch to PLC immediately once the event is triggered.
Device Status
Byte Name Access Value Description
0 Device Status ro 0 Unavailable
1 OK
2 Device bootup fails
1 Fault Status ro 0 Unavailable
1 OK
2 Device detect fault
2 Power 1 Status ro 0 Unavailable
1 OK
2 Power 1 fails
3 Power 2 Status ro 0 Unavailable
1 OK
2 Power 2 fails
4 DI 1 Status ro 0 Unavailable
1 Closed
2 Open
5 DI 2 Status ro 0 Unavailable
1 Closed
2 Open
6 Redundant Mode ro 0 Unavailable
1 RSTP
2 Turbo Ring V1
3 Turbo Ring V2
4 Turbo Chain
7 Ring Status ro 0 Unavailable
1 Healthy
2 Break
8 Redundant Port 1 Status ro 0 Unavailable
1 Link is up
2 Link is down
9 Redundant Port 2 Status ro 0 Unavailable
1 Link is up
2 Link is down
10 Ring Coupling Mode ro 0 Unavailable
1 Backup
2 Primary
3 Dual homing
11 Coupling Port 1 Status ro 0 Unavailable
1 Link is up
2 Link is down
12 Coupling Port 2 Status ro 0 Unavailable
1 Link is up
2 Link is down
13 Connection ro 0 Unavailable
1 OK
2 Connection failure
3-6
Industrial Protocols PROFINET I/O
Port Parameters
Step 7 Integration
3-7
Industrial Protocols PROFINET I/O
Then you can see the new object in the project. Double click on the Hardware.
3-8
Industrial Protocols PROFINET I/O
Drag a rack from the side bar to main dashboard. In here, we drag Rail, which is under the Rack-300
folder, to the main screen.
3-9
Industrial Protocols PROFINET I/O
Click Start to search devices. Use STEP 7 through PROFINET DCP to discover devices in networks. Find
PLC/switch IP addresses, MAC addresses, and device names here.
Then click Properties, the Ethernet interface dialog will pop out. Fill in your PLC IP address in IP address
column. Then click New in subnet to create a new Ethernet subnet. Here we will create a subnet named
PROFINET Ethernet
3-10
Industrial Protocols PROFINET I/O
3-11
Industrial Protocols PROFINET I/O
5. You will find the new MOXA switch under PROFINET IO > Additional Field Devices > Network
Components > MOXA EtherDevice Switch.
6. Use Drag & Drop to pull the MOXA switch onto the bus cable. And you can see the MOXA switch icon
displayed on the screen
Product Icons
Ex. File Name: EDS-405A.bmp, EDS-408A.bmp, EDS-510E.bmp, EDS-G508E.bmp, EDS-G512E-
4GSFP.bmp, EDS-G516E-4GSFP.bmp
Device Configuration
1. Browse the switch
Select PLC > Ethernet > Edit Ethernet Node to open the Browse dialog.
3-12
Industrial Protocols PROFINET I/O
After the Edit Ethernet Node dialog box appears, click Browse
3-13
Industrial Protocols PROFINET I/O
NOTE The field Device name does not allow any empty spaces in the name. If the device name is entered with a
space, the system will remove words after the space automatically.
After the IP has been assigned by DHCP, click Browse again to check the assigned IP address.
3-14
Industrial Protocols PROFINET I/O
3-15
Industrial Protocols PROFINET I/O
3-16
Industrial Protocols PROFINET I/O
After the project is configured, SIMATIC STEP 7 will load all information required for data exchange to the
I/O Controller (PLC), including the IP addresses of the connected I/O devices.
MOXA switches provide PROFINET I/O cyclic data for real-time monitoring. In side bar you can see Device
data and Port data.
Use Drag & Drop to pull the Device data onto slot 1. Right-click on slot 1, then select Monitor/Modify.
Use Monitor to check the input data value. In this dialog, you can see the status value of each address.
Please refer to the PROFINET Cyclic I/O data table in Chapter 5.1 to see the meaning of each bit. For
example, address 0.1 is Bit 1 in the PROFINET Cyclic I/O data table. It represents Power 1 status of the
switch. 1 means Power 1 exists and Green will be displayed in the Modify/monitor window
3-17
Industrial Protocols PROFINET I/O
NOTE: Refer to the PROFINET Cyclic I/O data table in chapter 5.1 for the meanings of each address.
To monitor Port data, follow the same steps, drag Port data in the side bar and drop it onto slot 2.
Then right click. Select Monitor/Modify. You will see a monitoring window.
3-18
Industrial Protocols PROFINET I/O
Module Information
MOXA switch supports SIMATIC STEP 7 Ethernet traffic information monitoring and PROFINET alarms.
These attributes can be monitored in module information dialog. Following are the steps of operation.
Select Statics tags. Find out each port traffic information list below.
3-19
Industrial Protocols PROFINET I/O
Statistics tab lists each port traffic status and the number of packets. Click Update to refresh the data.
Moxa PROFINET switches support PROFINET alarms. These alarm messages will be sent by the switch
immediately when an event is triggered. These alarms can be enabled/disabled using PROFINET I/O
parameters(see chapter PROFINET I/O Parameters ).
The Channel-specific diagnostics field is displaying link-down alarm information. Click Update to refresh
the data.
3-20
Industrial Protocols PROFINET I/O
Communication Diagnosis
Select a sub-module and use PLC: Module Information to see the diagnostic data.
Topology Editor
MOXA devices support SIMATIC STEP 7 Topology editor. Click Topology Editor. View each ports connection
status in table view tag.
In the Offline/Online Comparison tab, you can compare device partner ports. Click Start to discover
connection relationships.
3-21
Industrial Protocols PROFINET I/O
You can also draw the connection of each port manually in Graphic view tab.
3-22