MS9200 Technical Manual PDF
MS9200 Technical Manual PDF
Technical Man
ual
Manual
MS-9200
Addressab
le Fire Control P
anel
Addressable
Panel
(Expor
(Exportt Version)
DOCUMENT # 50428
7/28/97
REV:
Installation Precautions
- Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 721993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F and
at a relative humidity of 85% RH (non-condensing) at 30O C/86 O F. However, the
useful life of the system's standby batteries and the electronic components may
be adversely affected by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be installed in an
environment with a nominal room temperature of 15-27O C/60-80O F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
While installing a fire alarm system may make lower insurance rates
possible, it is not a substitute for fire insurance!
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Technical Publishing
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Document PRECAULG.PM6 12/31/96
Table of Contents
NFPA Standards
Underwriters Laboratories
I.
System Overview
1.0 Description
1.1 Features
1.2 Specifications
1.3 Controls and Indicators
1.4 Components
1.5 Optional Interface Modules
1.6 Accessories
7
7
7
8
9
10
13
14
II.
Installation
2.0 General
2.1 Cabinet Dimensions
2.2 Backbox Mounting
2.3 Power
Figure 2.1: DC Power Output Connections
2.4 Standard Relays
Figure 2.2: Relay Connections
2.5 Output Circuits
Figure 2.3: Circuit Connections
2.6 UL Power-limited Wiring Requirements
Figure 2.4: Typical Wiring Diagram for UL Power-limiting
2.6.1 RTM-8F Wiring
2.7 Wiring the Signaling Line Circuit
Table 2.1: Communications Loop Performance
Figure 2.5: Style 4: T-tapping Restrictions and Branch Resistance
Figure 2.6: Style 6 Wiring
Figure 2.7: Two Wire Communications Loop (Supervised & Power-limited)
Figure 2.8: Four Wire Communications Loop (Supervised & Power-limited)
Figure 2.9: Four Wire Communications Loop
Figure 2.10: Shield Termination in No Conduit
Figure 2.11: Shield Termination in Full Conduit
Figure 2.12: Shield Termination in Partial Conduit
2.8 The Isolator Module
Figure 2.13: Isolating Two Wire Communications Loops
2.9 Module Addressing
2.10 M300 Monitor Module
2.11 M301 Monitor Module
2.12 M302 Monitor Module
Figure 2.14: NFPA Style B Initiating Device Circuit (M300)
Figure 2.15: NFPA Style D Initiating Device Circuit (M300)
Figure 2.16: NFPA Style B Initiating Device Circuit (M302)
Figure 2.17: NFPA Style D Initiating Device Circuit (M302)
2.13 The Control Module
Figure 2.18: The C304 Control Module (Alarm polarity shown)
Figure 2.19: The C304 Control Module (Form-C Relay)
Figure 2.20: NFPA Style Y Notification Appliance Circuit
2.14 The Addressable Manual Pull Station
Figure 2.21: Wiring Addressable Manual Pull Stations
2.15 Wiring Detectors
Figure 2.22: Wiring the Detector with Removable Plug-in Connector
2.16 Optional Modules
Figure 2.23: Optional Module Location
Figure 2.24: ABS-8RF
Figure 2.25: UDACT-F Mounting to MS-9200
Figure 2.26: External UDACT-F Mounting in ABS-8RF
Figure 2.27: ACM-8RF Relay Control Module
Figure 2.27: RTM-8F Option Module Installation
Figure 2.28: RTM-8F Relay Transmitter Module
2.17 Printer/PC Interface Module
Figure 2.29: Remote Printer and Computer Connections
19
19
19
20
21
21
22
22
22
22
23
23
23
24
24
25
25
26
27
28
29
29
29
30
30
30
31
31
32
33
34
35
36
37
37
38
39
40
40
41
41
42
42
43
43
44
45
46
47
48
48
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Table of Contents
4
III.
Programming/Read Status
3.0 Initial Power-up
3.1 Programming
3.2 Program Change - Level One
3.2.01 Clear
3.2.02 Autoprogram
3.2.03 Point Edit
3.2.04 System Edit
3.2.05 Password Change
3.2.06 Load
3.3 Program Change - Level Two
3.3.01 Disable
3.3.02 Clear History
3.3.03 Walk Test
3.3.04 Set Time/Date
3.3.05 Check
49
50
51
52
52
52
56
57
58
59
59
60
60
61
62
62
IV.
