Building Control Guidance Note: Sprinkler Systems
Building Control Guidance Note: Sprinkler Systems
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/10/10 Rev Page 1
A new updated version of Approved Document B comes into force from the 6th April 2007.
Transitional Provisions.
Applications for any new building work that are made on or after 6th April 2007 will be required to follow the
new guidance.
This Guidance Note covers the main changes to Volume 2 Buildings other than Dwelling Houses.
Flats are not included in this guide but are covered by this Approved Document.
Rather than go through every provision of the new guidance, the main changes will be identified and guidance
provided.
Reference should be made to the full versions of the documents, which can be downloaded from Tameside
Web Page (link).
SPRINKLER SYSTEMS.
The document has expanded the guidance on sprinklers, which can significantly reduce the risk to life and
degree of damage incurred in a fire.
Sprinkler protection can be used as compensatory features against some of these Approved Documents
Recommendations.
As a general rule, sprinkler protection should be provided throughout the building where it is intended to be
provided. However, where the sprinklers are being installed as a compensatory feature to address a specific
risk or hazard, it may be accepted to only part of the building, for instance a separated part or separate fire
compartment.
NOTE: Any sprinkler system installed to satisfy Part B requirements must be a LIFE SAFETY SYSTEM.
However, there may be some circumstances where a particular life safety requirement, specified in BS 5306-2
or BS EN 12845 is inappropriate or unnecessary.
1
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/10/10 Rev Page 2
(5) whichever water storage arrangement is used at (3) or (4) above, the total capacity of water
supply, including any inflow for a reduced capacity tank should be at least equivalent to a
single full holding capacity tank complying with Table 9, 10 or clause 9.3.2.3 as appropriate to
the hazard and pipework design.
Where pumps are used to draw water from 2 tanks, then each pump should be arranged to draw water from
either tank and arranged so that any one pump on either tank could be isolated.
The sprinkler water supplies should generally not be used as connections for other services or fixed fire
fighting systems.
2
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 3
INCLUSIVE DESIGN.
Fire safety aspects of the Building Regulations apply to all persons, including people with disabilities.
Fire safety measure must be incorporated into a building taking in to account people of all ages and disabilities.
The guidance offered covers most reasonable standard provision, however, there may be some situations
where additional measures may need to be provided to accommodate special needs of certain groups of
people.
Healthcare Premises.
HTM 05 Firecode should be used for the design of hospitals and similar health care premises.
Schools.
Schools should now be designed in accordance with Building Bulletin 100. Part B will typically be satisfied
where the life safety guidance in this document is followed.
Sheltered Housing.
Many of the provisions set out in this guide for flats are applicable to sheltered housing, however, the
occupancy nature may necessitate some additional fire protection measures dependent upon the form of
development.
3
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2 .
Guidance Note Issued 01/01/07 Rev Page 4
SMALL BUILDINGS / PREMISES this could be a simple method of raising an alarm, e.g. if all occupants
can see and hear each other shouted warnings may be sufficient. It must be determined that the warning
can be heard and understood throughout the premise including for example in toilets, etc.
Manual sounders could be an improvement, i.e. gongs/hand bells may also be appropriate.
A simple manual call point combined with a bell, battery and charger would obviously be better still.
IN ALL OTHER CASES building should be provided with a suitable electrically operated fire alarm system
with manual call points sited adjacent to exit doors and sufficient sounders to be clearly audible throughout the
building, e.g. in compliance with BS 5839-1:2002.
Type P systems
P1 - systems installed throughout the protected building.
P2 - systems installed only in defined parts of the protected building.
Call points for electrical alarm system to comply with BS 5839-2:1983 or Type A BS EN54-11:2001 and be
installed in accordance with BS 5839-1. Type B call points only to be used with approval of Building Control.
To improve occupants response to an alarm activation, voice alarm systems have significant benefits in
advising occupants of an alarm situation. BS 5839-8:1998 provides guidance.
Fire alarm warning systems must be distinct from other signals, which may be in general use.
In certain premises, e.g. large shops, places of assembly, an initial alarm may be undesirable because of the
number of members of the public present. The need for fully trained staff to effect pre-planned procedures for
safe evacuation will therefore be essential. Activation of the fire alarm system will cause staff to be alerted,
e.g. by discreet sounders, personal paging systems. Provision will normally be made for full evacuation of the
premises by sounders or a message broadcast over the public address system. In all other respects, any staff
alarm systems should comply with BS 5839-1.
