0% found this document useful (0 votes)
638 views100 pages

MS9200 Technical Manual PDF

Uploaded by

rcq99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
638 views100 pages

MS9200 Technical Manual PDF

Uploaded by

rcq99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 100

12 Clintonville Road, Northford, CT 06472

Technical Man
ual
Manual

MS-9200
Addressab
le Fire Control P
anel
Addressable
Panel
(Expor
(Exportt Version)
DOCUMENT # 50428
7/28/97
REV:

P/N 50428:B1 ECN 97-316

Installation Precautions

- Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 721993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F and
at a relative humidity of 85% RH (non-condensing) at 30O C/86 O F. However, the
useful life of the system's standby batteries and the electronic components may
be adversely affected by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be installed in an
environment with a nominal room temperature of 15-27O C/60-80O F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.

Fire Alarm System Limitations

Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.

While installing a fire alarm system may make lower insurance rates
possible, it is not a substitute for fire insurance!

An automatic fire alarm system - typically made up of smoke detectors, heat


detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.

Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.

FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.

Technical Publishing

Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Document PRECAULG.PM6 12/31/96

Table of Contents

NFPA Standards

Underwriters Laboratories

I.

System Overview
1.0 Description
1.1 Features
1.2 Specifications
1.3 Controls and Indicators
1.4 Components
1.5 Optional Interface Modules
1.6 Accessories

7
7
7
8
9
10
13
14

II.

Installation
2.0 General
2.1 Cabinet Dimensions
2.2 Backbox Mounting
2.3 Power
Figure 2.1: DC Power Output Connections
2.4 Standard Relays
Figure 2.2: Relay Connections
2.5 Output Circuits
Figure 2.3: Circuit Connections
2.6 UL Power-limited Wiring Requirements
Figure 2.4: Typical Wiring Diagram for UL Power-limiting
2.6.1 RTM-8F Wiring
2.7 Wiring the Signaling Line Circuit
Table 2.1: Communications Loop Performance
Figure 2.5: Style 4: T-tapping Restrictions and Branch Resistance
Figure 2.6: Style 6 Wiring
Figure 2.7: Two Wire Communications Loop (Supervised & Power-limited)
Figure 2.8: Four Wire Communications Loop (Supervised & Power-limited)
Figure 2.9: Four Wire Communications Loop
Figure 2.10: Shield Termination in No Conduit
Figure 2.11: Shield Termination in Full Conduit
Figure 2.12: Shield Termination in Partial Conduit
2.8 The Isolator Module
Figure 2.13: Isolating Two Wire Communications Loops
2.9 Module Addressing
2.10 M300 Monitor Module
2.11 M301 Monitor Module
2.12 M302 Monitor Module
Figure 2.14: NFPA Style B Initiating Device Circuit (M300)
Figure 2.15: NFPA Style D Initiating Device Circuit (M300)
Figure 2.16: NFPA Style B Initiating Device Circuit (M302)
Figure 2.17: NFPA Style D Initiating Device Circuit (M302)
2.13 The Control Module
Figure 2.18: The C304 Control Module (Alarm polarity shown)
Figure 2.19: The C304 Control Module (Form-C Relay)
Figure 2.20: NFPA Style Y Notification Appliance Circuit
2.14 The Addressable Manual Pull Station
Figure 2.21: Wiring Addressable Manual Pull Stations
2.15 Wiring Detectors
Figure 2.22: Wiring the Detector with Removable Plug-in Connector
2.16 Optional Modules
Figure 2.23: Optional Module Location
Figure 2.24: ABS-8RF
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.26: External UDACT-F Mounting in ABS-8RF
Figure 2.27: ACM-8RF Relay Control Module
Figure 2.27: RTM-8F Option Module Installation
Figure 2.28: RTM-8F Relay Transmitter Module
2.17 Printer/PC Interface Module
Figure 2.29: Remote Printer and Computer Connections

19
19
19
20
21
21
22
22
22
22
23
23
23
24
24
25
25
26
27
28
29
29
29
30
30
30
31
31
32
33
34
35
36
37
37
38
39
40
40
41
41
42
42
43
43
44
45
46
47
48
48

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Table of Contents
4

III.

Programming/Read Status
3.0 Initial Power-up
3.1 Programming
3.2 Program Change - Level One
3.2.01 Clear
3.2.02 Autoprogram
3.2.03 Point Edit
3.2.04 System Edit
3.2.05 Password Change
3.2.06 Load
3.3 Program Change - Level Two
3.3.01 Disable
3.3.02 Clear History
3.3.03 Walk Test
3.3.04 Set Time/Date
3.3.05 Check

49
50
51
52
52
52
56
57
58
59
59
60
60
61
62
62

IV.

Operating Instructions
Figure 4.1: The MS-9200 Membrane Switch Panel
4.0 Control Switches
4.1 LED Indicators
4.2 Normal Operation
4.3 Trouble Operation
4.4 Alarm Operation
4.5 Supervisory Operation
4.6 Notification Appliance Circuit (NAC) Operation
4.7 Control-By-Event Operation
4.8 Detector Functions
4.9 Time Functions
4.10 Coder Operation - Notification Appliance (Bell) Circuit 1 Only
4.11 Presignal
4.12 Special System Timers
4.13 Style 6 Operation
4.14 Read Status

63
63
63
64
64
65
66
67
68
68
68
68
68
69
69
70
70

Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
Appendix F
Appendix G
Appendix H

Power Supply and Battery Calculations


Software Zones
LCD-40 Annunciator Wiring
AFM and LDM Series Annunciator Wiring
NFPA Standards Specific Requirements
Wire Requirements
Compatible Surge Suppressors
Screen Options Flowchart

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

72
76
83
84
88
93
94
95

THE MS-9200 COMPLIES WITH THE FOLLOWING NFPA 72-1993 NATIONAL FIRE ALARM CODE
STANDARDS:
Central Station Fire Alarm Systems (Automatic, Manual, and Waterflow) Protected Premises Unit
(requires UDACT-F).
Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems (requires RTM-8F).
Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems (Requires RTM-8F or
UDACT-F).
Proprietary (Automatic, Manual, and Waterflow) Fire Alarm Systems (Protected Premises Unit).
Automatic Fire Detectors.
Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems.
Testing Procedures for Fire Alarm Systems.
IN ADDITION TO THE ABOVE, THE INSTALLER SHOULD BE FAMILIAR WITH THE FOLLOWING
DOCUMENTS AND STANDARDS:

Underwriters Laboratories:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1971 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
UNDERWRITERS LABORATORIES OF CANADA (ULC) LISTED
Standard CAN/ULC-S527-M87
OTHER:
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
FIRE-LITE DOCUMENTS AND MANUALS RELATING TO THE MS-9200:
Fire-Lite Device Compatibility Document
Document# 15384
Annunciator Modules
Document# 15390
AFM-16ATF and AFM-32AF Annunciators
Document# 15970
AFM-16AF Annunciator
Document# 15210
MS-5012 Communicator
Document# 15465
MS-9200 Off Line Programming Utility
Document# 15677
UDACT-F Universal Digital Alarm
Communicator Transmitter
Document# 50049
FCPS-24FE Field Charger/Power Supply
Document# 50079
LDM Series Lamp Driver Modules
Document# 50055
LCD-40 Remote Fire Annunciator
Document# 50327
ACM-8RF Relay Control Module
Document# 50362

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

I SYSTEM OVERVIEW
1.0 Description
The FireLite MS-9200 is a compact, cost effective, addressable Fire Alarm Control Panel (FACP) with an
extensive list of powerful features. The combination of FireLite's 300 Series Addressable Devices and the MS9200 Fire Alarm Control Panel offers the latest in Fire Protection Technology. The power supply and all electronics are contained on a single circuit board housed in an attractive metal cabinet, providing a complete fire control
system for most applications. Optional modules, which plug into the main board, are available for special functions. Accessories available include LED, graphic and LCD annunciators, digital communicator, local downloading software and remote power expansion.

1.1 Features

Single standard SLC loop, meets NFPA Style 4,


6 and 7 requirements
198 addressable device capacity (99 detectors
and 99 monitor/control modules)
56 software zones
Two main board Notification Appliance (Bell)
Circuits expandable via control modules
Optional RTM-8F eight zone relay module with
local energy/reverse polarity transmitter
Optional ACM-8RF Relay Control Module
Optional Printer/PC Interface Module
3.6 amps system power expandable to 6.6 amps
3.0 amps NAC power expandable to 6.0 amps
40 character LCD display, backlit
Real time clock/calendar
History file with 500-event capacity
Advanced Fire Technology Features:
Automatic device type-code verification
Auto detector test
Maintenance alert
Point trouble identification
Waterflow (non-silenceable) selection per
module point
Supervisory selection per point with separate
system LED
System Alarm Verification selection
Walk Test, with report of two devices set to
same address
Presignal per NFPA 72
Annunciators
AFM LED Zone Annunciator Series
LDM Graphic Annunciator Series
LCD-40 Liquid Crystal Point Display

Document # 50428

Rev. B1

7/28/97

Silence inhibit timer option


Auto silence timer option
Continuous/March time/Temporal or California code
for main board Notification Appliance (bell) Circuits
Remote ACK/Silence/Reset/Drill via M300, M301
modules, AFM annunciators or LCD-40 Remote Fire
Annunciator
Auto-Program (learn mode) reduces installation time
Password and key-protected nonvolatile memory
Password is user programmable
Fully programmable from panel keyboard
Programmable from an off-line PC
Rapid poll algorithm for manual stations (U.S. Patent
Pending)
SLC operates up to 10,000 ft. (or 1,000 ft. with
untwisted, unshielded wire) U.S. Patent # 5,210,523
Uses FireLite 300 Series Addressable Devices:
CP300
Ionization Smoke Detector
SD300
Photoelectric Smoke Detector
SD300T
Photoelectric Smoke Detector
with 135o Thermal Detection
C304
Control Module
M300
Monitor Module
M301
Miniature Monitor Module
M302
2-Wire Detector Monitor Module
I300
Isolator Module
All 300 Series devices (except I300) feature decade
code wheels
300 Series addressable smoke detectors feature a
plug-in wiring connector for ease-of-installation and
maintenance
UDACT-F Digital Communicator, reports up to 56
zones or 198 points (all 300 Series devices) to a UL
Listed Central Station

P/N 50428:B1

1.2 Specifications
AC POWER - TB8
240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG with 600V insulation
BATTERY (LEAD ACID ONLY) - J3
Maximum Charging Circuit:
Normal Flat Charge27.6V @ .8 amp.
Maximum Battery Capacity:
17 AH.
1) Up to 7 AH batteries can be housed in the MS-9200 enclosure.
2) 12 to 17 AH batteries require the FireLite BB-17F or similar UL
listed battery cabinet.
3) 20 to 55 AH batteries require the FireLite R45-24E charger for
housing and charging the batteries.
COMMUNICATION LOOP - TB6
15 VDC nominal, 27.6 volts DC max. Maximum length is 10,000 ft. total twisted pair length. Maximum loop
current is 250mA (Max short circuit) or 100 mA (normal). Maximum loop resistance is 40 ohms. SLC is
supervised and power-limited.
Note: The Communication Loop may leave the protected premises provided an approved surge suppressor
is use (refer to Table G-1 in Appendix).
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
Non-regulated special purpose power
Power-limited circuitry
Maximum Voltage Drop in wiring: 2.0V
Operating Voltage Range: 18V to 30V
Current for all external devices: 3.0 amperes expandable to 6.0 amperes2.
Current Limit: Fuseless, electronic, power-limiting circuitry.
Max. signaling current/circuit: 2.50 amps
End-of-line resistor: 4.7KW , 1/2-Watt (part # 71252 UL listed) for Notification Appliance Circuits
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C
Supervisory: Form-A
Refer to Figure 2.2 for information on power-limited wiring for relay circuits.
FOUR-WIRE SMOKE DETECTOR POWER (24VDC nominal
nominal)) - TB4 TERMINALS 5 (+) & 6 (-)
Max. ripple voltage: 10 mVRMS
Max. standby current: 50 mA
Up to 300 mA is available for powering 4-wire smoke detectors 1, 2, 3.
Power-limited circuit
NONRESETTABLE REGULATED 24V POWER (24VDC nominal
)TB4 TERMINALS 3 (+) & 4 (-)
nominal)TB4
Max. ripple voltage: 10 mVRMS
Max. standby current: 150 mA
Total DC current available from this output is up to 300 mA 1, 2, 3
Power-limited circuit
NON-REGULATED SPECIAL PURPOSE 24V POWERTB4 TERMINALS 1 (+) & 2 (-)
Operating voltage range: 18V to 30V
Total DC current available for powering external devices is 2.5 amps 2
This power is not recommended for AFM, LDM or LCD-40 annunciators
Power-limited circuit
NOTES:
1. For power supply calculations, refer to Appendix A.
2. Total current for special purpose power, nonresettable power, four-wire smoke power, and two
Notification Appliance Circuits must not exceed 6.0 amperes. Total external system current in
excess of 3.6 amperes requires XRM-24E Transformer and 12AH or 17AH batteries, not 7.0 AH.
3. Total current for resettable 4-wire smoke power and non-resettable power must not exceed 600mA.
8

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

1.3

Controls and Indicators

LCD DISPLAY
The MS-9200 uses a 40 character (2 lines X 20
characters), high viewing angle, LCD display, with a
character height of 3/16". The display includes a
long-life LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the LED
backlight will turn off to conserve power.

SYSTEMS ALL NORMAL


10:00 A MON 07/10/95

LED INDICATORS

AC POWER (green)
FIRE ALARM (red)
SUPERVISORY (yellow)
ALARM SILENCE (yellow)
SYSTEM TROUBLE (yellow)

MEMBRANE PANEL
Mounted on the system board, the membrane switch panel includes a window for the LCD display and 5
system status LEDs. The membrane panel, which is visible with the cabinet door closed, has 21 keys,
including a 12 key alphanumeric pad, similar to a telephone keypad.
Function switches:
ACKNOWLEDGE/STEP
ALARM SILENCE
DRILL
SYSTEM RESET (lamp test)
Service/program switches:
Keypad with twelve Keys labeled 1-9

(Detector) Key

#(Module) Key

0(Recall) Key
Four cursor Keys (UP, DOWN, RIGHT, LEFT)
ENTER Key

LOCAL SOUNDER
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.

NOTIFICATION APPLIANCE (BELL) CIRCUITS


Two NACs configurable for Style Y (Class B) or Style Z (Class A) with various programmable features.
RELAYS
Three dry contact relays for System Alarm, System Trouble, and Supervisory.
Contacts are rated 2A at 30VDC (resistive) and 0.5 amps at 30VAC (resistive).

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

1.4

Components

MAIN CIRCUIT BOARD


The main circuit board contains the systems CPU,
power supply, other primary components and wiring
interface connectors. Optional modules plug-in and are
mounted to the main circuit board. The circuit board is
delivered pre-mounted in the MS-9200 cabinet.

CABINET
The MS-9200 cabinet is red with an attractive navy blue front overlay. The
backbox measures 15" x 14.5" x 2.625" and provides space for two batteries
(up to 7 amp-hours). Ample knockouts are provided for system wiring. Also
available is an optional dress panel, DP-9200, which mounts to the inside of
the cabinet (required and included on the ULC version). The dress panel
must be installed to meet FM requirements (refer to Section 1.6).

Standard
TRANSFORMER ASSEMBLY
One 100VA transformer is provided standard
with the panel. (3.6 Amps max.)
An optional 100VA transformer (XRM-24E) is available to
provide maximum accessory power. (6.6 Amps max.)

Field Option
XRM-24E

BATTERIES
The MS-9200 cabinet provides space for two 7 Amp-Hour (AH) batteries. 12AH to 17AH batteries require use of the FireLite BB-17F or
similar UL listed battery cabinet. 20 to 55 AH batteries can also be
connected to the system, however, a FireLite R45-24E charger is
necessary for housing and charging these batteries. Batteries must be
ordered separately.
10

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Battery Cable P/N 75287

Addressable Devices: 300 Series Detectors


FireLite's new 300 Series Addressable Detectors consist of the SD300 Photoelectric, SD300T Photoelectric with
thermal sensor and the CP300 Ionization smoke detectors. The detectors communicate with the main circuit board
CPU via an SLC loop. The MS-9200 CPU determines the alarm, maintenance, or normal status of each device. Each
detector responds to an address that is manually set via built-in rotary decimal switches. Each detector head has a
removable plug-in connector for ease of wiring and maintenance (or service), as well as a single LED and test
connections. Detector Specifications follow:
Voltage Range:
Standby Current:
LED Current:
Loop Resistance:
Air Velocity:

15 - 28 Volts DC Peak
Diameter:
5.0 inches (12.7 cm)
150uA @ 24 VDC
Height:
3.0 inches (7.6 cm)
7mA @ 24 VDC (latched 'ON')
Temperature: 0o to 49o C (32o to 120o F)
40 ohms Maximum
Rel. Humidity: 10% - 93% Non-condensing
CP300 = 1,500 Ft/Minute (7.6m/S) Max. SD300 = 3,000 Ft/Minute (15 m/S) Max.

SD300, SD300T
The SD300 is an Addressable Photoelectric Smoke Detector which provides smoke
sensing utilizing optical sense technology. The detector sends a unique 'type' code to aid the
automatic programming feature in the control panel. The SD300T includes a 135o F fixed
thermal sensor.
CP300
The CP300 is an Addressable Ionization Smoke Detector which measures the level of
combustion products in its chamber using the 'ionization principle'. The detector sends a
unique 'type' code to aid the automatic programming feature in the control panel.
RA400Z
The RA400Z is a Remote Single LED Annunciator that can be wired directly to an addressable
detector for annunciation of that detector's alarm status.

Addressable Devices: 300 Series Modules


The C304 Control Module plus the M300, M301 and M302 Monitor Modules provide an interface between the MS9200 and conventional initiating devices and notification appliances. All modules respond to an address that is set by
the installer via two built-in rotary decimal switches. A flashing LED indicates power is applied to the modules (except
for M301). A thermoplastic cover is provided with all modules except the M301, for mounting to a 4-inch square
mounting box.
M300
The M300 is an Addressable Monitor Module that can be used to monitor conventional normally-open contact alarm initiating devices, such as manual pull stations, 4wire smoke detectors, heat detectors, waterflow, and supervisory devices. The supervised circuit can be wired
NFPA Style B (Class B) or Style D (Class A). The M300 module will not support 2-wire smoke
detectors. The M300 modules can be tested with a test magnet available from FireLite (M0204-00). The magnet test checks the module electronics and connections to the control panel.
The module mounts to a 4-inch square electrical box with a minimum depth of 2-1/8".
M301
The M301 is an Addressable Monitor Module that is a miniature version of the M300. It connects with wire pigtails [Style B (Class B) only], and may be mounted directly in the electrical box
of the device being monitored. Dimensions of 2.75" L x 1.30" W x 0.50" D, allow for mounting in
existing single-gang electrical boxes, the device being monitored, or similar locations.

7
1

M300 and M302

9
8

0
2

Address

2
6

Loop

7
3

M302
M301
The M302 is an Addressable Monitor Module that can be used to interface and monitor
conventional 2-wire smoke detectors. All 2-wire detectors being monitored must be UL
compatible with the module (refer to the FireLite Compatibility Document). The supervised circuit can be wired
NFPA Style B or D. The M302 modules can be tested with a test magnet available from FireLite (P/N M02-04-00).
Separate regulated switched 24 VDC power is required. The module mounts to a 4-inch square electrical box with a
minimum depth of 2-1/8".
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

11

Addressable Devices: Modules (continued)

7
1

8
0

7
1

C304
The C304 is an Addressable Control Module that can be used as a Notification Appliance
or Speaker Circuit for powering and supervising compatible, UL listed Notification Appliances. The module's supervised circuit can be wired NFPA Style W, X, Y or Z. A 47 K
ELR is provided. By breaking two built-in tabs, the C304 can be employed as a Form-C
control relay. The module mounts to a 4-inch square electrical box with a minimum depth
of 2-1/8".