Operating Instructions
Figure 4.1: The MS-9200 Membrane Switch Panel
4.0 Control Switches
4.1 LED Indicators
4.2 Normal Operation
4.3 Trouble Operation
4.4 Alarm Operation
4.5 Supervisory Operation
4.6 Notification Appliance Circuit (NAC) Operation
4.7 Control-By-Event Operation
4.8 Detector Functions
4.9 Time Functions
4.10 Coder Operation - Notification Appliance (Bell) Circuit 1 Only
4.11 Presignal
4.12 Special System Timers
4.13 Style 6 Operation
4.14 Read Status
63
63
63
64
64
65
66
67
68
68
68
68
68
69
69
70
70
Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
Appendix F
Appendix G
Appendix H
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
72
76
83
84
88
93
94
95
THE MS-9200 COMPLIES WITH THE FOLLOWING NFPA 72-1993 NATIONAL FIRE ALARM CODE
STANDARDS:
Central Station Fire Alarm Systems (Automatic, Manual, and Waterflow) Protected Premises Unit
(requires UDACT-F).
Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems (requires RTM-8F).
Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems (Requires RTM-8F or
UDACT-F).
Proprietary (Automatic, Manual, and Waterflow) Fire Alarm Systems (Protected Premises Unit).
Automatic Fire Detectors.
Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems.
Testing Procedures for Fire Alarm Systems.
IN ADDITION TO THE ABOVE, THE INSTALLER SHOULD BE FAMILIAR WITH THE FOLLOWING
DOCUMENTS AND STANDARDS:
Underwriters Laboratories:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1971 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
UNDERWRITERS LABORATORIES OF CANADA (ULC) LISTED
Standard CAN/ULC-S527-M87
OTHER:
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
FIRE-LITE DOCUMENTS AND MANUALS RELATING TO THE MS-9200:
Fire-Lite Device Compatibility Document
Document# 15384
Annunciator Modules
Document# 15390
AFM-16ATF and AFM-32AF Annunciators
Document# 15970
AFM-16AF Annunciator
Document# 15210
MS-5012 Communicator
Document# 15465
MS-9200 Off Line Programming Utility
Document# 15677
UDACT-F Universal Digital Alarm
Communicator Transmitter
Document# 50049
FCPS-24FE Field Charger/Power Supply
Document# 50079
LDM Series Lamp Driver Modules
Document# 50055
LCD-40 Remote Fire Annunciator
Document# 50327
ACM-8RF Relay Control Module
Document# 50362
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
I SYSTEM OVERVIEW
1.0 Description
The FireLite MS-9200 is a compact, cost effective, addressable Fire Alarm Control Panel (FACP) with an
extensive list of powerful features. The combination of FireLite's 300 Series Addressable Devices and the MS9200 Fire Alarm Control Panel offers the latest in Fire Protection Technology. The power supply and all electronics are contained on a single circuit board housed in an attractive metal cabinet, providing a complete fire control
system for most applications. Optional modules, which plug into the main board, are available for special functions. Accessories available include LED, graphic and LCD annunciators, digital communicator, local downloading software and remote power expansion.
1.1 Features
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1.2 Specifications
AC POWER - TB8
240 VAC, 50 Hz, 1.2 amps
Wire size: minimum #14 AWG with 600V insulation
BATTERY (LEAD ACID ONLY) - J3
Maximum Charging Circuit:
Normal Flat Charge27.6V @ .8 amp.
Maximum Battery Capacity:
17 AH.
1) Up to 7 AH batteries can be housed in the MS-9200 enclosure.
2) 12 to 17 AH batteries require the FireLite BB-17F or similar UL
listed battery cabinet.
3) 20 to 55 AH batteries require the FireLite R45-24E charger for
housing and charging the batteries.
COMMUNICATION LOOP - TB6
15 VDC nominal, 27.6 volts DC max. Maximum length is 10,000 ft. total twisted pair length. Maximum loop
current is 250mA (Max short circuit) or 100 mA (normal). Maximum loop resistance is 40 ohms. SLC is
supervised and power-limited.
Note: The Communication Loop may leave the protected premises provided an approved surge suppressor
is use (refer to Table G-1 in Appendix).
NOTIFICATION APPLIANCE CIRCUITS - TB1 & TB2
Non-regulated special purpose power
Power-limited circuitry
Maximum Voltage Drop in wiring: 2.0V
Operating Voltage Range: 18V to 30V
Current for all external devices: 3.0 amperes expandable to 6.0 amperes2.
Current Limit: Fuseless, electronic, power-limiting circuitry.
Max. signaling current/circuit: 2.50 amps
End-of-line resistor: 4.7KW , 1/2-Watt (part # 71252 UL listed) for Notification Appliance Circuits
ALARM, TROUBLE, AND SUPERVISORY RELAYS - TB3
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Alarm and Trouble: Form-C
Supervisory: Form-A
Refer to Figure 2.2 for information on power-limited wiring for relay circuits.
FOUR-WIRE SMOKE DETECTOR POWER (24VDC nominal
nominal)) - TB4 TERMINALS 5 (+) & 6 (-)
Max. ripple voltage: 10 mVRMS
Max. standby current: 50 mA
Up to 300 mA is available for powering 4-wire smoke detectors 1, 2, 3.
