Caterpillar - The Impact of Generator Set Underloading - Online Community

Generator sets are designed to operate between certain load percentages to maximize efficiency and reliability over the long term. Operating outside these parameters, such as at loads less than 30% for extended periods, can negatively impact the generator set through issues like exhaust manifold slobber, deposit buildup, reduced lifecycles, and increased downtime. Both diesel and natural gas generator sets require proper loading and periodic operation at higher loads to clean deposits and avoid excessive wear.

Uploaded by

victor.cipriani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
371 views

Caterpillar - The Impact of Generator Set Underloading - Online Community

Generator sets are designed to operate between certain load percentages to maximize efficiency and reliability over the long term. Operating outside these parameters, such as at loads less than 30% for extended periods, can negatively impact the generator set through issues like exhaust manifold slobber, deposit buildup, reduced lifecycles, and increased downtime. Both diesel and natural gas generator sets require proper loading and periodic operation at higher loads to clean deposits and avoid excessive wear.

Uploaded by

victor.cipriani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

18/8/2015

CaterpillarTheImpactofGeneratorSetUnderloadingOnlineCommunity

OnlineCommunity : ElectricPowerGenerationDiscussion : BLOG:PowerPerspectives :


TheImpactofGeneratorSetUnderloading

TheImpactofGeneratorSetUnderloading
byBrian(bjabeck)
0316201506:49AMedited
0316201506:52AM

Systemhealthandreliabilityarecriticaltobackupandprimepowersolutionsforanyinstallationfrommissioncritical
datacenterstoneighborhoodgrocerystores.Whilepowersystemsvaryinoperation,applicationandloadprofile,theyre
alldesignedtoprovidereliablepowerandmaximizedefficiency.Thegeneratorsetisakeypieceofthepowersystem
thatrequiresspecialattentionforlongtermsystemreliability,availabilityanduptime.Toachievethese,itsimportantto
understandsystemoperation,loadprofileandrequiredmaintenance.Thisblogwillfocusongeneratorsetoperationin
lowloadscenarios,andwhatcanresultiftheyareusedoutsideofspecificparameters.

First,itisimportanttounderstandthatgeneratorsetsaredesignedtorunwithload.Thismayseemtrivial,butloadinga
generatorsetproperlyisessentialtoavailabilityandalongenginelife.Manufacturerserviceintervalsandprojected
componentlifearebasedonoperationinloadrangestodeliveranidealmixofproductperformance,powerdensityand
longtermoperationallife.

Incorrectgeneratorsetoperationcanresultinreducedoutput,componentdamage,reducedlifecycles,andunscheduled
downtime.Theidealoperationtargetsofeachgeneratorsetwilldependontheapplicationandrating.

UnderloadingDieselGeneratorSets

Generallyspeaking,standbyandprimerateddieselgeneratorsetsaredesignedtooperatebetween50and85percent
load,whilecontinuousrateddieselgeneratorsetsoptimizebetween70and100percentload.Operatingdiesel
generatorsetsatloadslessthan30percentforextendedperiodscanimpactuptimeandenginelife.

Themostprevalentconsequenceofunderloadingisexhaustmanifoldslobber,orwetstacking,whichistheblackoily
liquidthatcanleakfromtheexhaustjointswhentheenginedoesnotreachminimumtemperaturesandpressures.
Visibleengineslobberdoesntnecessarilyindicateaproblem,butitsignalspossibleunderloadingconcerns,low
ambienttemperaturesorjacketwatertemperaturesthataretoolow.Additionally,longperiodsoflightloadingcanleadto
depositbuildupbehindthepistonringsorinsidethecylinders,whichcancausepowerloss,poorperformance,
acceleratedwearandinextremecases,cylinderlinerpolishing.

UnderloadingGasGeneratorSets

Naturalgasandbiogasgeneratorsets,independentofapplicationandrating,aretypicallydesignedforoperation
between60and100percentload.Withoutenoughcylinderpressuretomaintainoilcontrolatlowloads,gasengines
candevelopashdeposits,areduceddetonationmarginanddamagedenginecomponents.Similartodieselgenerator
sets,depositbuilduponvalves,sparkplugsandbehindpistonringscanoccurwhichmaycausecylinderliner
polishing,powerloss,poorperformanceandacceleratedcomponentwearultimatelyincreasingthelikelihoodof
highermaintenancecostsanddowntime.

