Vav Diffusers Engineering Guide
Vav Diffusers Engineering Guide
VAV Diffusers
Please refer to the Price Engineers HVAC Handbook
for more information on VAV Diffusers.
Engineering Guide
Ceiling Diffusers
Diffuser Types
Conventional air distribution systems typically group several rooms
into a zone that is controlled by a single thermostat. Because rooms
within the zone can have different heating/cooling requirements, the
systems response to heating/cooling loads within the zone may not
be consistent with load requirements. The result can be a system
that compromises the comfort of the occupants in each room by
providing a blanket response to individual needs. As well, there is
resulting system inefficiency due to the overheating/overcooling
of rooms within the building.
Self-modulating Variable Air Volume (VAV) diffusers allow for
smaller, comfortable zones. They monitor local space conditions
and regulate air flow to satisfy the occupants selected level of
comfort. As air flow varies, the unique design of VAV diffusers
adjusts an integral damper to maintain face discharge velocities
and excellent throw characteristics. VAV diffusers can help solve
the inconsistent throws or dumping that may occur with some
overhead diffusers due to varying supply conditions.
Several different types of VAV diffusers exist, however most can be
grouped into two models: Thermally Powered and Electronically
Powered.
Thermally Powered VAV Diffusers
Thermally powered VAV diffusers, shown in Figure 1, commonly
use thermal actuators to modulate the flow rate of supply air into
a room according to a desired temperature setting. The diffuser
works independent of a BAS and does not require external power.
Based on this, the unit provides system flexibility and a low-cost
installation. Each occupant or small group of occupants can adjust
their local diffuser to their desired temperature, ensuring tailored
comfort levels for all occupants in the building.
A thermally powered VAV diffuser installs much like any other ceiling
diffuser. Once the supply duct is connected and air is flowing, the
thermally powered VAV diffuser begins to operate. Temperature setpoint adjustments and minimum air flow settings can be adjusted
on the diffuser core. The diffuser measures the room temperature
by inducing room air into the diffuser core and passing it over a
thermal actuator. Linkage contained within the core adjusts the
damper based on the difference between room and desired setpoint temperatures.Typically, diffusers are available for VAV cooling
and VAV cooling/heating with automatic changeover.
Electronically Powered VAV Diffusers
An electronically powered VAV diffuser, shown in Figure 2, uses
an electric modulating damper inside the diffuser core assembly.
The electronics to control the device are mounted on the top of the
backpan, out of sight from the occupied space. The analog or DDC
controller with proportional integral control will provide stable,
precise control with fast response. Space temperature control
within 1 F of set-point, true VAV cooling and heating, activation
of perimeter heat, and optional BACnet interface are all possible
with these types of units.
An electronically powered VAV diffuser will require an electrical
connection. Temperature set-point adjustment can be made in a
variety of ways:on board the unit, wall mounted thermostat, remote
control, or a building management system such as BACnet. The
room temperature is measured either by inducing room air into
the diffuser core or by the use of a wall thermostat. For a zone
larger than one diffuser, a master diffuser can drive several drone
diffusers. The drone units will adjust their dampers in unison as
dictated by the master unit.
C-188
ZONE
T-stat
ROOM
1
ROOM
2
ROOM
3
Rooftop
Controller
ZONE
1
ZONE
2
ZONE
3
Rooftop
Controller
ZONE
1
ZONE
2
ZONE
3
C-189
CEILING DIFFUSERS
Ceiling Diffusers
Operating Principles
Coanda Effect
When air passes over a static surface it will
follow the surfaces profile, providing there
are no sharp edges or abrupt changes.This is
what is known as the Coanda Effect (Figure
6) (ASHRAE, 2009) (Nevin, R. G., 1976). The
aerodynamic diffuser backpan ensures that
the supply air has a smooth transition from
the duct to the room. Supply air leaves the
diffuser, adhering to the ceiling as it flows
into the space, where it mixes with room air,
minimizing air pattern drop. By design, the
VAV diffuser backpan and internal damper
generate a tight high velocity jet pattern
with the Coanda Effect attaching it to the
ceiling surface. Without this design, the air
flow patterns may detach from the ceiling
prematurely and cause thermal discomfort.
