Reciprocating Compressors For Oxygen Service
Reciprocating Compressors For Oxygen Service
AIGA 048/12
GLOBALLY HARMONISED DOCUMENT
AIGA 048/12
GLOBALLY HARMONISED DOCUMENT
RECIPROCATING COMPRESSORS
FOR OXYGEN SERVICE
Code of Practice
Revised by the members of WG3 of EIGA
Harald BEKMANN
AIR LIQUIDE
Bernard COURTOY
AIR LIQUIDE
Kenneth KOVAK
AIR PRODUCTS
Andrea MARIOTTI
SOL
Sid PHAKEY
Dirk REUTER
MESSER GROUP
Inaki URIARTE
PRAXAIR
Andy WEBB
EIGA
AIR LIQUIDE
Disclaimer
All publications of AIGA or bearing AIGAs name contain information, including Codes of Practice, safety procedures and other
technical information that were obtained from sources believed by AIGA to be reliable and/ or based on technical information and
experience currently available from members of AIGA and others at the date of the publication. As such, we do not make any
representation or warranty nor accept any liability as to the accuracy, completeness or correctness of the information contained in
these publications.
While AIGA recommends that its members refer to or use its publications, such reference to or use thereof by its members or third
parties is purely voluntary and not binding.
AIGA or its members make no guarantee of the results and assume no liability or responsibility in connection with the reference to
or use of information or suggestions contained in AIGAs publications.
AIGA has no control whatsoever as regards, performance or non performance, misinterpretation, proper or improper use of any
information or suggestions contained in AIGAs publications by any person or entity (including AIGA members) and AIGA expressly
disclaims any liability in connection thereto.
AIGAs publications are subject to periodic review and users are cautioned to obtain the latest edition.
Reproduced with permission from the European Industrial Gases Association. All rights reserved.
Acknowledgement
This document is adopted from the European Industrial Gases Associations IGC 10/09 Reciprocating
compressors for oxygen service Code of Practice. Acknowledgement and thanks are hereby given for
permission granted for the use of their document.
AIGA 048/12
Table of Contents
1
Introduction ...................................................................................................................................... 1
1.1
Scope........................................................................................................................................ 1
1.1.1
Design of the compressor system (Sections 3 & 4) .......................................................... 1
1.1.2
Cleaning, Preservation and Inspection (Section 5) ........................................................... 1
1.1.3
Erection, Testing and Commissioning (Section 6) ............................................................ 1
1.1.4
Operation (Section 7) ........................................................................................................ 2
1.1.5
Planned Maintenance (Section 8) ..................................................................................... 2
1.2
Other Specifications.................................................................................................................. 2
1.3
Application of the Code ............................................................................................................ 2
1.3.1
Oxygen Purity .................................................................................................................... 2
1.3.2
Oxygen Enriched Gases ................................................................................................... 2
1.3.3
Moisture............................................................................................................................. 2
1.3.4
Discharge Pressure........................................................................................................... 3
1.3.5
Suction Pressure ...............................................................................................................3
1.3.6
Driver ................................................................................................................................. 3
1.4
Definition of Terms.................................................................................................................... 3
1.4.1
Terminology....................................................................................................................... 3
1.4.2
Maximum Continuous Speed of the compressor .............................................................. 3
1.4.3
Maximum Operating Temperature .................................................................................... 3
AIGA 048/12
3.3.6
Piston rings...................................................................................................................... 12
3.4
Drivers .................................................................................................................................... 13
3.4.1
Drivers in Hazard Area .................................................................................................... 13
3.5
Compressor Dynamic Analysis, Verification Tests and Data to be provided ......................... 13
3.5.1
Introduction...................................................................................................................... 13
3.5.2
Pulsations limits............................................................................................................... 13
3.5.3
Vibration Limits ................................................................................................................ 13
3.6
Earthing / Grounding .............................................................................................................. 13
4
AIGA 048/12
6.1
Erection................................................................................................................................... 23
6.1.1
Responsibility .................................................................................................................. 23
6.1.2
Tools................................................................................................................................ 23
6.1.3
Purging after Assembly ................................................................................................... 23
6.2
Testing and Commissioning ................................................................................................... 23
6.2.1
Introduction...................................................................................................................... 23
6.2.2
General............................................................................................................................ 24
6.2.3
Testing Objectives........................................................................................................... 24
6.2.4
Tests to be carried out..................................................................................................... 24
6.2.5
Commissioning on Oxygen ............................................................................................. 24
7
Operation ....................................................................................................................................... 25
7.1
General ................................................................................................................................... 25
7.1.1
Combustible Matter ......................................................................................................... 25
7.1.2
Machine Rubs.................................................................................................................. 25
7.1.3
Machine Vibrations.......................................................................................................... 25
7.1.4
Leaking Cooler Tubes ..................................................................................................... 25
7.1.5
Gas Leakage Hazard ...................................................................................................... 25
7.1.6
Oil Leakage Hazard......................................................................................................... 26
7.2
Qualifications and Training for Operating Personnel.............................................................. 26
7.3
Hazard Area............................................................................................................................ 26
7.4
Record of Machine Operation................................................................................................. 26
7.5
Monitoring Critical Operating Parameters .............................................................................. 26
7.5.1
Trip Override.................................................................................................................... 26
7.6
Interlock Systems ................................................................................................................... 26
7.7
Start-up Procedures................................................................................................................ 26
7.7.1
Advisory Requirements ................................................................................................... 27
7.7.2
Additional Requirements ................................................................................................. 27
Maintenance .................................................................................................................................. 27
8.1
General ................................................................................................................................... 27
8.1.1
Method............................................................................................................................. 27
8.1.2
Purging during Maintenance ........................................................................................... 27
8.1.3
Functional Test ................................................................................................................28
8.1.4
Cleanliness during Maintenance ..................................................................................... 28
8.2
Compressor Checks ............................................................................................................... 28
8.2.1
Compressor Checks after Shutdowns............................................................................. 28
8.2.2
Compressor Planned Maintenance Shutdowns .............................................................. 28
8.3
Spare Parts............................................................................................................................. 28
Instruction Manual.......................................................................................................................... 28
9.1
General ................................................................................................................................... 28
9.2
List of Minimum Information ................................................................................................... 28
9.2.1
Instruction Manual ........................................................................................................... 28
10
References ................................................................................................................................. 29
AIGA 048/12
Introduction
As a part of a programme of harmonization of industry standards, a working group has been set up
under joint lead of EIGA and JIGA by a group of experts representing major industrial gases
producers in Japan, Western Europe and North America and is based on the technical information
and experience currently available to the authors.
This document has been reviewed by a number of suppliers.