Power-limited circuit
NONRESETTABLE REGULATED 24V POWER (24VDC nominal
)TB4 TERMINALS 3 (+) & 4 (-)
nominal)TB4
Max. ripple voltage: 10 mVRMS
Max. standby current: 150 mA
Total DC current available from this output is up to 300 mA 1, 2, 3
Power-limited circuit
NON-REGULATED SPECIAL PURPOSE 24V POWERTB4 TERMINALS 1 (+) & 2 (-)
Operating voltage range: 18V to 30V
Total DC current available for powering external devices is 2.5 amps 2
This power is not recommended for AFM, LDM or LCD-40 annunciators
Power-limited circuit
NOTES:
1. For power supply calculations, refer to Appendix A.
2. Total current for special purpose power, nonresettable power, four-wire smoke power, and two
Notification Appliance Circuits must not exceed 6.0 amperes. Total external system current in
excess of 3.6 amperes requires XRM-24E Transformer and 12AH or 17AH batteries, not 7.0 AH.
3. Total current for resettable 4-wire smoke power and non-resettable power must not exceed 600mA.
8
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1.3
LCD DISPLAY
The MS-9200 uses a 40 character (2 lines X 20
characters), high viewing angle, LCD display, with a
character height of 3/16". The display includes a
long-life LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the LED
backlight will turn off to conserve power.
LED INDICATORS
AC POWER (green)
FIRE ALARM (red)
SUPERVISORY (yellow)
ALARM SILENCE (yellow)
SYSTEM TROUBLE (yellow)
MEMBRANE PANEL
Mounted on the system board, the membrane switch panel includes a window for the LCD display and 5
system status LEDs. The membrane panel, which is visible with the cabinet door closed, has 21 keys,
including a 12 key alphanumeric pad, similar to a telephone keypad.
Function switches:
ACKNOWLEDGE/STEP
ALARM SILENCE
DRILL
SYSTEM RESET (lamp test)
Service/program switches:
Keypad with twelve Keys labeled 1-9
(Detector) Key
#(Module) Key
0(Recall) Key
Four cursor Keys (UP, DOWN, RIGHT, LEFT)
ENTER Key
LOCAL SOUNDER
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1.4
Components
CABINET
The MS-9200 cabinet is red with an attractive navy blue front overlay. The
backbox measures 15" x 14.5" x 2.625" and provides space for two batteries
(up to 7 amp-hours). Ample knockouts are provided for system wiring. Also
available is an optional dress panel, DP-9200, which mounts to the inside of
the cabinet (required and included on the ULC version). The dress panel
must be installed to meet FM requirements (refer to Section 1.6).
Standard
TRANSFORMER ASSEMBLY
One 100VA transformer is provided standard
with the panel. (3.6 Amps max.)
An optional 100VA transformer (XRM-24E) is available to
provide maximum accessory power. (6.6 Amps max.)
Field Option
XRM-24E
BATTERIES
The MS-9200 cabinet provides space for two 7 Amp-Hour (AH) batteries. 12AH to 17AH batteries require use of the FireLite BB-17F or
similar UL listed battery cabinet. 20 to 55 AH batteries can also be
connected to the system, however, a FireLite R45-24E charger is
necessary for housing and charging these batteries. Batteries must be
ordered separately.
10
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
15 - 28 Volts DC Peak
Diameter:
5.0 inches (12.7 cm)
150uA @ 24 VDC
Height:
3.0 inches (7.6 cm)
7mA @ 24 VDC (latched 'ON')
Temperature: 0o to 49o C (32o to 120o F)
40 ohms Maximum
Rel. Humidity: 10% - 93% Non-condensing
CP300 = 1,500 Ft/Minute (7.6m/S) Max. SD300 = 3,000 Ft/Minute (15 m/S) Max.
SD300, SD300T
The SD300 is an Addressable Photoelectric Smoke Detector which provides smoke
sensing utilizing optical sense technology. The detector sends a unique 'type' code to aid the
automatic programming feature in the control panel. The SD300T includes a 135o F fixed
thermal sensor.
CP300
The CP300 is an Addressable Ionization Smoke Detector which measures the level of
combustion products in its chamber using the 'ionization principle'. The detector sends a
unique 'type' code to aid the automatic programming feature in the control panel.
RA400Z
The RA400Z is a Remote Single LED Annunciator that can be wired directly to an addressable
detector for annunciation of that detector's alarm status.
7
1
9
8
0
2
Address
2
6
Loop
7
3
M302
M301
The M302 is an Addressable Monitor Module that can be used to interface and monitor
conventional 2-wire smoke detectors. All 2-wire detectors being monitored must be UL
compatible with the module (refer to the FireLite Compatibility Document). The supervised circuit can be wired
NFPA Style B or D. The M302 modules can be tested with a test magnet available from FireLite (P/N M02-04-00).