Room Air Induction
Induction is the phenomenon of air being
drawn towards air in motion. As the speed
of air movement increases, the static pressure
in the local zone at the diffuser decreases,
pulling the surrounding air towards it. This
principle is important to the performance of
mixing systems; it is the elevated discharge
velocity that draws in room air and mixes it
with the supply air, as illustrated in Figure 7
(ASHRAE, 2007b). VAV diffusers rely on high
induction to effectively mix the supply and
room air to provide uniform room temperature
distribution with low room velocities.
No Turn-Down Effects
Conventional systems typically respond
to changes to the heating/cooling load by
varying the flow of air to the diffusers at
low loads. At low loads this can create low
velocity air streams at the diffuser, creating
the potential for unwanted drafts in the
occupied zone (ASHRAE, 2009).VAV diffusers
vary the volume of air supplied to a space
by modifying the diffuser outlet area. Face
velocities are maintained at a more consistent
level; high enough to maintain the Coanda
Effect and prevent diffuser dumping.Thus, the
performance of VAV diffusers is maintained
at all load levels due to the consistent face
velocities promoting increased room air
induction as illustrated in Figure 8.
Minimum Air Volume
To meet ventilation rate requirements, the
VAV diffuser must be set for a minimum
air volume. Both thermal powered and
electronically powered VAV diffuser, typically
have a means of setting this minimum air
volume which can be preset in the factory
or adjusted in the field. In some cases, this
minimum air volume setting may exceed the
cooling load, overcooling the space.To prevent
overcooling, some method of introducing
heat must be applied. With electronically
powered VAV diffusers, the control board can
activate perimeter radiation, radiant panels or
an upstream duct heater.Thermally powered
VAV diffusers will require an additional
thermostat to activate heat.
C-190
Ceiling
Coanda Effect
High Velocity
Discharge Air
Induced Air
Supply Air
Maintained ADPI
By definition, the air diffusion performance
index (ADPI) is the statistical percentage
of the points, when measured uniformly
within a space, whose local draft velocities
and temperatures fall within acceptable
comfort limits (ASHRAE, 2007b). An
explanation of the ASHRAE method for
estimating ADPI and selection procedures
can be found in Chapter 9Mixing
Ventilation in the Price Engineer's HVAC
Handbook (Table 1).
VAV diffusers are designed to maintain a
higher ADPI over the full range of movement
of their integral dampers within the
published operating range. As the damper
closes, the air volume discharged from the
diffuser is decreased; however, the velocity
of the air remains virtually constant due
to the resulting reduction in open area.
By maintaining the discharge velocity,
VAV diffusers ensure good induction and
mixing of the room through their operating
range. Furthermore, by maintaining the
velocity, the throw to 50 fpm is not reduced
as much as it is for a conventional air outlet
with a constant outlet area, which means
theT50/L ratio is not as significantly affected.
Therefore, the ADPI value should remain
acceptable as the integral diffuser damper
modulates.
