0% found this document useful (0 votes)
145 views1 page

Eq D

HFI 140 wires are equipment wires designed for use in cables. They have excellent low smoke, halogen free, flame retardant and radiation resistant properties. The wires come in AWG and metric sizes and constructions, with insulation made of extruded dual wall HFI 140. They are commonly used for control, signal and instrumentation applications.

Uploaded by

SKYhabia
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
145 views1 page

Eq D

HFI 140 wires are equipment wires designed for use in cables. They have excellent low smoke, halogen free, flame retardant and radiation resistant properties. The wires come in AWG and metric sizes and constructions, with insulation made of extruded dual wall HFI 140. They are commonly used for control, signal and instrumentation applications.

Uploaded by

SKYhabia
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

HFI 140 Single core: DSP 61-12 18/5 600V/120oC

D-D xxxx Application:


Equipment wire

Equipment wire
D-DM xxxx HFI 140 equipment wires are available in both AWG and metric (Class 5) sizes. Designed for use in the
SeaGuard range of wires, cables and coaxial cables as a Def Stan 61-12 Part 18 equipment wire, HFI
H-DM xxxx 140 has since found wide-ranging use in several other applications including Habiatron and RailGuard
product ranges due to its excellent Low Smoke, Halogen Free (LSZH), flame retardant (FR) and radiation
600/1000V resistant (Rad Tol) properties. It is commonly used for control, signal and instrumentation applications.
Items with the prefix: D- are fully released to the Def Stan 61-12 Part 18 specification.
-50oC to +120oC
Items with the prefix: H- are designed especially by Habia Cable to offer small, metric sizes.
Flame Retardant
Low Smoke Zero Halogen (LSZH) Wire construction:
Radiation Tolerant to 106 Gy Conductor: D-D xxxx: Tin Plated Copper (TPC), AWG sizes
Def Stan 61-12 Part 18 D-DM xxxx: Tin Plated Copper (TPC), Metric sizes
H-DM xxxx: Metric Tin Plated Copper (TPC)
RoHS Compliant Insulation: Extruded dual wall HFI 140 insulation

Available colours: 00 11 22 33 44 55 66 77 88 99 29 89 45
Replace ‘cc’ in the order reference with resistor colour code
(e.g. D-D 3001 Black = 430003001) Black Brown Red Orange Yellow Green Blue Violet Grey White Pink Natural Yw/Gn

Description Size Conductor Finished Wire Amps Order Reference


weight prefix colour /
AWG mm 2
stranding wire Ø core Ø tolerance at 40 C
o
size
(kg/km) D-D (M) H-D
D-D 3001 30 0,05 1 x 0,25 0,25 0,65 +0,05 -0,10 0,90 3 430 - cc3001
D-D 3007 30 0,06 7 x 0,10 0,30 0,70 +0,05 -0,10 1,10 3 430 - cc3007
D-D 2807 28 0,09 7 x 0,12 0,38 0,78 +0,05 -0,10 1,50 4 430 - cc2807
D-D 2601 26 0,12 1 x 0,40 0,40 0,80 +0,05 -0,10 2,00 5 430 - cc2601
D-D 2619 26 0,15 19 x 0,10 0,48 0,88 +0,07 -0,08 2,90 5 430 - cc2619
D-D 2419 24 0,24 19 x 0,12 0,60 1,00 +0,05 -0,10 3,40 7 430 - cc2419
D-D 2301 23 0,28 1 x 0,60 0,60 1,00 +0,05 -0,10 3,90 7 430 - cc2301
D-D 2219 22 0,40 19 x 0,15 0,76 1,16 +0,04 -0,11 4,90 10 430 - cc2219
H-DM 0,5 - 0,50 16 x 0,20 0,88 1,28 ±0,10 5,30 12 - 431 cc0050
D-D 2019 20 0,60 19 x 0,20 0,96 1,36 +0,14 -0,06 7,50 14 430 - cc2019
D-D 1901 19 0,63 1 x 0,90 0,90 1,30 +0,05 -0,10 7,90 14 430 - cc1901
H-DM 0,75 - 0,75 24 x 0,20 1,05 1,45 +0,13 -0,07 7,70 16 - 431 cc0075
D-D 1819 18 1,00 19 x 0,25 1,20 1,60 ±0,05 10,4 19 430 - cc1819
H-DM 1,0 - 1,00 32 x 0,20 1,20 1,60 +0,15 -0,05 9,50 19 - 431 cc0100
D-D 1619 16 1,20 19 x 0,30 1,42 1,82 +0,18 -0,02 16,5 23 430 - cc1619
H-DM 1,5 - 1,50 30 x 0,25 1,50 2,00 +0,12 -0,08 15,1 26 - 431 cc0150
D-D 1437 14 2,00 37 x 0,25 1,75 2,25 ±0,10 20,7 32 430 - cc1437
H-DM 2,5 - 2,50 50 x 0,25 1,95 2,45 ±0,10 23,2 37 - 431 cc0250
D-D 1237 12 2,60 37 x 0,30 2,10 2,60 ±0,10 27,1 43 430 - cc1237
D-DM 4 - 4,00 56 x 0,30 2,48 3,20 ±0,05 40,0 52 430 - cc0400
D-DM 6 - 6,00 84 x 0,30 2,92 4,00 ±0,05 61,4 68 430 - cc0600
D-DM 10 - 10,00 80 x 0,40 3,93 5,10 ±0,05 106,5 101 430 - cc1000

De-rating factors for current rating


10 20 30 40 50 60 70 80 90 100 110 - - -
Temperature de-rating ( C) o
1.22 1.15 1.08 1.00 0.92 0.84 0.75 0.65 0.54 0.42 0.28 - - -
2 3 4 6 8 10 12 16 20 24 28 32 36 40
Multicore de-rating factor
1.00 0.88 0.80 0.69 0.62 0.59 0.55 0.51 0.48 0.43 0.41 0.39 0.38 0.36

Note: All dimensions in mm and ±4% unless stated Date: 2010-02-02 Created: CJV Approved: TN Reference: EQ_D_10
Data provided indicates nominal values unless stated otherwise and is only valid for reference purposes at the time of publication and is subject to change without prior notice.

14 world class cable solutions www.habia.com

You might also like