Need For Protection
Need For Protection
the
flexibility to meet the future demands. A power system is designed: to generate electric power in sufficient quantity.
to meet the present and estimated future demands of the users in a particular
area.
to transmit it to the areas where it will be used.
and then distribute to generate electric power in sufficient quantity.
to meet the present and estimated future demands of the users in a particular
area.
to transmit it to the areas where it will be used and then distribute it within
that area on a continuous basis.
To ensure the maximum return on the large investment in the equipment,
which goes to make up the power system and to keep the users satisfied with
reliable service, the whole system must be kept in operation continuously without
major breakdowns. This can be achieved in two ways
The first way is to implement a system adopting components, which
should not fail and requires the least or nil maintenance to maintain the
continuity of service. By common sense, implementing such a system
is neither economical nor feasible, except for small systems
Basic
requirements
protection:-
of
A
protection apparatus has three main functions/duties:1. Safeguard the entire system to maintain continuity of supply.
2. Minimize damage and repair costs where it senses fault.
3. Ensure safety of personnel.
These requirements are necessary, firstly for early detection and localization of
faults, and secondly for prompt removal of faulty equipment from service.
Qualities
system:-
of
protection
1. Reliability:2.
3.
4.
5.
6.
Their function is to
monitor and give accurate feedback about the healthiness of a system. Accurate
protection cannot be achieved without properly measuring the normal and
abnormal conditions of a system. In electrical systems, voltage and current
measurements give feedback on whether a system is healthy or not. Voltage
transformers and current transformers measure these basic parameters and are
capable of providing accurate measurement during fault conditions without
failure.
3. Relays:To convert the signals from the monitoring devices, and give
instructions to open a circuit under faulty conditions or to give alarms when the
equipment being protected, is approaching towards possible destruction. The
measured values are converted into analog and/or digital signals and are made to
operate the relays, which in turn isolate the circuits by opening the faulty circuits.
In most of the cases, the relays provide two functions viz., alarm and trip, once the
abnormality is noticed. The relays in olden days had very limited functions and
were quite bulky. However, with advancement in digital technology and use of
microprocessors, relays monitor various parameters, which give complete history
of a system during both pre-fault and post-fault conditions
4. Fuses:Self-destructing to save the downstream equipment being
protected. Fuse is the self-destructing one, which carries the currents in a
power circuit continuously and sacrifices itself by blowing under
abnormal conditions. These are normally independent or stand-alone
protective components in an electrical system unlike a circuit breaker,
which necessarily requires the support of external components.
5. DC batteries:These give uninterrupted power source to the relays
and breakers that is independent of the main power source being
protected. The operation of relays and breakers require power
sources, which shall not be affected by faults in the main distribution.
Hence, the other component, which is vital in protective system, is
batteries that are used to ensure uninterrupted power to relays and
breaker coils.
The above items are extensively used in any protective
System and their design requires careful study and selection for
proper operation
Types of Protection:They are listed below:A Fuses: For LV Systems, Distribution Feeders and Transformers, PTs, Auxiliary
Supplies
B Over current and earth fault: Widely used in All Power Systems
Non-Directional
Directional
C Differential: For Distribution Feeders, Busbars, Transformers, Generators etc
High Impedance
Low Impedance
Restricted Earth Fault
Biased
The voltage gradient creates two problems, known as step potential and touch
potential.
Step potential :If we assume that there is a live wire touching the
foot of a pole and it has created a pool of electricity as shown
in figure. If there is person standing close to the location of the fault, and
he has placed one foot at point X and other foot at one step away at point
Y, the difference in voltage would cause the electricity to flow through
the body. This effect is know as step voltage and it could be fatal.
Step voltage = 180 90 = 90 volts
Instrument transformers:-
Main tasks of
transformers:-
instrument
The main tasks of instrument transformers are: To transform currents or voltages from usually a high value to a value
easy to handle for relays and instruments.
To insulate the relays, metering and instruments from the primary
high-voltage system.
To provide possibilities of standardizing the relays and instruments,
etc. to a few rated currents and voltages.
transformers is 100120 V (as per local country standards) for primary voltages
from 380 V to 800 kV or more.
Electromagnetic type :-
secondary has lesser turns however, the volts per turn on both primary and
secondary remains same.
The capacitor VT is more commonly used on extra high-voltage (EHV)
networks. The capacitors also allow the injection of a high-frequency signals onto
the power line conductors to provide end-to-end communications between
substations for distance relays, telemetry/supervisory and voice communications.