Separate regulated switched 24 VDC power is required. The module mounts to a 4-inch square electrical box with a
minimum depth of 2-1/8".
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
11
7
1
8
0
7
1
C304
The C304 is an Addressable Control Module that can be used as a Notification Appliance
or Speaker Circuit for powering and supervising compatible, UL listed Notification Appliances. The module's supervised circuit can be wired NFPA Style W, X, Y or Z. A 47 K
ELR is provided. By breaking two built-in tabs, the C304 can be employed as a Form-C
control relay. The module mounts to a 4-inch square electrical box with a minimum depth
of 2-1/8".
BG-10LX
The BG-10LX is an Addressable Manual Pull Station featuring a key-lock reset. The pull
station responds to an address set by the installer using the built-in rotary decimal
switches on the pull station. The Manual Pull Station includes a FireLite key.
I300
The Loop Isolator Module (I300) is an automatic switch which opens the circuit voltage
to the SLC Loop branch(es) whenever a wire-to-wire short circuit is detected on that loop.
The remainder of the Communications Loop leading up to the I300 will continue to operate, unaffected by the short. The isolator module has four terminal connections, allowing
input and output SLC connections. The isolator is bi-directional, meaning that it can
detect a fault condition between the input SLC terminals, or output SLC terminals. The
I300 is required to meet NFPA Style 7 requirements.
A UL listed End-Of-Line Power Supervision Relay is used to supervise the power to 4wire smoke detectors and Notification Appliances.
N-ELR
The N-ELR is a single End-of-Line Resistor plate which is required for use in Canada.
An ELR, which is supplied with each module and fire alarm control panel, must be
mounted to the plate. Resistors mounted to the N-ELR plate can be used for the supervision of an M300 and M301 Monitor Module and C304 Control Module circuit.
12
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
13
1.6 Accessories
595a-26044
DRESS PANEL
A red dead-front dress panel (DP-9200) is
available as an option (required for Canadian
installations). The dress panel restricts
access to the system wiring while allowing
access to the membrane switch panel.
BATTERY BOX
The BB-17F battery box may be used to house
two 12AH or 17AH batteries. The battery box
mounts directly below the MS-9200 cabinet.
The box is red in color and is provided with
knockouts.
14
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
+ - + - + -
T B+A+A-B- T B+A+A-BB 1 2 3 4
B 1 2 3 4
1
2
T
B
3
NO C NO NC C NO NC C
OPTION
PRINTER
& UP/DOWN LOAD
J11
T
B
5
T
B
6
B+ A+ B- A-
4
-
+ -
R45-24E
+
PS-12550
12 VDC
55-AH
Battery
+
PS-12550
12 VDC
55-AH
Battery
-+
Note: Apply primary AC power to MS-9200 via standard transformer or with additional option transformer XRM-24E.
See Appendix A.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
15
THE AFM-32AX
The Annunciator Fixed Module-32AX
contains 32 red alarm LEDs, a system
trouble LED, an ON LINE/POWER LED,
and a local piezo sounder with a local
Silence/Acknowledge switch. The AFM32AX is fixed at address 1, and will
accept one AEM-32AF expander.
AEM-16ATF
The Annunciator Expander Module16ATF connects to the AFM-16ATX and
adds 16 sets of red alarm LEDs and yellow trouble
LEDs. Three AEM-16ATFs may be added to an AFM16ATX.
AFM-16ATF
The Annunciator Fixed
Module-16ATF contains 16 red
alarm and 16 yellow trouble LEDs, a
system trouble LED, an ON LINE/
POWER LED, and a local piezo
sounder with switches for MS-9200
ACKNOWLEDGE, SILENCE,
RESET, and DRILL. The AFM16ATF is fixed at address '1' and
communication is via the EIA-485
data line.
16
AEM-32AF
The Annunciator Expander Module-32AF
connects to the AFM-32AX and adds 32
red alarm LEDs. The AEM-32AF is
identical in frontal appearance to the AFM32AX. Only one expander module is allowed.
AFM-16AF
The Annunciator Fixed Module-16AF
has 16 red alarm LEDs. Multiple
annunciators may be used by setting
all annunciators to Receive Only,
except the last AFM-16AF in line.
Each annunciator's address is internally fixed
at '1', and communication is via the EIA-485
data line. The Local Silence/Acknowledge
switch functions as local lamp test and silence
for annunciator piezo. LEDs include On
Line and System Trouble indicators.
