AccuTrak Rotary Position Monitors

Explosionproof NEC

Fully integrated and encapsulated rotary valve position


monitors that are certified for use in explosive atmospheres.

Features
Touch set cams are hand adjustable,
spring loaded and self-locking providing
quick calibration of position switches
and sensors.
Terminal strips are pre-wired and
numbered with generous working space
for ease of use.
Strong durable BeaconTM offers 360
visual indication available in a choice of
styles and colors.
Additional conduit for easy field wiring
and mounting accessories as standard.
Standardized mounting pattern for easy
adaptation to common bracketry.
NAMUR shaft output compliant to VDI/
VDE 3845 available.
Analog position transmitter option.
Eliminator option for easy integration of
external solenoid valve.
Aluminum enclosures with ultra-
low copper content (0.2% maximum)
ensure robust performance in corrosive
environments.
Technical Data Rugged stainless steel enclosures.
Agency approvals
Area classification (NEC 500)
Models 2007/5050/9479 Class I, Division 1, Groups C & D/ T6 Ta = 60C
Class II, Division 1, Groups E, F & G/ T6 Ta = 60C
Model 9479 Class I, Division 2, Groups A,B,C & D/T4 Ta = 60C
Model 5050 Class II, Division 2, Groups E, F & G/T6
Model 360/366 Without eliminator conduit option
Class I, Division 1, Groups B, C & D
Class II, Division 1, Groups E, F & G
With eliminator conduit option
Class I, Division 1, Groups C & D
Class II, Division 1, Groups F & G
Enclosure standards (ANSI/NEMA 250)
All enclosures Type 4, 4X
Switches
Model 2007 V3 mechanical switches, SPDT
DPDT mechanical switches
GO switches

Model 5050 Pepperl + Fuchs model NJ2-V3-N


Model 9479 Magnum (hermetically sealed proximity type)
MagPAC bifurcated switch pack
Models 360/366 V3 mechanical switches, SPDT
DPDT mechanical switches
Magnum (hermetically sealed proximity type)
Enclosures
Models 2007/5050/9479/360 Aluminum
Models 2007/9479/366 Stainless steel

www.westlockcontrols.com
Copyright Westlock. All rights reserved WESTDS-09005-US-1305
AccuTrak Rotary Position Monitors
Explosionproof NEC

Models 2007/5050/9479 dimensions


162.62 CONDUIT ENTRY x4 MAX
[6.402] SEE OPTIONS TABLE ON HOUSING 57.1 5
MACHINING DRAWING FOR DETAILS [2.250 ]
98.85
[3.892 ] 28.5 6
[1.124 ] 4 HOLES M6 X 1.0P X .375 DEEP

[ 1. 011]
[3. 059]
77.70

25.7

[ 0.69 6]
17.67
EXTERNAL
EARTH (M5)
[ 6. 118]

[1. 392]
155.40

35.36
[ 1. 011]
25.7
VIEW ON UNDERSIDE

64
[2.523]
4 HOLES 5/16 - 18 UNC X 0.50 DEEP
OR M8 X 1.25P X 8 DEEP
[ 6.210]
157.73

[ 0.350]

[ 0. 1 9 6]
8. 89

4.98

6.35

[ 0. 546]
A/F

[ 0. 250]
[0.250 ]

13.9

6 .3 5
9.52 5
9.51 3
[ .375
.374 5]
0

3.98
4.85
[ 1.297]

[ 1.124]

3.93 A/F
[ ]
28. 55

[0.191 ] .156 7
33

.154 7
OPTIONAL SHAFT ARRANGEMENT
9.52 5
9.51 3
[ .3750
.3745 ] NAMUR SHAFT ARRANGEMENT
56.11
[2.209 ]

Dimensions in inches, where available metric dimension (mm) in parentheses.


Technical specifications
Materials of construction
Enclosure Aluminum with powder coat finish
Shaft and hardware Stainless steel
Bushing Oil impregnated bronze
Beacon visual indicator Co-polyester
Drive shaft
Standard Double-D with A/F
Option NAMUR standard VDI/VDE 3845
Available switches
Model 2007 V3 mechanical switches, SPDT
DPDT (form CC) mechanical switches
GO switches
Model 5050 Pepperl + Fuchs model NJ2-V3-N
Model 9479 Magnum (hermetically sealed proximity type)
MagPAC bifurcated switch pack
Options
Models 2007/9479 Stainless steel enclosure
Models 2007/9479 4-20 mA position transmitter

Please consult your sales office for any other requirements

Notes
Conduit entries
Accutrak position monitors are available with a choice of conduit entries. Please see the
selection guide for standard entries.

Switches and sensors


For further information see our switches and sensors data sheet.

Eliminator fitting
A specialist eliminator fitting is available for the purpose of mounting an aftermarket solenoid
valve.