BG-10LX
The BG-10LX is an Addressable Manual Pull Station featuring a key-lock reset. The pull
station responds to an address set by the installer using the built-in rotary decimal
switches on the pull station. The Manual Pull Station includes a FireLite key.

I300
The Loop Isolator Module (I300) is an automatic switch which opens the circuit voltage
to the SLC Loop branch(es) whenever a wire-to-wire short circuit is detected on that loop.
The remainder of the Communications Loop leading up to the I300 will continue to operate, unaffected by the short. The isolator module has four terminal connections, allowing
input and output SLC connections. The isolator is bi-directional, meaning that it can
detect a fault condition between the input SLC terminals, or output SLC terminals. The
I300 is required to meet NFPA Style 7 requirements.

Addressable Device Accessories


E.O.L. RESISTOR FIRELITE P/N R-47K
The 47K End-Of-Line Resistor Assembly is used to supervise the M300 Monitor and
C304 Control Module circuits. The resistor is included with each M300 and C304 module.

A UL listed End-Of-Line Power Supervision Relay is used to supervise the power to 4wire smoke detectors and Notification Appliances.

N-ELR
The N-ELR is a single End-of-Line Resistor plate which is required for use in Canada.
An ELR, which is supplied with each module and fire alarm control panel, must be
mounted to the plate. Resistors mounted to the N-ELR plate can be used for the supervision of an M300 and M301 Monitor Module and C304 Control Module circuit.

12

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

1.5 Optional Interface Modules


The MS-9200 main circuit board includes option module connectors, located on the right side of the board. Available option modules include:

ACM-8RF RELAY CONTROL MODULE


The ACM-8RF Relay Control Module contains eight high current (5 amp) Form-C relays. The module interfaces to
host fire alarm control panels which employ an EIA-485 communications bus. ACM-8RF modules may be connected to the EIA-485 bus up to 6,000 feet away from the host control panel. Power-limited, regulated,
nonresettable power must be supplied by the host FACP or a UL listed power supply such as the FCPS-24F. (See
Figure 2.27 for wiring details).

RTM-8F RELAY MODULE


The Relay/Transmitter Module (RTM-8F) plugs into connector J6 and mounts on the bottom right side of the MS9200 main circuit board. When the module is installed, jumper JP4 must be cut in order to provide module placement supervision. The RTM-8F provides eight Form-C relays (5 Amp contacts). These relays track software
zones 1 through 8. The Relay/Transmitter Module also provides Municipal Box or Remote Station transmitters. An
MS-9200 equipped with an RTM-8F meets NFPA 72 (Auxiliary) and NFPA 72 (Remote Station) requirements. In
remote station applications, the RTM-8F can be configured to transmit alarm only or alarm and trouble. Disable
switches and indicators are provided on the module. (See Figure 2.27 and Figure 2.28.)

PIM-24 PRINTER/PC INTERFACE MODULE


The Printer/PC Interface Module may be used to permanently connect a printer to the MS-9200 for the purpose of
printing a history report, walktest file or program listing. Printers require 240 VAC, 50Hz primary power. Connect
the PIM-24 module (with cable P/N 75267) to the serial EIA-232 port on the printer. The module mounts to the J11
connector on the MS-9200 main circuit board. The PIM-24 is also used to connect a computer for Upload/Download of programming data. Refer to the Off Line Programming Utility Manual Document# 15677, for programming
information. See Figure 2.29 for information on connections and System Edit in the Programming/Read Status
Section of this manual for information on programming the MS-9200 for use with a printer or PC. (This option is
not available simultaneously with use of the DIM-485/LCD-40).

PK-9200 KIT FOR LOCAL DOWNLOADING


The PK-9200 Programming Utility can be used to program an MS-9200 directly from most IBM PC/XT/AT or
compatible computers, including laptops and portables, equipped with a serial port. MS-9200 program files can
also be created and stored on the PC, then downloaded to the panel. The PK-9200 Kit includes the MS-9200
Programming Utility software on 3-1/2" floppy disk P/N 75298, the Instruction Manual P/N 15677 and the PIM-24
(Printer/PC Interface Module with cable P/N 75267 and DB9F/25 connectors P/N 46029).

UDACT-F UNIVERSAL DIGITAL ALARM COMMUNICATOR TRANSMITTER


The UDACT-F transmits system status to UL Listed Central Station Receivers via the public switched telephone
network. The UDACT-F is compact in size and may be mounted inside the host control panel or may mount externally in a separate cabinet. EIA-485 annunciator communications bus and regulated 24 volt connections are
required. The UDACT-F transmits 198 points or 56 zones when connected to the MS-9200. The MS-9200 requires
firmware P/N 73580 or greater in order to be compatible with the UDACT-F. (Refer to Figures 2.25 and 2.26 for
wiring details and System Edit in the Programming/Read Status Section of this manual for information on programming the MS-9200 for use with the UDACT-F).
DIM-485 DISPLAY INTERFACE MODULE
The Display Interface Module (DIM-485) is required to connect an LCD-40 Remote Fire Annunciator to the MS9200 FACP. The DIM-485 plugs into connector J11 on the top right side of the MS-9200 main circuit board. Refer
to Appendix C for wiring details and System Edit in the Programming/Read Status Section of this manual for
information on programming the MS-9200 for use with the LCD-40. (This option is not available simultaneously
with use of the PIM-24).

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

13

ZDM-16F 16 ZONE LED MODULE


The ZDM-16F mounts to the back of the membrane switch panel with 2 screws and connects by cable
to J12 on the MS-9200 main circuit board. Sixteen individual red LEDs on the module annunciate alarms
for the first sixteen software zones.

1.6 Accessories

595a-26044

DRESS PANEL
A red dead-front dress panel (DP-9200) is
available as an option (required for Canadian
installations). The dress panel restricts
access to the system wiring while allowing
access to the membrane switch panel.

Note: The MS-9200 Addressable Fire Control


Panel installed with the DP-9200 dress panel,
has received Factory Mutual (FM) approval.
It is important to note that FM approval is
contingent on the proper installation of the
DP-9200 dress panel.

BATTERY BOX
The BB-17F battery box may be used to house
two 12AH or 17AH batteries. The battery box
mounts directly below the MS-9200 cabinet.
The box is red in color and is provided with
knockouts.

14

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Accessories: R45-24E Remote Battery Charger


The FireLite Remote Battery Charger (R45-24E) is
capable of charging 20-55 amp-hour batteries. This
unit is required in a system using 25 amp hour or larger
batteries. The batteries and charger are housed in the
R45-24E cabinet, which can be mounted up to 20 feet
away from the control panel. To determine the battery
size needed in a particular system, see the Standby
Power Requirements in Appendix A.

CONNECTING THE PRIMARY POWER SOURCE


With the breaker at the main power distribution panel turned off, connect the primary Hot line to Terminal 1 on
the R45-24E and the primary Neutral line to Terminal 2. All connections between the MS-9200 and the R45-24E
must be made in conduit, using #14 AWG wire. Do not route 240 VAC wiring in the same conduit as other control
panel circuits. Leave the main power breaker off until installation of the entire system is complete.
CONNECTING THE SECONDARY POWER SOURCE
Do not apply AC power or batteries until the system is completely wired and ready for testing. Refer to the Wiring
Diagram and Instructions for the R45-24E Charger (DWG. No. 1977-41 packaged with the R45-24E) for
additional information.

Remote Battery Charger Connection


240 VAC, 50 Hz,
0.5 Amp Primary Power
Source
Hot Neutral

24 VDC (supervised). The maximum charge current for standby


batteries is 2 amps (fast charge) or 20mA (trickle charge). Use
#14 AWG wire in conduit (20 feet or less).
T
B
4

+ - + - + -

T B+A+A-B- T B+A+A-BB 1 2 3 4
B 1 2 3 4
1
2

T
B
3

NO C NO NC C NO NC C

OPTION
PRINTER
& UP/DOWN LOAD
J11

T
B
5

T
B
6

B+ A+ B- A-

4
-

+ -

R45-24E

+
PS-12550
12 VDC
55-AH
Battery

+
PS-12550
12 VDC
55-AH
Battery

-+

cut terminals from MS-9200


battery cable connected to J3
use wire nuts

Note: Apply primary AC power to MS-9200 via standard transformer or with additional option transformer XRM-24E.
See Appendix A.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

15

Accessories: LCD Point Annunciator - LCD-40 Remote Fire Annunciator


(refer to Appendix C for detailed wiring requirements and System Edit in the Programming/Read Status Section of
this manual for information on programming the MS-9200 for annunciator use)
The LCD-40 is a compact, attractive, 40-character backlit LCD fire annunciator that is capable of displaying English-language text. It mimics the display
on the MS-9200 main control circuit board and will annunciate device type,
point alarm, trouble or supervisory condition, zone assignment plus any
custom alpha labels programmed into the control panel. It also provides
system status LEDs to display Power, Alarm, Trouble and Supervisory
conditions. Additionally, the LCD-40 is capable of performing critical system
functions such as acknowledge, silence, reset and drill, remotely from the
host control panel.
Communication between the control panel and the LCD-40 is accomplished over a serial interface employing the EIA485 communication standard (DIM-485 option module required). Up to 32 LCD-40s may be connected to the EIA-485
circuit. The annunciator may be powered from the host FACP or a remote UL listed, filtered, regulated power supply
such as the FireLite FCPS-24FE.

Accessories: LED Zone Type - AFM Series Annunciators


(refer to Appendix D for detailed wiring requirements and System Edit in the Programming/Read Status Section of
this manual for information on programming the MS-9200 for annunciator use)
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT annunciators display zone alarm
and trouble status. In addition, they provide remote ACKNOWLEDGE, SILENCE, RESET and DRILL functions. The
AFM/AEM-32 annunciators display zone alarm status only and provide no remote system switch functions. For more
detailed information, refer to the appropriate AFM Annunciator manual.
AFM-16ATX
The Annunciator Fixed Module16ATX contains 16 red alarm and 16
yellow trouble LEDs, a system
trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with
switches for MS-9200 ACKNOWLEDGE, SILENCE, RESET, and
DRILL. The AFM-16ATX is fixed at
address '1' and will accept up to 3
AEM-16ATF Expanders.

THE AFM-32AX
The Annunciator Fixed Module-32AX
contains 32 red alarm LEDs, a system
trouble LED, an ON LINE/POWER LED,
and a local piezo sounder with a local
Silence/Acknowledge switch. The AFM32AX is fixed at address 1, and will
accept one AEM-32AF expander.

AEM-16ATF
The Annunciator Expander Module16ATF connects to the AFM-16ATX and
adds 16 sets of red alarm LEDs and yellow trouble
LEDs. Three AEM-16ATFs may be added to an AFM16ATX.

AFM-16ATF
The Annunciator Fixed
Module-16ATF contains 16 red
alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/
POWER LED, and a local piezo
sounder with switches for MS-9200
ACKNOWLEDGE, SILENCE,
RESET, and DRILL. The AFM16ATF is fixed at address '1' and
communication is via the EIA-485
data line.
16

AEM-32AF
The Annunciator Expander Module-32AF
connects to the AFM-32AX and adds 32
red alarm LEDs. The AEM-32AF is
identical in frontal appearance to the AFM32AX. Only one expander module is allowed.
AFM-16AF
The Annunciator Fixed Module-16AF
has 16 red alarm LEDs. Multiple
annunciators may be used by setting
all annunciators to Receive Only,
except the last AFM-16AF in line.
Each annunciator's address is internally fixed
at '1', and communication is via the EIA-485
data line. The Local Silence/Acknowledge
switch functions as local lamp test and silence
for annunciator piezo. LEDs include On
Line and System Trouble indicators.

FIRE ALARM ANNUNCIATOR

ALARM ZONE 1
ALARM ZONE 2
ALARM ZONE 3
ALARM ZONE 4
ALARM ZONE 5
ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 8
ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 12
ALARM ZONE 13
ALARM ZONE 14
ALARM ZONE 15
ALARM ZONE 16
SYSTEM TROUBLE

PRESS
TO
SILENCE

ON LINE

AFM-32AF
The AFM-32AF is similar to the AFM-16AF except it has 32
red alarm LEDs for annunciating up to 32 points.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Accessories: Graphic Annunciator Driver - LDM Series Lamp Driver Modules


(refer to Appendix D for detailed wiring requirements and System Edit in the Programming/Read Status Section of
this manual for information on programming the MS-9200 for annunciator use)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are
used to provide an interface to a custom graphic LED annunciator. The master module provides power and control for
a maximum of three expander modules. The LDM-32F and LDM-E32F have output connectors which are used to
drive lamps or LEDs and input connectors which are used for remote switch functions. Refer to the LDM Series Lamp
Driver Modules Manual for a complete description.

The LDM-32F
The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs which sink current
to system common (-) on activation. A single positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all drivers are activated. The LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 external control switches may be wired to the LDM-32F. DIP switch SW3 is used
to enable or disable the onboard piezo, enable remote switch functions, select a flashing
LED function for new alarms and troubles, and other functions. Switch SW4 is used to
configure the module to annunciate 32 alarms or 16 alarms and 16 troubles. A green ONLINE LED flashes to indicate ongoing communications with the host FACP. One LDM-32F
supports up to 3 LDM-E32F modules. The LDM-32F is supplied with 4 standoffs and screws
for mounting to a CHS-4L chassis or custom backbox.

The LDM-E32F
Each LDM-E32F expander module provides 32 additional lamp/LED driver outputs from J5,
J6, J7 and J8. The expander module has a slide switch, SW4, for selecting alarm or alarm
and trouble annunciation and an input for a local lamp test switch. In alarm mode, use only
one LDM-32F and one LDM-E32F for a maximum of 56 alarm indicators and 8 system status
indicators. In alarm/trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of
56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control switch
inputs. Multiple sets of LDM-32s with LDM-E32F expanders increase the system annunciation capabilities beyond 56 zones or points. This is possible by various settings of address
switches SW1 and SW2 on the LDM-32F (refer to Appendices). Each LDM-E32F is supplied
with a 26-conductor expander ribbon cable, 4 standoffs and 4 screws.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

17

Accessories: System Power Expansion - FCPS-24FE Remote Field Charger Power Supply
The FCPS-24FE is a compact, remote power supply with battery charger. This remote power supply consists of a
filtered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits [four Style Y (Class
B) or two Style Z (Class A) and two Style Y (Class B)]. Alternately, the four Notification Appliance Circuits may be
used as auxiliary regulated power configured for resettable or nonresettable operation.
The FCPS-24FE may be used in a number of different applications. It may be used as a remotely-mounted power
supply and battery charger powering up to four, coded or non-coded, Notification Appliance Circuits. Alternately, any
or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors or any
device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs to
expand FACP auxiliary system power.

Style Y/Style Z
Notification
Appliance Circuit or
24 VDC Output #1

Notification
Appliance Circuit
Control Input #1
(from FACP)

Style Y Notification
Appliance Circuit or
24 VDC Output #2
Style Y/Style Z
Notification Appliance
Circuit or 24 VDC
Output #3

Notification
Appliance Circuit
Control Input #2
(from FACP)

Style Y Notification
Appliance Circuit or
24 VDC Output #4

Battery Charger

AC Power

Specific
FCPS Trouble
Application Contact Output
Power

One of the most common applications for the FCPS-24FE remote power supply utilizes the NAC expander mode. In
this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP NAC output(s)
to the remote power supply Control Input circuits. When these Control Input circuits activate (due to reverse polarity
of the NAC output), the power supply will activate its corresponding outputs. NAC Control Input #1 controls power
supply output circuits #1 and #2. NAC Control Input #2 controls output circuits #3 and #4.
During the inactive state, the remote power supply supervises its NAC field wiring for short and open circuits. If a
fault is detected, the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED (Output
Circuits 1-4). However, once the Notification Appliance Circuits are activated, the supervision is disabled and the
circuits are no longer supervised. Supervision of other power supply faults such as low battery, Earth Fault, AC loss
and battery charger failure will continue and may be monitored via the independent trouble relay contact.
If a specific application requires that all four outputs activate at the same time, only one NAC control input from the
FACP is necessary. For this application, the Notification Appliance Circuit from the FACP is wired into NAC Control
Input #1 of the remote supply and then a pair of wires are connected from NAC Control Output #1 to NAC Control
Input #2. Refer to the FCPS-24FE Installation, Operation and Application Manual for a complete description and
examples of applications.
A C304 Control Module, which can be located up to 10,000 feet from the FACP, may be used to activate the FCPS
power supply. The Control Module can be powered from the FCPS auxiliary 24 VDC power output (TB3 Terminals 8
& 9) and supervised by an EOL relay.

18

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

II INST
ALLA
TION
NSTALLA
ALLATION
2.0 General
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free
area where extreme temperatures are not encountered. The area should be readily accessible with sufficient
room to easily install and maintain the panel. Locate the top of the cabinet approximately five feet above the
floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be
installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. All wiring should be in accordance with the National and/or Local
codes for fire alarm systems.
To remove entire
knockout, strike here.

2.1 Cabinet Dimensions


Surface Mount w/BB-17F Battery Box

To remove inner
knockout, strike here.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

19

2.2 Bac
kbo
x Mounting
Backbo
kbox
1)

2)
3)
4)
5)
6)
7)

Remove the main PC board assembly by unscrewing the four screws in the corners of
the board. Two standoffs support the board in the center. Set the board aside in a safe, clean
place. Avoid static discharge which may damage the board.
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown.
Install two upper fasteners in the wall with the screw heads protruding.
Using the upper 'keyholes', mount the backbox over the two screws.
Mark and drill the lower two holes.
Complete backbox mounting by installing the remaining fasteners. Tighten all screws.
When the location is dry and free of construction dust, reinstall the main PC board.

TR-1-R Trim Ring


16 GA Ruby Red
#18308 Steel

20

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

2.3 P
o w er
Po
CAUTION: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables while this unit is energized.

AC POWER/EARTH GROUND CONNECTIONS


Primary power required for this panel is 240 VAC, 50 Hz, 1.2 amperes.
Overcurrent protection for this circuit must comply with Article 760 of the
National Electrical Code (NEC) and/or local codes. Use #14 AWG or larger
wire with 600 volt rating.
In order to comply with Compatibility Directive 89/336/EEC for European
Communities (EU Requirements), a Ferrite Bead, P/N 29085, must be
installed on the Mains for RF filtering. Refer to Document #50404 for details.
Connect one of the mounting screws for the system transformer to a known
solid earth ground. This connection is vital for maintaining the control panel's
immunity to unwanted transients generated by lightning and electrostatic
discharge.

- +

BATTERY POWER
Observe polarity when connecting the battery. Connect the battery cable to J3 on the MS-9200 main circuit board
using the plug-in connector provided. See Appendix A for calculation of the correct battery rating. CAUTION:
Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. If
contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.

Figure 2.1: DC Power Output Connections


All DC power outputs are power-limited
Power-limited
Non-Regulated Special
Purpose Power
2.5 amps, 24 VDC power for
Notification Appliance Circuits.
TB4 Terminal 1 (+) and 2 (-). Note:
This power is unsuitable for all EIA485 annunciation devices.

Power-limited
Nonresettable Power
300 mA, 24 VDC filtered, regulated,
non-resettable power can be drawn
from TB4 Terminals 3 (+) and 4 (-).