Interface between fire detection and fire alarm systems and other systems.
Fire detection and fire alarm systems are sometimes used to initiate the operation, or change of state of other
systems, e.g. smoke control systems, fire extinguishing systems, door releases, etc.
To ensure adequate means of escape is maintained, the interface between systems must have a high degree
of reliability.
Particular care should be taken if the interface is facilitated via another system. Where any part BS 7273
applies to actuation of other systems), the recommendations of that standard should be followed.
5
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 6
B1 - Means of Escape.
Schools references now removed throughout as now covered by Building Bulletin 100.
6
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 7
7
.
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 8
Escape routes should not be prejudiced by openings between floors, such as an escalator (see diagram 14).
(b) there is an alternative escape route which does not pass within 4.5m of the open connection.
8
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 9
9
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 10
Note 5 refers to determining floor space factors from concourses by Football Licensing Authority for
concourses in sports ground.
10
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 11
Note: where the number of persons (N) entering the lobby from the ground floor is more than 60 then the
distance from the foot of the stair, or the storey exit, to the final exit should be 2m minimum.
Where this cannot be achieved then the width of the final exit (W) should be no less than the width of the stair
plus the width of the storey exit.
Worked Example:
Ground floor storey exit 250 persons share a common final exit with 1.2m wide stair
Required final exit = ((250/2.5) + (1.2 x 60))/80 width (metres) = 2.150m
11
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 12
Protected Corridors.
3.24 Clarification added that recesses and extensions not exceeding 2m deep are not treated as dead end
conditions.
Any door which could provide a path for smoke to bypass the sub-division should be made self-closing (but
need not necessarily be fire resisting).
12
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
Issued 01/01/07 Rev Page 13
Small Premises.
Completely new section bringing in BS 5588-11 provisions into the Approved Document.
They do not apply to premises used principally for the storage and/or sale of highly flammable liquids or
materials.
In covered shopping complexes you must refer to small units design requirements in BS 5588-10.
Requirements:
(a) Premises to be in single occupancy and to comprise of no more than a basement, a ground floor and a
first floor. Maximum 280m2 floor area to each storey (see dia 18).
(b) Kitchens or other cooking arrangements to be sited at the extremity of any dead end and be remote
from the exits; and
(c) Planned seating accommodation or assessed standing accommodation (see Table C1) for small
premises comprising a bar or restaurant should not exceed 30 persons per storey. This can be
increased on the ground storey to 100 if it has an independent final exit.
13
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
Issued 01/01/07 Rev Page 14
Construction:
1. Floor areas to be generally undivided (except for kitchens, ancillary offices and stores) ensure that
exists are clearly visible from all parts of the floor areas.
2. Store rooms to be enclosed in fire resisting construction.
3. Sufficient glazed area to be provided in any partitions separating a kitchen or ancillary office from the
open floor area to enable inner room occupants to obtain early visual warning of a fire outbreak or
provide automatic fire detection in access room area.
Note: The distance of travel in small premises with an open stairway is measured to the foot of the stair in a
basement or to the head of the stair in the first storey.
The siting of 2 or more exists or stairs should be such that they afford effective alternative directions of travel
from any relevant point in a storey.
Design for Vertical Escape Clause 4.6 - Single Escape Stairs in Small Premises
Single stair may be used from:
(a) small premises (previously described above), other than bars or restaurants.
(b) an office building comprising N.MT 5 storeys above ground storey, provided that:
(i) all travel distances comply with one direction restrictions in table 2 above.
(ii) every storey at a height greater than 11m has an alternative means of escape.
(c) A factory comprising NMT:
(i) 2 storeys above ground storey (normal risk building) provided all travel distances comply with
single direction restrictions above; or
(d) Process plant buildings with NMT 10 occupants.
14
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
Issued 01/01/07 Rev Page 15
15
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Issued 01/01/07 Rev Page 16
Each storey used for residential care to be divided into minimum 3 protected areas by compartment walls
and all floors should be compartment floors.