Oxygen compression represents a special risk in that the compressor can burn violently. This code
defines design and operating parameters for reciprocating oxygen compressors. Compliance with this
code will reduce the likelihood of, and the hazards arising from, a fire in a compressor to be equal or
lower than those commonly accepted in the air separation industry. There is less demanding
technology in a reciprocating compressor than in a centrifugal one. Potential rubbing velocities, gas
velocities and inventories are all lower. For these reasons more flexibility in design is allowed in a
reciprocating compressor than in a centrifugal compressor as defined in the EIGA IGC Doc 27.
The Code has made a significant contribution to the safe compression of oxygen primarily because
the suppliers and users have fully and frankly shared their philosophies and experiences. It is
recognised by the Working Group members that the feed back of operating experiences makes a
powerful contribution to safe operation and design. The Code requires that all those who build and
operate reciprocating oxygen compressors that have been specified to comply with the Code should
contribute towards it by fully reporting the circumstances surrounding oxygen fires.
For the purpose of safe operation of the compressor and its auxiliaries the user and the supplier shall
establish full agreement on the possible and expected modes of compressor operation (e.g. specified
operating points, normal operating range, start-up and shut-down, etc).
1.1
Scope
This code applies to conventional ringed and labyrinth compressors having a crosshead and distance
piece. Most operating experience exists in compressors above 500 Nm3/hr at pressures up to 8.5
MPa gauge with oxygen purity of 90% or greater and with max 10 ppm water (volume basis).
Additionally experience suggests that at a discharge pressure below 0.2 MPa gauge the likelihood of
ignition is low and the consequence of ignition slight since the trapped inventory is small and fire is
difficult to sustain at low pressures. The authors of this code believe the document can be applied to
10 MPa gauge without further special precaution.
The safe and reliable compression of oxygen using reciprocating compressors can only be achieved
by the successful combination of many factors. The Code identifies and addresses these factors:
1.1.1 Design of the compressor system (Sections 3 & 4)
AIGA 048/12
Condition monitoring
Safety barriers
Emergency procedures
1.2
Other Specifications
Additional guidance on installation and operation can be found in CGA G-4.6, Ref [4]. The CGA and
EIGA are aligned in their aims and values and the CGA document shall be regarded as
complementary to this one.
In case of conflict between this Code and the users specification the information included in the order
shall take precedence. The supply shall be in conformity with the rules of the country of the user
and/or of the supplier.
1.3
AIGA 048/12
1.3.4 Discharge Pressure
The recommendations in this Code are based on the experience gained in the compression of oxygen
up to 10 MPa gauge.
1.3.5 Suction Pressure
Traditional experience is with compressor suction pressure of less than 0.2 MPa gauge. This is the
application that has been considered when putting forward the best design of ancillary systems.
However, if the compressor has an elevated suction pressure, it is possible that some ancillary
systems may need modification and appropriate risk assessment shall be made.
1.3.6 Driver
The majority of experience has been with the use of constant speed electric motor drivers. The code
has been written giving the best solution for this type of driver. However where another type of driver,
e.g. variable speed electric motor requires a different solution, this has been clearly pointed out in the
code (resonance, vibrations, and lubrication issues).
1.4
Definition of Terms
1.4.1
Terminology
Although the application of this document is voluntary, a clear distinction is made between the
definition of shall and should as used in the document:
May and need not are used when the application is optional.
Compressor Installation
2.1
Hazard Area
2.1.1 Description
The Hazard Area is defined as the area where an incident is most likely to occur and as a
consequence is capable of causing danger and/or injury to personnel. It is necessary to consider a
number of pertinent factors when determining whether or not an area should be classified as a hazard
area such as:
AIGA 048/12
compressor and other system equipment design factors such as type, size, materials of
construction, operating speed, internal clearances, type of seal system, etc;
extent of safety monitoring and shutdown devices that provide early detection of problems before
equipment failure;
proximity of oxygen equipment to personnel walkways, work areas and other equipment; and
Projectiles
Flash
It is the responsibility of the user to specify the extent of the hazard area on a case-by-case basis.
Note: The term hazard area should not be confused with Electrical Hazardous Area Classification.
2.1.2 Enclosure of the Hazard Area by a Safety Barrier
In most instances the hazard produced by a reciprocating oxygen compressor is such that the
resultant hazard area would be so large as to be impracticable unless its extent is reduced by
enclosing the compressor within a safety barrier. It is recognised that the extent of the hazard area is
specific to the size and pressure of each application.
If the user proposes not to enclose the hazard area within a safety barrier then the code requires that
the user shall analyse the hazard, shall determine the extent of the hazard area, and shall
demonstrate that the required safety criteria can be met without the use of a barrier.
Barriers shall be installed above 2 MPa gauge discharge pressure. However, in current practice, most
users have adopted a 0.4 MPa gauge limit. National regulation may require a safety barrier for less
than 0.4 MPa gauge.
2.1.3 Access to the Hazard Area
When the compressor is operating on oxygen, access to the hazard area is not permitted and warning
notices to this effect shall be posted. Maintenance access panels shall be closed. Routine visual
inspection shall be done remotely through approved safety windows or by using cameras or other
devices.
Before entering the hazard area, after the compressor has been shutdown or changed over to dry air
or nitrogen, the atmosphere within the enclosure shall be analysed to ensure that it is safe to enter. It
is recommended that the oxygen concentration should be between 19.5% and 23.5%. Continually
monitor the atmosphere for oxygen deficiency or enrichment when personnel are within the area.
AIGA 048/12
2.1.4 Equipment Location
2.1.4.1
-
2.1.4.2
Equipment and instrumentation that require operator attention when the machine is in operation shall
be located outside the hazard area. This would include:
-
2.1.4.3
2.1.4.3.1
The code requires that the power operated isolation valves and the discharge non-return valve shall
be protected from the effects of a fire so that they will function correctly and thus cut off the supply of
oxygen and put out the fire. The required protection can be achieved by either putting the valves
outside the hazard area or by putting them inside the hazard area with their own shields.
2.1.4.3.2
The Driver
Electric motor drive should be located outside the hazard area. However, if the motor is located within
the hazard area, it is recommended that the following precautions be taken:
If the motor is fitted with hydrodynamic bearings then migration from the bearings should be
prevented.
The safety barrier ventilation should be arranged in such a way that air from outside the enclosure is
drawn across the motor to ensure that in the event of an oxygen leak a concentration build up around
the motor is not allowed to occur.
2.1.5 Service Pipes and Electric Cables and junction boxes within the Hazard Area
If it is not possible to avoid the routing of service pipes, junction boxes and cables through the hazard
area then they should be protected against fire as far as practicable.
2.1.6 Lubricating Oil System
The lubricating oil system can be located inside or outside the hazard area. The number of
connections shall be minimized to prevent leaks in the oil piping within the enclosure. .