Document # 50428

Rev. B1

7/28/97

Power-limited
Resettable Power
300 mA, 24 VDC filtered,
regulated, resettable power can be
obtained from TB4 Terminals 5 (+)
and 6 (-).

P/N 50428:B1

21

2.4 Standard Rela


ys
Relays
The MS-9200 provides a set of Form-C alarm and a set of Form-C trouble contacts rated for 2.0 amps @
30VDC (resistive). The panel also provides a Form-A supervisory contact rated for 2.0 amps @ 30VDC
(resistive). Refer to Figure 2.4 for UL Power-limited wiring requirements.

Figure 2.2: Relay Connections


Note: Relay connections may be power-limited or nonpower-limited, provided that 0.25" spacing is maintained
between conductors of power-limited and nonpower-limited circuits.
SUPV

ALARM

TROUBLE

N O C NO NC C NO NC C

T
B
3

Power
Limited

Power
Limited

Note: If relays are used as power-limited


circuits, paste supplied label to terminal block
to indicate use of power-limited wiring.

2.5 Output Circuits


NOTIFICATION APPLIANCE CIRCUITS
The MS-9200 provides two Notification Appliance (bell) Circuits (Style Y or Z). Each circuit is capable of
2.5 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed 6.0
amps. Use UL listed 24 Volt notification appliances only. Circuits are supervised and power-limited. Refer
to the FireLite Device Compatibility Document for a listing of compatible notification appliances. The two
Notification Appliance Circuits located on the main circuit board may be expanded via the FireLite FCPS24FE Field Charger/Power Supply. Surge protection for notification appliances may be provided by using
one of the compatible surge suppressors listed in Table G-1 of the appendix.

Figure 2.3: Circuit Connections


Style Z Notification
Appliance Circuit
(Supervised and
power-limited)
Polarized Bell

Style Y Notification Appliance


Circuit (Supervised and powerlimited). 4.7KW , 1/2-Watt Part#
71252 UL listed.

Polarized Strobe
Polarized Horn

Note: Notification
Appliance Circuit
polarity shown in
alarm state.

B+

T
B
2

22

A+

A- B-

B+

A+

T
B
1
Document # 50428

A- B-

Polarized Bell
Polarized Horn
Polarized Horn

Dummy Load
all unused
Circuits

Rev. B1

7/28/97

P/N 50428:B1

2.6 UL P
o w er-limited Wir
ing Requirements
Po
Wiring
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A
typical wiring diagram for the MS-9200 is shown below.

Figure 2.4: Typical Wiring Diagram for UL Power-limited Requirements


Power-limited Circuits

Nonpower-limited Circuits

Power-limited Circuits

Power-limited Circuits

Nonpower-limited Circuits

AC Power

Note: Output is
nonpower-limited
only if programmed
as municipal box
output.
2.6.1 RTM-8F Wiring
Nonpower-limited and power-limited wiring must have a minimum
distance of 0.25" wire to wire. If this module is used to drive
nonpower-limited and power-limited circuits, follow the instructions below:
1. Skip a set of dry contacts to maintain the 0.25" required space
between power-limited and nonpower-limited circuits.
2. If this module is needed to drive power-limited and nonpowerlimited relays that are next to each other, make no connection
to the Normally Open contact which separates the two groups
of relays. Refer to the typical wiring diagram to the right.

Power-limited circuits

No connection

Nonpower-limited circuits

Refer to Figure 2.29 for additional information on the RTM-8F


Relay Transmitter Module.
Nonpower-limited circuit
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

23

2.7 Wir
ing the Signaling Line Circuit
Wiring
The MS-9200 communicates with addressable initiating, monitor and control devices through a Signaling
Line Circuit (SLC) Loop. This SLC loop can be wired to meet the requirements of NFPA Style 4 (see
Figure 2.7), Style 6 (see Figure 2.8) or Style 7 (see Figure 2.9). Surge protection for the SLC Loop may be
provided by using one of the compatible surge suppressors listed in Table G-1 of the Appendix. The SLC
Loop is allowed to leave the building only with use of an approved surge suppressor (refer to Table G-1).
Be certain to change the decade wheels on all detectors and modules from the factory '00' settings.
ISOLATOR MODULES
Isolator Modules permit a zone of detectors and modules to be electrically 'isolated' from the remainder of
the Communications Loop, allowing critical loop components to function in the event of a short circuit on
the SLC Loop wiring (see Figures 2.7, 2.8 and 2.9). These are required to meet the requirements of NFPA
Style 7.
MONITOR MODULES
Addressable Monitor Modules allow the control panel to monitor entire circuits of conventional normallyopen contacts, alarm initiating devices, manual pull stations, 4-wire smoke detectors, heat detectors,
waterflow, supervisory devices (see Figures 2.14 and 2.15) and conventional detectors (see Figures 2.16
and 2.17). The BG-10LX is an addressable manual pull station which contains a miniature monitor module
providing point annunciation (see Figures 2.7, 2.8 and 2.21).
CONTROL MODULES
Through addressable Control Modules, the control panel can selectively activate Notification Appliance
Circuits or Form-C output relays (see Figures 2.18 through 2.20).
ADDRESSABLE DETECTORS
Through the Communications Loop, the MS-9200 communicates with addressable ionization, photoelectric,
and photoelectric/thermal detectors (see Figure 2.22).
DEVICE CAPACITY
The capacity of each MS-9200 includes up to 99 addressable detectors, and an additional combination of
up to 99 addressable pull stations, control modules and monitor modules. In addition, the panel supports 2
Notification Appliance (Bell) Circuits.
Note: Refer to Appendix A and the installation drawings supplied with each loop device for rating and
specification information.

Table 2.1: Communications Loop Performance


Fault Condition
Single
Open on
Loop

Single
Ground on
Loop

Shorted
Loop

Loop
Shorted
and
Opened

Loop
Shorted
and
Grounded

Loop
Opened
and
Grounded

Communication
Loss

Notes:
1. Trouble indicates a trouble
signal will be generated at the
control panel during the abnormal
condition.

Style 4 (2-wire) Loop Operation (meets NFPA 72 Style 4 requirements)

Trouble

Alarm
Capability
Trouble 2

Trouble

Trouble

Trouble

Trouble

Trouble

2. Alarm Capability indicates an


alarm signal can be transmitted to
the control panel during the
abnormal condition.

Style 6 (4-wire) Loop Operation (meets NFPA 72 Style 6 requirements)


Alarm
Capability
Trouble

Alarm
Capability
Trouble

Trouble

Trouble

Trouble

Alarm
Capability
Trouble

Trouble

Style 7 (4-wire) Loop Operation (meets NFPA 72 Style 7 requirements)


Alarm
Capability
Trouble

24

Alarm
Capability
Trouble

Alarm
Capability
Trouble

Trouble

Alarm
Capability
Trouble

Alarm
Capability
Trouble

Document # 50428

Rev. B1

Trouble

7/28/97

P/N 50428:B1

3. Loop operation meeting Style 7


requirements isolates entire
physical zone on the communications loop from faults that occur
within other areas of the loop.

Figure 2.5: Style 4 Wiring: T-tapping Restrictions and Branch Resistance


T-tapping of the SLC loop wiring is allowed for two wire (Style 4) configurations. The total resistance
of any branch cannot exceed 40 ohms. Measure the resistance as illustrated below. The total wire
length of all combined branches cannot exceed 10,000 feet.

Communications Loop Out

Branch
E
Branch
D

Branch
B

Branch

Branch
C
Loop
Out

Branch
For each loop:
A
Add the lengths of all the branches
on one loop. This sum cannot
exceed 10,000 feet (12AWG
twisted, shielded).

+
+
+
+
=

Branch Resistance
With power removed, short the termination
point of one branch at a time and measure
DC resistance from the beginning of the
loop to the end of that particular branch.
The total DC resistance from panel to
each branch end cannot exceed 40 ohms.
Repeat this procedure for all remaining
branches.

(Branch A)
(Branch B)
(Branch C)
(Branch D)
(Branch E)
10,000 feet or less

Figure 2.6: Style 6 Wiring


T-tapping of the SLC loop wiring is not allowed for Style 6 configuration. The total resistance of the
complete wire run cannot exceed 40 ohms and total length cannot exceed 10,000 feet. Measure the
resistance as illustrated below.

No T-Tapping allowed

Total length of the Communications Loop pair


cannot exceed 10,000 feet (12AWG).

Loop Out

Return Loop
B+ and B- = Output Loop
A+ and A- = Return Loop

DC Resistance of the Communications Loop


pair cannot exceed 40 ohms.
With power removed, disconnect Loop Out and
Return at the control panel, short the two leads
of Communications Loop Return, and meter
Loop Out.

Loop Out

Loop Return
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

25

Figure 2.7: Two-Wire Communications Loop (Supervised and Power-Limited)


(meets NFPA 72 Style 4 requirements - may be T-tapped)

BG-10LX

- +
4

7
1

8
0

3
2

SD300

C304

M300
Separate T-Tap
to other Loop
devices

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

I300
Note: I300 devices
not required to meet
NFPA Style 4.

I300

Connect (+) to TB 6-3


Connect (-) to TB 6-5

26

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Figure 2.8: Four-Wire Communications Loop (Supervised and Power-Limited)


(meets NFPA 72 Style 6 requirements - cannot be T-tapped)

BG-10LX

7
1

8
0

7
1

8
0

SD300

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

C304

M300

I300

I300

Note: I300 devices


not required to meet
NFPA Style 6.

Connect Loop Out to TB 6-3 (+) and TB 6-5 (-).


Connect Loop Return to TB 6-4 (+) and 6-6 (-).

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

27

Figure 2.9: Four-Wire Communications Loop


(meets NFPA 72 Style 7 requirements - cannot be T-tapped)

I300
Isolator Module

I300
Isolator Module

Protected Premises
Zone '02"'

3
2

SD300

Protected
Premises
Zone '03'

Protected
Premises
Zone '01'

BG-10LX

CP300

4
I300
Isolator Module

I300
Isolator Module
2

Note: Terminal designations are


shown for all I300 modules.

CAUTION! Do not loop wiring under


any terminals. Break wire run to
maintain supervision.

Connect Loop Out to TB 6-3 (+) and TB 6-5 (-).


Connect Loop Return to TB 6-4 (+) and 6-6 (-).

Operation
By 'flanking' each communications loop device with a pair of I300 Fault Isolator Modules, each device is
protected from short circuit faults that may occur on other devices. For example, a fault on Zone 02 will not
affect Zones 01 and 03. The isolator modules on either side of Zone 02 will open the Loop. Zone 01 will still
operate from power on Loop Out and Zone 03 will operate from Loop Return. Since the MS-9200 will no
longer be able to communicate with Zone 02, a trouble signal(s) will be generated for that device.
No TTapping or branching is allowed on this circuit. The ratings and characteristics are the same as for a
four-wire circuit meeting NFPA Style 6 requirements.

28

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Shielded Wire Termination Requirements


Shielded wire is recommended for use on the SLC loop, EIA-485 and EIA-232 circuits (refer to Appendix F for additional wiring information). Proper termination of the shield is shown below for various applications such as no conduit,
partial conduit and full conduit. Nonshielded wire (max. 1,000 feet) may be used on the SLC loop, however, full
conduit is recommended for optimum EMI and RFI protection.

Figure 2.10: Shield Termination in No Conduit


MS-9200
Cabinet
Shield Drain Wire

SLC Loop +

All Styles of Wiring


Do not allow the shield drain wire to
enter the system cabinet. Connect
the drain wire to the outside of the
cabinet via a BX-type connector.

SLC Loop -

Figure 2.11: Shield Termination in Full Conduit


MS-9200
Cabinet
The shield must not be connected to earth
ground at any point.

SLC Loop +

SLC Loop -

All Styles of Wiring


The shield drain wire must be
connected to the shield terminal
TB6, Terminal 1 or 2. Do not allow
the shield drain wire or the shield
foil to touch the system cabinet.
For Style 6 or 7, connect only one
end of the shield to TB6.

Shield Drain Wire

Shield

Figure 2.12: Shield Termination in Partial Conduit


Shield Drain Wire

All Styles of Wiring


Do not allow the shield drain wire to
enter the system cabinet or the
conduit. Connect the drain wire to
the termination point of the conduit
run (such as a single-gang box as
illustrated above). The conduit
cannot be longer than 20 feet.

Note: Must employ metal conduit


and a metal box.

MS-9200
Cabinet
Nonshielded Wire

SLC Loop +
SLC Loop -

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

29

2.8 The Isolator Module


The Loop Isolator Module (I300) is used to protect critical elements of the communications loop from faults on other
branches or sections of the loop. The I300 continuously monitors the circuit connected to terminals 1 (-), 3 (-), 2 (+) and 4 (+). Upon power-up, an integral relay is
latched on. The I300 periodically pulses the coil of this relay. A short circuit on
either side of the loop resets the relay. The I300 senses the short and disconnects
Loop In ( - )
the faulty branch by opening the positive side of the loop (terminal 2 or 4). This
Loop In ( + )
I300
effectively isolates the shorted branch from the remainder of the loop. Once the
Loop Out ( - )
fault is removed, the I300 automatically reapplies power to the communications
loop branch. Figure 2.7 illustrates the use of an I300 on a two wire communications Loop Out ( + )
loop meeting NFPA Style 4 requirements; Figure 2.9 shows a four wire loop
meeting NFPA Style 7 requirements.
Note:
During a fault condition, the MS-9200 will register a trouble condition for each device isolated on the loop
branch.

Figure 2.13: Isolating Two-Wire Communications Loops


A short on any T-tapped branch off an I300 Isolator Module on the Communication Loop meeting NFPA Style 4 wiring
requirements, will be isolated from all devices installed both upstream of the I300 (Communications Loop In) and on
the continuation of the loop (shown as a dotted line). As an example, if a short were to occur on Branch A of the first
I300 shown, the isolator module would disconnect Branch A and its devices from the rest of the Communication Loop,
allowing all devices connected before and after that I300 to operate normally.

Continuation of the Communications Loop

Communications
Loop In

I300

I300

Branch B

Branch A

T-Tapped Branches off the Communications Loop

2.9 Module Addressing


Monitor and Control Modules have two rotary decimal switches which are used by the installer to set the module
address. Addresses from 01 to 99 may be set by positioning the left rotary switch to the value of the '10's
digit and the right switch to the value of the '1's digit. For example, address 31 would be set by pointing the left switch
to 3 and the right switch to 1 as shown below.

3
2

7
1

8
0

30

Document # 50428

7
1

8
0

Rev. B1

7/28/97

P/N 50428:B1

2.10 The M300 Monitor Module


The M300 Monitor Module is an addressable module that monitors normally-open contacts and shorting-type alarm
initiating devices. The supervised module circuits can be wired as NFPA Style B or Style D Initiating Device Circuits.
There is no limit to the number of contact-type devices installed on a monitor module circuit. Refer to Figures 2.14
and 2.15 for wiring diagrams.
COMMUNICATIONS LOOP CONNECTIONS
Connect the MS-9200 Communications SLC Loop to M300 terminals 1 (-) and 2 (+). The M300 occupies one module
address on the Loop. Use the rotary switches on the M300 to set the module to the required loop address.
NFPA STYLE B INITIATING DEVICE CIRCUIT
Connect the normally-open contacts of the alarm initiating devices to a single two-wire circuit (as shown in Figure
2.14). NOTE: This circuit cannot be T-Tapped or branched in any fashion, and must be terminated across the last
device by a listed ELR. Connect the circuit to M300 terminals 6 (-) and 7 (+).
NFPA STYLE D INITIATING DEVICE CIRCUIT
Connect the alarm initiating devices to a single four-wire circuit (as shown in Figure 2.15). NOTE: This circuit cannot
be T-Tapped or branched in any fashion. Connect the four-wire circuit to M300 Terminals 6 (-) and 9 (-), then 7 (+)
and 8 (+).
TEST SWITCH
The M300 includes a magnetic test switch located near the center front of the module. Activation of this switch will
cause an open circuit indication in the Style B/D loop.

2.11 The M301 Monitor Module


The M301 Monitor Module is an addressable module that is functionally and electrically identical to an M300 Monitor
Module (Style B circuits only), but offered in a smaller package for mounting directly in the electrical box of the
contact-type device being monitored.

Set the module


address with
these switches

IDC (-)
(Yellow)

IDC (+)
(Violet)
Loop (+)
(Red)

Loop ( - )
(Black)

NFPA STYLE B INITIATING DEVICE CIRCUIT


Terminate with a 47KW , 1/2 Watt ELR (N-ELR in Canada).

NOTES ON THE M300 AND M301 MONITOR MODULES:


1. The Initiating Device Circuit is supervised and current-limited to 230 microamperes @ 24 VDC (nominal).
2. The Initiating Device Circuit wiring may be up to 2,500 feet or a maximum of 40 Ohms for the M300 and 20
Ohms for the M301.
3. The Initiating Device Circuit provides the following services (DO NOT MIX):
Fire Alarm Service.
Automatic/Manual Waterflow Alarm Service with normally-open contact devices.
Sprinkler Supervision with normally-open contact devices.
4. The maximum SLC loop resistance due to wiring is 40 Ohms.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

31

2.12 The M302 Monitor Module


The M302 Monitor Module is an addressable module that interfaces and monitors UL compatible conventional 2-wire
smoke detectors. (See Fire-Lite Compatibility Document P/N 15384.) The supervised circuit may be wired as NFPA
Style B or D.
COMMUNICATIONS SLC LOOP CONNECTIONS
Connect the MS-9200 Communications SLC loop to M302 terminals 1(-) and 2(+). The M302 occupies one module
address on the loop. Use rotary switches on the M302 to set the module to the required loop address.
NFPA STYLE B INITIATING DEVICE CIRCUIT
Connect 2-wire smoke detectors to M302 terminals 6 (B-) and 7 (B+) (as shown in Figure 2.16). IDC installation
wiring must not exceed 25 ohms, 12-18 AWG wire. Use a 3.9K ELR across the last initiating device. (See Figure
2.16).
NFPA STYLE D INITIATING DEVICE CIRCUIT
Connect 2-wire smoke detectors to M302 terminals 6 (B-) and 9 (D-), 7 (B+) and 8 (D+) (as shown in Figure 2.17).
IDC installation wiring must not exceed 25 ohms, 12-18 AWG wire. (See Figure 2.17).
POWER CONNECTIONS
Power must be switched 24VDC isolated regulated and battery backed. Connect to M302 terminals 3 (-) and 4 (+)
(as shown in Figures 2.16 and 2.17).
NOTES ON M302 MONITOR MODULE
1. IDC and power connections are supervised by the M302 and reported to the MS-9200
2. Maximum current in alarm is 90 mA power limited
3. See Appendix F for device specifications
4. See Appendix A for power supply calculations
TEST SWITCH
The M302 includes a magnetic test switch sensor located near the center front of the module. Activation of this
switch by test magnet P/N M02-04-00 will cause an open circuit indication in the Style B/D loop.

Status LED
4

3
2

7
1

8
0

32

Document # 50428

Rotary Decade
Address Switches

7
1

8
0

Rev. B1

Magnet Test Position

7/28/97

P/N 50428:B1

Figure 2.14: NFPA Style B Initiating Device Circuit (Utilizing M300 Monitor Module)
Supervised and Power-limited

UL listed Power Supervision Relay


(Must be wired as last device on
loop as shown).

End-of-Line Resisto
Resistor
47KW , 1/2-watt
(N-ELR in Canada)

24 VDC Four-Wire
Smoke Detector

Manual
Pull Station

To Next Device
on Loop
+

Heat Detector

Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

M300

24V (+) TB4-5


24V (-) TB4-6

MS-9200

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Loop Out

SLC (+) TB6-3


SLC (-) TB6-5

33

Figure 2.15: NFPA Style D Initiating Device Circuit (Utilizing M300 Monitor Module)
Supervised and Power-limited
UL listed Power Supervision Relay
(Must be wired as last device on
loop as shown).

