1 OMC2015 ISA YOKOGAWA Optimization Vs Performance
1 OMC2015 ISA YOKOGAWA Optimization Vs Performance
Performance in the
modern process control systems
Massimiliano Veronesi
Sales Support and Marketing
Process Control & Safety Systems
Vigilant Plant Services & Solutions
Yokogawa Italy OMC 2015
Ravenna
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Contents
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Why we are here: the Industry Challenge
Increasing
Strong Regulations Supply/Demand
competition Fluctuation
Consumer
Safe &
Secure Streamlined power
Operational
Operation Production
Excellence
Maximum
Quality
Asset
Aging utilisation
Assurance
Operators
Plant
Lifecycle
Project Execution
Managing uncertainty, project complexity, late changes, cost overruns, and
deplays. The challenges gets even greater when the lack of manpower and
technical resources are factored in.
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Versatile Hardware and Flexible
Project Execution
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Design & development: Smart Engineering
Asset
Automation Design Suite Management
System
Integration
Yokogawa
repository Historian
(module library)
MES
A
Solution
Module Bulk Change Auto Doc Flexible Packages
engineering engineering management generation binding
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Software debugging: Virtual Test Function
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Avoiding Project Delays
Marshalling
Controller IOM Junction box
board
Universal I/O
Marshalling
Controller IOM Junction Box
baord
- 11 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Next Generation Smart I/O: N-IO (Network I/O)
Termination block
- 13 -
IO network Configuration
System Network Vnet/IP
Node Interface Unit
Up to 100m - Lower performance
- Heavy load in the
by copper FCS system network might
affect real-time
computations
N-ESB bus
- Less secure
- System network is
connected to OWS
- Less robust
- Field environment
might be hard for std.
switches, hubs
Performance
first !
N-ESB bus
Up to 50 Km by optical fiber, 100 Mbps
Cat5e cable
No hub or switch is required
- 15 - - 15 -
IO network Configuration
System Network Vnet/IP
Node Interface Unit
Up to 100m
by copper FCS
N-ESB bus
N-ESB bus
Up to 50 Km by optical fiber, 100 Mbps
Cat5e cable
No hub or switch is required
- 16 - - 16 -
Termination
Terminals
Terminal Board
Duct Duct
Smart IO
Terminal Board
Smart IO
Field Cables Field Cables
(Multicore) (Multicore)
- 18 -
Footprint: N-IO vs. Conventional IO
Conventional
X5 X5 X7 17
Cabinets
A-IO:
2,000
System Analog Mar. Digital Mar.
D-IO: Cabinet Cabinet Cabinet
3,000
Total:
5,000
10
N-IO
X1 X9
Cabinets
System N-IO
Cabinet Cabinet
<OMC2015_Yokogawa>
- 19
Copyright Yokogawa - Corporation
Electric
<March 24, 2015>
N-IO for Hazardous Applications
- 20 -
Field Loop-Check wihout the controller
HIS AD Suite Project
Database
Vnet/IP
SCS FCS FCS
Local Cabinet can ship to site w/o FCS.
ESB Bus ESB Bus
N-ESB Bus
Scope of New
Validation Tool (VT)
- 21 -
Comparing With Current work and Flexible Binding Workflow
Construction Phase
Current Workflow (CPU, Cabinet,
Transmitter)/
CPU
TEST
Connection /
indiv. Loop check
Total Loop
Check/
Commissioning
Opera-
tion
Execution FAT Shipping Wiring Work
I/O Binding
(Freeze specification) End of Execution
Construction
(Cabinet, CPU Total Loop
Connection / Opera-
CPU
Check/
Transmitter)/ indiv. Loop check Test Commissioning
tion
Wiring Work
Execution FAT Shipping
Work at site - 22 -
Work in-house
Virtualization
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Why virtualization in industrial plants now ?
- 25 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
CAPEX Reduction - General Evaluation -
Adopting VMware for
virtualization
1:10 server consolidation ratio
(10 virtualized machines can
run in a server)*
Lower electric power
consumption and cooling cost
Reduction of maintenance cost 600
Reduction of footprint
400
Smoother component migration
Easy backup and restore 200
KUSD
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
OPEX Reduction - General Information -
No. cabinet 3 1 8 1 15 2
Small/medium/large $200,000
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Types of Virtualization: Host type vs. Hypervisor type
- 28 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Comparison between Host type and Hypervisor type
Virtual Network
Actual network
Virtualization S/W
- 30 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
The performance issue
If the PC is a quad core machine then 3 virtual machines may be the
maximum to be deployed (1 core for the main application and 1 core for
each of the 3 virtual PCs). If Hyper-threading is enabled, then double the
number of cores are required.
