Location: Project: Date:: Bus Voltage Generation Load Load Flow XFMR
Location: Project: Date:: Bus Voltage Generation Load Load Flow XFMR
Project:
12.6.0H
Location:
Contract:
Date:
08-22-2016
SN:
Engineer:
Filename:
Page:
Study Case: LF
suraj
Revision:
Base
Config.:
Normal
Bus
ID
* Bus1
Bus2
Bus3
Bus4
Bus5
Voltage
kV
% Mag.
220.000
106.000
220.000
220.000
220.000
220.000
102.723
100.531
100.359
99.600
Generation
Ang.
0.0
-2.5
-4.8
-5.1
-6.0
MW
Load
Mvar
130.215
40.000
MW
38.835
0.000
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
Load Flow
Mvar
20.221
45.096
40.057
59.904
ID
0
10.110
15.032
5.007
9.984
MW
XFMR
Mvar
Amp
%PF
Bus2
89.059
28.247
231.3
95.3
Bus3
41.156
10.588
105.2
96.8
Bus1
-87.487
-26.801
233.8
95.6
Bus3
24.640
3.702
63.7
98.9
Bus4
27.883
3.747
71.9
99.1
Bus5
54.744
9.243
141.8
98.6
Bus1
-39.848
-9.330
106.8
97.4
Bus2
-24.282
-4.693
64.6
98.2
Bus4
19.034
-1.008
49.8
-99.9
Bus2
-27.427
-4.443
72.7
98.7
Bus3
-18.998
0.107
49.7
100.0
Bus5
6.368
-0.671
16.7
-99.5
Bus2
-53.569
-7.255
142.4
99.1
Bus4
-6.335
-2.729
18.2
91.8
%Tap