ManagingLowLoad

Ifmaintainedproperly,dieselandgasgeneratorsetscanoperateatlightloadsforlongperiodswithoutharmfuleffects.
Afterunderloading,thegeneratorsetsshouldrunatincreasedloadtoraisethecylinderpressureandtemperature,
whichwillcleanthedepositsfromthecombustionchamber.Regularlowloadoperationrequiresamoreaggressive
maintenanceplantoreduceexcessivecomponentwearandmayrequireenginemodification.

http://208.74.204.235/t5/blogs/blogarticleprintpage/blogid/EP_Blog/articleid/656

1/4

18/8/2015

CaterpillarTheImpactofGeneratorSetUnderloadingOnlineCommunity

Dieselenginesshouldrunataminimumof30percentloadforabout30minutesforeveryfourhoursoflightload
operation,andoperatorsshouldmeasureexhausttemperaturepriortotheturboforanalysis.Naturalgasenginesare
moresensitivetolowloads,sotherearespecificunderloadingtimelimitsrequiredtomaintainoptimalperformance,see
thechartabove.Afterthetimelimithasexpired,theengineshouldrunataminimumof70percentloadforatleasttwo
hours.

Powersystemunderloadingimpactsindividualcomponentsaswellasoverallperformance,soitshouldnotbetaken
lightly.Whilethesimplesolutionistooperategeneratorsetsataloadthatmeetsdesignrequirements,therealityisthat
systemneedssometimeschange.Thismakesunderloadingcommonintherealmofpowergenerationespeciallyin
standbyapplications.However,theeffectsofunderloadingcanbeminimizedwithathoroughoperationand
maintenanceplantopreservesystemhealthandavoidextracostsdowntheroad.

Wedliketohearfromyou.Tellushowgeneratorsetunderloadinghasimpactedyouroperation.
Whatstrategieshaveyouimplementedtoensureoptimalperformanceatlowloads?
Inyourexperience,howhasunderloadingdieselgeneratorsetsdifferedfromnaturalgasfiredengines?
WhatcanCaterpillardotoimprovesystemdesignandhelpreducetheimpactofunderloadingforyourapplication?

Formoreinformation,visitwww.catelectricpowerinfo.comorcontactyourlocalCatdealer.

Comments
byBamgles2on
0319201504:45AM
Byunderloadingthegeneratoritwillaffecttheserviceofthegeneratorandelectricalsystem.

bymikelon
0322201502:37PM
Ingeneral,atleastbasedonmyexperience,dieselenginestendtobemuchmorerobustindealingwithunderloading
issues.Ingeneralyoucanrunthedieselsunderloadedforafairlylongtimeperiod,andaslongasyouperiodicallyrun
theengineatahigherloadto"cleanitout"youcanminimizetheaffectsoflowloadoperation.Multiplefactorsdocomeinto
play,likeoriginalageanddesignoftheengine.Olderdesignswithrectangularpistonrings,valvestemsealsandlower
fuelinjectionpressurestendtobemuchmoretolerantoflongperiodsoflowloadoperationthannewerdesignengines
withkeystoneringsandhighfuelinjectionpressures.Turbochargersarealsonegativelyaffectedbylowloadoperation,
mostlyduetounevenbuildupofdepositscausingimbalanceandchangestotheturbo'sresponse.

Gasenginesusuallyseethenegativeimpactoflowloadoperationmuchsoonerintheservicecycle,mainlyduetospark
plugfouling,thatcauseshardstarting,roughruningandpooracceleration.Onceaplugisfouleditalmostalwaysrequires
theplugtoberemovedandcleaned.Arunathigherloadtypicallywon't"cure"afouledplug.Alsodepositformationdueto
lowloadoperationcanleadtoanincreaseincompressionratio,andwiththatincreasingtheriskofdetonation.On
engineswithoutdetonationprotectionsystemthiscanleadtomechanicaldamage,onengineswithprotectionsitwilllead
tounwantedshutdowns.