AIGA 048/12
2.2
Safety Barrier
2.2.1 Purpose
The primary purpose of a safety barrier is to prevent injury to personnel. It has a secondary function
in that it lessens damage to adjacent equipment. A safety barrier achieves the above by preventing
flames, jets of molten metal or projectiles from penetrating or collapsing the barrier in the event of an
oxygen fire, which has caused burn through of any of the oxygen containing equipment within the
hazard area.
2.2.2 Responsibilities
It is the responsibility of the user to design and specify the safety barrier. The supplier shall supply
any necessary information as required.
2.2.3 The Nature of Burn Through
2.2.3.1
The majority of fires starts in areas of high pressure or gas velocity, therefore the area around the
cylinders or recycle valve are likely sites. Burn Through is most likely to occur at places close to the
seat of the fire where the gas pressure is high and the thermal mass small therefore the primary risk
areas are:
The compressor cylinders and suction /discharge valves
The compressor distance piece.
The first elbow in the process pipe work immediately upstream and downstream of the
compressor flanges.
The recycle valve and its associated outlet pipe and the first downstream bend.
The damping capacity and coolers.
Drain and vent connections
Piping around safety valves
2.2.3.2
2.2.3.2.1
This will burn through equipment, on to which it impacts directly, unless this equipment is of large
thermal mass or is protected by a fire resistant heat shield. The barrier shall also be strong enough to
withstand the impact of the jet.
2.2.3.2.2
Accompanying the jet is a widening spray of molten metal, which spatters equipment over a wide
area.
2.2.3.2.3
This is caused by the release of high-pressure gas. This will cause the barrier to collapse unless it
has been allowed for in the design. Normally the barrier is designed to withstand a certain
overpressure and a sufficient vent area is provided to ensure that the design overpressure is not
exceeded. This is a particularly difficult design problem in the case where the safety barrier is also an
acoustic shield.
AIGA 048/12
2.2.4 Strength & Burn Through Criteria
The barrier shall withstand the force resulting from the impact of a jet of molten metal issuing from a
hole burnt in the compressor or pipe work, hitting the safety barrier, plus the overpressure due to the
release of the stored inventory of the oxygen. The above requires calculation on a case-by-case
basis because it varies with the size and the discharge pressure of the compressor. The minimum
force that the barrier shall be able to sustain is 2 KPa projected over the wall area. This value is based
on the accumulated experience of members of the Working Group.
The barrier shall be designed to resist the effect of a jet of molten steel for 30 seconds without being
breached. (See 2.2.5 - materials of construction).
Therefore, the design shall consider the following load types:
AIGA 048/12
Figure 1
If the barrier has a roof ventilation ports shall be located at high level pointing in a safe direction.
The safety barriers shall be designed to cope with the inventory of high-pressure gas that is released
when burn through occurs. If the barrier has an open top or a partial roof this does not represent a
problem. If the compressor is fully enclosed - normally for acoustic reasons then sufficient open area
shall be provided to avoid over pressurizng the enclosure. The following ways of achieving the
required open area are recommended:
A permanently open area with acoustic splitters.
Acoustic louvers, which are self-opening. These can be bought as proprietary items.
Acoustic doors, which are self-opening, hinged so as to have a small angular moment of inertia.
Concrete or steel caps, which are lifted by the gas pressure, provided that the caps are
adequately restrained.
AIGA 048/12
The above open area shall be sited away from the compressor where the hazard is least. The open
area shall be sited in a position such that the operation of the doors and the blast of hot gas shall not
cause a hazard to personnel.
2.2.7.1
Oxygen Accumulation
Since oxygen is denser than air it tends to accumulate in depressions or enclosed spaces. It is
preferred that trenches or pits are avoided. The safety barrier shall be provided with sufficient
ventilation to prevent a build up of oxygen around the compressor. If the barrier is open topped this is
normally adequate, however if it is enclosed then forced ventilation should be provided at the rate of
not less than 6 air changes per hour.
2.2.7.2
If the compressor has the facility for test run on inert gas (e.g. nitrogen) or inert gas is being used for
the purge gas then an asphyxiation hazard can exist. The barrier should be designed with at least two
outward openings in case of labyrinth entrance design, at each level and sufficient walkways to allow
quick exit.
2.3
Location
2.4.1 Introduction
Fires in oxygen compressors, once started, are nearly impossible to extinguish until all the contained
oxygen gas is consumed in the fire or vented to atmosphere. While it is true that once the oxygen
supply is cut off and the inventory reduced the actual oxygen fire will be over quickly, extensive
damage is likely and sometimes other combustible material, such as oil, is ignited and continues to
burn after the actual oxygen promoted fire is out. For the above reasons, it is imperative that oxygen
compressor systems shall be designed to prevent the initiation of any fires and to vent the oxygen
AIGA 048/12
inventory as quickly as possible in case of a fire or potential ignition. These are the most effective
ways of reducing the chance of personal injury and minimising equipment damage.
Fire protection should also include a strict housekeeping policy, developing an emergency plan with
local fire officials and supplying the proper fire fighting equipment.
2.4.2 Flammable Material
The presence of flammable materials in the hazard area constitutes a hazard and should be avoided
wherever possible. Where this cannot be avoided, for example, during maintenance operations, then
any flammable materials introduced into the hazard area should be removed before oxygen is
introduced to the compressor.
2.4.3 Protection of Personnel
Entry into an area of fire is to be discouraged and may only be justified where human life is at risk.
When a person has been in contact with an oxygen enriched atmosphere his clothes may have
become saturated with oxygen and even when he has returned to a safe area he shall be careful not
to approach any source of ignition (e.g. matches or an electric fire) until he has changed his clothes.
3
Compressor Design
3.1
Design Criteria
Debris Impact:
Screens - sizing or break-up, weld debris or slag, (friction/shock) maintenance debris, shot, sand.
Contamination:
Oil, faulty design of bearings/seals and/or faulty design of associated vents and drains.
Resonance:
Debris in dead areas.
Cooling system: design the system to avoid concentrating ethylene glycol in the process arising
from leakage.
3.2
Materials, General
10
AIGA 048/12
3.3.1.1
The following materials have proved satisfactory with regard to the criteria listed under section 3.3:
Welding of cast-steel and fabricated steel casings is permitted if the execution and heat treatment
are properly conducted.
3.3.1.2
Repairs
Any repair shall be agreed between supplier and user, with the appropriate procedure.
3.3.1.3
Sealing Material
If non-metallic materials are employed for sealing the cylinders, they shall be oxygen compatible and
agreed by the supplier and user. Liquid sealant shall be applied so as to prevent it from creeping and
projecting into the inside of the machine. If required, threads shall also be sealed by materials that
are compatible with oxygen.
3.3.1.4
Anti-galling Compound
If an anti-galling compound is to be applied to centering fits, bolts, studs, etc. only compounds
compatible with oxygen service shall be used. Molybdenum disulphides in powder form have proved
their value for oxygen service. Compounds shall be mutually agreed.
