600v Transformers Full Load Amp Chart PDF

This document provides tables listing the full load current ratings for various sizes of three-phase and single-phase transformers at different voltages. The three-phase table gives the current in amps for transformer capacities from 1 to 3750 KVA at voltages from 208 to 600 volts. The single-phase table lists currents from 10 to 500 KVA at voltages from 120 to 600 volts. Notes explain how to calculate KVA from voltage and current and indicate when current values exceed component capacities.

Uploaded by

vince acus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
103 views1 page

600v Transformers Full Load Amp Chart PDF

This document provides tables listing the full load current ratings for various sizes of three-phase and single-phase transformers at different voltages. The three-phase table gives the current in amps for transformer capacities from 1 to 3750 KVA at voltages from 208 to 600 volts. The single-phase table lists currents from 10 to 500 KVA at voltages from 120 to 600 volts. Notes explain how to calculate KVA from voltage and current and indicate when current values exceed component capacities.

Uploaded by

vince acus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

TRANSFORMER FULL LOAD CURRENT RATINGS

Three Phase 600V Class


To calculate full load current, use this formula: To calculate KVA, use this formula:
Amps = KVA Volts 1.732 x 1000 KVA = Volts x Amps x 1.732 1000
GENERAL PURPOSE DRIVE ISOLATION
VOLTAGE VOLTAGE
KVA KVA
208 240 480 575 600 230 460
1 2.8 2.4 1.2 1.0 1.0 7.5 18.8 9.4
2 5.6 4.8 2.4 2.0 1.9 11 27.6 13.8
3 8.3 7.2 3.6 3.0 2.9 14 35.1 17.6
5 13.9 12.0 6.0 5.0 4.8 20 50.2 25.1
6 16.7 14.4 7.2 6.0 5.8 27 67.8 33.9
7.5 20.8 18.0 9.0 7.5 7.2 34 85.3 42.7
9 25.0 21.7 10.8 9.0 8.7 40 100.4 50.2
10 27.8 24.1 12.0 10.0 9.6 51 128.0 64.0
15 41.6 36.1 18.0 15.1 14.4 63 158.1 79.1
30 83.3 72.2 36.1 30.1 28.9 75 188.3 94.1
45 124.9 108.3 54.1 45.2 43.3 93 233.5 116.7
75 208.2 180.4 90.2 75.3 72.2 118 296.2 148.1
112.5 312.3 270.6 135.3 113.0 108.3 145 364.0 182.0
150 416.4 360.9 180.4 150.6 144.3 175 439.3 219.7
225 624.6 541.3 270.6 225.9 216.5 220 552.3 276.1
300 832.7 721.7 360.9 301.2 288.7 275 690.3 345.2
500 1387.9 1202.8 601.4 502.1 481.1 330 828.4 414.2
750 2081.9 1804.3 902.1 753.1 721.7 440 1104.5 552.3
1000 2775.8 2405.7 1202.8 1004.1 962.3 550 1380.7 690.3
1500 4163.7 3608.5 1804.3 1506.2 1443.4 660 1656.8 828.4
2000 - - 2405.7 2008.2 1924.6 770 1932.9 966.5
2500 - - 3007.1 2510.3 2405.7 880 2209.1 1104.5
3000 - - 3608.5 3012.4 2886.8 990 2485.2 1242.6
3750 - - 4510.7 3765.4 3608.5
Fields containing " - " indicate the current value exceeds the capacity of some current-
carrying components such as bushings, cables, bussing, etc.

Single Phase 600V Class


To calculate full load current, use this formula: To calculate KVA, use this formula:
Amps = KVA Volts x 1000 KVA = Volts x Amps 1000

VOLTAGE
KVA
120 240 277 480 600
10 83.3 41.7 36.1 20.8 16.7
15 125.0 62.5 54.2 31.3 25.0
25 208.3 104.2 90.3 52.1 41.7
37.5 312.5 156.3 135.4 78.1 62.5
50 416.7 208.3 180.5 104.2 83.3
75 625.0 312.5 270.8 156.3 125.0
100 833.3 416.7 361.0 208.3 166.7 Alfa Transformer
167 1391.7 695.8 602.9 347.9 278.3 PO Box 6316
250 2083.3 1041.7 902.5 520.8 416.7 Fort Smith, AR 72906
333 2775.0 1387.5 1202.2 693.8 555.0 Ph 479.646.1668
500 4166.7 2083.3 1805.1 1041.7 833.3 www.alfatransformer.com