Set 6 Ans
Set 6 Ans
1
Y(t)/10 = 1
1 2
Overshoot = exp
1
1
f = T = 2
t sin
exp
1 2
1 2
Solution
(a) Percent overshoot = 25.4%
(b) Rise time = 1.0814 s
(d) Ultimate value of Y(t) = Y() = 10
(c) Maximum value of Y(t) = 12.54
(e) Period of oscillation = 3.4278 s
Rise time
t
1 tan 1
1 2
2. The two-tank system shown in Figure E-2 is operating at steady state. At time t = 0, 10 ft3
of water is quickly added to the first tank. Determine the maximum deviation in level (feet)
in both tanks from the ultimate steady-state value and the time at which each maximum
occurs. Data: A1 = A2 = 10 ft2, R1 = 0.1 ft/cfm, R2 = 0.35 ft/cfm.
Note: Q1 = h1/R1, if y(t) = (0) (unit impulse) then Y(s) = 1.
3
20 ft /min
10 ft
h1
R1
Q1
A1
h2
R2
Q2
A2
Figure E-2
Solution
t = 1.7539 min
H2d(t) = 0.6059 ft
1 25( s 1)
2
3.1Determine y(t = 0), y(t = 0.6), and y(t = ) if Y(s) = s s 2s 25
Solution
y(t = 0) = 0, y(t = 0.6) = 2.05, and y(t = ) = 1.
4.1 Sketch the response y(t) if Y(s) = exp(2s)/[s2 + 1.2s + 1]. Determine y(t) for t = 0, 1, 5, .
Solution
y(t) =0 for t = 0, 1,
>> t=5;
yt = 0.1396
5.2 The two tanks shown in Fig. E-6 are connected in an interacting fashion. The system is
initially at steady state with q = 10 cfm. The following data apply to the tanks: A1 = 1 ft2, A2
= 1.25 ft2, R1 = 1 ft/cfm, and R2 = 0.8 ft/cfm.
(a) If the flow changes from 10 to 11 cfm according to a step change, determine
H2(s),i.e., the Laplace transform of H2 where is the deviation in h2.
(b) Determine H2(1), H2(4), and H2().
Q
R
A
Figure E-6
Solution
(a)
1
0.8
2
H2(s) = s s 2.8s 1
(b)
t = 1 min H2(t) = 0.8+B*exp(-2.3798)+C*exp(-0.4202) = 0.1777 ft
t = 4 min H2(t) = 0.8+B*exp(-2.3798*4)+C*exp(-0.4202*4) = 0.6191 ft
t = H2(t) = 0.8 ft
6.1 The overhead vapor from a depropanizer distillation column is totally condensed in a
water-cooled condenser at 120oF and 230 psig. The vapor is 98 mol % propane and 2 mol %
isobutene. The vapor design flow rate is 40,000 lb/h and average latent heat of vaporization is
128 Btu/lb. Cooling water inlet and outlet temperatures are 75 and 100 oF, respectively. The
condenser heat transfer area is 1000 ft2. The cooling water pressure drop through the
condenser at design rate is 50 psi. A linear-trim control valve (air-to-closed, when CO = 20
mA, PV = 15 psig) is installed in the cooling water line. The pressure drop over the valve is
25 psi at design with the valve half open.
The process pressure is measured by an
electronic (4-20 mA) pressure transmitter whose range is 150-400 psig. An analog electronic
proportional controller with a gain of 2 is used to control process pressure by manipulating
cooling water flow. The electronic signal from the controller (CO) is converted into a
pneumatic signal in the I/P transducer.
Vapor
C o o lin g
w a te r
C o n tr o l v a lv e
C ondenser
PV
I/P
R e f lu x d r u m
PT
PM
PC
CO
SP
a) Calculatethecoolingwaterflowrate(gpm)atdesignconditions.Waterdensityis62.3
lb/ft3and1ft3=7.48gal
____________
409 gpm
b) If the cooling water flow rate is 250 gpm at design conditions, calculate the size
coefficient (Cv) of the control valve.
Cv = _________
0.5
Cv = 100 gpm/psi
(c) Calculate the value of the signal PM at design condition ________
PM = 9.12 mA
(d) Calculate the value of the signal PV at design conditions
_________
CO = 9 psig
(e) Suppose the process pressure jumps 20 psi, determine value for CO
_________
7.
CO = 9.44 mA
Express the function given the graph in the t-domain