Every protected area is to have minimum 2 exits to adjoining, but separate protected areas. Travel distance
not to exceed Table 2 distance.
The maximum travel distance from any point to be no more than 64m to a storey exit or final exit.
A fire in any one protected area should not prevent the occupants of any other area from reaching a final
exit (see diagram 19).
16
Escape routes should not pass through ancillary accommodation (as listed below).
Adjoining protected areas into which horizontal evacuation may take place should each have a floor area
sufficient to accommodate their own residents and the evacuated residents from the largest adjoining
protected area.
Fire Detection.
L1 BS 5839-1:2002 fire alarm and detection system to be installed.
Bedrooms.
All bedrooms to be enclosed in fire resisting construction, with fire doors and every corridor serving
bedrooms should be a protected corridor.
Bedrooms are not to contain more than 1 bed (including double bed).
Ancillary Accommodation.
To be enclosed in fire resisting construction, e.g.
a) chemical stores;
b) cleaners stores;
c) clothes storage;
d) day rooms
e) smoking rooms;
f) disposal rooms;
g) plant rooms;
h) linen stores;
i) kitchens;
j) laundry rooms;
k) staff changing and locker rooms; and
l) store rooms.
Sprinkler Systems.
Where sprinklers are installed, the following variations can be made:
(a) Fire doors to bedrooms do not need self-closers.
(b) Protected areas may have more than 10 beds.
(c) Bedrooms may contain more than one bed.
Note: Management procedure will need to take account of the larger number of residents that may need
assistance and the need to manually close bedroom doors during sleeping hours.
17
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note
Issued 01/01/07 Rev Page 18
Number of refuge spaces do not have to match the number of wheelchair users in the building.
Refuges are intended to form part of a management plan to evacuate disabled persons from the building.
Provisions
(a) Refuges formed by fire compartments (see dia 20)
(b) Refuges formed by protected lobby, protected corridor or protected stairway (see dia 21)
18
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note
Issued 01/01/07 Rev Page 19
(c) An area in open air such as a flat roof, balcony, podium or similar place, which is sufficiently protected
(or remote) from any fire risk and provided with its own means of escape.
Refuges to be at least 900mm x 1400mm to allow a wheelchair to be parked clear of the normal escape route
widths and should not reduce any escape routes or obstruct the flow of persons making escape.
Refuges and evacuation lifts must be suitably signed and where in a lobby or stairway area to be marked and
signed Refuge Keep Clear.
Communication.
To facilitate evacuation of persons in refuges, an emergency voice communication (EVC) system should be
installed. This allows persons in refuge to alert others and to receive reassurance that assistance is coming.
EVC to comply with BS 5839-9:2004. Type B outstations communicating with a master station in the building
control room (if one exists) or adjacent to the fire alarm panel.
19
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note
Issued 01/01/07 Rev Page 20
Phased Evacuation.
4.27 Buildings over 30m with phased evacuation strategy design to consider the interaction of fire fighters
with people escaping the building this could be discounting of stairs.
GENERAL PROVISIONS.
Doors on Escape Routes.
Additional guidance on electronic security devices to doors.
5.11 Doors on escape routes where secured against entry when the building or part is occupied, it should
only be fitted with a lock or fastening which is readily operated, without a key, from the side approached
by people making their escape.
Doors operated by codes/swipe cards, etc., must be overriddable from the escape side.
Any
Purpose
group
windowless
w.c.s
under 8m2
now
deleted
from
requiring
emergency
lighting.
20
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Issued 01/01/07 Rev Page 21
Evacuation Lifts.
Similar provisions with the additional provision, but where a fire fighting lift has been provided to safety
requirement B5, this can be utilised as part of a management plan for evacuating disabled people. Any such
plan should include a contingency for when the Fire and Rescue Service arrive.
Exhaust points should be sited as not to jeopardize the building i.e. sited away from final exits, combustible
claddings or roofing materials and openings into buildings.
Ventilation ducts supplying or extracting air directly to or from a protected escape route should not also
serve other areas. (Separate ventilation system should be provided for each protected stair).
Ductwork serving more than one part of a sub-divided escape routes, a fire damper should be provided
where ductwork enters each section of escape route operated by a smoke detector or suitable fire detection
system. Fire dampers are to close when smoke is detected.
