This document summarizes test results for a voltage transformer undergoing an upgrade from 2x6MVA to 2x20MVA transformers. Key details include: 1. Voltage transformer specifications, testing equipment used, and insulation resistance test results showing measurements within acceptable tolerance levels. 2. An overview of test cards showing the voltage transformer passed ratio and polarity tests on the specified date with no overload detected. 3. Secondary winding resistance measurement of 2.1 ohms was within acceptable limits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
494 views

Bet VT Test Report

This document summarizes test results for a voltage transformer undergoing an upgrade from 2x6MVA to 2x20MVA transformers. Key details include: 1. Voltage transformer specifications, testing equipment used, and insulation resistance test results showing measurements within acceptable tolerance levels. 2. An overview of test cards showing the voltage transformer passed ratio and polarity tests on the specified date with no overload detected. 3. Secondary winding resistance measurement of 2.1 ohms was within acceptable limits.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

UPGRADING MUWAILAH-1 33/11KV PRIMARY SUBSTATION

Project FROM 2X6 MVA TO 2 X20MVA AT NORTH BATIHAH


GOVERNORATE. T.No. 146/2015
Date 10-11-2016
Client
Report ref TLC-055-TR 24
Contractor Device 11 KV BET 1

TEST REPORT FOR VOLTAGE TRANSFORMERS


Feeder Ref: 11KV BUS-A EARTH TRUCK - 1

1. Voltage Transformer Details

SHAH ELECTRICAL
INDUSTRIES Voltage
Make & Model Ins. Level 12/28/75 KV
Transformer(DNVR-
11)
Serial Numbers SE/11 KV/433
Core Ratio Burden in VA Class
1 1a-1n 11KV/3 - 110V 50 3.0

2.Testing Equipment Details

Equipment Name Make & Model Serial Number Calibration Validity


Insulation Tester 5kV MEGGER MIT 510 TL-IT-OO1 19/03/2017
Digital Multi meter KYORITSU 2003A W8062721 29/04/2017
CPC-100 Omicron CPC100 QH804X 10/05/2017

3.IR TEST:

Applied Measured IR Value


CORE Voltage
Y-Phase
in KV
Primary Earth 5 1.5 T
Primary Secondary 5 1.03 T
Secondary Earth 0.5 5 G

4.Test Cards Overview:

Test Card Type Date/Time Results Assessment Overload

TESTED BY APPROVED BY

Sign Sign

Name : Name

Date: Date
UPGRADING MUWAILAH-1 33/11KV PRIMARY SUBSTATION
Project FROM 2X6 MVA TO 2 X20MVA AT NORTH BATIHAH
GOVERNORATE. T.No. 146/2015
Date 10-11-2016
Client
Report ref TLC-055-TR 24
Contractor Device 11 KV BET 1

Test Card Type Date/Time Results Assessment Overload


YPH(a-n) VTRatio 07/09/2016 15:03:43 yes n/a No

YPH(a-n):

Card Type: VTRatio


Date/Time: 07/09/2016 15:03:43
Overload: No
Assessment: n/a
Range: AC 2kV
Nominal values:
V prim.: 11000/3 V
V sec.: 110.0 V
Frequency: 50.00 Hz
V test: 2000.0 V
Automatic: Yes
Results:
V prim.: 2000.40 V 0.00
V sec.: 34.494 V 0.23
Ratio: 11000/3 V:109.5109 V -0.44 %
Polarity: OK

5.Secondary Winding Resistance Test : (Temperature- 26C )

Core (Terminals) Y-ph()

Core-1 (1a-1n) 2.1

6. Remarks/Observations: All the test results found satisfactory

TESTED BY APPROVED BY

Sign Sign

Name : Name

Date: Date