Alignment
V-Belt Drive Flexible Couplings
Proper alignment and balance of the V-belt is as impor- Direct-coupled fans, which are received factory assem-
tant as a well-balanced impeller. To insure smooth fan bled, on a common base plate, are accurately aligned
operation, the following should be checked: before shipment. However, base plates are flexible to
some extent and therefore must not be relied upon to
1. Fan and motor sheave must be in axial alignment.
maintain the factory alignment. Realignment is neces-
Shafts are parallel in both the vertical and horizontal
sary after the fan has been leveled, grouted, and the
planes (Figure 1).
foundation bolts tightened. Also, check lubricant, where
Drive applicable, following manufacturers recommendations
for type and amount of lubricant.
Fan
Motor
Fan For field installation, the coupling should be mount-
ed as follows:
1. Remove dirt or rust from fan and motor shafts and
Drive
Motor coat with grease or oil for ease of mounting.
Top View
(Horizontal Alignment)
2. Check fan and fan shaft alignment, making sure that
bearings are secure. Mount fan shaft coupling half
Side View Figure 1 flush to end of shaft and secure.
(Vertical Alignment)
3. Mount motor shaft coupling half flush to end of shaft
and secure.
2. Fan motor sheave must be in radial alignment. When
sheaves are of equal width, align with straightedge 4. Move motor into position, with the coupling faces
(Figure 1a). When sheaves are of unequal width, separated by the coupling manufacturers specified
align center of sheaves (Figure 1b). gap.
5. With a straightedge, tapered wedge, or a feeler
gauge, check for parallel and angular alignment
(Figure 2a).
1997 Aerovent
alignment, the faces of the couplings should be par-
Figure 4b
allel within .002". Rotation
Impellers
Fans, which are received factory assembled, have the
impellers already aligned and in place before shipment.
However, fans being flexible to some extent are some- Radial Backward Forward
Tip Curved Curved
times subject to movement during shipment. To insure
smooth operation and proper performance, the follow-
ing impeller alignment should be checked before
putting fan into operation.
Centrifugal Fans
The fan shaft should be approximately centered in the
Propeller Fans clearance hole in the fan housing and perpendicular to
the housing sides. Perpendicularity can be checked on
Fan shaft should be centered and parallel to fan casing. BI and BIA fans by measuring dimension A (Figure 5)
Center by checking gap (B) between propeller tip and at four points approximately 90 apart.
fan casing. Repeat at three additional points at approx-
imately 90 from each other (Figure 3b). Parallelism can Figure 5
be observed by measuring the axial distance (A) from Housing
one blade to the end of the fan casing at four points at Front Inlet
Wheel Plate Wheel/Cone
approximately 90 from each other (Figure 3a). Back Plate Geometry
Cone
A 45
Wheel Front
B Plate
A