Ducts passing through the protected escape route enclosure should be fire-resisting.
NOTE: Fire dampers activated only by fusible links are not suitable for protected escape routes (ES
classified fire and smoke damper activated by a suitable fire detection system may be used.)
Systems that re-circulates air must have smoke detectors fitted in the extract ductwork before the point of
separation of the re-circulated air and the air to be discharged to open air and before any filters or other air
cleaning equipment. Such detectors should:
a. Immediately shut down the system; and b. Switch the ventilation system from re-circulating mode to
extraction to open air, so as divert any smoke out to outside.
Non-domestic kitchens, carparks and plant rooms are to have separate and independent extraction systems
and the extracted air should not be re-circulated
Where a pressure differential system is installed, ventilation and air conditioning plant requirements are
given in BS5720: 1979
Guidance on the provision of smoke detectors in ventilation ductwork is given in BS5839-1; 2002. Refer
also to BS 5588: Part 9 Fire precautions - Code of practice for ventilation and air conditioning ductwork.
21
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note
Issued 01/01/07 Rev Page 22
Revised
wording
mentioning
automatic fire
suppression
systems.
SECTION 8 COMPARTMENTATION.
Flats additional requirements
8.14 Blocks of flats with a floor more than 30m above ground level should be fitted with a sprinkler system.
NOTE: Sprinklers to be fitted to flats only and do not have to be fitted to common areas. For the purposes of
this paragraph the limit on the scope of BS 9251: 2005 to buildings below 20m in height can be ignored.
22
Single storey
New Note 4 how to measure
max floor area /
Compartment Height i.e. from
height without
finished floor level to
sprinklers or
underside of roof or ceiling.
compartmentation
Compartment walls must be able to accommodate the predicted deflection of the floor above by either:
(a) having a suitable head detail between wall and floor, that can deform but maintain the junctions fire
integrity;
(b) wall to be designed to resist additional vertical load from the floor above as it says under fire conditions
and thus maintain integrity.
NOTE: Where compartment walls are located within the middle half of a floor between vertical supports, the
predicted deflection may be assumed to be 40mm unless a smaller value can be justified by
assessment. Outside this area the limit can be reduced linearly to zero at the supports for steel
beams that do not have the required fire resistance, reference should be made to SCI Publication 288
fire safe design A New Approach to Multi-Storey Steel-Framed Buildings.
Various changes.
8.29 - Note 1 - Thermoplastic roof lights should not be used in 1500mm compartment wall / roof zone.
8.31 375mm extension of compartment walls above roof coverings can be reduced to 200mm with roof
coverings AA, AB or AC.
23
Dia 30 revised and updated.
24
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 25
Previous Table 13 has been incorporated into the text of this section as to the location of cavity barriers to
avoid confusion and aid understanding.
25
Re numbered table
9.10 Under floor service voids now require cavity barrier sub-division.
9.13 Window frames and doors frames are now regarded as cavity barriers and if they are constructed of
steel or timber they must comply with the relevant requirements, i.e. timber minimum 38mm thick / steel
0.5mm thick watch the use of upvc windows, a hr cavity closer will be required.
Diagram 34
amended
cavities to be
closed around
full opening,
including cill
(which was
previously not
required).
26
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 27
Some exceptions if occupants can make their own escape unaided and a L1 fire alarm system is install
throughout are:
(a) If on detection of smoke, the alarm system signals the immediate evacuation of all occupants, then fire /
smoke dampers are not needed; and
(b) If the building is divided into fire compartments and the alarm system is arranged to signal the
immediate evacuation of all occupants of the fire compartment in which the fire has been detected, then
smoke detector operated fire/smoke dampers need only be provided where ductwork enters or leaves
the fire compartment.
NOTE Fire dampers actuated only by fusible links are not suitable for protecting escape routes. However, an
ES classified fire and smoke damper, which is activated by a suitable fire detection system, may be used.
Reference to BS 5720: 1979 on design and installation / BS EN 1366-2 and BS EN 13501-3 as to testing
dampers.
(d) If the building is also used for any other purpose, the part forming the car park is a separated part
and the fire resistance of any element of structure that supports or carries or gives stability to
another element in the other part of the building should be NLT the minimum period of fire
resistance for the elements it supports, and
(e) All materials used in the construction of the building, compartment or separated part should be
NON COMBUSTIBLE.