3.3.2 Distance piece
The distance piece and frame oil head shall be designed to positively prevent the contact of
crankcase oil with the process oxygen stream. The distance piece should be longer than the stroke
length to allow the fitting of a slinger ring.
The interior of each distance piece should be painted white to detect presence of oil or pollution.
Piston rod slinger shall be provided to form a positive barrier against oil migration along the rod. Open
distance piece is recommended to prevent oxygen enrichment. If distance piece covers are provided
in case of hostile or polluted environment, positive purging system shall be provided (dry air or
nitrogen) to ensure that oxygen enrichment is not possible; in this case the concentration of oxygen
should be analysed continuously at the vent of the distance piece. Oil migration shall be checked on a
regular basis.
11
AIGA 048/12
3.3.3 Cylinder Valves
Compressor valves contain thin materials and represent a particular hazard. No firm rule exists for the
design and construction of valves. Therefore only proven design shall be used. Actual experience of
the members of the working group is listed here under but not limited.
3.3.3.1
Ported plate valves with damping plates should be used for oxygen applications. Valve size should be
sufficient to keep pressure losses across the valve below 5% of nominal suction and discharge
pressures. Valve lift should be designed to keep opening impacts below 3.5 m/s and closing impact
below 1.3 m/s to ensure maximum lifetime and safety. Valve motion natural frequencies should not
correspond to system pulsation frequencies since this can lead to rapid valve failure.
3.3.3.2
Valve seat and guard: X20Cr13, X5CrNi1810, AISI 305, AISI 410, JIS SUS 420
Valve plate: X20Cr13, X5CrNiCuNb177, AISI 410, JIS SUS 630
Valve springs: X5CrNiCuNb177, Nimonic, JIS SUS 304
Centre bolt: martensitic stainless steel, JIS SNB7
Nut: austenitic stainless steel.
3.3.4 Piston
Maximum mean piston velocity shall not exceed 4 m/sec for ringed piston, and 5 m/sec for labyrinth
piston.
3.3.5 Piston rod
Suitable materials for pressure above 4.5 MPa include K-Monel. Martensitic stainless steel can be
used below 4.5 MPa gauge.
If a piston rod coating is used, it shall be of a proven technology that includes chrome plating or
nitrited steel, or tungsten carbide coating.
3.3.6 Piston rings
Ringed (as distinct from labyrinth) compressors normally have piston rings to seal the gas and rider
rings to carry the piston weight. The choice of ring material is important because the rubbing ring is
itself a source of ignition and secondly wear of the rider ring can allow the metal piston to rub on the
cylinder creating heat and a possible fire. Piston rings have successfully been made of PTFE with one
or some combination of the following fillers:
Glass fibre
Lead powder
Copper powder
Bronze powder
Graphite
Strict quality controls shall be imposed on the piston ring supplier to ensure that manufacture is
conducted with virgin materials and cleanliness appropriate to oxygen use. Rider ring specific loading
should not exceed 35 kPa based on the diameter multiplied by rider ring width. Rider rings should not
over-run valve ports by more than 30% of their width. To avoid piston to liner touches a rod drop trip
12
AIGA 048/12
system should be installed on horizontal or Y type machines. The rider ring groove depth should be at
least 150% equal to the diametral difference between the piston outer diameter and the cylinder bore
Piston ring expansion springs shall not be used as they can break and cause an ignition source.
3.4
Drivers
3.5.1 Introduction
Note:
Due to their physical nature any responding vibrations or pulsations that occur can always be related
either to forced, to self excited or to parameter excited vibrations. The sources of these vibrations and
their effects on the compressor system shall be analysed by calculations, if they are expected to occur
in the actual design.
3.5.2 Pulsations limits
Pulsation level shall be not higher than API 618 Approach 1, within the limit of the Original Equipment
Manufacturers (OEM) scope
3.5.3 Vibration Limits
For stroke of 250 mm and less, vibration level shall be not higher than 12 mm/s RMS on compressor,
and 20 mm/s RMS on piping system.
For stroke greater than 250 mm, vibration level shall be not higher than 20 mm/s RMS on compressor
and piping with stress raisers (for example a junction, or an instrument connection) and 35 mm/s RMS
on plain piping system.
3.6
Earthing / Grounding
Great care shall be taken to earth the electric drive motor correctly to prevent currents circulating
through the compressor, which, experience has shown, can damage the bearings. The electrical
continuity between all piping equipments shall be ensured with the appropriate devices.
4
Auxiliaries Design
4.1
Cooling
13
AIGA 048/12
4.1.2 Types of Cooler
Any type of cooler can be accepted, provided that materials are oxygen compatible and that cleaning
can be achieved (See also 5.3)
4.1.2.1
This type of cooler has cooler heads containing the water channels to tube bundle. .
To assure a positive inspection for oxygen cleanliness, they should have removable tube bundles.
4.1.2.2
Care shall be taken that components, e.g. bolts, are positively secured so as to avoid the danger of
them coming loose and being carried into the oxygen stream.
The design shall minimize the risk of leaks between the oxygen and the water sides.
Care shall be taken to ensure that the cooler tubes are properly supported and are not susceptible to
machine or fluid induced vibration. The tube supports and baffles shall be of a suitable design and
materials to ensure that they do not do damage to the tubes. Experience has shown that to achieve
this it is advisable that the support material that is in contact with the tube should be softer than the
tube material.
When the tubes are expanded into the tube plates the lubricant used shall be oxygen compatible.
4.1.2.4
Material Selections that are common to both types of Cooler - Oxygen side only
The materials of the tubes and fins (if any) in contact with the oxygen shall be copper or copper alloy.
Commonly used materials are Muntz metal, or naval brass for the tubesheets and admiralty brass or
90/10 copper/nickel for the tubes. The fins are normally made of copper.
Tubesheets made from carbon steel could also be used provided that cooling water quality assures to
avoid corrosion problems (for example with closed circuits or appropriate water treatment).
Gasket material in contact with the oxygen stream shall be compatible with oxygen and agreed
between the supplier and the user. Gaskets shall not protrude into the gas stream.
4.1.2.5
One of the concerns with this type of cooler is the oxygen cleanliness of the cooler bundle because:
It requires special equipment to clean it after assembly or reclean it if it becomes contaminated.
There is not a simple way of checking its cleanliness in the field.
Use of this type of cooler shall be agreed between supplier and user.
4.1.2.6
It is easy to establish oxygen cleanliness in this type of cooler, because the oxygen side of tubes are
straight and smooth and the gas header can be detached for easy cleaning and inspection.
14
AIGA 048/12
No special cleaning equipment is needed and this type of cooler is easy to check for oxygen
cleanliness in the field.
4.1.3 Vents and Drains
Suitable means shall be provided to vent all high points and to drain all low points on the waterside.
It shall be possible to check for cooling water leaks prior to starting and thereafter if the compressor is
stopped with cooling water circulating. If the oxygen side drains can be operated on oxygen then they
shall be led into a well-ventilated area.