Hence, in EHV national grid networks of utilities, the CVTs are commonly used
for both protection and communication purposes.
Connection
of
transformers:-
voltage
El
ectromagnetic voltage transformers may be connected inter phase or between
phase and earth. However, capacitor voltage transformers can only be connected
phase-to-earth. Voltage transformers are commonly used in three-phase groups,
generally in starstar configuration. Typical connection is shown in Figure below.
With this arrangement, the secondary voltages provide a complete replica of the
primary voltages as shown below and any voltage (phase-to-phase or phase-toearth) may be selected for monitoring at the secondary.
Protection
of
transformers:-
voltage
It is possible to
protect a voltage transformer from secondary short-circuit by incorporating fuses
in the secondary circuits. Short-circuit on the secondary winding gives only a few
amperes in the primary winding and is not sufficient to rupture a high-voltage fuse.
Hence high-voltage fuses on the primary side do not protect the transformers, they
protect only the network in case of any short-circuit on the primary side.
Current transformers:-
Types
of
transformers:-
current
There
Connection
of
transformers:-
current
Current transformers for protection are normally provided in groups of three, one
for each phase.
Application
of
transformers:-
current
Current
transformers are used so that the high primary currents are transformed down to
manageable levels that can be handled comfortably by protection equipment as
shown in figure below:-
Circuit breakers:-
Protective relaycircuit
breaker combination:The protective relay detects and evaluates the fault and
determines when the circuit should be opened. The circuit breaker functions under
control of the relay, to open the circuit when required. A closed circuit breaker has
sufficient energy to open its contacts stored in one form or another (generally a
charged spring). When a protective relay signals to open the circuit, the store
energy is released causing the circuit breaker to open. Except in special cases
where the protective relays are mounted on the breaker, the connection between the
relay and circuit breaker is by hard wiring.
Important
breaker:-
parts
of
circuit
From the
protection point of view, the important parts of the circuit breaker are: the trip coil,
latching mechanism,
main contacts
and auxiliary contacts.
The roles played by these components in the tripping process is clear from Figure
above and the following step by step procedure takes place while isolating a fault
(the time intervals between each event will be in the order of a few electrical cycles
i.e. milliseconds):
The relay receives information, which it analyzes, and determines that the
circuit should be opened.
Relay closes its contacts energizing the trip coil of the circuit breaker.
The circuit breaker is unlatched and opens its main contacts under the
control of the tripping spring.
The trip coil is de-energized by opening of the circuit breaker auxiliary
contacts.
Circuit breakers are normally fitted with a number of auxiliary
contacts, which are used in a variety of ways in control and protection
circuits (e.g. to energize lamps on a remote panel to indicate whether the
breaker is open or closed).
Important characteristics of
CB:The important characteristics from a protection point of view are:
The speed with which the main current is opened after a tripping impulse is
received
The capacity of the circuit that the main contacts are capable of interrupting.
Arc Phenomenon:-
i
i
p i
C
u
l
o
B B
e
r
ke
a
k
e
r
Advantages of Oil Circuit Breaker:Oil Circuit Breaker has the following advantages: Ability of cool oil to flow into the space after current zero and arc goes out
Cooling surface presented by oil.
Absorption of energy by decomposition of oil.
Action of oil as an insulator lending to more compact design of switchgear.
Disadvantages of Oil Circuit Breaker:Oil Circuit Breaker has the following disadvantages: Inflammability (especially if there is any air near hydrogen)
Maintenance (changing and purifying).
In the initial stages, the use of high-volume (bulk) oil circuit breakers was
morecommon. In this type, the whole breaker unit is immersed in the oil. This type
had the disadvantage of production of higher hydrogen quantities during arcing and
higher maintenance requirements. Subsequently these were replaced with low oil
(minimum oil) types, where the arc and the bubble are confined into a smaller
chamber, minimizing the size of the unit.
Contacts:-
Comparison
Circuit
Of
Types Of
Breaker:-
ISOLATOR: Mechanical switch use to isolate the transmission line or other equipment from
the source of energy.
Isolator are of 3-poles.Each pole consists of 2 or 3 insulator posts.
Conducting rods are of copper or aluminum. During the opening, conducting rod
move to one side and thus circuit breaks.
PROPERTIES:-
Properties Of Insulators:
Rigidity
High resistance
Greater dielectric strength.
Non porous.