27
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 28
28
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 29
Minor addition to clarify how this table should be used, i.e. the total percentage of unprotected area is found by
dividing the total unprotected area by the area of a rectangle that encloses all the unprotected areas and
multiplying this result by 100.
29
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 30
17.9 Buildings with sprinklers fitted throughout sufficient fire fighting shafts to be provided so that every
part of the storey that is more than 18m above Fire Service vehicle access level (or above 7.5m for
Purpose Groups 4, 5 and 6), is N.MT 60m from a fire main outlet in a fire fighting shaft, measure on a
route suitable for laying hoses.
17.10 Buildings without sprinklers every part of every storey over 18m or 7.5m as previous above Fire
Service access level is not more than 45m from a fire main outlet contained in a protected shaft and
60m from fire main outlet in a fire fighting shaft measured along a route suitable for laying hoses.
NOTE: To meet the 45m distance it may be necessary to provide additional fire mains in escape stairs
(these do not all have to be designed as fire fighting shafts).
30
B5 ACCESS FOR FIRE FIGHTING.
Various amendments made.
Guidance on other aspects of the design and construction of fire mains, not included in the provisions of this
Approved Documents, should be obtained from BS 9990:2006 (new code).
NOTE: Wet fire mains should be provided in buildings with a floor as more than 50m (previously 60m) above
Fire and Rescue Service vehicle access level. In lower buildings where fire mains are provided, either wet or
dry mains are suitable.
Each fire hydrant should be clearly indicated by a plate affixed nearby in a conspicuous position in accordance
with BS 3251:1976.
Where no piped water supply is available or where there is insufficient pressure and flow in the water main, or
an alternative arrangement is proposed, the alternative source of supply should be provided in accordance with
the following recommendations:
(a) A charged static water tank of at least 45,000 litre capacity; or
(b) A spring, river, canal or pond capable of providing or storing at least 45,000 litres of water at all times of
the year, to which access space and a hard standing are available for a pumping appliance; or
(c) Any other means of providing a water supply for fire fighting operations considered appropriate by the
Fire and Rescue Authority.
Vehicle Access.
Provisions similar, other than you are now required for blocks of flats to have fire fighting pump vehicle access
to within 45m of all points within each dwelling (previously it was only to flat entrance doors).
Dia 49 Relationship between building and hardstanding / access roads for high reach appliance and
Table 20 Typical fire and rescue service vehicle access route specification-
Notes added that - not all fire fighting appliances are standardised and you much check with the Building
Control Body and Fire and Rescue Service for relevant dimensions and ground load bearing capacity.
(Establish GMC provisions update information)
16.5 Every elevation to which fire fighting vehicle access is provided should have suitable doors, NLT
750mm wide giving access to the buildings interior.
New requirement Doors should be provided such that there is no more than 60m between each door
and / or the end of that elevation (e.g. a 150m elevation would need at least 2 doors).
31
Variations for Block of Flats.
17.14 Provided compartmentation and design of the flats is in accordance with the Approved Document you
do not have to provide a fire fighting lobby between the fire fighting stair(s) and the protected corridor or lobby
provided for means of escape purposes.
Similarly, the fire fighting lift can open directly into such a protected corridor or lobby, but the fire fighting lift
landing doors are to be N.M.T. 7.5m from the fire fighting stair door.
32
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 33
APPENDIX A.
Table A2 - Minimum periods of fire resistance.
Flats over
Updated and minor changes. 30m require
sprinkler
protection.
Note 4 -
added on
unprotected
steelwork/fire
resistance.
33
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 34
European
standards
34
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 35
New notes
added
35
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 36
APPENDIX E DEFINITIONS.
New definitions added:
EXIT PASSAGEWAY A protected passageway connecting a protected stairway to a final exit (exit
passageways should be protected to the same standard as the stairway they serve).
FIRE DAMPER Mechanical or intumescent device within a duct or ventilation opening which is operated
automatically and designed to prevent the passage of fire and which is capable of achieving an integrity E
classification and/or an ES classification to BS En 13501-3:2005.
