Ref Abb Ret670

This document contains transformer test data including: 1) Operating characteristics such as a minimum idling current of 10% and a differential current of 3A. 2) Fault current measurements for lines A, B, C and the star point at various phases. 3) CT and input data including primary and secondary currents. 4) Characteristic values showing the relationship between bias current and differential current.

Uploaded by

Zoki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
236 views

Ref Abb Ret670

This document contains transformer test data including: 1) Operating characteristics such as a minimum idling current of 10% and a differential current of 3A. 2) Fault current measurements for lines A, B, C and the star point at various phases. 3) CT and input data including primary and secondary currents. 4) Characteristic values showing the relationship between bias current and differential current.

Uploaded by

Zoki
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

Transformer Data

IBase /A 759.67

Operating characteristic
Idmin / % 10

Fault data
Idif 3
Ibias 4.7

Line Star Point


I/A Phi / I/A Phi /
IA 0.539 -60 0.000 0
IB 1.428 180 0.057 180
IC 0.539 60 0.000 0
CT Data Input Data (This data has to be entered
Line Star Point
I prim / A 2500 1000 Test Currents (These are the magnitude
I sec / A 1 1

11

10

0
0 1 2 3 4 5 6 7 8 9 10
(This data has to be entered for the calculation)

ts (These are the magnitudes and angles of the resulting test currents)

8 9 10 11 12
Characteristic Values

Ibias Idif
0 0.1
1.25 0.1
2.535714 1
11.53571 10