24 VDC
Four-Wire
Smoke
Detector

Manual
Pull
Station

To Next Device
on Loop
+

Heat
Detector
See note

Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

M300

24V (+) TB4-5


24V (-) TB4-6

SLC (+) TB6-3


SLC (-) TB6-5

MS-9200

Note: ELR is not required when wiring Style D (Class A).

34

Document # 50428

Rev. B1

7/28/97

Loop Out

P/N 50428:B1

Figure 2.16: NFPA Style B Initiating Device Circuit (Utilizing M302 Monitor Module)
Supervised and Power-limited

End-of-Line Resisto
Resistor
3.9K (included)

UL listed Compatible
Smoke Detector

UL listed Compatible
Smoke Detector

To Next Device
on Loop
+
-

UL listed Compatible
Smoke Detector
+
+

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)

M302

24V (+) TB4-5


24V (-) TB4-6

MS-9200

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Loop Out

SLC (+) TB6-3


SLC (-) TB6-5

35

Figure 2.17: NFPA Style D Initiating Device Circuit (Utilizing M302 Monitor Module)
Supervised and Power-limited

UL listed Compatible
Smoke Detector

UL listed Compatible
Smoke Detector

To Next Device
on Loop
Resistor
End-of-Line Resisto
+
3.9K (included)

UL listed Compatible
Smoke Detector
Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

M302

24V (+) TB4-5


24V (-) TB4-6

36

Loop Out

SLC (+) TB6-3


SLC (-) TB6-5

MS-9200

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

2.13 The Control Module


The C304 Control Module is an addressable module that supervises and switches power to a Notification
Appliance Circuit. The C304 can be wired as NFPA Styles W, X Y or Z Notification Appliance or Speaker
Circuits. Alternately, the C304 module can be employed as a Form-C control relay.

Figure 2.18: The C304 Control Module (Alarm polarity shown)

Style X/Z (+)


Loop (-)
Loop (+)

Style X/Z (-)

C304

Style W/Y (-)

24VDC Power (-)

Style W/Y (+)

24VDC Power (+)

COMMUNICATIONS LOOP CONNECTIONS


Connect the MS-9200 Communications SLC Loop to C304 terminals 1 (-) and 2 (+). The C304 occupies
one module address on the Loop. Set the rotary switches on the C304 to the particular Loop address
required.
NFPA STYLE W OR Y NOTIFICATION APPLIANCE OR SPEAKER CIRCUIT
Connect polarized alarm Notification Appliances or speakers to a single two-wire circuit. NOTE: This circuit
cannot be T-Tapped or branched in any fashion, and must be terminated across the last device by a 47KW ,
1/2-watt ELR (Part # A2143-00). Connect the circuit to C304 terminals 6 (+) and 7 (-). See Figure 2.19.
NFPA STYLE X OR Z NOTIFICATION APPLIANCE OR SPEAKER CIRCUIT
Connect polarized alarm Notification Appliances or speakers to a single four-wire circuit. Connect the
circuit to C304 terminals 6 (+), 9 (+), 7 (-) and 8 (-).
NOTIFICATION APPLIANCE POWER
Connect Notification Appliance power from MS-9200 TB4 terminal 1 to C304 terminal 4 (+24 VDC) and MS9200 TB4 terminal 2 to C304 terminal 3 (-24VDC). This power must be supervised by a UL listed Power
Supervision Relay, wired as shown in Figure 2.20.
CODED OPERATION
Connect Notification Appliance power from either TB1 (NAC 1 Output) terminals 1 and 4 or TB2 (NAC 2
Output) terminals 1 and 4 to C304 Control Module terminals 3 and 4. Be certain to place an ELR across
the last device on the module (use only one ELR) for Style B operation. Set NAC 1 or NAC 2, which is now
used to drive the C304, for appropriate coded function. Refer to Section 3.2.03 Point Edit for additional
information.

Note: When wiring Style Z, do not install an ELR since one is built into the C304 Control Module.

TEST SWITCH
The C304 Control Module includes a magnetic test switch sensor located near the center front of the
module. Activation of this switch by test magnet P/N M02-04-00 will cause a short circuit indication for the
Style W/X/Y/Z circuit connected to the module.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

37

Figure 2.19: The C304 Control Module (Utilized as a Form-C Relay)

+ To next Device
- on Loop
CAUTION! Do not loop
wiring under any terminals.
Break wire run to maintain
supervision.

C304

MS-9200
A

T
B
6

B B+
2

A+

B-

A-

Common Contact
Normally-Closed Contact

SLC (+) TB6-3


SLC (-) TB6-5

Break-off Tabs
Normally-Open
Contact

BREAK TABS
To configure a C304 as a Form-C relay, the two break-off tabs shown must be broken off of the module. Use
a pair of needle-nose pliers to break off each tab.
Caution: Failure to break tabs when configuring for Form-C Relay operation can cause damage to the C304
module.
COMMUNICATIONS LOOP CONNECTIONS
Connect the MS-9200 Communications SLC Loop to C304 Terminals 1(-) and 2(+). The C304 occupies one
module address on the Loop. Set the rotary switches on the module to the particular Loop address required.
CONTACT CONNECTIONS
Wire the common and the normally-open or normally-closed contacts to the module as needed.
CONTACT RATINGS
Resistive: 2 Amps @ 30 VDC*
Inductive: 1 Amp @ 30 VDC (0.6 PF)
Pilot Duty: 0.6 Amps @30 VDC (0.35 PF)
0.3 Amps @ 110 VDC (0.35 PF)
0.3 Amps @ 120 VAC (0.35 PF)

*Certain electromechanical devices exhibit inductive loading characteristics. For these types of devices, derate the outputs to
1 Amp. Refer to the Device Compatibility document for load characteristics by device.
38

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Figure 2.20: NFPA Style Y Notification Appliance Circuit (Utilizing C304 Module)
All circuits are supervised and power-limited

UL listed Power Supervision Relay


(Must be wired as last device on
loop as shown).

End-of-Line Resistor 47KW , 1/2-watt.


(N-ELR in Canada)
Note: If more than one C304 Notification
Appliance Circuit is provided, install the power
supervision relay after the last Notification
Appliance.

24VDC
Notification Appliance
(See Fire-Lite Compatibility
Document for compatible devices)
To Next Device
on Loop
+

C304

CAUTION! Do not loop


wiring under any terminals.
Break wire run to maintain
supervision.

24V (+) TB4-1


24V (-) TB4-2

Loop Out

SLC (+) TB6-3


SLC (-) TB6-5

MS-9200

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

39

2.14

The Addressab
le Man
ual Pull Station
Addressable
Manual

The BG-10LX is an addressable manual pull station with a FireLite key-lock reset feature.
BG-10LX INSTALLATION
1) Connect the MS-9200 Communications SLC Loop to terminal screws (+) and (-) on the BG-10LX.
2.) The BG-10LX is factory preset with address 00. Set the address for the pull station by using a
screwdriver to turn the rotary address switches on the back of the unit to the appropriate settings.

Figure 2.21: Wiring Addressable Manual Pull Stations

SLC (+) TB 6-3


SLC (-) TB 6-5

40

BG-10LX (back view)

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

2.15

Wir
ing Detectors
Wiring

INSTALLATION
Connect the MS-9200 Communications SLC Loop to Terminal (-) and Terminal (+) of the removable
terminal block.
If an RA400Z Remote LED Annunciator is being employed, connect the RA400Z positive terminal to the
RA+ terminal on the removable terminal block and the negative terminal to the RA(-) terminal on the
removable block.
Before installing the appropriate addressable detector head, set the detector's address on the
head with a small slotted screwdriver. Mark this address on the head.
Place the removable terminal block into the connector in the detector head. Be certain to align properly
and snap-in securely.

Figure 2.22: Wiring the Detector With Removable Plug-in Connector

Channel (+)
Channel ( - )

Channel (+)

Communications
SLC Loop

Channel ( - )
to next device
on Loop

SD300 with removable


plug-in connector

RA400Z Remote
LED Annunciator

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

41

2.16

Optional Modules

The MS-9200 supports option modules, using connectors J6, J11, J12 and J16 on the main board. There are
five optional modules available for the MS-9200; the RTM-8F Relay/transmitter Module, PIM-24 Printer/PC
Interface Module, the UDACT-F Universal Digital Alarm Communicator Transmitter, the DIM-485 LCD-40
Display Interface Module and the ZDM-16F 16 zone LED Module. Jumper JP4 must be cut before installation of the RTM-8F optional module to enable module placement supervision. Note that devices connected
to the standard EIA-485 connector, the optional EIA-232 connector, the optional EIA-485 connector (via the
PIM-24 or DIM-485) or SLC Loop may be protected from voltage transients by using one of the compatible
surge suppressors listed in Table G-1 of the appendix.

Figure 2.23: Optional Module Location


J11 accepts PIM-24 or DIM-485

J12 accepts ZDM-16F

J16 accepts UDACT-F

Cut JP4 for RTM-8F


supervision

J6 accepts RTM-8F

MS-9200 Main Circuit Board

Comm
unicators
Communicators
UDACT-F Universal Digital Alarm Communicator
Transmitter
Transmits system status to UL Listed Central Station Receivers
via the public switched telephone network. It is capable of
reporting up to 56 software zones or up to 198 addressable
points. The UDACT-F may be mounted directly to the MS-9200
main circuit board, or remotely in a UBS-1F (as shown) or ABS8RF enclosure. The MS-9200 requires software P/N 73580 or
higher to support the UDACT-F. For additional information,
refer to the UDACT-F Manual P/N 50050.

UBS-1F Enclosure
42

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

UDACT-F Mounting Options


The UDACT-F may be mounted directly to the MS-9200 main circuit board
or remotely in an ABS-8RF or UBS-1F enclosure up to 6,000 feet away
from the control panel. All power must be removed from the Control Panel
before making any connections to prevent circuit damage. The EIA-485
serial interface is connected between the Control Panel and UDACT-F using
twisted, shielded pair wire. Power should be wired from the Control Panel's
24VDC (nominal) filtered, nonresettable output to TB1 on the UDACT-F
(except when mounted in the MS-9200).

Figure 2-24: ABS-8RF Enclosure


Mounting Inside MS-9200 Enclosure
The MS-9200 must have firmware with a Part Number of 73580 or higher installed to allow use of the UDACT-F.
Remove all power from the MS-9200 by disconnecting AC and batteries. Install the supplied standoffs (three
nylon and one aluminum standoff) in the appropriate holes located on the right side of the MS-9200 main circuit
board as illustrated in Figure 2.25. Position J10, located on the back of the UDACT-F, over connector J16 which
is located center right on the main MS-9200 circuit board, and carefully connect. Secure the UDACT-F to the
aluminum standoff with the screw provided. Caution: Damage can occur if female connector J10 is not properly
aligned with male connector J16.
The EIA-485 circuit and 24VDC power are provided directly from connector J16 of the MS-9200. Note: A 120
ohm EOL resistor is not required on the UDACT-F EIA-485 terminals when it is installed inside the MS-9200
cabinet. The EOL resistor is required at the last device on the EIA-485 line external to the MS-9200 panel.
Programming
Refer to System Edit in the Programming/Read Status Section of this manual for information on programming
the MS-9200 to function with the UDACT-F.
MS-9200

3/4" aluminum standoff


with nut required for
transient protection
UDACT-F

3/4" Nylon
Standoffs

Figure 2.25: UDACT-F Mounting to MS-9200


Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

43

Supervised and Power Limited EIA-485 and power connections.


(Surge protection can be provided by using one of the compatible
surge suppressors listed in Table G-1 of the Appendix).
To
Phone
Lines
(Supervised)

+24 VDC
Nonresettable
Power (TB4)

Solid
Earth
Ground
Connection

Future Use
Ferrite
Cores
P/N 29090

Shield

Install 120 ohm EOL


resistor (P/N: 71244)
on TB1 terminals 3
& 4 if last or only
device on EIA-485
line.

MS-9200
Cabinet

UDACT-F in ABS-8RF
(shown with cover removed)

MS-9200

Notes:
1) This arrangement allows use of the UDACT-F simultaneously with the RTM-8F module.
2) Ferrite cores are recommended for all applications.
3) Recommended wire is 12 AWG to 18 AWG twisted/shielded pair.
4) If shielded wire is used, connect only one end of shield:
a) shield may be connected to cabinet (earth ground) at fire alarm panel, or
b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT-F. NOTE: The shield
end that is not connected should be insulated to prevent accidental grounding. Do not
connect both ends of shield under any circumstance since a ground fault may result.
5) Conduit is recommended for external wire runs. Consult local building codes.
6) Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on
UDACT-F to a solid building earth ground. Conduit alone will not provide a reliable earth ground.
7) UDACT-F may be located up to 6,000 feet away from the host control panel.
8) Refer to Specifications Section for power requirements.
9) UDACT-F TB1 Terminals 6 and 7 are for future use.

Figure 2.26: External UDACT-F Mounting in ABS-8RF

44

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Capabilities
The ACM-8RF Module provides eight Form-C relays with contacts rated for 5 amps.
When installed with an MS-9200 Fire Alarm Control Panel (FACP), the ACM-8RF Relay
Control Modules provide relay activation for each of the 56 possible FACP zones plus
special functions. Options exist to allow for alarm only or alarm and trouble activations
per zone. Output activation for general alarm, general trouble, general supervisory,
NAC fault, AC fail, walktest start and battery trouble are also available. Refer to the
ACM-8RF Manual Appendix for information on setting module switches for addressing
and relay functions.
The ACM-8RF is installed on the standard EIA-485 communication bus and wiring is
supervised by the FACP. Power for the module must be power-limited and may be
provided by the FACP or by a UL listed power supply such as the FCPS-24F. Up to 32
ACM-8RF Relay Control Modules may be placed onto the EIA-485 communication bus
(if no other devices are installed on the bus). Removable terminal blocks are provided
for ease of wiring installation and servicing. Refer to the ACM-8RF Manual for UL
power-limited wiring requirements and switch SW4 receive/transmit selection options.

ABS-8RF Enclosure

The ACM-8RF module can be mounted remotely in an ABS-8RF annunciator surface-mount backbox.

CAUTION!
CAUTION!: It is vitally important that, following relay programming, all relays be tested for correct activation by
triggering zones and/or special functions at the FACP. It should also be noted :
ACM-8RF relays will activate during the Alarm Pre-signal Sequence.
ACM-8RF relays will not activate during the Alarm Verification Retard and Reset periods.

ACM-8RF

Nonresettable 24 VDC
Power Out
TB4 - 3(+) & 4(-)

EIA-485
TB5 - 1(+) & 2(-)

MS-9200

Figure 2.27: ACM-8RF Relay Control Module Installation


Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

45

Figure 2.28: RTM-8F Option Module Installation


Insert the three nylon standoffs (provided) into the holes located on the right-side edge of the main circuit
board. Insert the metal standoff on the lower right corner. Carefully align the pins of J6 on the main
board with connector J1 on the RTM-8F option board. Press firmly on the option board until it locks in
place on the standoffs. Be certain to tighten the screw into the metal standoff on the lower right corner.
This is critical to the RTM-8F transient protection. Affix the terminal identification labels provided with the
option module.

RTM-8F Option
Module

Standoffs

Main Circuit Board

use metal
screw and
standoff here

insert here

3/4" nylon standoffs

RTM-8F
Main Circuit Board

46

Document # 50428

3/4" aluminum standoff with nut


required for transient protection
Rev. B1

7/28/97

P/N 50428:B1

Figure 2.29: RTM-8F Relay Transmitter Module


JP2 - Jumper Settings:

Note: If relays are used as powerlimited circuits, paste supplied


label to terminal block as indicated.

Alarm/Trouble Polarity Reversal


Remote Station (Power-limited)

Power
Limited

Alarm only Polarity Reversal


Remote Station (Power-limited)

Local Energy Municipal Box


(Nonpower-limited)

Zone 1

Local Energy Municipal


Box Trouble LED (yellow)

Zone 2

JP1 - Cut for polarity reversal


remote station operation
JP2Transmitter Module Select

Zone 3
Zone 4

Switch
Settings

Zone 5

Disconnected

Zone 6
Zone 7

Normal
Zone 8
Metal Standoff
Transmitter Output
(-) normal
(+) normal
J1 (on back of board)

Relay Disconnect Switch


Transmitter Disconnect Switch

Relay Disconnect LED (yellow)


Transmitter Disconnect LED (yellow)
Notes:
1) Zone Relay Contact Ratings
Max. Switched Power: 170W or 1800VA
Max. Switched Current: 6 amps Max. Switched Voltage: 30VDC or
300VAC
UL Rating: 6A @ 28VDC or 120/300VAC 1/8HP @120/240VAC (100,000 CYC) 1.5/0.8 A at 120/240 VAC,
Pilot Duty 30,000 CYC
Contact Material: Silver Nickel, Gold Plated
2) Polarity Reversal Output: 24VDC (nominal), 18.5mA max. rated current Internal Resistance: 1200 ohms (nominal)
Intended for connection to the polarity reversal circuit of a remote station receiving circuit (such as the FireLite
RS-82) having compatible ratings. The RTM-8F is not suitable for separate transmission of both alarm and trouble
signals simultaneously to a remote station. Output is power-limited and wiring can leave the building.
3) Municipal box output: Supervised for open circuit. Output is nonpower-limited and wiring can leave the
building.Yellow Trouble LED when on indicates open circuit condition. Check wiring and make certain Municipal
Box is reset according to local codes. Max. current (short circuit): 0.6 amp
Max. Voltage (open circuit):30.0V
Max. Wire Resistance: 3 ohms
4) To prevent the yellow Trouble LED from turning on when the Transmitter Output is not used (no connections),
move jumper JP2 to the Local Energy Municipal Box position (bottom two pins) and install a dummy load across
the Transmitter Output terminals as shown below. The dummy load is a 1N4004 diode. The cathode must be
connected to the terminal labeled '(-) normal' in Figure 2.29 above, and the anode must be connected to the
terminal labeled '(+) normal'. Polarity must be observed or the Trouble LED will remain on. Caution: Diode must
be removed when using the Transmitter Output in order to properly supervise the connections.

Transmitter Output
Document # 50428

Rev. B1

1N4004
7/28/97

P/N 50428:B1

47

2.17

Printer/PC Interface Module

A remote serial printer may be permanently connected to provide a hard-copy printout of program entries, history
file and walktest data. The Printer/PC Interface Module Part Number PIM-24 provides an EIA-232 conversion to
adapt to most 40 and 80 column printers and most IBM PC/XT/AT or compatible computers including laptops and
personal computers. (This option is not available simultaneously with use of the DIM-485/LCD-40).

CAUTION: DO NOT connect a printer or PC to the MS-9200 Fire Alarm Control Panel if a ground fault exists on
the panel. Circuit damage may result.
PROGRAMMING
Refer to System Edit in the Programming/Read Status Section of this manual for printer programming instructions.
INSTALLATION
Remote printers and PCs require a separate 240 VAC, 50Hz primary power. Also required is the PIM-24 which
includes the Printer/PC Interface Module, interface cable prewired to a DB9F connector as shown in Figure 2.30
and a DB25 adapter. Connect the Printer/PC Interface board to J11 on the MS-9200 main circuit board and the
attached cable to the serial EIA-232 port on the printer or PC. Use the DB25 adapter if a nine pin connector is not
available on your printer or PC. Note that a ground fault may occur on the MS-9200 panel, dependent upon the
printer used, when this connection is made. For this reason, it is important that there be no preexisting ground fault
on the panel. Consult the factory for recommended printers.
PRINTER CONFIGURATION
The PIM-24 is required. Also refer to the documentation supplied with your printer. Set the printers options as
listed in the table which follows.
Typical Printer Settings

COMMUNIC. SETUP:
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:

LARGE
7
EVEN
1 STOP
2400

PC CONFIGURATION
Kit PK-9200 includes the MS-9200 Programming Utility software on 3-1/2"
floppy disk P/N 75298, the Instruction Manual P/N 15677 and the PIM-24
(Printer/PC Interface Module with cable and DB9F/25 connectors).