ALARM ZONE 1
ALARM ZONE 2
ALARM ZONE 3
ALARM ZONE 4
ALARM ZONE 5
ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 8
ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 12
ALARM ZONE 13
ALARM ZONE 14
ALARM ZONE 15
ALARM ZONE 16
SYSTEM TROUBLE
PRESS
TO
SILENCE
ON LINE
AFM-32AF
The AFM-32AF is similar to the AFM-16AF except it has 32
red alarm LEDs for annunciating up to 32 points.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
The LDM-32F
The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs which sink current
to system common (-) on activation. A single positive (+) voltage is required to supply total
operating power for all lamps or LEDs when all drivers are activated. The LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 external control switches may be wired to the LDM-32F. DIP switch SW3 is used
to enable or disable the onboard piezo, enable remote switch functions, select a flashing
LED function for new alarms and troubles, and other functions. Switch SW4 is used to
configure the module to annunciate 32 alarms or 16 alarms and 16 troubles. A green ONLINE LED flashes to indicate ongoing communications with the host FACP. One LDM-32F
supports up to 3 LDM-E32F modules. The LDM-32F is supplied with 4 standoffs and screws
for mounting to a CHS-4L chassis or custom backbox.
The LDM-E32F
Each LDM-E32F expander module provides 32 additional lamp/LED driver outputs from J5,
J6, J7 and J8. The expander module has a slide switch, SW4, for selecting alarm or alarm
and trouble annunciation and an input for a local lamp test switch. In alarm mode, use only
one LDM-32F and one LDM-E32F for a maximum of 56 alarm indicators and 8 system status
indicators. In alarm/trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of
56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control switch
inputs. Multiple sets of LDM-32s with LDM-E32F expanders increase the system annunciation capabilities beyond 56 zones or points. This is possible by various settings of address
switches SW1 and SW2 on the LDM-32F (refer to Appendices). Each LDM-E32F is supplied
with a 26-conductor expander ribbon cable, 4 standoffs and 4 screws.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
17
Accessories: System Power Expansion - FCPS-24FE Remote Field Charger Power Supply
The FCPS-24FE is a compact, remote power supply with battery charger. This remote power supply consists of a
filtered 24 VDC output that may be configured to drive up to four Notification Appliance Circuits [four Style Y (Class
B) or two Style Z (Class A) and two Style Y (Class B)]. Alternately, the four Notification Appliance Circuits may be
used as auxiliary regulated power configured for resettable or nonresettable operation.
The FCPS-24FE may be used in a number of different applications. It may be used as a remotely-mounted power
supply and battery charger powering up to four, coded or non-coded, Notification Appliance Circuits. Alternately, any
or all of these circuits may be used as 24 VDC output circuits capable of powering four-wire smoke detectors or any
device that requires filtered power. These circuits may be configured as resettable or nonresettable outputs to
expand FACP auxiliary system power.
Style Y/Style Z
Notification
Appliance Circuit or
24 VDC Output #1
Notification
Appliance Circuit
Control Input #1
(from FACP)
Style Y Notification
Appliance Circuit or
24 VDC Output #2
Style Y/Style Z
Notification Appliance
Circuit or 24 VDC
Output #3
Notification
Appliance Circuit
Control Input #2
(from FACP)
Style Y Notification
Appliance Circuit or
24 VDC Output #4
Battery Charger
AC Power
Specific
FCPS Trouble
Application Contact Output
Power
One of the most common applications for the FCPS-24FE remote power supply utilizes the NAC expander mode. In
this application, one or two Notification Appliance Circuits (NACs) are connected from the main FACP NAC output(s)
to the remote power supply Control Input circuits. When these Control Input circuits activate (due to reverse polarity
of the NAC output), the power supply will activate its corresponding outputs. NAC Control Input #1 controls power
supply output circuits #1 and #2. NAC Control Input #2 controls output circuits #3 and #4.
During the inactive state, the remote power supply supervises its NAC field wiring for short and open circuits. If a
fault is detected, the supply will enter a trouble condition and illuminate the corresponding NAC trouble LED (Output
Circuits 1-4). However, once the Notification Appliance Circuits are activated, the supervision is disabled and the
circuits are no longer supervised. Supervision of other power supply faults such as low battery, Earth Fault, AC loss
and battery charger failure will continue and may be monitored via the independent trouble relay contact.
If a specific application requires that all four outputs activate at the same time, only one NAC control input from the
FACP is necessary. For this application, the Notification Appliance Circuit from the FACP is wired into NAC Control
Input #1 of the remote supply and then a pair of wires are connected from NAC Control Output #1 to NAC Control
Input #2. Refer to the FCPS-24FE Installation, Operation and Application Manual for a complete description and
examples of applications.
A C304 Control Module, which can be located up to 10,000 feet from the FACP, may be used to activate the FCPS
power supply. The Control Module can be powered from the FCPS auxiliary 24 VDC power output (TB3 Terminals 8
& 9) and supervised by an EOL relay.