Copyright Westlock. All rights reserved Page 2


AccuTrak Rotary Position Monitors
Explosionproof NEC

Models 360/366 dimensions

3.19
[81.01]
TYP

30
TYP

CONDUIT SIZE AVAILABLE: 3/4 NPT


CONDUITS TO BE SPECIFIED AT TIME OF ORDER
5.00 COVER LOCKING SCREW
[127.41]

*5.25
[133.29] *7.44 CLEARANCE FOR VOER
REMOVAL
.29 3.07
[7.27] [77.92] 2.26
.54 [57.35]
[13.75]

EXTERNAL EARTH M6
BEACON FIXING M6 SEE DETAIL A
CONDUIT A
.3750 CONDUIT B

.3745 3.15 4X M8 x 1.25P CONDUIT C
2.25 SEE NEMUR
THRU
[57.15] SHAFT DETAIL
.248 SQU
.246 .3750
ACROSS FLAT .3747

.59
[14.99]

.255 3.10 1.18 4.41 5.24 .157


[6.47] [78.33] [29.97] [111.81] [132.90] [3.98] .35
[8.89]

.191
[4.85] .078
.124 [1.98]
DETAIL A
.157
.123 4X .22 THRU
1.13 SCALE 2:1 [3.98]
[28.57] DETAIL B
DETAIL A
SCALE 2:1 1.57 SCALE 2:1
[39.87]
6.54
[166.16] NAMUR SHAFT DETAIL

Dimensions in inches, where available metric dimension (mm) in parentheses.

Technical specifications
Materials of construction
Enclosure
Model 360 Aluminum with powder coat finish
Model 366 Stainless steel with electropolished finish
Shaft and hardware Stainless steel
Bushing Oil impregnated bronze
Beacon visual indicator Co-polyester
Drive shaft
Standard Double-D with A/F
Option NAMUR standard VDI/VDE 3845
Available switches
V3 mechanical switches, SPDT
DPDT (form CC) mechanical switches
Magnum, SPDT hermetically sealed switches,
with tungsten contacts
Magnum, SPDT hermetically sealed switches,
with rhodium contacts
Options
Models 360/366 4-20 mA position transmitter
Please consult your sales office for any other requirements

Notes
Conduit entries
Accutrak position monitors are available with a choice of conduit entries. Please see the
selection guide for standard entries.

Switches and sensors


For further information see our switches and sensors data sheet.

Eliminator fitting
A specialist eliminator fitting is available for the purpose of mounting an aftermarket solenoid
valve.

Copyright Westlock. All rights reserved Page 3


AccuTrak Explosionproof Rotary Position Monitors
Model 2007 Selection Guide

Base model
2007 Aluminum enclosure
Shaft output
S Standard (double-D with Flats)
N NAMUR
Beacon
BY BM2-Y (standard)
RG BM2-RG (Red Closed/Green Open)
FE BM2-Y-FE (French/English)
AB BM2-B
AR BM2-R
B1 BM3-1
B3 BM3-3
B5 BM3-5
B7 BM3-7
B9 BM3-9
FC Flat cover
Conduit
2B Two NPT (F)
4B Four NPT (F)
2E One NPT (F) and one NPT (M) eliminator fitting
4E Three NPT (F) and one NPT (M) eliminator fitting
4F Two NPT (F) and two NPT (M) eliminator fittings
Position switches
2M02 Two SPDT mechanical switches - 8 pt. TS
4M02 Four SPDT mechanical switches - 16 pt. TS
6M02 Six SPDT mechanical switches - 24 pt. TS
2M04 Two DPDT mechanical switches - 16 pt. TS
4M04 Four DPDT mechanical switches - 24 pt. TS
2M03 Two SPDT GO switches - 12 pt. TS
4M03 Four SPDT GO switches - 16 pt. TS
Analog position transmitter
00 None
CS 4-20 mA position transmitter (not available with 4M04, 6M02, 2M03, 4M03 switch options)
12 pt. TS w/2M02;
16 pt. TS w/2M04 and 4M02

2007 N BY 2B 2M02 00 = Model number 2007NBY2B2M0200

For stainless steel enclosure, please add 00124 to the end of your part number built with the selection guide above.

Notes
Specifying your position monitor
Specifying a position monitor is a complex process as there are many variables which affect
each individual application. To ensure that you receive the best possible combination for your
monitoring requirement, please contact your local sales office for advice and guidance from one
of our experts.

Hazardous area classification


Please see our data sheet for further information on the global standards affecting the
specification and installation of equipment in hazardous areas.

Copyright Westlock. All rights reserved Page 4


AccuTrak Explosionproof Rotary Position Monitors
Model 5050 Selection Guide

Base model
5050 Aluminum enclosure

Shaft output
S Standard (double-D with Flats)
N NAMUR
Beacon
BY BM2-Y (standard)
RG BM2-RG (Red Closed/Green Open)
FE BM2-Y-FE (French/English)
AB BM2-B
AR BM2-R
B1 BM3-1
B3 BM3-3
B5 BM3-5
B7 BM3-7
B9 BM3-9
FC Flat cover
Conduit
2B Two NPT (F)
4B Four NPT (F)
2E One NPT (F) and one NPT (M) eliminator fitting
4E Three NPT (F) and one NPT (M) eliminator fitting
4F Two NPT (F) and two NPT (M) eliminator fittings
Position switches
2M08 Two P+F sensors model NJ2-V3-N - 8 pt. TS
Analog position transmitter
00 Not available

5050 N BY 2E 2M08 00 = Model number 5050NBY2E2M0800

Notes
Specifying your position monitor
Specifying a position monitor is a complex process as there are many variables which affect
each individual application. To ensure that you receive the best possible combination for your
monitoring requirement, please contact your local sales office for advice and guidance from one
of our experts.

