Mitigation of Power Quality Problems Using Custom Power Device
Mitigation of Power Quality Problems Using Custom Power Device
1806
ISSN 2321 3361 2016 IJESC
`
Research Article
Volume 6 Issue No. 6
Abstract:
A Power quality problem is an occurrence manifested as a nonstandard voltage, current or frequency that results in a failure or a
mis-operation of end user equipments. Utility distribution networks, sensitive industrial loads and critical commercial operations
suffer from various types of outages and service interruptions which can cost significant financial losses. In developing countries
like India, where the variation of power frequency and many such other determinants of power quality are themselves a serious
question, With the restructuring of power systems and with shifting trend towards distributed and dispersed generation, the issue of
power quality is going to take newer dimensions. The present work is to identify the prominent concerns in this area and hence the
measures that can enhance the quality of the power are recommended. At present, a wide range of very flexible controllers, which
capitalize on newly available power electronics components, are emerging for custom power applications. Among these, the
distribution static compensator is a most effective device which is based on the VSC principle. D-STATCOM injects a current into
the system to correct the voltage sag, swell and interruption. Comprehensive results are presented to assess the performance of
each device as a potential custom power solution. The modeling and simulation of the proposed series compensator was
implemented in Matlab Simulink work space. Simulation results showed that the proposed series compensator was efficient in
mitigating voltage sags and harmonics and thus improve the power quality of the isolated power system. This approach is different
from conventional methods and provides effective solution. If this method is enhanced in future it could provide much more
improved power quality.
Keywords: D-Statcom, MATLAB, voltage dips, swells, interruption, power quality, VSC.
I. INTRODUCTION quality, failure/malfunction of equipments etc., (ii) the
Power Electronics and Advanced Control technologies have occurrence of harmonics in the system can cause excessive
made it possible to mitigate power quality problems and losses and heating in motors, capacitors and transformers
maintain the operation of sensitive loads. Among power system connected to the system. To avoid those undesirable affects the
disturbances, voltage sags, swells and harmonics are some of proposed method mitigates the problems caused by voltage sag
the severe problems to the sensitive loads. The shunt and harmonics. The proposed system protects the sensitive load
compensation method is best suited to protect such loads by mitigating the voltage sags and harmonics using shunt
against those disturbances.The role of the compensator is not compensation technique D-STATCOM.
only to mitigate the effects of voltage sag, but also to reduce
the harmonic distortion due to the presence of non linear loads One of the most common power quality problems
in the network. In this paper, a series compensator is proposed today is voltage dips. A voltage dip is a short time (10 ms to 1
and a method of harmonic compensation is described and a minute) event during which a reduction in r.m.s voltage
method to mitigate voltage sag is investigated. magnitude occurs. It is often set only by two parameters,
depth/magnitude and duration. The voltage dip magnitude is
The proposed series compensator consists of Energy ranged from 10% to 90% of nominal voltage (which
Storage System (ESS) and Voltage Source Inverter (VSI), corresponds to 90% to 10% remaining voltage) and with a
Injection Transformer. The ESS can be a capacitor of suitable duration from half a cycle to 1 min. Voltage dips are one of the
capacity. ESS would act as a buffer and generally provides the most occurring power quality problems. Off course, for an
energy needed for load ride-through during voltage sag. industry an outage is worse, than a voltage dip, but voltage
Injection Transformer is used to inject the voltage in dips occur more often and cause severe problems and
transmission line in appropriate level. In this way the terminal economical losses. Utilities often focus on disturbances from
voltage of the protected sensitive load can be regulated to end-user equipment as the main power quality problems. This
maintain a constant level. is correct for many disturbances, flicker, harmonics, etc., but
voltage dips mainly have their origin in the higher voltage
Among power system disturbances, voltage sags, levels. A new PWM-based control scheme has been
swells and harmonics are some of the severe problems to the implemented to control the electronic valves in the two-level
sensitive loads, because (i) the occurrence of voltage sag in the VSC used in the D-STATCOM
system can cause devices/process down time, effect on product
International Journal of Engineering Science and Computing, June 2016 7650 http://ijesc.org/
II. MAIN SOURCES OF DISTORTION conventional voltage and VAR control elements, load
tap changing transformers, voltage regulators and switched
Power Quality is Any power problem manifested in voltage, capacitors used in distribution systems.
current, or frequency deviations that results in failure or
misoperation of customer equipmentssome of the primary
source of distortion can be identified as below.
International Journal of Engineering Science and Computing, June 2016 7651 http://ijesc.org/
It may be mentioned that the effectiveness of the
DSTATCOM in correcting voltage sag depends on the value of
Zth or fault level of the load bus. When the shunt injected
current Ish is kept in quadrature with VL, the desired voltage
correction can be achieved without injecting any active
power into the system. On the other hand, when the value of
Ish is minimized, the same voltage correction can be achieved
with minimum apparent power injection into the system. The
control scheme for the D-STATCOM follows the same
principle as for DVR.
International Journal of Engineering Science and Computing, June 2016 7652 http://ijesc.org/
FIGURE 4: Simulink model of D-STATCOM test system.
Figure-4 shows the test system implemented in FIGURE 9: Voltage Vrms at the load point: with Energy
Storage of 40.7kv
International Journal of Engineering Science and Computing, June 2016 7654 http://ijesc.org/