Relays:-
A device that detects the fault and initiates the operation of the
circuit breaker to isolate the defective element from the system.
Type of Relays:
Directional Relays: Responds to fault only in one direction, either to the left or to the right of its
location
Operation depends upon the direction (lead or lag) of the fault current with
respect to a reference voltage.
The directional element of these relays checks the phase angle between the
current and voltage of one phase, and allows the over-current unit to operate
if this phase angle indicates current in the reverse direction.
Ratio Relays:-
Operate for certain relations between the magnitudes of voltage, current and
the phase angle between them.
Measures the distance between the relay location and the point of fault, in
term of impedance, reactance and admittance.
Respond to the ratio of two phasor quantities as example Voltage and
Current (Z = V/R)
Also called impedance or distance relay
Differential Relays: Respond to the vector difference between two currents within the zone
protection determined by the location of CTs.
Not suitable for transmission-line protection because the terminals of a line
are separated by too great a distance to interconnect the CT secondaries.
Used for the protection of generators, transformers and busbars.
Most differential-relay applications are of the current-differential type.
Types of Faults : Ground faults:Those faults, which involve only one of the phase
conductors and ground, are called ground faults.
Faults
statistics
with
reference to power system
elements :Power system element
Overhead lines
50
Underground cables
Transformers
10
Generators
Switchgear
12
12
Total
100%
Disadvantages:
Biased
medium-impedance
differential:Advantages: High speed 813 ms
Fault sensitivity 20%
Excellent stability for external faults
Normal CTs can be used with minimal requirements
Other protection can be connected to same CTs
No limit to number of circuits
Secondary voltages low (medium impedance)
Well proven 10000 systems worldwide
Any busbar configuration
No need for duplicate systems
No work on primary CTs
Low-impedance
protection:-
busbar
Electronics detect CT saturation shorts out differential path. Inhibit circuit only
allows narrow spikes in differential coil. Relay stable.
For an internal fault, differential current in phase with saturated CT current,
Inhibit pulses remove insignificant portion of differential current.
Relay operates
Setting range: 20200%
Operating time: Less than 20 ms
CT supervision: Alarms and blocks or trips after 3 s for CT open cct
Remarks: Cheapest.
Total Shut down in case of a fault.
In the 500KV switch yard, the scheme being used is Circuit Breaker
Scheme as shown in figure below:-
Inter-turn faults:-
Core faults:Heavy fault currents can cause the core laminations to move,
chafe and possibly bridge causing eddy currents to flow, which can then generate
serious overheating. The additional core loss will not be able to produce any
noticeable change in the line currents and thus cannot be detected by any electrical
protection system. Power frequency overvoltage not only increases stress on the
insulation but also gives an excessive increase in magnetization current. This flux
is diverted from the highly saturated laminated core into the core bolts, which
normally carry very little flux. These bolts may be rapidly heated to a temperature,
which destroys their own insulation, consequently shorting out core laminations.
Fortunately, the intense localized heat, which will damage the winding insulation,
will also cause the oil to break down into gas. This gas will rise to the conservator
and detected by the Buchholz relay (see later).
Tank faults:Loss of oil through a leak in the tank can cause a reduction of insulation and
possibly overheating on normal load due to the loss of effective cooling. Oil sludge
can also block cooling ducts and pipes, contributing to overheating, as can the loss
of forced cooling pumps and fans generally fitted to the larger transformer.
Differential
protection:-
Under internal fault conditions (i.e. faults between the CTs) the relay operates,
since both the CT secondary currents add up and pass through the relay as seen
below:-
Buchholz protection:-
Failure of the winding insulation will result in some form of arcing, which can
decompose the oil into hydrogen, acetylene, methane, etc. Localized heating can
also precipitate a breakdown of oil into gas.
Severe arcing will cause a rapid release of a large volume of gas as well as oil
vapor. The action can be so violent that the build-up of pressure can cause an oil
surge from the tank to the conservator.
The Buchholz relay can detect both gas and oil surges as it is mounted in the pipe
to the conservator
Symbols Title
Description
O.N.A.N Oil Natural This is widely
Air Neutral used for
O.N.A.F
O.F.A.F
O.F.W.F
A.N
transformers
up to 30MVA
Oil Natural This is widely
Air Forced used for
transformers
between
30MVA to
60MVA
Oil Forced This method is
Air Forced used for
transformers
above 60MVA
Oil Forced The heat is
Water
exchange from
Forced
oil to cooling
water
Air Natural The ambient air
is used for
cooling
Application of Protective
Scheme in Power
Transformer:Faults
Protection scheme
Primary
Back-up
Phase faults
Percentage differential
relay
Over-current /distance
Ground faults
Percentage differential
relay
Over-current /distance
Inter-turn faults
Buchholz relay
Oil leaks
Buchholz relay
Overloads
Over-fluxing
Transmission Lines
A Vital Part of the Power System:
Provide path to transfer power between generation and load.
