Loads On Walls Calc1

This document provides load calculations for various structural elements of a two story villa, including walls, parapets, stairs, water tanks, beams, and columns. It calculates surface loads, self weights of structural elements, and point loads. Reactions and bending moments are determined for beams at the landing level and tie beams. Reinforcement requirements are specified for the beam at the landing level.

Uploaded by

Wanda Beasley
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views2 pages

Loads On Walls Calc1

This document provides load calculations for various structural elements of a two story villa, including walls, parapets, stairs, water tanks, beams, and columns. It calculates surface loads, self weights of structural elements, and point loads. Reactions and bending moments are determined for beams at the landing level and tie beams. Reinforcement requirements are specified for the beam at the landing level.

Uploaded by

Wanda Beasley
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

Villa (G+1)

LOADS ON BEAMS
For First Slab
Height of the wall above the Slab
Weight of Wall (20cm thickness)
USE

= Height F/F- Slab Thickness


= 4.2-0.20
= 4.0 m
= (4.0) X3.5 =14.0 kN /m
= 14.0 kN/m

Weight of Wall (10cm thickness)


USE

= (4.0) X2.5 =10.0 kN /m


= 10.0 kN/m

For parapets
Weight of Parapet (15cm thick.)
USE
Weight of Parapet (15cm thick.)
USE

= 1.2 X0.15X25 =4.5 kN /m


= 4.5 kN/m
= 1.9 X0.15X25 =7.13 kN /m (Sloped)
= 7.2 kN/m

Stairs Weight
Weight of Stair (20cm thick.)

= 57 kN/m

Water Tank Load on Roof


Load from tank base (10cm thick.)

= 1.4X0.10 X25 = 3.50 kN /m2

Load from water (1200 US glns)

= 73 / 3.05/2.1 = 11.33kN /m2

Total Surface Load (Factored)

14.83 kN/m2

COLUMNS LENGTH UNDER TIE BEAMS


Assume:
The thickness of footing
= 50 cm
The depth of the formation level
=120 cm
The thickness of tie beam
=50 cm
Level of Plinth Level
=150
The length of columns from plinth level up to the top of footing
=120+150-50-50
= 170 cm

Villa (G+1)

Loads on Beam @ Landing Level


In the Staircase Tower

COL. # 1
112 KN

COL. # 2
112 KN

2.80 m

112KN

112 KN
79 KN.m

Self Weight (Factored)


Wall Weight (Factored)
Stair Weight (Factored)
Total
Reaction on each side
Max. Moment on beam

= 0.2X 0.5X 25 X1.4


= 14.0X 1.4

= 80.10 X 2.8 /2
= 80.10 X 2.82 /8

=3.50 kN/m
=19.6 kN/m
=57.0 kN/m
=80.10 kN/m
=112.0 kN
=78.50 kN.m

[USE 3Y16 BOT. REINF. FOR BEAM @ LANDING LEVEL]

LOADS ON TIE BEAMS


For TB (+150 cm)
Height of the wall above the Slab
Weight of Wall (20cm thickness)
USE
Weight of Wall (10cm thickness)
USE

= Height F/F- Slab Thickness


= 4.0-0.20
= 3.80 m
= (3.8) X3.5 =13.3 kN /m
= 13.3 kN/m
= (3.8) X2.5 =9.50 kN /m
= 9.50 kN/m