3rd Lecture
3rd Lecture
Transformer Classification
In terms of number of windings
Conventional transformer: two windings
Autotransformer: one winding
Others: more than two windings
In terms of number of phases
Single-phase transformer
Three-phase transformer
Depending on the voltage level at which the winding is operated
Step-up transformer: primary winding is a low voltage (LV)
winding
Step-down transformer : primary winding is a high voltage (HV)
winding
Basic Transformer
Transformer
1. Electrical device constructed of two or more
coils of wire (windings)
2. Electromagnetically coupled to each other
3. With a mutual inductance to transfer power from
one coil to the other coil
Schematic symbols indicate the type of core.
Air core
Ferrite core
Iron core
Basic Transformer
Turns ratio
Ratio of turns in the secondary winding (Nsec) to the
number of turns in the primary winding (Npri)
n
N sec
N pri
n = turns ratio
Nsec = number of secondary windings
Npri = number of primary windings
* Based on the IEEE dictionary definition for electronics power transformers.
Direction of windings
Determines the polarity of the voltage across the
secondary winding with respect to the voltage across the
primary.
Phase dots are sometimes used to indicate polarities.
Phase Dots
In phase
Out of phase
V sec N sec
Vpri
Npri
N sec
V sec
Vpri
Npri
V sec nVpri
n = turns ratio
120 Vrms
?30 Vrms
Isolation transformers
A special transformer with a turns ratio of 1 is called
an isolation transformer.
Because the turns ratio is 1, the secondary voltage is
the same as the primary voltage
ac is passed from one circuit to another.
Isolation
transformer
1:1
120 Vac
120 Vac
Current
Transformers cannot increase the applied power.
If the secondary voltage is higher than the primary
voltage, then the secondary current must be lower than
the primary current.
If the secondary voltage is less than the primary
voltage, then the secondary current must be higher
than the primary current.
Ppri=VpriIpri
Ideally
Psec=VsecIsec
Current
The ideal
transformer turns
ratio equation for
current is
I pri
I sec
Non-ideal transformers
Operational losses occur due to:
Leakage flux: flux that goes through one of the transformer windings
but not the other one
Mutual flux: flux that remains in the core and links both windings
P M LP
S M LS
Magnetization Current
E1
E1
qo
Excitation current, Io
Magnetization current IM
(current required to produce flux
in the core)
IM
Io
S V1 I1 V2 I 2 100 MVA
V1 N1 138 kV
10
V2 N 2 13.8 kV
+
V1
-
N1
I2
N2
+
V2
-
100 MVA
I2
7250 A
V2
13.8 kV
S
100 MVA
I1
725 A
V1
138 kV
31
Power Ratings
short-circuit test
Voc I oc
V
I
oc oc
The power factor is always lagging for a transformer, so the current will
lag the voltage by the angle q. Therefore, the admittance YE is:
YE
I
1
1
j
oc cos 1 PF
RC
X M Voc
Vsc I sc
Vsc I sc
V
R p a 2 Rs j X p a 2 X s sc cos 1 PF
I sc
Short-circuit test
(on primary)
Voc = 8000 V
Vsc = 489 V
Ioc = 0.214 A
Isc = 2.5 A
Poc = 400 W
Psc = 240 W
Answer to Example 2
Vs full load
100
Transformer Efficiency
Power Output
Power Input
Power Input Losses
Power Input
1
1
Losses
Power Input
Pcopper
Pcopper
loss
loss
Pcore loss
Transformer efficiency
The efficiency of a transformer is the ratio of power
delivered to the load (Pout) to the power delivered to the
primary (Pin).
Pout
Pin
100%
eta
Vpri
120 Vrms
15 Vrms
RL
100 W
Transformer efficiency
VL 2
15 V 2
Pout
R
100 W 100% 94%
L
100%
100%
120 V 0.020 A
Pin
Vpri I pri
Vpri
120 Vrms
15 Vrms
RL
100 W
94%
Example 2
Example 2: You have a transformer thats primary power is 150W. If 10.5 W are
dissipated in the winding resistances, what is the output power to the load,
neglecting any other losses?
Example 3
A single-phase, 100-kVA, 1000:100-V, 60-Hz transformer has the
following test results:
Open-circuit test (HV side open): 100 V, 6 A, 400 W
Short-circuit test (LV side shorted): 50 V, 100 A, 1800 W
Draw the equivalent circuit of the transformer referred to the highvoltage side. Label impedances numerically in ohms and in per unit.
PU System
Per unit system, a system of dimensionless parameters, is used for
computational convenience and for readily comparing the performance
of a set of transformers or a set of electrical machines.
PU Value
Actual Quantity
Base Quantity
VAbase
V base
PU
I base
V base
ohm
Z base
2
2
V base V base
V base
RS = 0.05 ohm
XP = 45 ohm
XS = 0.06 ohm
RC = 250,000 ohm
XM = 30,000 ohm
Find the equivalent circuit of the transformer referred to the highvoltage side.
b)
b)
c)
Assume that the transformer is supplying rated load at 480 V and 0.8
power factor lagging. What is this transformers input voltage? What is
its voltage regulation?
d)
Secondary with
center-tap
Transformer
7200 V
120 V
CT Ne
utral
120 V
Service
entrance
Building
120 V
240 V
120 V
Distribution
or breaker box
Earth
ground
Tapped
Tappedand
andmultiple-winding
multiple-windingtransformers
transformers
Three-phase transformers
Three-phase power is used for power transmission and
industrial applications.
Voltages in a three-phase system can be transformed with
1. three identical single phase transformers or
2. one three-phase transformer.
Three-phase transformers
Three-phase transformers are wired in either a wye or a delta
configuration or a combination of both.
This transformer is a
wye-to-delta
configuration, which is
generally used in step
down cases.
The delta-wye (not
shown) is generally
used in step up cases.
Three-phase
wye to delta
transformer
Vpri
Vsec
Delta to Wye
Delta to Delta
Wye to Delta
Wye to Wye