Operating Principles
Figure 9: Thermally powered diffuser
with minimum air flow adjustment
Table 1: Air diffusion performance index (ADPI) selection guide (ASHRAE, 2007b) - IP
Terminal
Device
High Sidewall
Grilles
Circular Ceiling
Diffusers
1
Sill Grille
Straight Vanes
Ceiling Slot
Diffusers (T100 /L)
Light Troffer
Diffusers
Perforated &
Louvered Ceiling
Diffusers
Room
Load Btu/
hft2
T50 /L for
Maximum
Max. APDI ADPI
ADPI
Greater
Than
Range
of T50 /L
80
1.8
68
60
1.8
71
70
1.5-2.2
40
1.6
78
70
1.2-2.3
20
1.5
85
80
1.0-1.9
80
0.8
76
70
0.7-1.3
60
0.8
83
80
0.7-1.2
40
0.8
88
80
0.5-1.5
20
0.8
93
90
0.7-1.3
80
1.7
61
60
1.5-1.7
60
1.7
72
70
1.4-1.7
40
1.3
86
80
1.2-1.8
20
0.9
95
90
0.8-1.3
80
0.7
94
90
0.8-1.5
60
0.7
94
80
0.6-1.7
40
0.7
94
20
0.7
94
80
0.3
85
80
0.3-0.7
60
0.3
88
80
0.3-0.8
40
0.3
91
80
0.3-1.1
20
0.3
92
80
0.3-1.5
60
2.5
86
80
<3.8
40
1.0
92
90
<3.0
20
1.0
95
90
<4.5
11.51
2.0
96
90
1.4-2.7
80
1.0-3.4
Includes square cone diffuser (SCD) and square plaque diffuser (SPD). Since VAV diffusers
are based on the geometry of a square plaque diffuser, they will be included in this
category as well.
1
C-191
CEILING DIFFUSERS
Example 1
Ceiling Diffusers
In the following example, the ADPI will be evaluated for an electronically powered VAV diffuser and standard perforated diffuser
at the same room condition. Consider a 18 ft x 18 ft x 9 ft room with a 24 in. x 24 in. outlet centered in the ceiling.
Space Considerations
Some of the assumptions made for the space are as follows:
T50
T50 /L
ADPI
Perforated 4 way
Model
9 ft
15 ft
1.7
90
VAV
9 ft
12 ft
1.3
90
T50
T50 /L
ADPI
Perforated 4 way
Model
9 ft
8 ft
0.9
<80
VAV
9 ft
8 ft
0.9
90
Both diffusers provide good ADPI at the maximum flow. At minimum flow, the VAV diffuser has a much greater ADPI compared to the
perforated diffuser, which does not achieve the minimum acceptable ADPI level of 80.
C-192
Zoning Solutions
Figure 11: Solution 1 - Zones call for heating and cooling. Rooftop supplies either
cool air or warm air.
North
AHU
CEILING DIFFUSERS
North
Radiant Panels
AHU
C-193
Ceiling Diffusers
Example 1
Solution 3
Duct heater stations, an alternative to
Perimeter Radiation or Radiant Panels,
allow for thermal and ventilation demands
in a larger multiple demand zone system
(Figure13). For zones that require heating,
specific duct heater stations can energize
to supply heat to the specific zones rather
than supplying hot air from the rooftop to all
zones. The zones in which VAV diffusers are
located will automatically switch to heating
mode (if the option is selected) ensuring that
there is adequate zone ventilation for each
specific zone demand, and allowing other
zones to continue to function in cooling
mode. A major drawback for duct heater
station design is the additional energy costs
required to cool then reheat the air.
Solution 4
By using a rooftop unit with both cooling
and heating coils and a DDC rooftop unit
controller, BACnet networked VAV diffusers
can control the system to supply cooling or
heating based on the demand in the various
zones or rooms. Weighted and average
polling strategies can be used to determine
the overall building need for heating and
cooling, and control the rooftop unit directly
to ensure that these needs are met.
In the example shown in Figure14, the red
diffusers require 85% heating, the green
diffusers are 100% neutral, and the blue
diffusers require 30% cooling.
Under the polling average strategy, the total
system demand for the building is shown
in Table 2.
In this case, it would not make sense
to supply cooling to the blue diffusers
since they are a minority with respect
to the buildings overall heating/cooling
requirements. Under this control method,
the rooftop would supply heated air until
the demand was satisfied.
The advantage of this solution is that it takes
into account the size of the demand for
either heating or cooling, where the other
solutions simply energize heat when there
is a demand for heat. This method is more
energy efficient.