18
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
II INST
ALLA
TION
NSTALLA
ALLATION
2.0 General
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free
area where extreme temperatures are not encountered. The area should be readily accessible with sufficient
room to easily install and maintain the panel. Locate the top of the cabinet approximately five feet above the
floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be
installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and
pull the required conductors into the box. All wiring should be in accordance with the National and/or Local
codes for fire alarm systems.
To remove entire
knockout, strike here.
To remove inner
knockout, strike here.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
19
2.2 Bac
kbo
x Mounting
Backbo
kbox
1)
2)
3)
4)
5)
6)
7)
Remove the main PC board assembly by unscrewing the four screws in the corners of
the board. Two standoffs support the board in the center. Set the board aside in a safe, clean
place. Avoid static discharge which may damage the board.
Mark and predrill holes for the top two keyhole mounting bolts using the dimensions shown.
Install two upper fasteners in the wall with the screw heads protruding.
Using the upper 'keyholes', mount the backbox over the two screws.
Mark and drill the lower two holes.
Complete backbox mounting by installing the remaining fasteners. Tighten all screws.
When the location is dry and free of construction dust, reinstall the main PC board.
20
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
2.3 P
o w er
Po
CAUTION: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables while this unit is energized.
- +
BATTERY POWER
Observe polarity when connecting the battery. Connect the battery cable to J3 on the MS-9200 main circuit board
using the plug-in connector provided. See Appendix A for calculation of the correct battery rating. CAUTION:
Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. If
contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
Power-limited
Nonresettable Power
300 mA, 24 VDC filtered, regulated,
non-resettable power can be drawn
from TB4 Terminals 3 (+) and 4 (-).
Document # 50428
Rev. B1
7/28/97
Power-limited
Resettable Power
300 mA, 24 VDC filtered,
regulated, resettable power can be
obtained from TB4 Terminals 5 (+)
and 6 (-).
P/N 50428:B1
21
ALARM
TROUBLE
N O C NO NC C NO NC C
T
B
3
Power
Limited
Power
Limited
Polarized Strobe
Polarized Horn
Note: Notification
Appliance Circuit
polarity shown in
alarm state.
B+
T
B
2
22
A+
A- B-
B+
A+
T
B
1
Document # 50428
A- B-
Polarized Bell
Polarized Horn
Polarized Horn
Dummy Load
all unused
Circuits
Rev. B1
7/28/97
P/N 50428:B1
2.6 UL P
o w er-limited Wir
ing Requirements
Po
Wiring
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring
must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A
typical wiring diagram for the MS-9200 is shown below.
Nonpower-limited Circuits
Power-limited Circuits
Power-limited Circuits
Nonpower-limited Circuits
AC Power
Note: Output is
nonpower-limited
only if programmed
as municipal box
output.
2.6.1 RTM-8F Wiring
Nonpower-limited and power-limited wiring must have a minimum
distance of 0.25" wire to wire. If this module is used to drive
nonpower-limited and power-limited circuits, follow the instructions below:
1. Skip a set of dry contacts to maintain the 0.25" required space
between power-limited and nonpower-limited circuits.
2. If this module is needed to drive power-limited and nonpowerlimited relays that are next to each other, make no connection
to the Normally Open contact which separates the two groups
of relays. Refer to the typical wiring diagram to the right.
Power-limited circuits
No connection
Nonpower-limited circuits
Rev. B1
7/28/97
P/N 50428:B1
23
2.7 Wir
ing the Signaling Line Circuit
Wiring
The MS-9200 communicates with addressable initiating, monitor and control devices through a Signaling
Line Circuit (SLC) Loop. This SLC loop can be wired to meet the requirements of NFPA Style 4 (see
Figure 2.7), Style 6 (see Figure 2.8) or Style 7 (see Figure 2.9). Surge protection for the SLC Loop may be
provided by using one of the compatible surge suppressors listed in Table G-1 of the Appendix. The SLC
Loop is allowed to leave the building only with use of an approved surge suppressor (refer to Table G-1).
Be certain to change the decade wheels on all detectors and modules from the factory '00' settings.
ISOLATOR MODULES
Isolator Modules permit a zone of detectors and modules to be electrically 'isolated' from the remainder of
the Communications Loop, allowing critical loop components to function in the event of a short circuit on
the SLC Loop wiring (see Figures 2.7, 2.8 and 2.9). These are required to meet the requirements of NFPA
Style 7.
MONITOR MODULES
Addressable Monitor Modules allow the control panel to monitor entire circuits of conventional normallyopen contacts, alarm initiating devices, manual pull stations, 4-wire smoke detectors, heat detectors,
waterflow, supervisory devices (see Figures 2.14 and 2.15) and conventional detectors (see Figures 2.16
and 2.17). The BG-10LX is an addressable manual pull station which contains a miniature monitor module
providing point annunciation (see Figures 2.7, 2.8 and 2.21).