The minimum size of drain connections should be 20 mm and equipped with a full bore valve. Vent
and drain connection could run in critical flow conditions; therefore care shall be taken of high
velocities and associated risks.
4.1.4 Closed circuit cooling system
Closed circuit cooling water systems are often filled with water containing up to 50% ethylene glycol.
Ethylene glycol is flammable and will concentrate if it leaks into an oxygen system and the water
evaporates. Members have good experience with closed circuit systems having 50% ethylene glycol
but such systems shall have all low points checked for leakage.
4.2
Because of the dangers resulting from the fractures of pipes or other components, both mechanical
vibration and gas pulsation must be limited. Pulsation can be limited by either pipe work design or by
damping. Damping can be achieved by various methods, for example, capacities, orifices and
vessels. The material used in any pulsation-damping device must be suitable for use with oxygen at
the pressure and velocities concerned. It is recommended to define admissible pulsation limits in
accordance with API 618, last edition.
Special care to ensure cleanliness must be taken in the manufacture of damping vessels where the
design incorporates internal components, such as partitions, impingement plates, and tubes that
prevent complete visual inspection of all internal surfaces after completion of welding.
4.3
AIGA 021/12 /EIGA IGC13/12/ CGA 4.4 Oxygen pipeline and piping systems harmonized Code Ref
[2] states that it does not apply to oxygen compressor units. However compressor process piping
specification, fabrication, cleaning and inspection shall follow the criteria shown in Sections 5 to 7 of
reference code.
4.3.1 Extent
The recommendations contained in this section shall be limited to the piping directly associated with
the oxygen compressor and included within the oxygen compressor unit. In general terms this is
limited to the piping downstream of the suction isolating valve and will include the inlet filter system, all
piping between the compressor and non-integral coolers, by-pass valves and associated piping and
discharge piping from the compressor through to the outlet shut-off valve.
4.3.2 Vents to Atmosphere
Vent outlets shall be directed away from personnel
concentration of oxygen is avoided. In the case of
dispersion calculation be carried out. The vent line is
shall therefore be constructed of corrosion resistant
preclude the accumulation of water.
15
AIGA 048/12
4.3.3 Special Piping
Piping downstream of a recycle, dump, or relief valve shall be considered as a pressure letdown
station. The use of stainless steel could be agreed between the supplier and the user in vent duties
considering that:
they operate infrequently and for a short duration;
they have an atmospheric downstream pressure.
A type of pressure reducing system which has proved satisfactory is the use of a matched
combination of a valve plus a static pressure reducing device this is typically either a multi hole radial
diffuser or a multi plate axial diffuser. In this system the pressure let down is shared between the
valve and device and it is normally designed so that the velocity in the pipe work downstream of the
device is sufficiently low to permit the pipe work to be made of carbon steel.
Note: The velocity in the individual diffuser holes will be sonic and the materials used shall take this
into account.
It is recommended that the valve and pressure-reducing device be bought as a matched pair from the
same supplier.
Whatever solution is chosen it shall result in a low noise and low vibration pressure reducing system.
The recycle system shall be designed to pass full flow, at all operating conditions up to the maximum
continuous speed. This includes the point of entry to the main suction line and the main suction line
itself.
The entry of the recycle stream into the suction line shall be upstream of the suction filter. In order to
prevent damage to the suction filter the distance between the entry point and the suction filter shall be
not less than twice the diameter of the suction piping.
4.3.4 Bellows
Because of the vibration inherent to the reciprocating machine, bellows shall not be installed on
oxygen piping.
4.3.5 Acoustic and Thermal Insulation
Pipe external acoustic and thermal insulation material shall be compatible with oxygen at atmospheric
pressure. Care shall be taken to ensure that the pipe insulation is sealed against the ingress of oil
vapour. The supplier and the user shall agree the material used. Pipe internal insulation is not
permitted by the Code.
4.3.6 Silencers
Silencers are forbidden in the recycle or inter-stage pipe work. It is preferred that silencing of the
suction is achieved by insulating the suction pipe but if this is not practical then the use of suction
silencers is permitted. Suction silencers, if fitted, shall be located upstream of the suction filter. The
silencer shall be manufactured using oxygen compatible materials and the design shall be such that
the possibility of the internals breaking up is prevented.
4.4
Valves
16
AIGA 048/12
4.4.2 Safety relief valves
A full flow safety relief valve shall protect each stage of the compressor. Safety valves normally
operate in critical flow conditions, therefore care shall be taken of high velocities and
recommendations in 4.3.3 shall apply.
4.5
A filter shall be provided in the main suction line as close as practicable to the machine inlet flange. It
shall be installed before start-up and remain throughout the life of the machine.
4.5.1 Rating
The filter rating should be 150 micron maximum.
4.5.2 Materials
The filter media should be preferably manufactured from Cu-alloy or Ni-alloy. Stainless steel shall not
be used above 0.2 MPa gauge. If non-metallic materials are used then they shall be oxygen
compatible. In both cases the materials used shall be approved by both supplier and user.
4.5.3 Design
In designing the filter, due regard shall be given to providing adequate strength so as to avoid failure
of the filter element by the following causes:
Pressure pulsations
Where particle separators are used the design should take into account the possibility that separated
material may lift due to a sudden pressure drop.
4.5.4 Flow Direction
The filter unit shall be designed so that all attachments are upstream of the filter elements so as to be
contained within the elements should failure occur.
4.5.5 Precaution against Installation Errors
The filter unit shall be designed so as to prevent incorrect installation. An external indicator, such as
an arrow, shall be provided to indicate the direction of flow.
4.5.6 Inspection
The filter element shall be easy to remove for inspection and cleaning. During removal it should fully
retain all foreign particles.
4.6
4.6.1 General
Parts requiring operator attention or on-line maintenance should be outside the enclosure.
Lubricating oil pipes within the hazard area shall be kept as short as possible and be routed clear of
oxygen pipe work where possible. The number of joints shall be kept to a minimum and, where their
use is unavoidable, they shall be easily accessible and located so as to avoid the possibility of
lubricating oil dripping onto pipe work or other equipment.
17
AIGA 048/12
4.6.2 Pumps
A mechanically driven main oil pump which provides adequate lubrication during run down, caused by
total loss of power, is the method preferred by the code for motor driven units. .
4.6.3 Oil Heater
The surface area of the oil heater, if provided, shall be such that no local over heating or cracking of
the oil can occur. Oil heater shall not have any active heating surface that is not immersed in the oil.
Provisions shall be taken to avoid exposing heating surfaces dry.
4.6.4 Crankcase Vents
Crankcase vents if provided shall be piped away from the hazard area.
4.7
The capacity control shall be designed, manufactured and operated with special consideration given
to the prevention of a fire. Systems having a capability of dust accumulation or metallic friction or
shocks should not be used. The use of this system shall be agreed between supplier and user.