Figure 2.30: Remote Serial Printer and Computer Connections


TX RCV GND

Plug this DB9F


connector into
the EIA-232
Port of the
printer or PC.

48

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

III PROGRAMMING/READ STATUS


The MS-9200 is completely field programmable, and requires no special software skills. Programming may
be accomplished in one of three ways:
The Autoprogram feature - This method is very convenient for quickly bringing the system on-line or for
program editing.
Manual Programming or editing, using the MS-9200 keypad.
The Off Line Programming feature - This method allows creation of site-specific programs using a DOSbased computer. For programs requiring a large amount of data entry, this method may be preferred. A
programming kit (PK-9200) may be ordered for this purpose.
When a programmed system is normal with no active alarms, troubles or supervisories, the 'SYSTEMS
ALL NORMAL' screen will be displayed as shown below:

SYSTEMS ALL NORMAL


10:00 A MON 03/04/96
In order to (1) program the system, (2) read system status, (3) print, (4) edit, or (5) walktest, the ENTER
key must first be pressed. After pressing ENTER, the screen shown below is displayed:

1=PROGRAMMING
2=RD STATUS 3=AC/BAT
1 = Programming: Programming the system may only be accomplished by an authorized user. Before
attempting to program the system, place the SW1 Write Protect switch in the down position. SW1 is located
on the lower right side of the MS-9200 main circuit board (see page 6). If the switch is in the up 'Write
Protect' position while attempting to enter the Programming Mode, the LCD will display the following:

WRITE PROTECT!!!
PRESS BACKSPACE

In order to program the system, a valid password must first be entered. Once the correct password is
entered, the user may select Autoprogram or Program Editing. After programming is completed, return SW1
to the Write Protect position.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

49

NOTE: There are two programming levels. Program Level 1 is for system configuration in which data relating
to device types, zoning, messages, etc. is entered into the system memory. Program Level 2 is where a
qualified operator can access features such as Disable, Clear History, Walktest, Time Change and Program
Check. For Program Level 2, the SW1 Write Protect switch should remain in the up (Write Protect) position.
2 = Read Status: Entering Read Status allows the user to read the status of any point/zone in the system plus
display or print the history file or print the entire user program. The Read Status feature is NOT password
protected. Read Status is explained in Section IV Operating Instructions.
3 = AC/BAT: Entering AC/BAT allows the user to read the battery voltage and AC line voltage. The AC/BAT feature
is NOT password protected.

BATTERY: 24V
AC LINE: 240V
Section 3.1 on the following page describes initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system. Make certain the SW1 Write Protect switch
is in the down position before attempting any Level 1 Programming functions.

3.0 Initial P
o w er-up
Po
Once wiring of addressable devices to the SLC loop is completed, power up the system. Since the addressable
devices have not yet been programmed, their LEDs will not flash, the System Trouble LED will be on and the LCD
display will alternate between the following two displays:

TROUBLE IN SYSTEM
PROGRAM CORRUPTED

TROUBLE IN SYSTEM
NO DEVICES INSTALL
If the system remains unprogrammed, the piezo will sound after a few minutes. It can be silenced by pressing the
Acknowledge/Step switch, but it will continue to resound until the system is programmed.

50

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

3.1 Programming
Press the ENTER key. The screen below will appear:

1=PROGRAMMING
2=RD STATUS 3=AC/BAT

To enter the programming mode, press '1'. The display will read as follows:

KEY IN 5 DIGIT
PASSWORD, THEN ENTER

Entering the Level 1 password (default 00000) will cause the following screen to appear: (Refer to Section 3.2)

0=CLR 1=AUTO 2=POINT


3=SYS 4=PWORD 5=LOAD

Entering the Level 2 password (default 11111) will cause the following screen to appear: (Refer to Section 3.3)

1=DISABL 2=CLR HIST


3=WALK 4=TIME 5=CHEK

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

51

Passwords
There are two factory set programming passwords, 00000 and 11111, which will access two different screens as
indicated on the previous page. From either of the screens, access to specific system and device programming
may be obtained. All programming entries are stored in nonvolatile memory. The factory set passwords can be
changed by the user, and a method exists to clear one or both passwords. Note: For Canadian applications, both
passwords must be changed from the factory settings. If an invalid password is entered, the display shows:
'INCORRECT PASSWORD'. To exit from Programming operations at any time, press the Backspace (Left Arrow)
key repeatedly.

3.2 Program Change - Level One


When the correct password is entered, the MS-9200 will enter Level One program mode. In this mode, the trouble
relay is activated and the System Trouble LED flashes (and cannot be changed to steady). The piezo sounder is
off. The following display will appear:

0=CLR 1=AUTO 2=POINT


3=SYS 4=PWORD 5=LOAD

3.2.01 Clear
Pressing '0' will clear all general system programming options as defined in Section 3.2.04 and all programmed
addressable devices from the nonvolatile memory of the MS-9200. Before executing the CLEAR command, the
display will prompt the user to press ENTER in order to verify the command before the system actually clears
programming data. CLEAR is a useful command when the unit is first installed, prior to autoprogramming. NOTE:
It is necessary to 'Autoprogram' after using the clear function.

3.2.02 Autoprogram
Pressing '1' enters the AUTOPROGRAMMING mode. The main purpose of autoprogramming is to allow the
installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is
brought on-line, it must be autoprogrammed. Autoprogram is also the only way to add or delete devices.
Once autoprogram is selected, the MS-9200 automatically polls all devices installed/wired to the SLC loop. The
panel communicates with each individual addressable device and displays the type of device at each address
location starting with detectors and then modules.
While autoprogramming the system, the MS-9200 will display the following:

AUTOPROGRAM
PLEASE WAIT
Verification of each device address and type installed on the SLC may now occur. If information is correct press
the ENTER key, if not press the left arrow key to delete. In addition, adjective and noun descriptors plus zone
assignments may be added to the display field per device address. If the Reset key is pressed at this time or the
panel is allowed to timeout (after 10 minutes), a 'System Corrupted' message will appear. Be certain to step
through all devices using the Enter or Left Arrow key.
52

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

The first time that autoprogramming is selected, all points installed on the SLC loop are identified. Default device
type (monitor, smoke detector, control) and software zone assignments for each device are displayed. On any
successive enabling of the autoprogram feature, the LCD will display only the newly installed, deleted or changed
devices on the SLC loop.
Devices which match the program already in memory are not changed and are not shown to the operator. Devices
which do not match the program (not the same address and/or type) are shown to the operator. Devices inadvertently set to the same address are identified, and displayed on the screen.
I. NEW DETECTORS
For each new detector, the Autoprogram feature selects default program values and presents the information to
the user. A typical example:

PROGRAM SMOKE DET P01


<ADJ><NOUN>
Z00

where: the 'P' in P01 represents the actual type code (photo) of the detector found at address 01. ('I' represents Ion type detector.)
The adjective and noun fields are blank, but may be user programmed.
Z00 is the default zone selection meaning 'general alarm' (main circuit board NAC outputs 1 & 2). See Appendix B for Software Zone Assignment.
After the new detector is displayed, press ENTER to accept the default information shown. Alternately, press
LEFT CURSOR (the triangle to the left of ENTER) to reject the autoprogram information, and not enter it into
memory. In most cases, adjective, noun descriptors and zone assignments will be added by using the following
procedure.
The MS-9200 will lead you through the program editing process. A blinking cursor moves through the fields as
you press the RIGHT CURSOR key (the triangle to the right of ENTER). After moving into other fields, you
may return to a previous field by pressing LEFT CURSOR. Change the blinking fields by pressing the UP
CURSOR key, the DOWN CURSOR or by pressing the appropriate numeric key.
Custom words may be entered via the keypad. The alphanumeric operation of the keypad changes a blinking
letter in the ADJ and NOUN fields.. For example, to enter the letter R, press the 7 key to step through 7, P, R
and S; stop on R; then press the RIGHT CURSOR (not ENTER) to move to the next letter position.
To reduce the number of key presses, the user may also select from a library of stored words. The ADJ field
library provides five character words selected by the UP cursor or DOWN cursor from the list below.
_____
blanks (default)
NORTH
SOUTH
_EAST
_WEST
FRONT
CENTR
_REAR
UPPER
LOWER
_MAIN

FIRST
__2ND
__3RD
__4TH
__5TH
FLR_1
FLR_2
FLR_3
FLR_4
FLR_5
RM___

The ADJECTIVE field may be loaded from the library list above, and then modified letter-by-letter if desired.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

53

Pressing the UP or DOWN cursor keys steps through the library. Once the UP or DOWN keys
are pressed, the blinking cursor moves to the last character of the ADJECTIVE field, assuming
that the user will next want to move beyond this field.
Pressing a key on the 12-key pad changes the letter indicated by the blinking cursor. Any
alphanumeric character may be entered.
Pressing the RIGHT or LEFT cursor key moves the blinking cursor one letter right or left.
When the RIGHT cursor key is pressed with the blinking cursor on the last letter of the ADJECTIVE label, the
cursor will move to the first letter of the NOUN field.
Altering the NOUN field is done in a similar way. Use the UP or DOWN cursor keys to step through the
NOUN library (shown below).
__________
(all blanks - default)
_BASEMENT_
_BOILER_RM
_CLASSROOM
_CLOSET___
_CORRIDOR_
_ELECT._RM
_ELEVATOR_
_ENTRANCE_
_FLOOR____
_GARAGE___
_HALLWAY__
_HVAC-ROOM
_KITCHEN__
_LOBBY____
_OFFICE___
_PATIENT__
_RESTROOM_
_ROOM_____
_STAIRWAY_
_STOREROOM
_WING_____
_ZONE_____
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the
ADJ or NOUN field as follows:
If the Zero is pressed, a '0' is placed in the first letter position.
If the Zero key is then pressed a second time with no intervening key actions, the entire ADJECTIVE field is replaced with the field entered for the previous device programmed, and the cursor
moves to the last character of the field (Recall function). The Recalled ADJECTIVE or NOUN field
may now be changed letter by letter.
If the Zero key is pressed again with no other intervening key actions, and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a '0'. If the last character goes from 9 to 0, and the characters to the left of the last
character are also numbers, they are also incremented (overflow).
The above increment function may be repeated with each press of the Zero key.

54

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

As an example, the user could quickly enter 'FLR_3_ROOM_305' as follows:


1) The cursor is on the first letter of the ADJ field. Press the Zero key twice to display 'FLR3'.
2) With the cursor on the first letter of the NOUN field, press the Zero key twice to recall the display
'ROOM304'. The cursor automatically jumps from the first to the last letter of the noun field.
3) With the cursor on the last letter of the NOUN field, press the Zero key again to increment the room
number to 305.
4) Press the Right arrow cursor to advance to the Zone field.
5) Select a zone number from 00 to 56. Z00 (default zone) is the general alarm zone. Z01 through Z56
may be selected to link software zones. Only zones Z01 through Z16 will be displayed on the
optional ZDM-16F LED module.
To load the addressable device's program into memory at any time, press the ENTER key. After pressing
ENTER, autoprogram displays the next new detector. If a detector had been previously entered into memory,
but is missing (no answer), the display shows the following:

PROGRAM SMOKE DET P01


NO ANSWER DELETE?
If ENTER is pressed, the device is deleted from memory and autoprogram displays the next new device. If the
LEFT CURSOR is pressed, the program is unchanged, and the next new device is displayed.
After all new detectors are presented for editing, the autoprogram feature displays the modules on the SLC loop
starting with the device found at the lowest address.
II.
MONITOR MODULE AUTOPROGRAM
Monitor Module Autoprogram is similar to Detector Autoprogram. When a new monitor module is presented, a
typical display might be:

PROGRM MONITOR M01


<ADJ><NOUN>
Z00
The major program editing for monitor modules is the selection of the Type Code on the first line. To change
this selection, use the UP and DOWN cursor keys as the entire field blinks. The default selection is monitor, as
shown in the screen above. Note that selection of a type code may change the functional operation of the
addressable device.
TYPE CODE LABEL

SPECIAL FUNCTION

MONITOR
PULL BOX
HEAT DET
SMOKE ZON
WATERFLOW
SUPERVISY
TAMPER_SW
_________
ACK_SW__
SILENC SW
RESET SW
DRILL_

NONE (DEFAULT)
NONE
NONE
NONE
CAUSES NON SILENCEABLE ALARM
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
NONE (BLANK LABEL)
FUNCTIONS LIKE ACKNOWLEDGE SWITCH
FUNCTIONS LIKE SILENCE SWITCH
FUNCTIONS LIKE RESET SWITCH
FUNCTIONS LIKE DRILL SWITCH

Follow the same procedure as described in Section I New Detectors, for editing of the ADJECTIVE and NOUN
fields.
The default zone selection is Z00 (main circuit board NAC outputs 1 & 2) and may be set to Z01 through Z56 if
desired. See Appendix B Software Zone Assignment.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

55

III.
CONTROL MODULE AUTOPROGRAMMING
A typical control module Autoprogram screen would be:

PROGRM CONTROL CNN


<ADJ>
Znn Znn Znn
Control modules default to zone Zone 00 (general alarm). All type code options are silenceable except Relay
and Strobes. The selection of control module type codes may change their function.
Select the type code from the library list below. Use the cursor keys as described in Section I New Detectors.
TYPE CODE

SPECIAL FUNCTION

NONE (DEFAULT) Silenceable


Silenceable
Silenceable
Silenceable
(BLANK LABEL) Silenceable
IGNORE OPEN CIRCUIT (Non-silenceable)
Non-silenceable

2
3
4
5
6
7

CONTROL
BELL CKT
HORN CKT
SOUNDERS
_________
RELAY
STROBES

Select an adjective descriptor from the library list shown in Section I New Detectors. Use the cursor keys as
described in Section I.
Control modules may be assigned to a maximum of three software zones. (See Appendix B). Zone Z00
represents general alarm. All control modules are assigned to Zone Z00 upon initial power up.

3.2.03

Point Edit

While displaying the Program Level One Menu screen (see Section 3.2), pressing '2' allows for editing of the point
(addressable device) descriptor screens. These screens show the device type, the device address, adjective and
noun field descriptors and the software zone locations that the point (addressable device) is assigned to. Point
editing is performed after autoprogramming and may be done at any time, except during an alarm condition. The
display shows:

POINT PROG. EDIT


PRESS */#, AA, ENTER
For example, select Detector address 3 program edit by pressing the * key (* = detector), followed by numeric key
3, followed by ENTER. Select Module address 3 program edit by pressing the # key (# = module), followed by the
numeric key 3, followed by ENTER. If there is no device installed at this address, the panel displays the next
higher address where a device is installed. After editing is complete, and ENTER is pressed, the display returns to
the above menu. Rather than reentering the next point number, the user may press the UP or DOWN key to display
the next lower or higher existing point. Using software P/N 73750 or greater, to edit NAC1 or NAC2, press the *
key, then the # key, then press '1' for NAC 1 or '2' for NAC 2. Select either 'BELL_CKT' for silenceable functionality or 'STROBE' for nonsilenceable functionality. Use the system edit menu described in Section 3.2.04 to select
coding. Coding is only possible if the NAC is programmed as 'BELL_CKT'. The point display formats and the
method of editing are described in Section 3.2.02, Autoprogramming.

56

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

3.2.04

System Edit

The System Edit function is selected by pressing '3'. The system edit screen appears as shown below for software
releases prior to P/N 73750. This software does not support the LCD-40 Annunciator:

VF=N SI=N AS=N PS=N


CD=N AN=N ST=4 REM=N
Use the Up and Down arrow keys to scroll through the choices for each option and the Left and Right arrow keys to
move from option to option.
There are eight system function options for software releases prior to P/N 73750. The factory default selections
and user option selections are shown below:
FUNCTION

DEFAULT

VF = Alarm Verification (N)one


SI = Silence Inhibit
(N)one
AS = Auto-Silence
(N)one
PS = Pre-signal
(N)one
CD = Bell Code 1
(M)arch Time
Note: Bell 2 is fixed steady
AN = Annunciators

(N)one

ST = SLC loop style


(4) = Style 4
REM = Alarm/Trouble (N)o
Reminder

SELECTION
(Y)120 seconds
(Y)60 seconds1
(Y)10 minutes1
(Y)3 minutes with 15 second Acknowledge1
(N) = None
(T) = Temporal
(C) = California
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F2
(6) = Style 6
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or
silence key has been pressed.

Requires prior approval of Local Authority Having Jurisdiction.

When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation, up to 56 zones, use AFM
Series Annunciators or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.

The system edit screen appears as shown below for software P/N 73750 or greater. This software is required to
support the LCD-40 Annunciator:

V=N I=N A=N P=N C=N


A/U=N L/P=N S=4 R=N

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

57

There are nine system function options for software P/N 73750 or greater. The factory default selections and user
option selections are shown below:

FUNCTION

DEFAULT

SELECTION

V = Alarm Verification
I = Silence Inhibit
A = Auto-Silence
P = Pre-signal
C = Bell Code

(N)one
(N)one
(N)one
(N)one
(N)one

(Y)120 seconds
(Y)60 seconds1
(Y)10 minutes1
(Y)3 minutes with 15 second Acknowledge1
(M) = March Time
(T) = Temporal
(C) = California
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F2
L = LCD-40 installed (requires DIM-485)
P = Printer or local PC installed (requires PIM-24)
(6) = Style 6
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or silence key
has been pressed.

A/U = Annunciators
(N)one
with or without UDACT-F

L/P = LCD-40 or
Printer/PC in use
S = SLC loop style
R = Alarm/Trouble
Reminder

(N)one
(4) = Style 4
(N)o

Requires prior approval of Local Authority Having Jurisdiction.

When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation use AFM Series Annunciators
or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.

3.2.05

Password Change

While displaying the Program Menu, press '4' to change either of two passwords. One high level password,
defaulted to 00000, allows for point and system programming. A second lower level password, defaulted to
11111, allows for status changes such as: (1) disable points/zones (2) clear history file, (3) walk test enable,
(4) time and date set and (5) program check. Pressing '4' will display:

*,NNNNN, E=LEVEL 1 PW
#,NNNNN, E=LEVEL 2 PW

Select the password to change by typing * or #, then enter the new password. As the new program or status
password is entered it is displayed. When ENTER is pressed, the display reads "PRESS ENTER IF OK,
NNNNN = NEW PROGRAM PW". After ENTER is pressed, the new password is stored in EEPROM memory
and the program returns to the program change screen. If BACKSPACE is entered, the password remains
unchanged and the program returns to the program change screen.

58

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

3.2.06

LOAD

While displaying the Program Menu, program selection '5' sets up the MS-9200 for transfer of its application
database from/to a DOS-based computer. This may be used to save the program that exists in an MS-9200 for
security and future service reasons; or may be used to transfer a program created off-line to the MS-9200. Refer
to Document# 15677 for more information. When the Load option is selected, the following screen will be displayed:

CONNECT COMPUTER NOW


RUN PROGRAM FROM PC
The LEFT CURSOR may be used to return to the program change screen. The PC connects to the EIA-232 printer
interface (instructions provided with the Upload/Download software kit). Continue to press the Backspace key (left
cursor) to return to the main program screen.