Underloadingaffectstheoperationoftheprimemover,itcausesproblemswithstarting,rampingtoratedspeed,abilityto
respondtotransientconditions,andstability.Itwillalsocauses"slobbering"anddepositsofincompletelyburnedfueland
oilintheexhaustsystemsthatcanleadtoexcessivesmokeandinsomecases,exhaustfires.

Idon'tthinkunderloadinghasanegativeaffectonthegeneratorendortheelectricalsystemastheelectricalsideofthe
systemismorepronetoproblemsduetooverloadingandheat.

Exhaustaftertreatmentifinstalledalsocanhavemanyproblemswithextendedperiodsofoperationbelowrecommended
minimumloadsduetofoulingofcatalysts,inabilitytoregeneratepartculatetraps,visibleemissions(smoke)andoutof
http://208.74.204.235/t5/blogs/blogarticleprintpage/blogid/EP_Blog/articleid/656

2/4

18/8/2015

CaterpillarTheImpactofGeneratorSetUnderloadingOnlineCommunity

complianceonpermittedexhaustgasconstituents.

Mytwocentsworth,MikeL

byProgen904on
0326201504:39PM
HowisitpossibletohaveanEPAratedengineatanyTierlevelthatproducesexcessiveexhaustemissionsatanyload
level???

bymikelon
0326201511:15PM
Byoperatingitoutsideof"standardconditions".Thingssuchasapluggedaircleaner,excessiveexhaustrestriction,wrong
grade/typeoffuel,incorrectairinlettemperture.whenyoulookattheTMIexhaustemissionsdataattheendyouseealot
ofdefinitionsthatdefinethenormaloperatingcharacterisiticsthatarerequiredtomaintainemissionscompliance.

Atierratedenginestilldoesnothaveanyformofactivefeedbackcontrols(suchasCEMSsystem)andwhileitdoeshas
moreextensiveprotectionstolimitdeviationfromdesiredemissionslevels,theycanstilloperateunderscertainconditions
outofcompliance.

byProgen904on
0327201507:56AM
SothenthequestionmaybeammendedtoreadhowisitpossibletohaveaproperlyinstalledandmaintainedEPArated
engineatanyTierlevelthatproducesexcessiveexhaustemissionsatanyloadlevel???

byBrian(bjabeck)on
0330201501:47PM

ProgenThisisaverygoodquestionandonewereceiveoftenandtherearemultiplescenarioswhereemissions
maybemeasuredaboveEPApublishedlimits.

1)Mfr'sthatprovidestationaryenginescertifiedtoEPAemissionsstandardsreportemissionsbasedon5engine
operatingloadsandspeedsandresultsarereportedasweightedaveragetestcycleemissions.Weighted
averagemeansthatsomeofthetestpointscountmorethanothersintheaverage.Further,theweightedcycle
meansthatanindividualtestconditionmaybeabovetheEPAlimits,buttheweightedaverageofall5testpoints
mustbebelowtheEPAemissionslimits.
2)Measurementvariabilityandordifferenttestmethodscanresultinemissionslevelsthatdifferfromthose
providedbythemanufacturer.
3)Localsiteconditionswhichincludeambienttemperature,humidity,barometricpressurecanalsoresultin
emissionsabovetheEPApublishedemissionslimits.
4)Theenginemaybeoperatingoffthetestcyclewhichmayallowslightlyhigheremissionsthanthestandardyet
remaincappedbyEPA.ThesearecalledNTEornottoexceedemissionslevels.
5)Theequipmentmaybeexperiencingacomponentproblemduetoage,lackofmaintenanceormanufacturing
defectwhichcanberesolvedbycontactingtheappropriatedealertodiagnoseandprovideamechanicalrepair.
.
BelowistheinformationthatdealersprovidewithourU.S.EPATier4certifiedemissionsdata.
EmissionsdatameasurementproceduresareconsistentwiththosedescribedinEPACFR40Part89,SubpartD
&EandISO81781formeasuringHC,CO,PM,NOx.Datashownisbasedonsteadystateoperatingconditions
of77F,28.42inHgandnumber2dieselfuelwith35APIandLHVof18,390btu/lb.Thenominalemissions
datashownissubjecttoinstrumentation,measurement,facilityandenginetoenginevariations.Emissionsdatais
basedon100%loadandthuscannotbeusedtocomparetoEPAregulationswhichusevaluesbasedona
weightedcycle.Emissionsvaluesaretailpipeoutwithaftertreatmentinstalled.Valuesshownaszeromaybe
greaterthanzerobutwerebelowthedetectionleveloftheequipmentusedatthetimeofmeasurement.