FIRE AND SMOKE DAMPER Fire damper which when tested in accordance with BS EN 1366-2:1999 meets
the ES classification requirements defined in EN 13501-3:2005 and achieves the same fire resistance in
relation to integrity, as the element of the building construction through which the duct passes.
GALLERY A floor or balcony, which does not extend across the full extend of a buildings footprint and is
open to the floor below.
LIVE/WORK UNIT A flat, which is intended to serve as a workplace for its occupants and for persons who do
not live on the premises.
PLACES OF SPECIAL FIRE HAZARD Now revised deleting reference to school labs/mat stores as
guidance in Building Bulletin 100 should be used.
Oil filled transformer and switchgear rooms, boiler rooms, storage spaces for fuel or other highly flammable
substances and rooms housing a fixed internal combustion engine.
SCHOOL A place of education for children older than 2 and younger then 19 years. Includes nursery
schools, primary schools and secondary schools as defined in the Education Act 1996.
STOREY includes:
(a) any gallery in an assembly building (Purpose Group 5); and
(b) any gallery in any other type of building if its area is more than half that of the space into which it
projects; and
NOTE: Where there is M.T one gallery and all the total area of the galleries in any one space is more
than half of the area of the space then the building should be regarded as being a multi storey
building.
36
Subject APPROVED DOCUMENT B (FIRE 14B
Building Control
SAFETY) VOLUME 2
Guidance Note Buildings other than dwelling houses
(2006 Edition) MAIN CHANGES.
Issued 01/01/07 Rev Page 37
fire safety information means information relating to the buildings or extensions design and
construction, and the services, fittings and equipment provided in or in connection with the building or
extension which will assist the responsible person to operate and maintain the building or extension with
reasonable safety;
a relevant building is a building to which the Regulatory Reform (Fire Safety) Order 2005 applies (S.I.
2005/1541, see article 6), or will apply after the completion of building work;
a relevant change of use is a material change of use where, after the change of use takes place, the
Regulatory Reform (Fire Safety) Order 2005 will apply, or continue to apply, to the building; and
responsible person has the meaning given in article 3 of the Regulatory Reform (Fire Safety) Order
2005.
The information below is only intended as a guide as to the type and level of information to be provided, as it
will vary from building to building and should be therefore be considered on a case-by-case basis.
Simple Buildings.
For most buildings basic information on the location of fire protection measures may be all that is necessary.
An as-built plan of the building should be provided showing:
a. escape routes;
b. compartmentation and separation (i.e. location of fire separating elements, including cavity barriers in walk-
in spaces);
c. fire doors, self-closing fire doors and other doors equipped with relevant hardware (e.g. panic locks).
d. locations of fire and/or smoke detector heads, alarm call-points, detection/alarm control boxes, alarm
sounders, fire safety signage, emergency lighting, fire extinguishers, dry or wet risers and other fire fighting
equipment and location of hydrants outside the building;
e. any sprinkler system(s), including isolating valves and control equipment;
f. any smoke-control system(s) (or ventilation system with a smoke-control function), including mode of
operation and control systems;
g. any high-risk areas (e.g. heating machinery);
h. specifications of any fire safety equipment provided, in particular any routine maintenance schedules; and
i. any assumptions in the design of the fire safety arrangements regarding the management of the building.
j. any provision incorporated into the building to facilitate the evacuation of Disabled people. This information
can then be used when designing suitable Personal Emergency Escape Plans.
37
Complex Buildings.
These require a more detailed record of the fire safety strategy and procedures for operating and maintaining
any fire protection measures of the building. Further guidance is available in BS 5588-12:2004 - Fire
precautions in the design, construction and use of buildings: Managing fire safety (Annex A Fire Safety
Manual).
Sprinkler system(s) design, including isolating valves and control equipment; and
Smoke-control system(s) (or HVAC system with a smoke-control function) design, including mode of
operation and control systems.
h. Any high-risk areas (e.g. heating machinery) and particular hazards.
i. As-built plans of the building showing the locations of the above.
j. Specifications of any fire safety equipment provided, including operation details, operators manuals,
software, system zoning and routine inspection, testing and maintenance schedules. Records of any
acceptance or commissioning tests.
k. Any provision incorporated into the building to facilitate the evacuation of disabled people.
38