CONTROL MODULES
Through addressable Control Modules, the control panel can selectively activate Notification Appliance
Circuits or Form-C output relays (see Figures 2.18 through 2.20).
ADDRESSABLE DETECTORS
Through the Communications Loop, the MS-9200 communicates with addressable ionization, photoelectric,
and photoelectric/thermal detectors (see Figure 2.22).
DEVICE CAPACITY
The capacity of each MS-9200 includes up to 99 addressable detectors, and an additional combination of
up to 99 addressable pull stations, control modules and monitor modules. In addition, the panel supports 2
Notification Appliance (Bell) Circuits.
Note: Refer to Appendix A and the installation drawings supplied with each loop device for rating and
specification information.
Single
Ground on
Loop
Shorted
Loop
Loop
Shorted
and
Opened
Loop
Shorted
and
Grounded
Loop
Opened
and
Grounded
Communication
Loss
Notes:
1. Trouble indicates a trouble
signal will be generated at the
control panel during the abnormal
condition.
Trouble
Alarm
Capability
Trouble 2
Trouble
Trouble
Trouble
Trouble
Trouble
Alarm
Capability
Trouble
Trouble
Trouble
Trouble
Alarm
Capability
Trouble
Trouble
24
Alarm
Capability
Trouble
Alarm
Capability
Trouble
Trouble
Alarm
Capability
Trouble
Alarm
Capability
Trouble
Document # 50428
Rev. B1
Trouble
7/28/97
P/N 50428:B1
Branch
E
Branch
D
Branch
B
Branch
Branch
C
Loop
Out
Branch
For each loop:
A
Add the lengths of all the branches
on one loop. This sum cannot
exceed 10,000 feet (12AWG
twisted, shielded).
+
+
+
+
=
Branch Resistance
With power removed, short the termination
point of one branch at a time and measure
DC resistance from the beginning of the
loop to the end of that particular branch.
The total DC resistance from panel to
each branch end cannot exceed 40 ohms.
Repeat this procedure for all remaining
branches.
(Branch A)
(Branch B)
(Branch C)
(Branch D)
(Branch E)
10,000 feet or less
No T-Tapping allowed
Loop Out
Return Loop
B+ and B- = Output Loop
A+ and A- = Return Loop
Loop Out
Loop Return
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
25
BG-10LX
- +
4
7
1
8
0
3
2
SD300
C304
M300
Separate T-Tap
to other Loop
devices
I300
Note: I300 devices
not required to meet
NFPA Style 4.
I300
26
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
BG-10LX
7
1
8
0
7
1
8
0
SD300
C304
M300
I300
I300
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
27
I300
Isolator Module
I300
Isolator Module
Protected Premises
Zone '02"'
3
2
SD300
Protected
Premises
Zone '03'
Protected
Premises
Zone '01'
BG-10LX
CP300
4
I300
Isolator Module
I300
Isolator Module
2
Operation
By 'flanking' each communications loop device with a pair of I300 Fault Isolator Modules, each device is
protected from short circuit faults that may occur on other devices. For example, a fault on Zone 02 will not
affect Zones 01 and 03. The isolator modules on either side of Zone 02 will open the Loop. Zone 01 will still
operate from power on Loop Out and Zone 03 will operate from Loop Return. Since the MS-9200 will no
longer be able to communicate with Zone 02, a trouble signal(s) will be generated for that device.
No TTapping or branching is allowed on this circuit. The ratings and characteristics are the same as for a
four-wire circuit meeting NFPA Style 6 requirements.
28
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
SLC Loop +
SLC Loop -
SLC Loop +
SLC Loop -
Shield
MS-9200
Cabinet
Nonshielded Wire
SLC Loop +
SLC Loop -
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
29
Communications
Loop In
I300
I300
Branch B
Branch A
3
2
7
1
8
0
30
Document # 50428
7
1
8
0
Rev. B1
7/28/97
P/N 50428:B1
IDC (-)
(Yellow)
IDC (+)
(Violet)
Loop (+)
(Red)
Loop ( - )
(Black)
Rev. B1
7/28/97
P/N 50428:B1
31
Status LED
4
3
2
7
1
8
0
32
Document # 50428
Rotary Decade
Address Switches
7
1
8
0
Rev. B1
7/28/97
P/N 50428:B1
Figure 2.14: NFPA Style B Initiating Device Circuit (Utilizing M300 Monitor Module)
Supervised and Power-limited
End-of-Line Resisto
Resistor
47KW , 1/2-watt
(N-ELR in Canada)
24 VDC Four-Wire
Smoke Detector
Manual
Pull Station
To Next Device
on Loop
+
Heat Detector
Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)
M300
MS-9200
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Loop Out
33
Figure 2.15: NFPA Style D Initiating Device Circuit (Utilizing M300 Monitor Module)
Supervised and Power-limited
UL listed Power Supervision Relay
(Must be wired as last device on
loop as shown).