4.7.1 General
Protective controls and instrumentation shall be provided for every oxygen compressor in accordance
with but not necessarily limited to those described in the following paragraphs. The minimum alarm
and trip requirements are tabulated in 4.7.6. All measurements taken inside the hazard areas whilst
the machine is on oxygen service shall be remotely read in a safe environment.
The trip system may be executed by computer software provided that the reliability is not less than the
equivalent hard-wired system.
The speed of the tripping system should be as fast as possible therefore the slowing down of the
system to avoid trips due to transient voltage dips, etc. should be kept to an absolute minimum
commensurate with the engineering of a reliable system.
If a fluid is used in a pressure transducer that is in contact with oxygen, then it shall be oxygen
compatible.
A first up alarm system is recommended.
Electrical pressure switches directly actuated by oxygen shall be of a design avoiding contact
between oxygen and switching element. Electric, pneumatic or hydraulic power failure of any system
or mandatory trip shall actuate the respective controls in a failsafe manner.
4.7.2 Recycle System
Cooling will be required if recycle oxygen can cause excessive temperature in the machine.
4.7.3 High Oxygen Temperature Protection
Compressor failures are generally associated with gas temperature rise. Monitoring the gas
temperature from each stage can indicate potential trouble. Fast response sensors should be installed
in the oxygen path at each process stage suction and discharge. They should be positioned as close
as possible to the valves and before the first elbow if any.
The measurement and indication of each stage temperature, shall allow for the compressor to be
tripped at preset levels. The tripping temperatures will be related to and in excess of the maximum
normal operating discharge temperature experienced. However, maximum normal values are
recommended: 170C for ringed compressors, 200C for labyrinth compressors
18
AIGA 048/12
4.7.4 Vibration
Compressors shall be provided with a vibration shut down system. .
4.7.5 Compressor Isolation and venting
In the event of a trip, the compressor unit must be quickly isolated from the rest of the oxygen system.
A means of venting the oxygen shall be provided.
4.7.5.1
A non-automatic isolation valve shall be provided in the suction pipe work to the compressor and a
non-automatic isolation valve shall be provided in the discharge pipe work.
4.7.5.2
A non-return valve shall be installed in the discharge pipe work of each compressor. This valve should
be down stream of any recycle branch. A plate type check valve is recommended. Any type of swing
type check valve shall not be used.
Non-return valves shall be marked with an arrow to indicate correct direction of flow. The non-return
valve may be of the same design and materials as the compressor stage valves.
4.7.5.3
In addition to the suction and discharge isolation valves (4.7.7 & 4.7.8), an automatically actuated
fast-acting isolation valve shall be installed in the suction pipe work when the normal suction pressure
is greater than 0.1 MPa gauge and in the discharge pipe work. These valves shall be arranged to
close on every routine shutdown or trip, and on instrument air failure or electrical failure.
4.7.5.4
To limit the duration and extent of any fire, which occurs, automatic venting shall be considered. For
example, an automatically actuated fast-acting vent valve may be installed in the delivery between the
final stage cylinder discharge flange and the non-return valve. This valve should open on every
routine shutdown and trip on instrument air failure or electrical failure and discharge the bulk of gas
contained in the compression system quickly to atmosphere. Experience with such system is very
limited but it is considered that to be effective there should be a substantial pressure fall in a few
seconds. In case of a compressor trip due to an emergency, the primary consideration should be to
isolate the compressor from the oxygen supply and immediately dump the oxygen inventory so that
the pressure in the entire compressor system falls to 0.1 MPa gauge in not more than 20 seconds. To
achieve this, automatic and quick operation of isolation and vent valves is normally required.
For large compressors a vent valve at an intermediate stage may be required in addition to the
discharge vent valve. For machines with a normal final discharge pressure less than 2 MPa gauge
and with an inventory of oxygen below 10Kg (measured from inlet of suction strainer to discharge
isolation) an automatic vent system is not necessary.
It is considered that for a low inventory, low-pressure system the consequences of a fire are small and
any system breach is likely to depressurize the system in less time than a dedicated dump system
would take to operate.
19
AIGA 048/12
Function
1.0
1.1
1.2
1.3
1.4
1.5
Oxygen
Compressor Suction pressure (after filter)
Compressor Final discharge pressure
Suction filter diff. pressure
Compressor suction temperature
Temperature of main gas stream at each process
stage outlet (See 4.7.3).
Cooling Water System
Main supply flow
Bearings and Lube Oil System
Filter diff. pressure
Pressure after filter and cooler
Temperature in supply manifold after the oil cooler
Vibration system
Miscellaneous
Rod drop indicator (non vertical cylinders)
2.0
2.1
3.0.
3.1
3.2
3.3
4.0
5.0
5.1
Hi, Lo
= Not required
= Mandatory
= Recommended
1.
2.
Indicator
Alarm
Trip
Lo
(Hi)
(Lo)
Lo
-
Hi
Hi
()
(Lo)
Lo
(Hi)
(Hi)
Lo
2
(Hi )
Hi
(Hi)
(Hi)
Interlock
(Lo )
a)
b)
On
Compressor
Shutdown
On Loss of
Electrical
Signal
On Loss of
Motive
Power
SPEED OF
ACTION
Shut
Shut
Shut
10 secs max
Shut
Shut
Shut
10 secs max
Open
Open
Open
2 secs. max.
auto reclose
after
depressurization
The relatively slow closing of the isolation valves is to ensure that the dump vent valves have opened first. This is
desirable to prevent the safety relief valves to open.
The failure mode and operating speed of the recycle valve is not related to safety
20
AIGA 048/12
4.7.8 Reciprocating Oxygen Compressor System flow diagram
5.1
Introduction Code
Compressors can be shipped from suppliers works either as fully assembled, tested, and oxygen
clean units or as separate components to be erected on site. This latter implies pipe work to be site
fabricated.
Any combination between the two above extremes is also possible.
5.2
Responsibility
Whatever the extent of prefabrication there shall be a designated person responsible for ensuring
that the compressor is correctly built. On request, supplier shall provide from his staff an experienced
oxygen compressor erector, who will be in charge of the unit till it is handed over to the user. It can be
seen however that, if units or subassemblies are brought to site cleaned, tested and sealed, then the
designated persons responsibilities extend back to the suppliers and major sub suppliers works.
5.3
Cleaning methods and acceptance criteria to be followed shall be those shown in AIGA 012/04
Cleaning of equipment for oxygen service Ref.[3]. Given hereunder are:
Some comments on topics that are specific to reciprocating oxygen compressors.
A summary for the convenience of code users.
21
AIGA 048/12
5.3.1 Extent
The criteria clean for oxygen service shall apply to:
All parts that come in contact with oxygen;
Systems that supply gas to the oxygen compressor (e.g. start up gas) shall comply to the extent
that the gas supplied is free of particles and hydrocarbons.