A drawback of this system design is that
not everyone is satisfied as the polling
scheme determines when the system is
in heating and cooling. However, this
can be adjusted through the addition of
reheat stations, perimeter heat or multiple
AHUs depending on the size of the space.
This method of measuring load can be
more energy efficient and comfort can be
addressed through proper polling schemes.
C-194
North
Duct Heater
AHU
AHU
North
AHU
425% Heat
3 x 30%
90% Cooling
3 x 100%
300% Neutral
Total Demand
815%
Selection Procedure
Selection of a VAV diffuser is dependent
on two main criteria: noise and pressure
dependent flow rate.
1. Determine the duct pressure for the
system based on pressure drop between
the fan discharge and the farthest
outlet. The static pressure should be
a maximum of in. w.g. entering the
VAV diffuser inlet to minimize the noise
generation.
2. Determine the maximum and minimum
flow rate to the diffuser based on the
room load and ventilation rate.
3. Select the VAV diffuser size from the
Modulated Flow Selection Table (see
0.10 Duct Ps
0.20 Duct Ps
cfm
Throw, ft
NC
cfm
Throw, ft
NC
6 in.
20
54
77
109
0-0-1
0-1-2
0-1-3
1-2-3
15
17
28
79
111
152
0-1-2
0-1-3
1-2-3
2-2-4
16
23
25
27
8 in.
46
112
170
242
1-1-3
2-3-5
3-4-7
4-6-9
20
23
26
64
158
240
342
1-2-4
3-4-7
4-6-9
6-4-10
24
31
33
36
10 in.
95
190
274
365
1-2-4
3-4-8
4-6-11
6-9-12
23
26
28
29
135
268
388
517
2-3-6
4-6-10
6-8-13
8-10-14
33
36
38
39
12 in.
120
202
311
478
2-3-6
3-4-9
5-7-11
8-10-14
27
28
29
30
169
285
441
675
3-4-8
4-6-11
6-9-13
10-12-17
38
38
39
40
14 in.
139
213
370
555
3-4-8
3-5-9
5-8-12
9-11-15
27
28
30
30
197
302
524
785
4-5-9
5-7-11
8-10-15
10-13-18
36
37
39
40
C-195
CEILING DIFFUSERS
Example 2
Ceiling Diffusers
C-196
Return
Supply
Pressure
Relief Collar
Supply
Return
CEILING DIFFUSERS
VFD
Return
Pressure Controller
Supply
C-197
Retrofit Applications
Reduce Thermal Comfort Complaints
When multiple occupants exist in a single
zone, chances are one or more people will be
thermally uncomfortable. VAV diffusers may
be a solution to this problem by subdividing
the zone and allowing the occupants to
adjust their local zone for temperature.
Either thermally or electronically actuated
VAV diffusers can be utilized for this. The
decision is usually made by weighing the
installation requirements versus the type of
temperature set-point control desired.
Facility Renovations
Instead of installing terminal units to
subdivide a large zone, VAV diffusers are
a practical alternative. Both thermally
and electronically powered models may
be used with the decision mainly based
on preference and requirements of the
diffusers. If the building already has or is
being upgraded to a building management
system, the preferred choice would be
the electronically powered models, as
outputs such as room temperature, supply
temperature and damper position would be
useful in troubleshooting the HVAC system.
Ceiling Diffusers
References
ASHRAE (2007a). Chapter 46. ASHRAE handbookHVAC applications. Atlanta,
GA: American Society of Heating, Refrigeration, Air-Conditioning Engineers.
ASHRAE (2007b). Chapter 56. ASHRAE handbookHVAC applications. Atlanta,
GA: American Society of Heating, Refrigeration, Air-Conditioning Engineers.
ASHRAE (20 09). Chapter 20. ASHRAE handbookFundamentals. Atlanta,
GA: American Society of Heating, Refrigeration, Air-Conditioning Engineers.
Nevins, R. G. (1976). Air diffusion dynamics, theory, design and application. Birmingham,
MI: Business News Publishing Company.
C-198