1.3Balanced lines
A balanced line is a transmission line, consisting of two
conductors of the same type, and equal impedance to ground and
other circuits. This includes twisted pairs which are commonly
used for terrestrial telephone communications.
1.4Classification
Classification of line length depends on:
Source-to-line Impedance Ratio (SIR), and
Nominal voltage
Length considerations:
Short Lines: SIR > 4
Medium Lines: 0.5 < SIR < 4
Long Lines: SIR < 0.5
.
Power transmission lines carry electric power from generating
sources to users. The power transmission lines are typically high
voltage lines and the electric voltage is typically transformed to a
lower voltage at a power substation, before being distributed to
individual electric power users such as homes, factories, business
buildings etc. At many power substations, protective relays are
installed.
thermal faults,
conditions.
caused
by
over
current
and
overvoltage
for protection
of
Distance Relays
51
50/51
67
50/67
67
51
67
Zone Distance
21
51N
50N/51N
Product Overcurrent
67N
67N/50N
67N
67N
67N
21N
Phase comparison
Medium Lines:
Phase comparison
Step Distance
Current Differential
Long Lines
Phase comparison
Step Distance
Current Differential
I*Z - V
F2
First step
IT is not advisable to set the reach of the distance protection to 100% So set to
reach up to 80-90% of the length of line section.
Second Step
Third Step
The 3rd step is provided with an intention to give full back up to the adjoining lie
section it covers the line section under consideration 100% of the next line section
and reaches further in to the system the operating time of this unit is instantaneous
this is known as fault detector
Purpose
Reach
Operating
time
1St step
Primary
protection
80-90% of line
section
Instantaneous
2nd step
Primary
protection of
remaining 2010%
100% of line
under
consideration
+ 50% of the
shortest
adjoining line
Selective time
interval =T1
3rd step
Backup
protection
100% of line
under
consideration
+100%
longest
adjoining line
+10-20% extra
T1+selective
time
interval=T2
Scheme does not provide tripping for faults beyond RU reach if remote
breaker is open or channel is inoperative.
effect has been called the "mutual impedance" effect. It will be evident that, if I1
and I2 are out of phase, the impedance (I2/I1) ZB will have a different angle from
ZB. If the distance relays are adjusted to operate for a fault
4.8 Hybrid
POTT
Intended for three-terminal lines and weak infeed conditions
The mho type is best suited for phase-fault relaying for longer lines,
and particularly where severe synchronizing-power surges may occur. It is the least
likely to require additional equipment to prevent tripping on synchronizing-power
surges.1 When mho relaying is adjusted to protect any given line section, its
operating characteristic encloses the least space on the R-X diagram, which means
that it will be least affected by abnormal system conditions other than line faults; in
other words, it is the most selective of all distance relays. Because the mho relay is
affected by arc resistance more than any other type, it is applied to longer lines.
The fact that it combines both the directional and the distance measuring functions
in one unit with one contact makes it very reliable.
The impedance relay is better suited for phase-fault relaying for
lines of moderate length than for either very short or very long lines. Arcs affect an
impedance relay more than a reactance relay but less than a mho relay.
Synchronizing-power surges affect an impedance relay less than a reactance relay
but more than a mho relay. If an impedance-relay characteristic is offset, so as to
make it a modified relay, it can be made to resemble either a reactance relay or a
mho relay but it will always require a separate directional unit.
First Zone
It is the practice to adjust the first, or high-speed, zone of distance relays to reach
to 80% to 90% of the length of a two-ended line or to 80% to 90% of the distance
Second Zone
The principal purpose of the second-zone unit of a distance relay is to provide
protection for the rest of the line beyond the reach of the first-zone unit. It should
be adjusted so that it will be able to operate even for arcing faults at the end of the
line. To do this, the unit must reach beyond the end of the line. Even if arcing faults
did not have to be considered, one would have to take into account an
underreaching tendency because of the effect of intermediate current sources, and
of errors in: (1) the data on which adjustments are based, (2) the current and
voltage transformers, and (3) the relays. It is customary to try to have the secondzone unit reach to at least 20% of an adjoining line section; the farther
this can be extended into the adjoining line section, the more leeway is allowed in
the reach of the third-zone unit of the next line-section back that must be selective
with this second-zone unit. The maximum value of the second-zone reach also has
a limit. Under conditions of maximum overreach, the second-zone reach should be
short enough to be selective with the second-zone units of distance relays on the
shortest adjoining line sections .