5.4
5.4.1 Equipment
All equipment sent to site clean for oxygen service shall be protected against contamination and
corrosion. A label stating, cleaned for oxygen service shall be visible from outside the package.
The size and complexity of the equipment being shipped dictates the appropriate method of
preservation. The only methods of preservation, which are acceptable to the code, are as follows.
5.4.2 Individual Components
Individual items such as pistons, cylinder valves, regulators, filters etc which are being shipped
separately shall be protected, either by sealing within a strong clean plastic bag or for smaller
components by vacuum wrapping.
Note: If the component requires protection against rusting then the plastic bag shall contain bags of
desiccant with a colour change additive to detect moisture.
5.4.3 Sub-assemblies, which can be made Pressure Tight
5.4.3.1
Sub-assemblies that do not require protection against rusting shall have their openings sealed with
full-face gaskets of oxygen compatible material and substantial covers of wood or metal. Plastic plugs
or gaskets secured with tape are not permitted.
Example: Gas in shell cooler with a zinc coated shell.
5.4.3.2
Sub-assemblies that require protection against rusting shall have their openings sealed with gaskets
and metallic covers. Their integrity shall be demonstrated before leaving the suppliers works by leak
checking against a small internal pressure. All spaces shall be blown out with dry oil free air or
nitrogen before the sub-assembly is sealed.
Rust protection can be provided by one of the following means:
Bags of desiccant, which contain colour change additive to detect moisture, shall be attached to the
inside of appropriate opening covers and elsewhere within the sub-assembly as required. The
number and position of the desiccant bags shall be painted on the sub-assembly exterior.
Pressurising the sub-assembly with dry oil free nitrogen. The sub-assembly shall be fitted with a
pressure gauge and have a notice painted on it warning that it is pressurised.
Colour change type moisture detectors shall be fixed to the inside of selected opening covers to give
confirmation that the preservation measures have been effective.
22
AIGA 048/12
5.4.4 Arrival on Site
When oxygen clean components and subassemblies arrive on site the preservation arrangements
shall only be altered/broken with the approval of the designated person.
If the preservation is found not to be intact and if the moisture detectors, if fitted, have changed colour
then the subassembly shall be opened for inspection and recleaned until the designated person is
satisfied that the equipment is clean for oxygen service.
6
6.1
Erection
6.1.1 Responsibility
(See 5.2 - inspection and shipping).
The increased emphasis on packaged compressors means that the responsibility for the correct
erection and the maintenance of cleanliness of the compressor system may well extend back to the
suppliers and major sub-suppliers works. The statement under 5.3 - inspection and cleanliness
standards applies to the cleanliness standards throughout the erection of the compressor unit. On
request, the designated person shall keep a chronological record showing who carried out the main
assembly work and who took the as built measurements and carried out the testing. This applies
even if the person concerned came from another firm. It is also recommended that he keeps an
Oxygen Cleanliness Log which records the time, the person and the place that each part of the
oxygen circuit, including the gas feeds to the compressor were approved as clean for oxygen
service. It should also record the inspection method used, e.g. ultra violet light, solvent analysis, etc.
6.1.2 Tools
The tools, appliances and measuring devices used during installation and assembly of the
compressor and auxiliary equipment which come into contact with oxygen shall be cleaned with a
suitable cleaning agent and maintained in a clean condition during their use for this purpose. Tools
used for the lubricating oil system or other parts of the machine shall not be used for oxygen carrying
components, unless they are properly cleaned first. Only lint free cleaning cloth shall be used. When
using lifting tackle, any contamination by oil from the ropes, gears or other sources of lubrication shall
be prevented.
6.1.3 Purging after Assembly
If the compressor cannot be put into operation at the time erection is completed, appropriate
measures shall be taken to protect it against possible damage:
Cooling water spaces of compressor and coolers shall be drained, and drain valves left open.
An oil-free, dry, non-flammable gas purge shall be maintained in the compressor as necessary to
ensure that a non-corrosive atmosphere is maintained in the machine.
6.2
6.2.1 Introduction
In some instances compressor is shipped from the suppliers works as a complete fully tested, oxygen
clean compressor system. However, in other instances the compressor system is site erected and
fabricated. Therefore the test plan employed must be adapted to the circumstances presented by the
specific installation while meeting the objectives stipulated below.
23
AIGA 048/12
6.2.2 General
Any instrumentation required for testing the machine, e.g. pressure gauges, flow meters should only
be used for this duty. When they are used on site they shall be specifically cleaned and marked for
oxygen use only. All parts that are normally under pressure including the instrumentation, gas and oil
pipe work shall be subjected to a pressure test, unless specified elsewhere in the code. The type of
test and test pressure shall be agreed between supplier and user.
6.2.3 Testing Objectives
It is not permitted to put the compressor into oxygen service unless the testing has achieved the
following objectives:
Demonstration of the mechanical integrity of the complete compressor system over the predicted
operating range.
Verification of the predicted operating temperatures.
Functional demonstration of the instruments and controls.
6.2.4 Tests to be carried out
6.2.4.1
A leak test followed by a mechanical test (run test) shall be performed. During run test operating
conditions, vibration amplitudes and frequencies, stages and valves temperatures and bearings and
oil temperatures shall be monitored and logged.
After run test compressor:
Cylinders and rods shall be checked for scoring, scuffing or other types of damage
Distance pieces and piston rods shall be inspected for contamination or oil carryover.
Crosshead inspection covers shall be removed to inspect the crosshead slide for scoring or damage.
Piston rod lock nuts shall be inspected for any looseness or movement.
Piston to cylinder clearances shall be checked and logged again.
6.2.4.2
Prior to running the compressor all the instruments shall be calibrated and loop checked. Functional
checks shall be carried out of the following:
a)
b)
c)
d)
e)
6.2.5.1
Before any attempt to run the compressor on oxygen the designated person shall satisfy himself
that:
a) All the test objectives have been met.
24
AIGA 048/12
b) The entire compressor system has been certified clean for oxygen service.
c) That run in with inert gas or dry air has been successfully performed and no leaks and/or
abnormal running conditions have been detected.
d) There is satisfactory proof that the pipeline upstream of the compressor has been cleaned for
oxygen service. In addition this can be demonstrated by blowing through with dry air upstream of
the filter at a velocity not less than normal operating velocity for a period of several hours. This
blow through shall be vented upstream of the suction filter and as close to it as possible.
The hazard area is clean and tidy and free from all combustible materials and fully functional
6.2.5.2
Before running the compressor on oxygen, the hazard area shall be cleared of all personal. Oxygen
should first be introduced to the running machine slowly blending it in until the unit is brought to
design purity. During the start-up and until establishment of constant operation all indicating
instruments should be constantly watched, with special attention devoted to the gas pressures and
temperatures and the valves temperatures, and the vibration levels. The values indicated should be
logged at short intervals (about every 15 minutes). After about four hours of operation readings may
be taken and logged at hourly intervals.