3.3

Prog
vel Tw o
Progrr am Change - Le
Lev

While the MS-9200 system is normal with no active alarms, troubles or supervisories, the screen shown below
will be displayed:

SYSTEMS ALL NORMAL


10:00 A MON 03/04/96
To access the programming mode, the ENTER key must be pressed. After pressing ENTER, the following
screen is displayed:

1=PROGRAMMING
2=RD STATUS 3=AC/BAT

Pressing '1' will cause the following screen to appear:

KEY IN 5 DIGIT
PASSWORD,THEN ENTER

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

59

Enter the Level 2 password (default = 11111) then press the ENTER key to access Programming Change Level
Two. The screen below will appear:

1=DISABL 2=CLR HIST


3=WALK 4=TIME 5=CHEK
From this screen, the available function choices include point DISABLE, CLEAR HISTORY, WALKTEST, SET
TIME and CHECK programming.

3.3.01 Disable
Pressing '1' displays the following screen:

DISABLE/ENABLE
PRESS */#, AA, ENTER
Press the * key to display detectors, the # key to display modules, followed by the device address, then the
ENTER key. A typical display is shown below:

ENABLE SMOKE DET P01


NORTH BASEMENT Z01
A point is then displayed on the screen similar to a Point Edit display but with the current status label (ENABLE)
blinking. The current status label may show: NORMAL, TROUBL, DISABL, ALARM, ACTIVE, PROGRM, TEST 01,
ON, OFF. The status label can be changed to DISABL or back to its present status by pressing the UP or DOWN
keys. The disable status is entered/stored in memory by pressing ENTER. The display then returns to the DISABLE/ENABLE screen shown above. The operator may then enter a new point number, or may press UP/DOWN
to bring up the next lower/higher address point. The disabling of initiating devices that are in alarm or control
points that are ON occurs after the RESET key is pressed.
All disabled points will scroll on the LCD display and the system will remain in trouble until all programmed points
are enabled.

3.3.02 Clear History


Pressing '2' displays the following screen:

ENTER TO CLEAR HIST.


BACKSPACE TO ESCAPE
Press the ENTER key to clear the 500-event History file. Press the left cursor key (Backspace) to exit without
clearing the History file. Caution: Pressing Enter will clear all History events associated with this panel. Care
should be taken to ensure this is the appropriate action.
60

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

3.3.03 Walk Test


If '3' is pressed, followed by ENTER, the following is displayed:

WALK TEST 1-SILENT


2-PULSE SOUNDERS
Press '1' to perform a silent walktest with all sounding devices, control modules and the bell 1 and bell 2 outputs
OFF. Select '2' to perform an audible walktest which sounds all silenceable control modules and bells 1 and 2 (if
programmed as 'BELL_CKT' as explained in Section 3.2.03) output during walktest. (Disabled NAC outputs will not
activate during Walktest). Each alarm and trouble condition (short and open) will be printed in real time and stored
in the 500 event history buffer. After pressing either '1' or '2', the screen shown below will appear:

ENTER START WALKTEST


BACKSPACE TO STOP
If ENTER is pressed, the second line goes blank, and the unit is in Walk Test mode. Walk test may be stopped at
any time by pressing Backspace, returning the unit to the main screen. A one hour time-out automatically returns
the system to normal operation.
Shorted/Alarm Condition
When in Walk Test, the panel responds to each new alarm and activates its programmed control outputs for four
seconds, if those control outputs have been programmed for silenceable activation. It also stores each alarm in
the history file and printer with a "TEST XX" status label. XX is a count of the number of times a device with this
address has been tested. Note that this is a convenient way to identify two detectors that are erroneously set to
the same address. A complete Walktest will cause a TEST 02 indication for the addresses to which both devices
are set and no TEST report for the address that one of the devices should have been set to.
Note that if the system under test includes one or more enabled M302 monitor modules, the following may apply:
If the M302 monitor module is used for a supervised, 2-wire smoke zone, alarming any monitor module in the
system will result in the activation of programmed control outputs for an additional eight seconds or less. This
is caused by the temporary removal of 24 VDC resettable power from the M302. The M302 reports this loss
of power as an open condition in addition to the alarm condition.
Open Condition
300 Series devices as well as both main circuit board NACs are monitored for fault conditions during Walktest
Mode. When a new trouble condition occurs, it activates all control modules programmed for WALK test and Bell
Circuit 1, then shuts them off after an 8 second interval (4 seconds longer than alarms). The trouble status label is
"TEST T".
While in Walk Test, the trouble relay is on, and the System Trouble LED flashes (as in all of Program and Status
change operations). The alarm relay is not activated. The LCD displays the following:

ENTER START WALKTEST


Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

61

3.3.04 Set Time/Date


If '4' is pressed, the following is displayed:

CHANGE TIME/DATE
10:00 A MON 03/04/96

The first digit of the hours is flashing and may be changed with the numeric pad. The RIGHT CURSOR moves to
the next digit and the UP/DOWN cursor selects (A)M or (P)M and day of the week. Pressing the ENTER key
stores the time and date and returns to the level 2 main screen.

3.3.05 Check
Program selection '5' performs a check on software zone assignments. The MS-9200 looks for output devices
assigned to a software zone that does not contain any input devices (detectors, monitor modules). If multiple
devices fail the check, the UP/DOWN keys are used to step through the list of devices. The user must return to
point editing to correct any errors.

NOTE: The system continues monitoring alarm conditions during all Programming and Read Status operations
with theexception of Walktest.

At the completion of system programming, Switch SW1 (Write Protect switch) should be set to the Write Protect
position to prevent inadvertent changes to programmed features. Slide the switch to the up position to select the
Write Protect feature. See Figure 2.23 for the location of SW1.

62

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

IV OPERATING INSTR
UCTIONS
NSTRUCTIONS

Figure 4.1: The MS-9200 Membrane Switch Panel

4.0

Control Switches

ACKNOWLEDGE/STEP
The Acknowledge/Step key silences the piezo sounder and changes all flashing LEDs to steady. Only one
press is necessary regardless of the number of new alarms, troubles or supervisory signals. When the
piezo is silenced, an 'ACKNOWLEDGE' message is sent to the printer and the history file. Multiple active
events are scrolled on the display at a three second rate.
ACKNOWLEDGE also automatically sends a 'SILENCE PIEZO' command to the LCD-40, AFM and LDM
annunciators.
When more than one event exists, the first press of the Acknowledge/Step switch silences the piezo and
changes all flashing LEDs to steady. The second press of the switch stops the scrolling and holds the
event on the display for 1 minute. Subsequent pressing of the switch 'steps' through each active event.

DRILL HOLD 2 SEC


When the DRILL switch is held for two seconds (time required to prevent accidental activations), the MS9200 turns on both main panel NAC outputs and all silenceable circuits (all control modules/Notification
Appliance circuits that are programmed silenceable) and turns off the ALARM SILENCE LED. The 'MANUAL
EVACUATE' message is shown on the LCD display. The same message is sent to the printer and history
file. The Silence key operates on silenceable NAC outputs only.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

IV. Operating Instructions

ALARM SILENCE
The Alarm Silence switch performs the same functions as ACKNOWLEDGE/STEP. In addition, if an alarm
exists, it turns off all silenceable circuits and causes the ALARM SILENCE LED to turn on. It also sends an
'ALARM SILENCED' message to the printer, the history file and the LCD-40. A subsequent new alarm will
resound the system.

63

SYSTEM RESET
Pressing the System Reset switch turns off all control modules and Notification Appliance Circuits, temporarily turns off resettable power to 4-wire detectors, causes an 'All Systems Normal' message to be displayed on the LCD, and stores 'System Reset' in the printer and history file. It also turns on all LEDs,
piezo, and LCD display segments as long as SYSTEM RESET is held (lamp test). Any alarm or trouble
that exists after System Reset will resound the system.

4.1

LED Indicators

The six LED indicators on the front panel operate as follows:


AC POWER
This is a green LED which illuminates if 240 VAC power is applied to the system.
FIRE ALARM
This is a red LED that flashes when one or more alarms occur. It illuminates steadily when the ACKNOWLEDGE or SILENCE switch is pressed. The Alarm LED turns off when the SYSTEM RESET switch
is pressed.
SUPERVISORY
This is a yellow LED that flashes when one or more supervisory conditions occur, such as a sprinkler
valve tamper condition. It illuminates steadily when the ACKNOWLEDGE or SILENCE switch is pressed.
It turns off when SYSTEM RESET is pressed.
ALARM SILENCE
This is a yellow LED that turns on after the ALARM SILENCE key is pressed (preceded by a fire alarm
condition). It turns off when the ALARM ACTIVATE or SYSTEM RESET switch is pressed.
SYSTEM TROUBLE
This is a yellow LED that flashes when one or more trouble conditions occur. It stays on steady when the
ACKNOWLEDGE or SILENCE switch is pressed. The LED turns off when all trouble conditions are cleared.
This LED will also illuminate if the microprocessor watchdog circuit is activated.

4.2

Normal Operation

With no alarms or troubles in the system, the display message is SYSTEMS ALL NORMAL along with
the current time and date as shown below. To set the time and date, see Section 3.3.04.

SYSTEMS ALL NORMAL


10:00 A MON 03/04/96
The MS-9200 performs the following functions at regular intervals while in normal mode:

64

Polls all devices on SLC loop. Checks for valid reply, alarms, troubles, etc.
Monitors AC input voltage and battery capacity.
Refreshes LCD display and updates time.
Scans keyboard.
Performs detector auto test.
Tests memory.
Updates/Reads EIA-485 communications bus.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

4.3

Troub
le Oper
ation
rouble
Operation

With no alarms, the detection of a trouble in the system will cause the piezo to sound, the System Trouble LED to
flash, and the trouble relay to activate. A message will appear on the LCD display indicating the trouble condition.
The same message is sent to the printer and history file, along with time and date.
Addressab
le Smok
e Detectors
Addressable
Smoke
Detectors: For addressable Ion or Photoelectric smoke detectors, the following is a typical
message that could appear on the LCD display for a detector in trouble.

TRBL_# SMOKE DET P01


<ADJ> <NOUN>
Z00
The information displayed in the first line in the example above provides the following information:
The type of event - in this example TRBL indicates Device Trouble.
The Specific Device Trouble - the # symbol will be replaced by a digit representing a specific trouble
condition. (Refer to the list of Specific Device Troubles below).
Type of device - in this example SMOKE DET indicates smoke detector.
Point type and address - in this example P01 indicates Photoelectric detector assigned to address 01.
The information displayed in the second line in the example above provides the following information:
<ADJ> - user programmed adjective descriptor from library list or custom entry (five characters max.).
<NOUN> - user programmed noun descriptor from library list or custom entry (ten characters max.).
Zone - zone to which the point is assigned.
The # symbol in the display will be replaced by a digit that represents the Specific Device Troubles as listed below:
1 = Invalid Reply:
An Invalid Reply may be due to: (1) incorrect pulse width received from a detector, (2) no answer from a
detector due to either a complete device failure or removal from the SLC loop, or (3) an incorrect identification code received, i.e. a photoelectric detector replaced by an ion detector or vice-versa.
2 = Maintenance Alert:
A Maintenance Alert indicates that a detector has been within 80% of its alarm threshold for 24 hours,
indicating that the detector needs cleaning.
3 = Fail Automatic Test:
Fail Automatic Test indicates that a detector's sensing chamber and electronics (which are tested for
normal safe operation every two hours) has failed.
Monitor and Control Modules
Modules: The following is a typical message that could appear on the LCD display for monitor
modules and control modules in trouble.

TRBL_# MONITOR M01


<ADJ> <NOUN>
Z00

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

65

The information displayed in the first line in the previous example provides the following information:
The type of event - in this example TRBL indicates Device Trouble.
The Specific Device Trouble - the # symbol will be replaced by a digit representing a specific trouble
condition. (Refer to the list of Specific Device Troubles below).
Type of device - in this example MONITOR indicates monitor module.
Point type and address - in this example M01 indicates monitor module assigned to address 01.
The information displayed in the second line in the previous example provides the following information:
<ADJ> - user programmed adjective descriptor from library list or custom entry (five characters max.).
<NOUN> - user programmed noun descriptor from library list or custom entry (ten characters max.).
Zone - zone to which the point is assigned.
The # symbol in the display will be replaced by a digit that represents the Specific Device Troubles as listed below:
1 = Invalid Reply:
An Invalid Reply may be due to: (1) incorrect pulse width received from a module, (2) no answer from a
module due to either a complete device failure or removal from the SLC loop, or (3) an incorrect identification code received, i.e. a monitor module replaced by a control module or vice-versa.
2 = Short Circuit Control Module:
A Short Circuit exists across a control module's Notification Appliance Circuit (NAC).
3 = Open Circuit Monitor/Control Module:
An Open Circuit exists on a control module's Notification Appliance Circuit (NAC) or the monitor
module's Initiating Device Circuit (IDC).
Pressing the Acknowledge switch will cause the piezo to silence and the System Trouble LED to go on steady.
This occurs regardless of the number of troubles, alarms and supervisory events active in the system (block
acknowledge). When Acknowledge is pressed, and at least one new alarm or trouble exists in the system, the
ACKNOWLEDGE message is sent to the printer and history file.
If the trouble clears, either before or after ACKNOWLEDGE, the CLEAR TROUBLE message is sent to the printer.
For example:
CLR TRBL_# SMOKE DET P01 <ADJ><NOUN> ZONE # TIME and DATE
If all troubles clear and there are no supervisory or fire conditions active in the system, the system returns to
normal operation status, and the SYSTEMS ALL NORMAL message is shown on the LCD display and stored in the
history and printer files. Trouble restore occurs even if the troubles were never acknowledged (auto restore).
If ALARM SILENCE is pressed when only troubles exist, it will have the same effect as ACKNOWLEDGE/STEP.
The ALARM SILENCE LED will not be illuminated unless there was also an alarm in the system.
If multiple trouble conditions exist in the system, they will be scrolled on the LCD display automatically at a three
second rate. If a combination of alarms, troubles and/or supervisory conditions occur in the system simultaneously, only the alarms are scrolled on the display. If the ACKNOWLEDGE/STEP key is pressed, the display
stops on the present item for one minute, or until the ACKNOWLEDGE/STEP key is pressed again. As the ACKNOWLEDGE/STEP key is pressed, the MS-9200 displays events in the following priority order:
Alarms, in order of address
Supervisory, in order of address
Troubles, in order of address

66

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

4.4

Alarm Operation

Alarm operation is similar to trouble operation, but with the following differences:

The Piezo produces a steady sound, not pulsed


The System Alarm (not Trouble) LED flashes
ALARM: device name, type, and address are displayed
Alarms latch and are not allowed to clear automatically
Alarms activate software zones (control by Event Logic) if so programmed
Timers (Silence Inhibit, Auto Silence, Trouble Reminder) are started
Alarms activate the general alarm relay and zone Z00 (NAC1 and 2)
The Trouble Relay is not activated

A typical alarm display would be:

ALARM: PULL STATION M02


<ADJ><NOUN> ZONE #

4.5

Supervisory Operation

Supervisory operation is similar to alarm operation, but with the following differences:

The Piezo is a warbling sound


The Supervisory LED (not Alarm) flashes
The Display Status label is ACTIVE
Supervisory Relay is activated
Silenced alarms are not resounded
Timers are not started
The alarm relay is not activated

A typical supervisory event would display:

ACTIVE TAMPER M02


<ADJ><NOUN> ZONE #
Note that, like alarms, supervisory signals latch and can be assigned to a software zone. Supervisory
alarms do not cause resound as do other alarm conditions. Open circuits in supervisory wiring are processed by the MS-9200 the same way as other trouble conditions.

4.6

Notification Appliance Circuit (NA


C) Oper
ation
(NAC)
Operation

There are two Notification Appliance (bell) Circuits on the MS-9200. For software releases prior to P/N
73750, NAC 1 is programmable and factory defaulted to general alarm, silenceable and March Time coding
operation. NAC 2 is not programmable and is fixed as general alarm, nonsilenceable and may not perform
coded functions.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

67

For software releases 73750 or greater, both NAC 1 and NAC 2 are programmable. Both NACs may be either
silenceable or nonsilenceable and may be programmed as steady or coded operations. Coded operation includes
March Time, Temporal or California types. Refer to Section 4.10 for additional information on coding.

4.7

Control-By-Event Operation

Each addressable detector and monitor module can be assigned to one software alarm zone. Control modules
may be assigned to a maximum of three software zones. A General alarm zone (Z00) may be listed for output
(control) points, but it is not necessary to list Z00 for input points, as this is the default zone. Z00 is not activated
by supervisory points.
When an input device (detector, M300 series modules) alarms and is not disabled, it activates all software
zones assigned to it. An output device (control module or Notification Appliance Circuit) that is not disabled is
turned on when any of the software zones to which it is mapped become active.

4.8

Detector Functions

MAINTENANCE ALERT
Each detector is monitored by the control panel for its maintenance status. If a detector is within 80% of its alarm
threshold for a 24 hour period, a 'maintenance alert' message will be displayed automatically signaling that the
detector needs cleaning.
AUTOMATIC TEST OPERATION
An automatic test of each detector is performed every two hours. The detector's sensing chamber and electronics
are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. System
Reset clears this trouble.
TYPE CODE SUPERVISION
The MS-9200 monitors hardware device type codes (CP300, SD300, SD300T, M300, M301, M302, and C304) at slow
intervals. Mismatch of any type code, compared to the system program, will cause a device trouble.
SYSTEM ALARM VERIFICATION
The panel may be programmed to perform alarm verification. Alarm verification applies to detectors only. Refer to
Section 4.12 for a description of the Alarm Verification Timer.

4.9

Time Functions

REAL TIME CLOCK OPERATION


The MS-9200 includes a crystal time base clock that provides time of day, date, and day of week. Time is displayed
as 12 hour time with month/day/year, and is stored in RAM. If both AC and battery power are lost, the time must
be reset.

4.10

Coded Operation - Notification Appliance (Bell) Circuits 1 and 2

Shown below are the pulse rate outputs via NAC 1 or NAC 2 when coded operation is selected. Note that software
releases prior to P/N 73750 only allow coding on NAC 1. Releases 73750 or greater allow coded functions on both
NAC 1 and NAC 2.
CONTINUOUS NO PULSE
MARCH TIME PULSES AT 120PPM.
TEMPORAL CODE PULSES TEMPORAL CODE (0.5 sec. On, 0.5 sec. Off, 0.5 sec. On, 0.5 sec. Off,
0.5 sec. On, 1.5 sec. Off).
CALIFORNIA CODE 10 sec. On, 5 sec. Off
68

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

4.11

Presignal

Presignal is used to delay output activation (control modules and NACs) while allowing for visual verification by a
person. Once a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the
Notification Appliance (bell) Circuits are not activated for 15 seconds. During this time, if the acknowledge switch
is pressed, the piezo is silenced and the Notification Appliances will not activate for up to 3 minutes. After 3
minutes, the Notification Appliances will activate if the source of the alarm is not cleared. This does not affect
monitor modules programmed as waterflow or supervisory. Presignal operation requires the approval of the local
Authority Having Jurisdiction.