Transient overreach need not be considered with relays having a
high ratio of reset to pickup because the transient that causes overreach will have
expired before the second-zone tripping time.
Third Zone
The third-zone unit provides back-up protection for faults in adjoining line
sections. So far as possible, its reach should extend beyond the end of the longest
adjoining line section under the conditions that cause the maximum amount of
underreach, namely, arcs and intermediate current sources..
The third zone time delay is usually about 0.4 second to 1.0 second. To
reach beyond the end of a long adjoining line and still be selective with the relays
of a short line, it may be necessary to get this selectivity with additional time delay.
Typical Zones
NO Cicuit
Rout
330 KM
957 KM
327 KM
1075 KM
Tarbela - Peshawar
117 KM
347 KM
First Hub-Jahmsoro
182 KM
181 KM
10
259 KM
11
Sibbi - Quetta
194 KM
12
272 KM
Appendices
Auxiliary relay
An all-or-nothing relay used to supplement the performance of another relay, by
modifying contact performance for example, or by introducing time delays.
Back-up protection.
A protective system intended to supplement the main protection in case the
latter should be in-effective, or to deal with faults in those parts of the power
system that are not readily included in the operating zones of the main
protection.
Biased relay.
A relay in which the characteristics are modified by the introduction of some
quantity other than the actuating quantity, and which is usually in opposition to
the actuating quantity.
Characteristic angle.
The phase angle at which the performance of the relay is declared. It is usually
the angle at which maximum sensitivity occurs.
Characteristic curve.
The curve showing the operating value of the characteristic quantity
corresponding to various values or combinations of the energizing quantities.
Characteristic quantity.
A quantity, the value of which characterizes the operation of the relay, e.g.
current for an over current relay, voltage for a voltage relay, phase angle for a
directional relay, time for an independent time delay relay, impedance for an
impedance relay.
Characteristic impedance ratio (C.I. R.)
The maximum value of the System Impedance Ratio up to which the relay
performance remains within the prescribed limits of accuracy.
Check protective system.
An auxiliary protective system intended to prevent tripping due to inadvertent
operation of the main protective system.
Conjunctive test.
A test on a protective system including all relevant components and ancillary
equipment appropriately interconnected. The test may be parametric or specific.
a. Parametric conjunctive test.
A test to ascertain the range of values that may be assigned to each parameter when
considered in combination with other parameters, while still complying with the
relevant performance requirements.
b. Specific conjunctive test.
A test to prove the performance for a particular application, for which definite
values are assigned to each of the parameters.
Dependent time delay relay.
A time delay relay in which the time delay varies with the value of the
energizing quantity.
Discrimination.
Energizing quantity.
The electrical quantity, either current or voltage, which alone or in combination
with other energizing quantities, must be applied to the relay to work.
Rating
The nominal value of an energizing quantity which appears in the designation of
a relay. The nominal value usually corresponds to the CT and VT secondary
ratings.
Resetting value
The limiting value of the characteristic quantity at which the relay returns to its
initial position.
Stability
The quality whereby a protective system remains inoperative under all
conditions other than those for which it is specifically designed to operate.
Stability limits
The R.M.S. value of the symmetrical component of the through fault current up
to which the protective system remains stable.
Time delay
A delay intentionally introduced into the operation of a relay system.
Time delay relay
A relay having an intentional delaying device.
Unit electrical relay
A single relay which can be used alone or in combinations with others.
Unit protection
A protection system which is designed to operate only for abnormal conditions
within a clearly defined zone of the power system.
Unrestricted protection
A protection system which has no clearly defined zone of operation and which
achieves selective operation only by time grading.
Fault
An unplanned occurrence or defect in an item which may result in one or more
failures of the item itself or of other associated equipment .
Non-damage fault
A fault which does not involve repair or replacement action at the point of
the fault
Damage fault
A fault which involves repair or replacement action at the point of the fault
67
68
74
76
78
79
81
83
85
86
87
94
Auxiliary
tripping
relay