(Number of requested cores) = (CPU reservation frequency) (Frequency of
CPU of physical server) x 2 if HT is enabled
(CPU reservation frequency) = (CPU req. frequency) x (Number of cores) 2
Es.: Required CPU resources are 3.00 GHz and 4 cores, with 2.8GHz physical Server:
(CPU reservation frequency) = 3.00 GHz x 4 cores 2 = 6 GHz
(Number of req. cores) = (6/2.8) 2 = 2.14 2 = 4.28 5 (rounded up)
Condition:
[CPU reservation frequency of Yokogawa Products] x 1.25 < [CPU
resource]
Where [CPU resource] = [CPU frequency - in GHz] x [No. of cores] x [No. of CPUs]
Es. Sum of CPU reservation frequency = 6.00 + 6.00 = 12.00 GHz
the CPU resource for one server machine with frequency 2.60 GHz and 8 cores is 2.6 GHz x
8 cores = 20.8 GHz
12.0 x 1.25 (VMSphere Overhead) < 20.8
- 31 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
The performance issue
Using SAS3 or RAID4 configuration to secure the performance is needed.
Using SSD5 is not recommended because of lower endurance.
VMware allows three types of formatting for virtual storages. It is strongly recommended
to adopt Thick provisioning (Eager Zeroed) with securing area in advance and with
executing zero formatting. Using Thin provisioning causes lower performance, and Lazy
Zeroed causes disk access error.
It is mandatory to configure the Yokogawa product to use enough memory
area exclusively to secure performance in both off and on-process.
Generally the clock of guest OSs may be delayed when the load on
Hypervisor becomes too high. If the demand of time synchronization is
severe, the synchronization period should be set shorter.
One physical server PC failure stops multiple server functions: highly
available industrial server is recommended
SAS (Serial Attached SCSI): The interface to connect up devices for hard disk drives to computers
RAID : Redundant Array of Independent Disks
SSD : solid-state drive using flash memory
- 32 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Virtualization Benchmarking
Current Yokogawa
System architecture
Virtualized Architecture
Vnet or Vnet/IP
FCS
- 35 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Example of on-process systems
Client stations
VM Server
AMS Instr.
Historian Pilot APC KPI
SOE Maint.
Win
Win 7 Win 7 Win 7 Win 7 Win 7
ENG/HIS HIS 2008
OPC
VMware
Vnet or Vnet/IP
FCS
- 36 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Example of off-process systems Operator Training systems
VMWare
OTS on VM Server
- 37 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Other performance vs. optimization
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Integration with subsystems: which way ?
Sub-system communications Modbus / Profibus
Redundant Configuration is
Data for HMI: OPC/ModbusTCP available.
Client (redundant) workstation
can manage up to 100,000
variables DCS network
Data for control logics: put
(redundant) communication UGS
module in one rack of the related
CPU in charge
RTU network
- 40 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Integrated Process Control & Safety System
Integrated Control+Safety system provides optimization
+ performance at the same time
Application SIS Application DCS
SIS DCS
Data Tagnames equalization Data
base base
EWS EWS
SIS DCS
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Multi-monitor vs. performance
Multi-monitor/Graphic windows
Each mimic call data from the system bus
while one single operator cannot pay
attention to more than 512 windows at the
same time: prevent it by limiting the number
of graphic windows which can be called by
the operator by FIFO mechanism.
- 42 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Others ways to optimization
Alarm optimization
Complying to ISA18.2 and Eemua-191 Standard
Control Loop Performance Monitoring
Evaluate improvements through simulations
Best Practices Employment
Operator sequences executed by flow-charts
Plant performance quantitative
measurements
KPI, Downtime analysis, Data reconciliation
Sequence of events and Safety Functions
monitoring
Energy management
Monitoring or optimization
APC
Multivariable Predictive Control
- 43 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
APC: Multivariable Predictive Control
104
100
PERCENT OF LIMIT
98
Benefits
96
94
Operator target
92 Standard deviation
SETPOINT MOVED of controlled variable
BEFORE APC APC ONLINE CLOSER TO LIMIT
90
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Optimization aimed solutions
Safety and
Production Asset Energy Knowledge
Security
Human
Production Asset Energy Asset Procedure
Performance Performance Performance Environment Performance
Protection
Process
Supply Chain Greenhouse
Predictive Control Knowledge
Management Environment
Maintenance Domain Retention
Performance Control
Security
- 45 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Wireless Transmitters: be careful with PID control
- 46 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Conclusions
Different kind of Optimization or Functions are attractive and may lead to
significant Capex/Opex reductions
but also to some performance issues.
Clever engineering should carefully consider the right balance between
optimization and performance with respect to the specific application
- 47 - <OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
<March 24, 2015>
Thank you for your
attention!
<ISD-MASP-S13070>
Copyright Yokogawa Electric Corporation <OMC2015_Yokogawa>
<Feb. 2014> Copyright Yokogawa Electric Corporation
<March 24, 2015>
Any question ?
<OMC2015_Yokogawa>
Copyright Yokogawa Electric Corporation
Proprietary <March
info goes here
24, 2015>
50