4.12

Special System Timers

SILENCE INHIBIT TIMER (NONE OR 60 SECONDS)


This option, if selected, prevents the ALARM SILENCE switch from functioning for 60 seconds after an
alarm. A new alarm during the initial 60 seconds will cause the timer to restart with a new 60 seconds.
Silence Inhibit operation requires the approval of the local Authority Having Jurisdiction.
AUTO SILENCE TIMER (NONE OR 10 MINUTES)
If Auto Silence is selected, the Notification Appliances will be silenced automatically after ten minutes of
activation. Pressing DRILL will restart the timer with a new 10 minutes. Auto Silence operation requires
the approval of the local Authority Having Jurisdiction.
TROUBLE REMINDER
If selected, this feature causes a reminding 'beep' every 15 seconds during an alarm (after the Silence
switch is pressed) and a 'beep' every two minutes during a trouble condition after the Acknowlede or
Silence switch is pressed. The 'beeps' from the onboard piezo will occur until the alarm or fault is cleared.
ALARM VERIFICATION (NONE OR 2 MINUTES)
If alarm verification is selected, an addressable smoke detector's alarm is ignored for a retard time of 13
seconds and the detector's alarm condition is automatically reset. There will be no alarm indication at the
FACP during the Retard period. A confirmation period of 1 minute and 47 seconds follows, during which a
subsequent alarm from the same detector will cause the panel to immediately activate the appropriate
outputs and indicate the alarm condition at the FACP. If a different detector alarms any time during the
first detectors verification period, the panel will immediately activate all appropriate outputs and indicate
the alarm condition at the FACP. If no additional detector alarms occur within 2 minutes of the first alarm
(13 second retard plus 1 minute and 47 second confirmation), the timer resets and the panel is ready to
verify any new detector alarms which may occur.
0 Sec.
Detector Alarm Verification
(Retard + Confirmation)

Detector Goes Into Alarm

13 Sec.

120 Sec

RETARD

Alarm Ignored

Different Detector Alarms


During First Detector's
Verification Period

CONFIRMATION

Control Panel Processes Alarm if Same Detector is Still in Alarm

Control Panel Immediately Processes Alarm

WATERFLOW CIRCUITS OPERATION


If an alarm exists from a monitor module point that has a Waterflow type code, the ALARM SILENCE
switch will not function.
DISABLE/ENABLE OPERATION
Input points which are disabled do not cause an alarm or any CBE (Control-By-Event) activity. Disabled
output points are held in the off state. All disabled points are treated as if they were in trouble except the
status label displayed is DISABL
DISABL.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

69

4.13

Style 6 Operation

If the SLC is wired and programmed for Style 6, and a single fault occurs, the control panel will detect
the fault and drive both ends of the line, fully recovering from the fault. The panel latches the trouble and displays
it until the System Reset switch is pressed. The display shows STYLE 6 trouble type.

4.14

Read Status

Read Status functions do not require a password. The MS-9200 will continue to provide fire protection while in
read status mode. Read status may be entered while in alarm or trouble. If a new alarm or trouble occurs
during these functions, the Read Status is aborted to prevent confusion.
READ STATUS ENTRY
The operator presses the ENTER key, and the LCD display shows:

1=PROGRAMMING
2=RD STATUS 3=AC/BAT
The operator presses 2, and the display shows:

DISPLAY POINT=*/#, AA
HISTORY=1 PRINT=2
From this display, an operator may select one of three choices:
To DISPLAY POINT status, the type of device to be read must first be identified by pressing the (*) key for
a detector or the (#) key for a module. The two digit device address is keyed in next, followed by the
ENTER key.
To DISPLAY ZONE status, press the (*) key, then press the (*) key again. Next, key-in the zone number
(1-56) and press ENTER. The UP and DOWN cursor keys are used to view the next or previous zone.
To DISPLAY SYSTEM PARAMETERS, press the (*) key then press the (*) key again followed by ENTER.
To DISPLAY BELL CIRCUIT status, press the (*) key, followed by the (#) key, then the digit 1 or 2, then
ENTER.
To display the 500-event HISTORY file on the LCD, press the 1 key, then ENTER. The UP and
DOWN Arrow keys are used to step through the entries in the file.
To PRINT PROGRAM CONTENTS and CURRENT SYSTEM STATUS or HISTORY FILE, press the 2 key,
then ENTER. A new Menu appears which prompts to press 1 to print Program/Status or 2 to print History
file.
During this and all subsequent operations except print operations, a two minute timer is started that
will return to the previous display if no key is pressed. Each key press restarts the two minute timer.
Press of the left CURSOR (backspace) deletes the previous entry. If there is no entry, it will abort the
Read Status operation and return to the previous display. System Reset will also abort the Read
Status.
70

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

DISPLAY POINT
DISPLAY POINT operations display addressable device status on the LCD display. After the
status of the device is displayed, the UP key may be used to display the status of the next highest
addressable device, and the DOWN key to display the status of the previous addressable device.
The sequence of point display is Detector points 01-99, Module points 01-99, NAC bell circuits 0102, System parameters, and Zones 1-56.
A typical Read Status display is as follows:

NORMAL SMOKE DET P01


WEST HALLWAY Z56

NORMAL is the present status (could be ALARM, TRBL_#, DISABL, etc.)


SMOKE(DET) is the device type, P indicates that this is a Photoelectric detector (could be I if
Ionization, PULL BOX, HORN CKT, etc.), and 01 is the device address.
WEST HALLWAY is the custom label programmed for this device.
Z56 is the assigned software zone.
If the point is not installed, a Read Status command to that point will result in a NOT INSTALLED
message on the display.

READ HISTORY:
The MS-9200 has a 500-event history buffer. Stored events include Point Status, System
Troubles, and ACKNOWLEDGE/STEP, ALARM SILENCE, DRILL and SYSTEM RESET key
presses. All events are recorded with the time and date. History events are stored in volatile
memory, therefore, removal of primary AC power and secondary battery power will clear the
history buffer. To clear the History file without removing power, see Section 3.3.02. To view
events in the history file, use the Up and Down arrow keys to step through the events.
PRINT PROGRAM:
All user programmed options including device types, software zone assignments and system
parameters may be printed. The printout also includes current system status. See Section 2.16
for instructions on connecting a printer.
PRINT HISTORY:
The entire 500-event history file may be printed using the PRINT HISTORY feature. Refer to
Section 2.16 for instructions on connecting a printer.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

71

APPENDIX A: SUPPL
Y CALCULA
TIONS
UPPLY
ALCULATIONS
1. The A
C Br
anch Circuit
AC
Branch
The MS-9200 requires connection to a separate dedicated AC branch circuit (240 VAC), which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the
protected premises. No other equipment may be powered from the fire alarm branch circuit. The branch
circuit wire must run continuously, without any disconnect devices, from the power source to the fire
alarm control panel. Overcurrent protection for this circuit must comply with Article 760 of the National
Electrical Code as well as local codes. Use #14 AWG wire with 600 volt insulation for this branch circuit.

Table A-1: AC Branch Circuit Requirements

@240 VAC

Use Table A-1 to determine the total amount of current, in AC amps, that must be supplied to the system.

Un i t
Ty p e

Nu m b er
o f Un i t s

MS-9200

R45-24E
Charger

Cu r r en t
Dr aw
(am p s )

To t al
Cu r r en t p er
Dev i c e

1.2

0. 5

To t al AC B r an c h Cu r r en t Req u i r ed

72

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

1.2

amps

APPENDIX A
SUPPL
Y CALCULASUPPLY
TIONS

2. The Main P
o w er Supply
Po

The MS-9200 provides regulated power for operating the fire alarm control panel, operating external devices, and operating the standby battery. The power for operating external devices is limited. Use Table A2A (standby or non-alarm) and Table A-2B (alarm) to determine if external loading is within the capabilities
of the MS-9200 power supply.

Concerning smoke detectors: Refer to the manufacturers data sheet packaged with each smoke detector to
find the standby and alarm current draws to use in the tables of this Appendix. Be sure to power detectors
from TB4, Terminals 5 and 6.

Table A-2A: Regulated Load in Standby @24 VDC


External Devices connected to TB4 only
Dev i c e Ty p e

# o f Dev i c es

Main Circuit Board

RTM-8F

ACM-8RF

St an d b y
Cu r r en t
(A m p s )
X

0.08

] one max.

0.009

0.030

ZDM-16F

] one max.

0.00005

AFM-16ATX
AFM-32AX

] one max.

0.04

AEM-16ATF
AEM-32AF

0.002

AFM-16ATF
AFM-32AF

0.04

AFM-16AF

0.025

UDACT-F

] one max.

0.04

LDM-32F

0.04

LDM-E32F

0.002

LCD-40

0.054

4-Wire Smoke
Detector

Power Supervision
Relay

0.025

CP300

0.00015

SD300

0.00015

SD300T

0.0002

M300

0.0002

M301

0.0002

M302

0.007

BG-10LX

0.0002

C304

0.0002

I300

0.0004

Su m Co l u m n f o r St an d b y L o ad

Notes:
1)
2)
3)
4)
5)
6)

To t al
Cu r r en t
(A m p s )

0.08

Amps

TB4, Terminals 1 and 2: Non-Regulated, 24 VDC, 2.5 amps.


TB4, Terminals 3 and 4: Regulated, Filtered 24 VDC +/- 5% 120Hz ripple @10 mVRMS
TB4, Terminals 5 and 6: Regulated, Filtered 24 VDC +/- 5% 120Hz ripple @10 mVRMS
TB4, Terminals 3 and 4; are nonresettable auxiliary power, 300 mA.
TB4, Terminals 5 and 6 are resettable (smoke detector power), 300 mA.
Refer to Current Limitations on next page.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

73

Table A-2B: Regulated Load in Alarm

@24 VDC

External Devices connected to TB2 and TB4


Dev i c e Ty p e

# of
Dev i c es

Cu r r en t
(A m p s )

To t al Cu r r en t
(A m p s )

Main Circuit Board

0.168

RTM-8F

0.1464

ACM-8RF

[ ]

0.15810

ZDM-16F

0.085

AFM-16ATX
AFM-32AX

[ ]

0.0566

AEM-16ATF
AEM-32AF

[ ]

0.0186

AFM-16ATF
AFM-32AF

[ ]

0.0566

AFM-16AF

[ ]

0.0655

UDACT-F

[ ]

0.0757

LDM-32F

[ ]

0.056

LDM-E32F

[ ]

0.018

LCD-40

[ ]

0.054

4-Wire Smoke
Detector

[ ]

_____

Power Supervision
Relay

[ ]

_____

Addressable
Devices

Max.Draw
All Devices

0.2

Notification
Appliances

[ ]

_____

Sum Column for Alarm Load

0.168

0.2

Amps9

Refer to next page for battery calculations using Total Standby and Total Alarm Loads.
Notes:
1) Current limitations of terminals:
TB4, Terminals 1 and 2 = 2.50 Amps.
TB4, Terminals 3 and 4 = 0.300 Amp.
TB4, Terminals 5 and 6 = 0.300 Amp.
TB1 and TB2, Any one circuit = 2.50 Amps.
2) Total current draw of terminals listed above cannot exceed:
3.6 Amps - With Standard Transformer (4000TAE) installed alone.
6.0 Amps - With both Standard Transformer (4000TAE) and optional Transformer (XRM-24E) installed.
Total current from TB4, Terminals 3 and 4, 5 and 6 not to exceed 0.600 amperes.
Total System power is 6.6 amps max.
3) M302 Monitor Module current limit at 90 mA in alarm.
4) All RTM-8F Relays activated.
5) All 16 ZDM-16F LEDs on.
6) All Annunciator LEDs on.
7) UDACT-F actively making phone call to Central Station. If the normally open contact is used, current
consumption increases to 100mA.
8) LDM-32F with LEDs on.
9) This column must not exceed 6.6 amps.
10) All eight ACM-8RF Relays activated on a single module.
74

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

BATTERY CALCULATIONS
Use the Total Standby and Alarm Load Currents calculated in Tables A-2A and A-2B for the following
battery calculation.

Standby Load
Current (Amps)
[
]

Required Standby Tim


Hours (24 or 60 Hou
[
]

Alarm Load
Current (Amps)
[
]

Required Alarm Time in


(i.e. 5 min. = 0.084
[
]

Add Standby and Alarm Load for Required Ampere Hour Batt

Multiply by the Derating Factor of 1.2

Total Ampere Hours (AH) Required

NOTE:
1) 7 AH battery can be located in the MS-9200 Backbox.
2) 12 AH and 17 AH batteries require the FireLite BB-17F Battery box.
3) 20 AH to 55 AH batteries require the FireLite R45-24E Charger for housing and charging batteries.

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

75

APPENDIX B: SOFTW
ARE ZONES
SOFTWARE
Setup and configuration of an addressable system is quite different than a conventional system. In a
conventional system, assignment of input devices (detectors, pull stations, heat detectors, etc.) to zones
is straight forward. Wiring is direct from clearly marked panel terminals to any device assigned to a particular
zone. Connection of output devices (horns, bells, strobes, etc.) in a conventional system is done by direct wiring
of the output device to terminals marked 'bell'.
With addressable systems, the same pair of wires is used to connect to all addressable input and output devices.
Communications between the panel and all addressable devices takes place over one pair of wires originating from
the panel. Software programming is used to configure the system, versus direct wiring. Zone assignment is
created via software means, hence the term 'software zones'.
Setup of an MS-9200 software zone is straightforward. Any zone may have a minimum of one and a maximum of
99 addressable input devices. Each detector is automatically assigned to a general alarm output. A zone may
also have a minimum of one and a maximum of 99 addressable output devices.
Use the charts on the following pages to help in 'zoning' the system. Note that monitor and control modules make
up one group of 99 addresses. It is critical that addresses of detectors are not duplicated and that monitor and
control addresses are not duplicated.
In the following example, photo detectors (SD300) at addresses 01 and 02, along with a monitor module (M300) at
address 01 and control modules (C304) at addresses 03, 04 and 05 have been assigned to zone 1. Zone 2 consists of ion detectors (CP300) at addresses 03 and 04, monitor module (M301) at address 02 and control modules
(C304) at addresses 03, 06 and 07. Zone 3 consists of two photo detectors (SD300) at addresses 05 and 06 plus
one ion detector (CP300) at address 07 and control modules (C304) at addresses 03, 08 and 09.
This example points out some of the key assignment features of the MS-9200. Addresses of detectors are not
duplicated. Addresses of monitor and control modules are not duplicated. The control module at address 03 is
assigned to the maximum three software zones (provides for floor above and floor below). Detectors and monitor
modules are assigned to one software zone.
Take care to properly plan the installation prior to installing any devices.

76

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

SD300
01

SD300
02

ZONE
01

C304
04

M300
01

C304
05

M301
02

C304
03

CP300
03

ZONE
2

C304
06

CP300
04

C304
07

SD300
05

SD300
06

C304
08

ZONE
3

CP300
07

C304
09

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

77

DETECTOR

78

ADJ
NOUN

(Up
(Up

to
to

ZONE

ADDRESS

DEVICE
TYPE

ZONE
NUMBE

01

SD300

02

SD300

ELEV.

03

CP300

2ND

04

CP300

05

SD300

3RD

FLOOR

06

SD300

MEZZANINE

07

CP300

FIRST

5
Characters)
10
Characters)

HALL

LOBBY

FLOOR

ROOM

MECH.

ADDR

210

ROOM

08

09

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

MONITOR/CONTROL

MODULE

ADJ (Up to 5 Characters)


NOUN (Up to 10
Characters)

ADDRESS

DEVICE
TYPE

ZONE
NUMBER

01

M300

02

M301

03

C304

1,2,3

2ND

FLOOR

53

04

C304

1ST

FLOOR

54

05

C304

HALL

55

06

C304

LOBBY

56

07

C304

MEZZANINE

57

08

C304

3RD

58

09

C304

MECH.

WEST
EAST

EAST
ELEV.

ADDR

HALL

51

STAIRWELL

52

FLOOR
ROOM

59

10

60

11

61

12

62

13

63

14

64

15

65

16

66

17

67

18

68

19

69

20

70

21

71

22

72

23

73

24

74

25

75

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

79

80

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

DETECTOR
ADDRESS

DEVICE
TYPE

ZONE
NUMBE

ADJ
NOUN

(Up
(Up

to
to

ZONE
5
Characters)
10
Characters)

ADD

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

81

MONITOR/CONTROL
ADDRESS

82

DEVICE
TYPE

ZONE
NUMBE

ADJ
NOUN

(Up
(Up

MODULE
to
to

5
Characters)
10
Characters)

ADD

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

APPENDIX C: LCD-40 Ann


unciator Wir
ing
Annunciator
Wiring
The following drawing illustrates the wiring of two LCD-40 Remote Annunciators to an MS-9200 FACP. A maximum
of 32 LCD-40s may be connected to a single control panel. The EIA-485 wiring must pass through a Ferrite Core
in each LCD-40. The illustration shows power supplied to the annunciators by the MS-9200. For system applications requiring greater than the 300 ma of nonresettable power the MS-9200 can supply, or for remote locations,
use the FireLite FCPS-24FE Field Charger Power Supply.
The DIM-485 interface module is required when using the LCD-40. Insert the plastic standoff, supplied with the
DIM-485, into the hole located near the J11 connector on the top right side of the MS-9200 main circuit board.
(Note that older MS-9200 circuit boards do not have a hole near J11, thus preventing the insertion of the standoff).
Align the connector on the DIM-485 board with J11 on the MS-9200 main circuit board and align the hole on the
DIM-485 with the standoff inserted into the main circuit board. Carefully seat the DIM-485 connector on the main
circuit board J11 connector and press to seat the DIM-485 on the standoff.

LCD-40 in grounded box

Ferrite Core P/N 29090 Required

1234

EIA-485
24 VDC TB4 Terms
3 (+) and 4 (-)

1234

J11

LCD-40 in grounded box

MS-9200 in grounded box

1234

DIM-485 CONNECTIONS
DIM-485

L CD-40 3

Terminal 1 - OUT (+)

P1 Terminal 2

Terminal 2 - IN (+)

P1 Terminal 1

Terminal 3 - OUT (-)

P1 Terminal 4

Terminal 4 - IN (-)

P1 Terminal 3

Ferrite Core P/N 29090 Required

P1
(+) EIA-485
IN
(-) EIA-485

(+) (-)
EIA-485
OUT

Notes:
1) The above table shows terminal to terminal wiring between the DIM485 and one LCD-40.
2) If more than one LCD-40 is installed, the wiring to the DIM-485 In (+)
Terminal 2 and In (-) Terminal 4 will be from the Out terminals of the
last installed LCD-40.
3) The LCD-40 must have the two supplied R120 (120 ohm) resistors
installed across the In Terminals 2 & 4 and Out Terminals 1 & 3.
These resistors are required for impedance matching.
4) Refer to the LCD-40 Technical Manual Document #50327 for detailed
wiring information.
Document # 50428

P2

Rev. B1

Earth
Ground Optional
Shield
Connect

n/c

(+) 24 VDC
IN
(-) 24 VDC
(+) (-)
24 VDC
OUT

7/28/97

P/N 50428:B1

83

APPENDIX D: AFM and LDM Series


Ann
unciator Wir
ing
Annunciator
Wiring
The following drawings illustrate the various configurations which may be wired utilizing AFM Series annunciators.
LDM Series annunciators may be used in a similar manner. All drawings show power supplied to annunciators by
the MS-9200. For system applications requiring greater than the 300 ma of nonresettable power the MS-9200 can
supply, use the FireLite FCPS-24FE Field Charger Power Supply.
AFM-16ATX

AEM-16ATF

RIBBON
CABLE

8 Zones (Alarm &


Trouble)
4 Switches (ACK,
SIL, DRILL, RESET)
System Trouble LED
On-Line/Off-Line Power
LED, Piezo

AEM-16ATF

RIBBON
CABLE

16 Zone
Alarm & Trouble

AEM-16ATF

RIBBON
CABLE

16 Zone
Alarm & Trouble

16 Zone
Alarm & Trouble

The above configuration provides: 56 Zones of Alarm and Trouble indication, Remote Acknowledge/Step, Alarm
Silence, Drill, and System Reset keys, System Supervisory, AC fail, and Trouble indications. Use AKS-1F
keyswitch to prevent unauthorized actuation of control switches.