7
Operation
7.1
General
Factors requiring specific attention in the operation of an oxygen compressor can be tabulated as
follows
7.1.1 Combustible Matter
Dust, oil, grease and other forms of combustible matter readily ignite in oxygen. Combustible
materials shall not be stored in the vicinity of oxygen compressors.
7.1.2 Machine Rubs
Rubs in a machine can cause ignition, due to localised high temperatures being generated.
7.1.3 Machine Vibrations
Machine vibrations stemming from misalignment, mechanical defects, etc. can cause bearing failures,
subsequently leading to rubs.
7.1.4 Leaking Cooler Tubes
Leaking cooler tubes can result in rusting of the oxygen containing components due to water intrusion
when the equipment is in an un-pressurized condition. The resulting scale can serve to promote
ignition in the compressor.
7.1.5 Gas Leakage Hazard
Although high efficiency packing and packing cases are used and leakage recovery piping provided, it
is possible for oxygen leakage into the distance pieces to occur. Provisions shall be taken to avoid
oxygen concentration build up. Packing performance should be monitored for increases in leakage,
which indicate excessive wear and the need for replacement.
Care shall be taken during compressor inspection, even with shutdown machinery. Leakage and
accumulations of gases can occur without operators being aware of this. Any source of open flames
or ignition can cause a conflagration in an operators clothes that may be impregnated with oxygen.
Oxygen deficiency from nitrogen leakage during compressor run in can cause asphyxiation.
25
AIGA 048/12
7.1.6 Oil Leakage Hazard
It is a primary safety concern that the lubricating oil in the crankcases of reciprocating oxygen
compressors shall not be allowed to migrate up the piston rods into the distance pieces. To prevent
this from happening the frame oil heads are provided with high performance oil scrapers to clean any
oil off the piston rods before they enter the distance pieces.
Because these scrapers are subject to wear their performance can deteriorate over time and therefore
their performance shall be routinely monitored so that a potentially hazardous condition can be
avoided.
7.2
The operating personnel should have special training in machine operation and should be fully aware
of the special significance to be attached to variation in instrumentation readings.
Certain knowledge of the machine construction is necessary to fully understand the importance of
oxygen safety.
7.3
Hazard Area
If it is considered necessary to enter the hazard area for the analysis of defects when the machine is
operating it must first be changed over to dry clean air or inert gas. It should be noted that, in the
vicinity of the hazard area, both an oxygen enrichment and an oxygen deficiency can occur, due to,
for example leaking flanges or defective seal systems. For safe working the oxygen concentration
should be between 19,5% and 23,5%.
7.4
A log of normal operating conditions shall be prepared, derived from commissioning and design data,
and this shall form the basis of the log sheet for use by operating personnel.
Log sheets should be regularly compiled for the machine. Automatic logging may be used.
A record of the number of machine starts and hours run shall be kept.
7.5
Critical operating parameters should be monitored at least once per shift. In cases where plants are
computer controlled, trend monitoring is easily accomplished. Where such equipment is lacking, data
should be recorded on a regular basis. Data should be compared with previous readings to confirm
that proper operation is continuing or if corrective action is required. No readings are to be taken
within the barrier unless it can be done through an inspection port.
7.5.1 Trip Override
The compressor shall not be run on oxygen with any trip by-passed. Where a machine is shutdown
by one of its protective trip functions it shall not be restarted until the reasons have been investigated.
7.6
Interlock Systems
Operators must be conversant with the principles and operations of any interlock system that may be
fitted.
7.7
Start-up Procedures
Routine operation of an oxygen compressor may require shut-down and subsequent start-up as a
normal procedure. The decision as to whether to start up directly on oxygen or on dry clean air or
inert gas must be taken by the user.
26
AIGA 048/12
7.7.1 Advisory Requirements
Start-up on dry clean air or inert gas is recommended on the following occasions:
- Start-up of a new machine after erection
- Star-up of a machine after a prolonged standstill
- Start-up of a machine after maintenance of the following type:
Maintenance that has necessitated the purging of the machine with dry clean air or
inert gas
Replacement of bearings
Replacement of piston, piston rings, packing, etc
7.7.2 Additional Requirements
Start-up on dry clean air or inert gas, or on oxygen is permissible for the following occasions:
-
Maintenance
8.1
General
8.1.1 Method
The frequency and content of maintenance work should be based on the suppliers recommendation
and the operators experience. In the event of adverse trends being observed in machine operation
the machine should be shutdown for examination and remedial action taken. Regular and detailed
analysis of the running data is of the utmost importance in ensuring the safe operation of the
compressor. This data can be used as a guide in establishing the period between major overhauls.
It is not possible to state a precise period between major overhauls, which covers all circumstances.
The period will depend upon the following:
If the operator has insufficient capability, then it is recommended that the supplier be involved in major
maintenance or repair work. The requirements and standards covered in section 6 must be complied
with.
Note: It has been noted that a number of fires have occurred immediately after overhauls. It is
therefore recognised that internal inspections could also be the cause of an increased risk.
8.1.2 Purging during Maintenance
Prior to conducting any maintenance work on an oxygen compressor provisions shall be taken to
ensure that the equipment is purged and positively isolated. It should be noted that both an oxygen
enrichment and an oxygen deficiency can occur, due to, for example leaking flanges or defective seal
systems. For safe working the oxygen concentration around the compressor should be between
19.5% and 23.5%.
27
AIGA 048/12
8.1.3 Functional Test
The correct operation of the compressor trip system and the dump and isolation valves is an important
contributor to the safe operation of oxygen compressors. In order to ensure correct operation, all the
components shall be recalibrated and the system subjected to a full functional test at least once every
3 years.
8.1.4 Cleanliness during Maintenance
During maintenance of the compressor the standards of cleanliness specified in 5.3 - inspection and
cleanliness standards should be observed.
8.2
Compressor Checks
Piston rods shall be checked for scoring, scuffing or other type of damage.
Distance pieces and piston rods shall be inspected for contamination or excessive oil carryover.
Spare Parts.
All components that come into contact with oxygen gas should be preserved as specified in 5.4
Preservation of Oxygen Cleanliness during Shipping and Storage.
9
Instruction Manual
9.1
General
The instruction manual must highlight the specific safety aspects in operating and maintaining oxygen
compressors and the need for a high standard of cleanliness.
9.2
28
AIGA 048/12
b) Description of the following systems, placing emphasis on the details which are special for oxygen
service:
Cooling system
Safety devices
Piston rod
Piston nut
d) Compressor operation, including start-up, shutdown and restarting procedures to safeguard the
compressor.
e) Maintenance with disassembly and assembly procedures and overhaul check list.
f)
j)
10
References
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
29