http://208.74.204.235/t5/blogs/blogarticleprintpage/blogid/EP_Blog/articleid/656

3/4

18/8/2015

CaterpillarTheImpactofGeneratorSetUnderloadingOnlineCommunity

Pleaseletusknowifyouhaveanyotherquestions.

byProgen904on
0331201510:20AM
Brian,
ThankyouforthesummaryonEPAlimitsandcertification.Ihopethatwemaycontinuethisblogformanymore
discussions.DoesCaterpillarhaverecordsofanydocumentedcaseswhereunderloadingcausedeventualfailureofthe
enginetopowertheconnectedload?Thesewouldbecaseswhereaddingadditionalconnectedloadsolvedtheproblem
withoutanymechanicalorelectricalrepairs.Forinstanceconsiderasinglegeneratorsetwitha100kWrating.The
connectedloadwhenitwasinstalledwas25kWsteadystatewithanoccasionallargemotorstartthatmightadd5kWfor
tenseconds.Thisisatypicalscenariowherethegeneratorsetwassizedtomeetvoltagedipminimumsduringmotor
starting.Ifthevoltagedipissueislaidasideforsimplicity,anyproblemscreatedbyunderloadingwouldhavetorender
inoperablethe75%reserve(unusedcapacity)oftheengine.Somedocumentedcasesofthisactuallyoccuringwouldbe
veryinteresting.

byvisittheirwebsiteon
0512201502:48PM
Oneofkeyconsiderationsforgeneratorsisabilitytorefuelyourgeneratorseasily.Oftenageneratorisplacedin
undergroundparkinglotsinbuildingswithnearlyimpossibletorefill.Greatateventofemergencynotsogoodwhenyou
havetorefuelafter8hours?

bykzon
0519201502:17PM
Thisismoreofaquestionandashoutforadvicethanacomment.Pleasenote*Sparesareamajorissue*
Enginesrunningat1200RPM.
IamonaJackupwith5x3516Bgensets.IamnewherebutIhavenoticedthatwefrquentlyhave3catsrunningonlight
loads,around30%.Thereisevidenceofslobberingandwehavesootysmokefromourexhaustsystem.
TherehavebeenregularinjectorissuesbutthereplacementpartsalthoughstampedwithCatmaynotbeOEM.Recent
CutouttestshavecomebackwithseveraloftheinjectorsasNOTOKevenafterbeingchangedfornew,Ihavenoother
infoonthis.
Irecentlychangedaheadwheretheexhaustvalvewasstuckabout10mminsidetheheadbodywhichwascokedupand
whenIinspectedtheCylinderboretherewasabuildupoflaquerandsignsofdetonationdistressonthecrown.The
rockerarmhadalsoshearedintheprocess.
Theseengineshavealldonearoundthe22Kmarkwithnooverhauls.
Isthereanywaybackfromthis?WoulditmakeanydifferenceatthisstageifIimplementedapolicywherebytheload
sharewasdecreasedi.e.convincedtheguystorun2enginesathigherloads(50/60%)insteadof3.

Anypointerswelcome.

by3512BGon
0818201503:44PM
Thisarticlematchesmyexperiences,thoughdieselenginesdonotlikelightloads,itleadstocrankcasedilutionand
slobberingorwetstacking.
Sometimes,however,theloadprofilemakeslightrunningunavoidable.
Astooilchangefrequency:someofthecomputercontrolledenginessettheirownoilchangeintervalbasedonan
algorithmwhichallowsextendedintervalswhentheengineislessthanfullyloaded.
Duetothepossibilityofcrankcasedilutionatlightloadsitmaynotbewisetoextendchangeintervalsonverylightly
loadedsets.

2 min to Spreed

http://208.74.204.235/t5/blogs/blogarticleprintpage/blogid/EP_Blog/articleid/656

4/4