Engineering Flow Calculations

1) This document calculates the flow requirements and pipe sizing for a plumbing system that includes 6 water closets, 1 wash basin, and 2 showers. 2) The total flow is calculated to be 6.6 cubic meters per hour (0.11 cubic meters per minute). With a pump capacity of 0.22 cubic meters per minute and a run time of 5 minutes, the total volume is 0.275 cubic meters. 3) Minor head losses are calculated for pipe fittings like elbows, valves, and reductions. With a pipe diameter of 50 mm, length of 50 meters, and roughness of 0.000007, the friction head loss is calculated to be 3.2289 meters.

Uploaded by

wado11
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
232 views4 pages

Engineering Flow Calculations

1) This document calculates the flow requirements and pipe sizing for a plumbing system that includes 6 water closets, 1 wash basin, and 2 showers. 2) The total flow is calculated to be 6.6 cubic meters per hour (0.11 cubic meters per minute). With a pump capacity of 0.22 cubic meters per minute and a run time of 5 minutes, the total volume is 0.275 cubic meters. 3) Minor head losses are calculated for pipe fittings like elbows, valves, and reductions. With a pipe diameter of 50 mm, length of 50 meters, and roughness of 0.000007, the friction head loss is calculated to be 3.2289 meters.

Uploaded by

wado11
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Flow Calculation :Fixure Unit

W.C
W.B
Shower

F.U.L

Total
6
1
2

6
5
4
Total

Total Flow =
Total Flow =
Pump Capicity=
Assume:Pump Running Time=
Volume=
Assume:Velocity=
Pipe Diameter=
Pipe Length=
Head Static=
Actual Pipe=
Actual Velocity=
pumps minor losses:
Gate Valve (discharge)
Tee, through side outlet (discharge)
Rounded entrance
Swing Check Valve (Fully Open,discharge)
Reduction Sudden D2=(0.8 to 0.5)

Rising main minor losses:


Standard short radius Elbow (discharge)
Tee
Exit Loss

Pump Capicity=
Pipe Diameter=
Velocity=
Pipe Length=
Renold Number=
Pipe Roughness=
Friction Loss=

6.6 Cu.m/hr
0.11 Cu.m/min
0.22 Cu.m/min
5 min
0.275 Cu.m
2 m/s
0.0483265608 m
50 m
4m
50 mm
1.8683651805 m/s
Coefficient of
Velocity Head

Number

0.16
1.8
0.2
2

1
1
1
1
1

Coefficient of
Velocity Head
0.75
0.75
1

Number
3
1
1

0.0036666667 Cu.m/s
0.05 m
1.8683651805 m/s
50 m
92768.8768851585
0.000007
0.018148136

hf=
Outlet Pressure
Total Head=
Efficiency
Power Claculation=
Power Claculation=
Sump Pit Geometry:Volume=
Water Level At Pump Start=
Water Level At Pump Stop=
Area=
Depth=
Length=
Width=

3.2289145565 m
10 m
18.6473203956 m
0.7
0.958205878 kw
1.2849540825 hp

0.275 Cu.m
1m
0.2 m
0.275 Sq.m
1m
0.69 m
0.525 m

Total Load

Flow GPM
36
5
8
49

29

0.030555556
3.666666667

Diameter
m
0.05
0.05
0.05
0.05
0.05

Diameter
m
0.05
0.05
0.05

Velocity
Minor Loss
m/s
m
1.86836518 0.028467184
1.86836518 0.320255821
1.86836518 0.03558398
1.86836518 0.355839801
1.86836518 0.05420997
0.794356756
Velocity
Minor Loss
m/s
m
1.86836518 0.400319776
1.583769285 0.095883989
1.583769285 0.127845318
0.624049083