Transducer1: Test Object - Device Settings Substation/Bay
Transducer1: Test Object - Device Settings Substation/Bay
. .
Test Object - Device Settings
. . .
Substation/Bay:
Substation: TRAM 500KV Substation MEKONG 2.2 - PHU
address: MY- TAN THANH- BA
RIA VUNG TAU
Bay: Bay address:
. . .
Device:
Name/descriptio MEASUREMENT Manufacturer: FRANCE
n: TRANSDUCER
Device type: PAR 1233 B TNE 4F Device address:
1636
Serial/model 2318484 D
number:
Additional info MEKONG 2.2
1:
Additional info
2:
Test Settings
Point 1 2 3 4 5
Nominal Input: -30.000 MW 165.000 MW 360.000 MW 555.000 MW 750.000 MW
Test runs: 1 1 1 1 1
Voltage L1: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L1: 0.000 0.000 0.000 0.000 0.000
Current L1: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L1: 180.000 0.000 0.000 0.000 0.000
cos (Phi) L1: -1.0000 1.0000 1.0000 1.0000 1.0000
Voltage L2: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L2: -120.000 -120.000 -120.000 -120.000 -120.000
Current L2: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L2: 60.000 -120.000 -120.000 -120.000 -120.000
cos (Phi) L2: -1.0000 1.0000 1.0000 1.0000 1.0000
Voltage L3: 288675.135 V 288675.135 V 288675.135 V 288675.135 V 288675.135 V
Phase (V) L3: 120.000 120.000 120.000 120.000 120.000
Current L3: 34.641 A 190.526 A 415.692 A 640.859 A 866.025 A
Phase (I) L3: -60.000 120.000 120.000 120.000 120.000
cos (Phi) L3: -1.0000 1.0000 1.0000 1.0000 1.0000
Frequency: 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz 50.000 Hz
Waveform: Sine Sine Sine Sine Sine
Comment
. .
Test Module
Name: OMICRON Transducer Version: 3.00
Test Start: 28-Nov-2016 14:49:11 Test End: 28-Nov-2016 14:49:31
User Name: Manager:
Company:
.
Test State:
Test
failed