Refer to the AFM Manual for further details.

Annunciator Power (12 to 18 AWG)

+ - + - + T
B
4

B+

T
B
2

A+ A-

B+

B-

T
B
1

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

OPTION
PRINTER
& UP/DOWN LOAD
J11

MS-9200

T
B
5

T
B
6

B+

A+

B-

A-

Two-wire EIA485 circuit Max. 6000 ft. @


16 AWG

RIBBON
CABLE

RIBBON
CABLE

Data Communication Port:


EIA-485 @ 20K Baud

84

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

RIBBON
CABLE

AFM-32AX

+ - + - + T
B
4

B+

A+ A-

B+

B-

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

T
B
1

T
B
2

B+

A+

B-

A-

T
B
6

T
B
5

OPTION
PRINTER
& UP/DOWN LOAD

AEM-32AF

J11

MS-9200

RIBBON CABLE

The configuration shown above provides: 56 Zones of alarm indication, a system Trouble LED, an On Line/ Power
LED, local piezo, and a Local Silence/Acknowledge switch.

AFM-16ATF

+ - + - + T
B
4

B+

A+ A-

B+

B-

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

T
B
1

T
B
2

OPTION
PRINTER
& UP/DOWN LOAD

B+

A+

B-

A-

T
B
6

T
B
5

J11

MS-9200MS-9200
MS-9200

This configuration provides 16 Alarm and


Trouble LEDs, System Trouble LED, On
Line/Power LED, Local Silence/Acknowledge, Drill, and Reset remote switches,
and piezo.
ONLY ONE PER SYSTEM.

AFM-32AF

+ - + - + T
B
4

B+

T
B
2

A+ A-

B+

B-

T
B
1

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

OPTION
PRINTER
& UP/DOWN LOAD

T
B
5

B+

A+

B-

A-

T
B
6

J11

MS-9200
This configuration provides 32 Alarm LEDs,
On Line/Power LED, System Trouble LED,
and Local Silence/Acknowledge switch.
ONLY ONE PER SYSTEM

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

85

EIA-485
Power
+ - + - + T
B
4

B+

T
B
2

A+ A-

B+

B-

T
B
1

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

OPTION
PRINTER
& UP/DOWN LOAD

T
B
5

B+

A+

B-

A-

T
B
6

J11

FIRE ALARM ANNUNCIATOR

FIRE ALARM ANNUNCIATOR

FIRE ALARM ANNUNCIATOR

ALARM ZONE 1

ALARM ZONE 1

ALARM ZONE 1

ALARM ZONE 2

ALARM ZONE 2

MS-9200

ALARM ZONE 2

ALARM ZONE 3

ALARM ZONE 3

ALARM ZONE 3

ALARM ZONE 4

ALARM ZONE 4

ALARM ZONE 4

ALARM ZONE 5

ALARM ZONE 5

ALARM ZONE 5

ALARM ZONE 6

ALARM ZONE 6

ALARM ZONE 6

ALARM ZONE 7

ALARM ZONE 7

ALARM ZONE 7

ALARM ZONE 8

ALARM ZONE 8

ALARM ZONE 8

ALARM ZONE 9

ALARM ZONE 9

ALARM ZONE 9

ALARM ZONE 10

ALARM ZONE 10

ALARM ZONE 11

ALARM ZONE 11

ALARM ZONE 11

ALARM ZONE 12

ALARM ZONE 12

ALARM ZONE 12

ALARM ZONE 13

ALARM ZONE 13

ALARM ZONE 13

ALARM ZONE 14

ALARM ZONE 14

ALARM ZONE 14

ALARM ZONE 15

ALARM ZONE 15

ALARM ZONE 16

ALARM ZONE 16

SYSTEM TROUBLE

PRESS
TO
SILENCE

SYSTEM TROUBLE

PRESS
TO
SILENCE

ON LINE

ON LINE

AFM-16AF
Receive Only

AFM-16AF
Receive Only

ALARM ZONE 10

ALARM ZONE 15
ALARM ZONE 16
SYSTEM TROUBLE

PRESS
TO
SILENCE

ON LINE

AFM-16AF
Receive/
Transmit

The configuration shown above provides: 16 red Alarm LEDs, System Trouble LED, On Line/Power LED, Local
Silence/Acknowledge switch, and piezo. All AFM-16AF annunciators will show the same information.

86

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

56 Zone Annunciator Configuration

AFM-32AX

AEM-32AF

RIBBON
CABLE

+ - + - + T
B
4

B+

T
B
2

A+ A-

B+

B-

T
B
1

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

OPTION
PRINTER
& UP/DOWN LOAD

T
B
5

B+

A+

B-

A-

T
B
6

J11

MS-9200
Receive Only
No Control Switches

AFM-16ATX

AEM-16ATF

RIBBON
CABLE

NOTE: In this example, 56


zones are being annunciated
on the first two annunciators.
56 zones are annunciated on
the second four annunciators. The same 56 zones
are annunciated on the last
four annunciators (which
duplicate the previous set).

AEM-16ATF

AEM-16ATF

RIBBON
CABLE

RIBBON
CABLE

Receive Only
System Switches
Don't Function

AFM-16ATX

AEM-16ATF

RIBBON
CABLE

RIBBON
CABLE

AEM-16ATF

AEM-16ATF

RIBBON
CABLE

Receive/Transmit &
Control Switches

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

87

APPENDIX E: NFP
A STAND
ARD-SPECIFIC
NFPA
ANDARD
REQUIREMENTS
The Fire-Lite MS-9200 has been designed for use in commercial, industrial, and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this Appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
MS-9200 Control Panel containing the main control board, cabinet (backbox and door), main supply
transformer and power supply.
Batteries (refer to Appendix A for Standby Power Requirements).
Initiating Devices - connected to one of the control panel's Initiating Device Circuits.
Notification Appliances - connected to the control panel's Notification Appliance Circuit or via a control
module.
The following additional equipment is needed for compliance with the NFPA 72-1993 standards listed
below:
NFPA 72-1993 Fire Alarm Systems for Central Station Service (Protected Premises Unit) and Remote Station Service
MS-5012for connection to a compatible listed Central Station DACR or Protected Premises Receiving
Unit. This unit must be installed as outlined in Figure E-1.
OR
UDACT-F may be installed as illustrated in Section II.

NFPA 72-1993 Auxiliary Fire Alarm System


RTM-8F Relay-Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This
unit must be installed as outlined in Figure E-2.

NFPA 72-1993 Remote Station Fire Alarm System


RTM-8F Relay-Transmitter Module for connection to the Fire-Lite RS82 Remote Station Receiver. See
Figure E-3 for installation instructions for this unit

NFPA 72-1993 Proprietary Fire Alarm System


MS-9200 Alarm, Trouble and Supervisory contacts connected to Transmitter(s) . See Figure E-4 for
installation instructions for this unit.

88

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Figure E-1: NFPA Signaling Systems for Central Station Service (Protected Premises Unit)
This Figure illustrates use of an MS-5012. The UDACT-F may also be used. Refer to Section II for
information on installation.
Secondary
Phone Line
Primary
Phone Line

Modular Cable
P/N MCBL-6

Alarm

TB2

Secondary
Active

J2

Kissoff

J3

Trouble

Primary
Active

5
6
7
8

AC POWER

TROUBLE

ALARM

SUPERVISORY

Supervisory

9
10

RESET

11

MODE

SILENCE

12
13TB3
14

Red
yellow

Black

120 VAC
yellow

HOT

Neutral

12VDC
Battery
2-7AH

Black

Ground
White
Green

AC Wiring for DACT/FACP must


be connected to the same branch
circuit.
ELR = 2.2 KW (supplied with MS-5012)
+ - + - + T
B
4

B+

T
B
2

A+

A-

B+

B-

T
B
1

A+ A-

NO C NO NC C NO NC C

B-

T
B
3

OPTION
PRINTER
& UP/DOWN LOAD

T
B
5

B+

A+

B-

A-

T
B
6

J11

MS-9200

MS-5012

MS-9200

TB2-1

TB3-5

TB2-2

TB3-3

TB2-3

TB3-8

TB2-4

TB3-6

TB2-9

TB3-2

TB2-10

TB3-1

Alarm

Trouble

Supervisory

NOTES:
1) Reference the MS-5012 Manual for additional information.
2) Program the MS-5012 for slave application.
3) SW2 Trouble/No AC switch located on bottom right of MS-9200 main circuit board, must be positioned in the
down position for this application. This prevents the transmission of a trouble on the loss of AC power.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

89

Figure E-2: NFPA 72 Auxiliary Fire Alarm System


All connections are power limited and supervised. This application is not suitable for separate transmission
of sprinkler supervisory or trouble conditions.
NOTES:
1) 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2) Cut JP4 on MS-9200 System Board to supervise placement of RTM-8F Module and circuit.
MUNICIPAL BOX CONNECTED TO RTM-8F RELAY TRANSMITTER MODULE

Municipal Box
Circuit

Jumper JP2 must be in


position LE MUNCPL.
BOX for use in this
application

Gamewell
Model M34-56
Local Energy
Municipal Box

Nonpowerlimited
+
-

Polarities shown in
alarm condition
(Dummy load with a 1N4004 diode
when no connection is made)

Transmitter Output

Note: Refer to Figure 2.4 and Section 2.5.1 for information on UL Power-limited wiring requirements.

90

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Figure E-3: NFPA 72 Remote Station Protective Signaling System


Remote Station Connection Using RTM-8F Module
Note: Cut Jumper JP-4 on MS-9200 System Board to supervise placement of the RTM-8F module..

Fire-Lite RS82
Remote Station Receiver UL listed.
Refer to Fire-Lite Alarms, Inc., Instruction
Manual for Remote Station Receiver
Model RS-82.

Polarity
Shown is
Normal Standby

Cut
JP1
Jumper JP2 must be in position
ALARM/TROUBLE REVERSE
POLARITY for use in alarm and
trouble transmission or ALARM
ONLY for alarm transmission
only
JP2 Jumper Settings:

RTM-8F Relay
Transmitter
Module
(not suitable for
transmission of
separate alarm
and trouble
signals to
Remote Station)

Alarm/Trouble Polarity
Reversal Remote Station

Alarm only Polarity


Reversal Remote Station

Power-limited
+
-

Note: Refer to Figure 2.4 and Section 2.5.1 for information on UL Power-limited wiring requirements.
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

91

Figure E-4: NFPA 72 Proprietary Protective Signaling Systems

MS-9200 Addressable Fire Control Panel

TB3
MS-9200 Main Board
Form-C Alarm contact
programmed to activate
on General Alarm.
Form-C Trouble contact
which will automatically
activate on any Trouble
condition.

5
7

1
Form-A relay contact
programmed to activate
on Supervisory condition.

Notes:
1) Connection between MS-9200 and the
transmitter are supervised by the transmitter.
2) This MS-9200/Transmitter arrangement
can be employed for NFPA 72D Proprietary
Protective Signaling System.

92

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

APPENDIX F:

WIRE REQUIREMENTS

T-tapping of the SLC loop wiring is allowed for two wire (Style 4) configuations. The total resistance of any branch
cannot exceed 40 ohms. The total wire length of all combined branches cannot exceed 10,000 feet.
Connecting external system accessories to the MS-9200 main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, wire gauge, and wire run length per each MS-9200
circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200 circuit.
NOTE: If the SLC Loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders (such as MA/SS-24D) instead of more
electronically noisy notification appliances such as electromechanical bells or horns.

WIRE REQUIREMENTS

CIRCUIT CONNECTIONS

CIRCUIT TYPE

CIRCUIT FUNCTION

SLC Loop
(power-limited)

Connects to Addressable
Devices

RECOMMENDED
MA X DISTA NCE
(FEET)

WIRE GUAGE

Twisted, shielded pair, 40


ohms maximum per length
of Style 6 and 7 loops. 40
ohms per branch maximum
for Style 4 loops 1

10,000
8,000
4,875
3,225

12 AWG
14 AWG
16 AWG
18 AWG

Untwisted, unshielded pair1

1,000

12-18 AWG

WIRE TYPE A ND
L IMITATIONS

Si g n al 88202 Belden 9583


Si g n al 88402 Belden 9581
Si g n al 88602 Belden 9575
Si g n al 88802 Belden 9574

EIA-485
(power-limited

Connects to annunciator
modules

Twisted, shielded pair with a


characteristic impedance of
120 ohms

6,000

18 AWG

EIA-232
(power-limited)

PIM-24 output connects to


remote printer and PC computer

Twisted, shielded pair

50

18 AWG minimum

M300 and M301


(power-limited)

Initiating Device Circuit

Maximum loop wire


resistance is 40 ohms for
the M300 and 20 ohms for
the M301

2,500

12-18 AWG

M302
(power-limited)

Initiating Device Circuit

No more than a 2.4 volt


drop allowed at end of
circuit. Maximum loop wire
resistance is 25 ohms

2,500

12-18 AWG

C304
(power-limited)

Notification Appliance Circuit

In alarm, no more than a


1.2 volt drop allowed at end
of circuit

Distance limitation set


by 1.2 volt maximum
line drop

12-18 AWG

24 VDC Regulated
Resettable and
Nonresettable
(power-limited)

Connects to annunciators and


other accessories

No more than 1.2 volt drop


allowed from supply source
to end of any branch

Distance limitation set


by 1.2 volt maximum
line drop

12-18 AWG

24 VDC
Nonregulated
(power-limited)

Connects to C304 control


modules and accessories

No more than 1.2 volt drop


allowed from supply source
to end of any branch

Distance limitation set


by 1.2 volt maximum
line drop

12-18 AWG

R45-24E

Remote secondary power


source

12 AWG in conduit

20

12-18 AWG

WPW999
WPW995
WPW991
WPW975

When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.

Table F-1: 9200 Wire Specifications


Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

93

APPENDIX G: Compatib
le Surge Suppressors
Compatible
Surge supressors are protective devices which are designed to limit surge voltages due to power line fluctuations,
voltage transients or lightning. They can be placed on circuits to reduce the possibility of damage to sensitive
equipment due to unexpected voltage surges. Table G-1 lists the surge suppressors which have been tested with
the MS-9200 and have been found capable of reducing the risk of damage to the corresponding circuits due to
voltage fluctuations.

Surge Suppressors Compatible with FACP


Use the Following Models to Protect:
Manufacturer
SLC Loop

RS-232

RS-485

DLP-DS1
has 24V relay
F
orm-C contact,
Nor thern
p
Technologies, Inc. rotects one pair

DLP-DS1
has 24V relay
Form-C contact,
protects one pair

DLP-DS1
DLP-43
has 24V relay
protects one pair
Form-C contact,
protects one pair

DLP-42
protects two pair

DLP-42
protects two pair

DLP-42
protects two pair

FA 24
protects one pair

FA 24
FA 24
Not available
protects one pair protects one pair

FAS-1-033HC
protects one pair

PC642C-020
protects two pair

PC642C-008LC
protects two pair

FAS-1-060HC
protects one pair

FAS-2-033HC
protects two pair

PCB1B
protects two pair

PCB1B
protects two pair

FAS-2-060HC
protects two pair

Eclips

Edco

TER-030
protects one pair

TER-060
protects one pair

Table G-1: Surge Suppressors

94

Notification
Appliances

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

APPENDIX H: SCREEN OPTIONS FLO


WCHAR
T
FLOWCHAR
WCHART
(Software P/N 73750 or greater)
Trouble in System
No Device Installed
TRBL_# <type> <addr>
<adj> <noun> Z##

SYSTEM
NORMAL

(SYSTEM
TROUBLE)

(UNPROGRAMMED SYSTEM)

Trouble in System
Program Corrupted

Press 'ENTER'

1 = Programming
2 = Read Status
3 = AC/BAT

Write
Protect
Press '2'

Press '1'

Key Password, 'ENTER'

Press '3'
Battery: 24V
AC Line: 240V

Continued on Next Page

Press '11111'
Press 'ENTER'
1 = Disable 2 = Clr Hist
3 = Walk 4 = Time 5 = Chek

Press '1'
Disable/
Enable Point

Press '2'
Clear Event
File

Press '3'
Walk test

ENTER to Clear Hist


Disable/Enable
Press */#,AA,ENTER Backspace to Escape

Press '5'
Program
Check

Press '4'
Time

Walktest 1 = Silent Change Time/Date


Program Check OK
2 = Pulse Sounders 00:00A TUE 00/00/00 Retest Panel Now

Press '00000'
Press 'ENTER'
0 = Clr 1 = Auto
2 = Point 3 = Sys
4 = Pword 5 = Load

Press '0'
Press 'ENTER'

Press '2'
Press 'ENTER'

Press '1'
Press 'ENTER'

V=N I=N A=N P=N C=M


A/U=M L/P=N S=4 R=N

Autoprogram
Please Wait
ENTER to Clear Program
Backspace to Escape

Press '4'
Press 'ENTER'

Press '3'
Press 'ENTER'

Point Program Edit


Press *,/#,AA,ENTER

Document # 50428

Rev. B1

7/28/97

Press '5'
Press 'ENTER'

Connect Computer Now


Run Program From PC

*,NNNNN, E=Level 1 PW
#, NNNNN,E=Level 2 PW

P/N 50428:B1

95

Press '2'

Display Point = */#,AA


History = 1 Print = 2

Press *AA
Press 'ENTER'

Press #AA
Press 'ENTER'

EXAMPLE:
NORMAL MONITOR M01
Z##

EXAMPLE:
NORMAL SMOKE DET I01
Z##

Press **AA
Press 'ENTER'

Press **
Press 'ENTER'

Press *#AA
Press ENTER

EXAMPLE:
OFF SOFTWARE ZONE
Z##

V=N I=N A=N P=N C=M


A/U=M L/P=N S=4 R=N

EXAMPLE:
OFF BELL CKT
PANEL CIRCUIT

Press '1'
Press 'ENTER'

Program/Status Print

LEGEND
Text inside box actually
appears in LCD display
Text inside oval indicates
key press
Write
Protect
96

Write Protect Switch on


MS-9200 motherboard
Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Press '1'

Press '2'

EVENT HISTORY START


EVENTS IN HIST:XXXX

B01
Z##

Press '2'
Press 'ENTER'

History Print

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

97

98

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

Document # 50428

Rev. B1

7/28/97

P/N 50428:B1

99

Limited Warranty
Fire-Lite warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation
of Fire-Lite is to repair or replace, at its option, free of charge for parts and labor,
any part which is defective in materials or workmanship under normal use and service.
For products not under Fire-Lite manufacturing date-stamp control, the warranty is
eighteen (18) months from date of original purchase by Fire-Lite's distributor unless
the installation instructions or catalog sets forth a shorter period, in which case the
shorter period shall apply. This warranty is void if the product is altered, repaired or
serviced by anyone other than Fire-Lite or its authorized distributors or if there is a
failure to maintain the products and systems in which they operate in a proper and
workable manner. In case of defect, secure a Return Material Authorization form
from our customer service department. Return product, transportation prepaid, to
Fire-Lite, 12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by Fire-Lite with respect to its
products. Fire-Lite does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that Fire-Lite is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.
Fire-Lite GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL Fire-Lite BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
Fire-Lite PRODUCTS. FURTHERMORE, Fire-Lite SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF,
OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by FireLite. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
"Fire-Lite" is a registered trademark.

12 Clintonville Road, Northford, CT 06472


Phone: (203) 484-7161
FAX: (203) 484-7118

Technical Publishing

Document WARFBG-C.PM6 04/02/96

You might also like