Hazardous area classification


Please see our data sheet for further information on the global standards affecting the
specification and installation of equipment in hazardous areas.

Copyright Westlock. All rights reserved Page 5


AccuTrak Explosionproof Rotary Position Monitors
Model 9497 Selection Guide

Base model
9479 Aluminum enclosure
Shaft output
S Standard (double-D with Flats)
N NAMUR
Beacon
BY BM2-Y (standard)
RG BM2-RG (Red Closed/Green Open)
FE BM2-Y-FE (French/English)
AB BM2-B
AR BM2-R
B1 BM3-1
B3 BM3-3
B5 BM3-5
B7 BM3-7
B9 BM3-9
FC Flat cover
Conduit
2B Two NPT (F)
4B Four NPT (F)
2E One NPT (F) and one NPT (M) eliminator fitting
4E Three NPT (F) and one NPT (M) eliminator fitting
4F Two NPT (F) and two NPT (M) eliminator fittings
Position switches
2M06 Two SPDT Magnum switches with tungsten contacts - 8 pt. TS
2M12 Two SPDT Magnum switches with rhodium contacts - 8 pt. TS
2M13 MagPAC module (SPST bifurcated switches with LEDs)
4M06 Four SPDT Magnum switches with tungsten contacts - 16 pt. TS
4M12 Four SPDT Magnum switches with rhodium contacts - 16 pt. TS
6M06 Six SPDT Magnum switches with tungsten contacts - 24 pt. TS
6M12 Six SPDT Magnum switches with rhodium contacts - 24 pt. TS
Analog position transmitter
00 None
CS 4-20 mA position transmitter (not available w/6M06 and 6M12)
12 pt. TS w/2M06 and 2M12
16 pt. TS w/4M06 and 4M12

9479 N BY 2B 2M12 00 = Model number 9479NBY2B2M1200

For stainless steel enclosure, please add 00124 to the end of your part number built with the selection guide above.

Notes
Specifying your position monitor
Specifying a position monitor is a complex process as there are many variables which affect
each individual application. To ensure that you receive the best possible combination for your
monitoring requirement, please contact your local sales office for advice and guidance from one
of our experts.

Hazardous area classification


Please see our data sheet for further information on the global standards affecting the
specification and installation of equipment in hazardous areas.

Copyright Westlock. All rights reserved Page 6


AccuTrak Explosionproof Rotary Position Monitors
Models 360/366 Selection Guide

Base model
360 Aluminum enclosure
366 Stainless steel enclosure
Shaft output
S Standard (double-D with Flats)
N NAMUR
Beacon
BY BM2-Y (standard)
RG BM2-RG (Red Closed/Green Open)
Conduit
2B Two NPT (F)
3B Three NPT (F) (360/366 only)
2E One NPT (F) and one NPT (M) eliminator fitting
3E Two NPT (F) and one NPT (M) eliminator fitting
Position switches
2M02 Two SPDT mechanical switches - 10 pt. TS
2M04 Two DPDT mechanical switches - 14 pt. TS
2M06 Two SPDT Magnum switches - 10 pt. TS
2M12 Two SPDT Magnum switches with rhodium contacts - 10 pt. TS
4M02 Four SPDT mechanical switches - 14 pt. TS
4M06 Four SPDT Magnum switches - 14 pt. TS
4M12 Four SPDT Magnum switches with rhodium contacts - 14 pt. TS
Analog position transmitter
00 None
CS 4-20 mA position transmitter - 10 pt. TS (only available with 2M02, 2M06, 2M12 switch options)

360 N BY 2B 2M12 00 = Model number 360NBY2B2M1200

Notes
Specifying your position monitor
Specifying a position monitor is a complex process as there are many variables which affect
each individual application. To ensure that you receive the best possible combination for your
monitoring requirement, please contact your local sales office for advice and guidance from one
of our experts.

Hazardous area classification


Please see our data sheet for further information on the global standards affecting the
specification and installation of equipment in hazardous areas.

US/Canada: Saddle Brook, NJ South America: Sao Paulo, Brazil Europe: Kent, England Asia: Singapore
Ph: +1 201 794 7650 Ph: +55 11 2588 1400 Ph: +44 1892 516277 Ph: +65 6768 5850
Fax: +1 201 794 0913 Fax: +55 11 2588 1410 Fax: +44 1892 707620
E-mail: [email protected] E-mail: [email protected] E-mail: [email protected] E-mail: [email protected]

Copyright Westlock. All rights reserved Page 7