DC Machine Design
DC Machine Design
1
OUTPUT EQUATION
Pa = power developed by armature in kW
P = rating of machine in kW
E = generated emf , volts; V = terminal voltage, volts
p = number of poles; Ia = armaure current , A
Iz = current in each conductor, A
a = number of parallel path; Z = number of armature conductor
N = speed in rpm; n= speed in rps
D= armature diameter, m ; L = core length, m
= flux per pole, weber ; p = pole pitch
7
Armature reaction: if using high value of ac, armature mmf
becomes high. This means under loaded condition there will
be grater distortion of field form resulting in a large reduction
in the value of flux. To compensate this field ampere turns are
needed to be increased. Thus over all cost of copper in the
machine will increase.
Commutation: a high value of ac means either ampere
conductors used are more or diameter is small. Reactance
voltage increases with high ampere conductors. With small
diameter, deeper slots are used. Deeper slots also give higher
reactance voltage. Higher reactance voltage results in bad
commutation. Thus using higher ac affects the commutation
badly.
The value of ac varies from 15000 to 50000 ampere conductors
per meter.
8
Core length:
Factors affecting the length of core:
i) Cost : the manufacturing cost of a machine with large core
length, is less. This is because the proportion of inactive
copper to active copper is smaller for grater the length of
core. Therefore it is desirable to have large core length for
less cost.
ii) Ventilation: the ventilation of large core length is difficult
because the central portion of the core tends to attain a high
temperature rise. If long armature are necessary special
means for ventilation of core must be provided.
Limiting value of core length: the emf induced in a conductor
should exceed 7.5/TcNc in order that the maximum value at
load between adjacent segments limited to 30 V.
9
The voltage in a conductor at no load ez = Bav L Va
For a limiting case: Bav L Va = 7.5/ Tc Nc
Limiting value of core length L = 7.5/ ( Bav Va Tc Nc)
Bav = average gap density wb/m2
Va = peripheral speed, m/s
Tc = turns per coil
Nc = number of coils between adjacent segments
Armature diameter:
The peripheral speed lies between 15 to 50 m/s. As the diameter of the
armature increases, the peripheral velocity of the armature v = DN/60
m/s , centrifugal force and its effects increases. Therefore the machine
must be mechanically made robust to withstand the effect of centrifugal
force. This increases the cost of the machine. In general for normal
construction, peripheral velocity should not be greater than 30 m/s as
for as possible.
10
Limiting value of armature diameter:
Output P = E Ia x 10 -3 kW
E = emf per conductor x conductors per parallel path
= ez Z/a
P = ( ez Z/a) Ia x 10-3 = ez (Iz . Z/a ) x 10-3
= ez D ac x 10-3
D = (P x 10-3)/ ( ac ez)
11
Selection of number of poles
Factors affecting the number of poles:
1. Frequency: As the number of poles increases, frequency of the
induced emf f = 120/PN increases, core loss in the armature
increases and therefore efficiency of the machine decreases.
2. Weight of the iron used for the yoke: Since the flux carried by the
yoke is approximately /2 and the total flux T = p is a constant
for a given machine, flux density in the yoke
13
14
15
16
17
Length of air gap:
i) Armature reaction: to prevent excessive distortion of field form by
armature reaction the field mmf must be large as compare to armature
mmf. A machine designed with long air gap requires large field mmf.
Thus the distortion effect of armature reaction can be reduced by large
air gap length.
ii) Circulating current: if air gap length is small, a slight irregularity in
the air gap would result large circulating current.
iii) Noise: the operation of machine with large air gap length is
comparatively quite.
iv) Cooling: machine with large air gap length have better ventilation.
v) Pole face losses: if the length of air gap is made large, the variation in
air gap flux density due to slotting are small. Therefore pulsation loss
in the pole faces decreases.
18
Estimation of air gap length:
Mmf required for air gap ATg = 800000 Bg Kg lg
And armature mmf per pole ATa = ac/2
The value of gap mmf is normally between 0.5 to 0.7 of armature
mmf. The usual value is 0.55.
ATg = (0.5 to 0.7) ATa = (0.5 to 0.7) ac/2
19
20
21
Number of armature conductors
The generated emf in the armature
E = V + Ia Rm for generator
E = V - Ia Rm for motor
where V = terminal voltage and
Rm = sum of voltage drop in the armature winding, inter-pole winding,
series winding and brush contact drop
i) For large 500 volt machine IaRm = 2 to 2.5% of terminal voltage
ii) For small 250 volt machine IaRm = 5 to 10% of terminal voltage
Total number of conductors in series Zc = E/mean emf per conductor
= E/ez
For a simplex lap winding Zc represent total number of armature
conductor per pole. (A=P)
For a simplax wave winding Zc represent half the total number of
conductor on the armature irrespective of number of poles. (A=2) 22
23
Number of armature slots:
The following factors are to be considered while selecting the
number of slots:
1. Flux pulsations:- flux pulsation means changes in the air gap
flux because of changes in the air gap reluctance between he
pole faces and irregular armature core surface. Flux pulsation
losses rise to eddy current losses and produce magnetic noise.
The flux pulsations are reduced with increased number of
slots.
2. Cooling:-for large number of slots, lesser number of
conductors per slot therefore, cooling is better.
3. Commutation:- for commutation point of view, large number
of slots and smaller number of conductors per slot are better.
24
4. Tooth width:- for large number of slots the slot pitch reduces
and also the tooth width. With reduction in tooth width flux
density at the minimum section of tooth increases causing
increase in iron losses.
5. Cost:- cost of punching slots in stampings increases with the
number of slots to be punched.
25