24 VDC
Four-Wire
Smoke
Detector
Manual
Pull
Station
To Next Device
on Loop
+
Heat
Detector
See note
Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)
M300
MS-9200
34
Document # 50428
Rev. B1
7/28/97
Loop Out
P/N 50428:B1
Figure 2.16: NFPA Style B Initiating Device Circuit (Utilizing M302 Monitor Module)
Supervised and Power-limited
End-of-Line Resisto
Resistor
3.9K (included)
UL listed Compatible
Smoke Detector
UL listed Compatible
Smoke Detector
To Next Device
on Loop
+
-
UL listed Compatible
Smoke Detector
+
+
Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)
M302
MS-9200
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Loop Out
35
Figure 2.17: NFPA Style D Initiating Device Circuit (Utilizing M302 Monitor Module)
Supervised and Power-limited
UL listed Compatible
Smoke Detector
UL listed Compatible
Smoke Detector
To Next Device
on Loop
Resistor
End-of-Line Resisto
+
3.9K (included)
UL listed Compatible
Smoke Detector
Resettable 24 VDC
four-wire smoke
detector power
(300 mA max.)
M302
36
Loop Out
MS-9200
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
C304
Note: When wiring Style Z, do not install an ELR since one is built into the C304 Control Module.
TEST SWITCH
The C304 Control Module includes a magnetic test switch sensor located near the center front of the
module. Activation of this switch by test magnet P/N M02-04-00 will cause a short circuit indication for the
Style W/X/Y/Z circuit connected to the module.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
37
+ To next Device
- on Loop
CAUTION! Do not loop
wiring under any terminals.
Break wire run to maintain
supervision.
C304
MS-9200
A
T
B
6
B B+
2
A+
B-
A-
Common Contact
Normally-Closed Contact
Break-off Tabs
Normally-Open
Contact
BREAK TABS
To configure a C304 as a Form-C relay, the two break-off tabs shown must be broken off of the module. Use
a pair of needle-nose pliers to break off each tab.
Caution: Failure to break tabs when configuring for Form-C Relay operation can cause damage to the C304
module.
COMMUNICATIONS LOOP CONNECTIONS
Connect the MS-9200 Communications SLC Loop to C304 Terminals 1(-) and 2(+). The C304 occupies one
module address on the Loop. Set the rotary switches on the module to the particular Loop address required.
CONTACT CONNECTIONS
Wire the common and the normally-open or normally-closed contacts to the module as needed.
CONTACT RATINGS
Resistive: 2 Amps @ 30 VDC*
Inductive: 1 Amp @ 30 VDC (0.6 PF)
Pilot Duty: 0.6 Amps @30 VDC (0.35 PF)
0.3 Amps @ 110 VDC (0.35 PF)
0.3 Amps @ 120 VAC (0.35 PF)
*Certain electromechanical devices exhibit inductive loading characteristics. For these types of devices, derate the outputs to
1 Amp. Refer to the Device Compatibility document for load characteristics by device.
38
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Figure 2.20: NFPA Style Y Notification Appliance Circuit (Utilizing C304 Module)
All circuits are supervised and power-limited
24VDC
Notification Appliance
(See Fire-Lite Compatibility
Document for compatible devices)
To Next Device
on Loop
+
C304
Loop Out
MS-9200
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
39
2.14
The Addressab
le Man
ual Pull Station
Addressable
Manual
The BG-10LX is an addressable manual pull station with a FireLite key-lock reset feature.
BG-10LX INSTALLATION
1) Connect the MS-9200 Communications SLC Loop to terminal screws (+) and (-) on the BG-10LX.
2.) The BG-10LX is factory preset with address 00. Set the address for the pull station by using a
screwdriver to turn the rotary address switches on the back of the unit to the appropriate settings.
40
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
2.15
Wir
ing Detectors
Wiring
INSTALLATION
Connect the MS-9200 Communications SLC Loop to Terminal (-) and Terminal (+) of the removable
terminal block.
If an RA400Z Remote LED Annunciator is being employed, connect the RA400Z positive terminal to the
RA+ terminal on the removable terminal block and the negative terminal to the RA(-) terminal on the
removable block.
Before installing the appropriate addressable detector head, set the detector's address on the
head with a small slotted screwdriver. Mark this address on the head.
Place the removable terminal block into the connector in the detector head. Be certain to align properly
and snap-in securely.
Channel (+)
Channel ( - )
Channel (+)
Communications
SLC Loop
Channel ( - )
to next device
on Loop
RA400Z Remote
LED Annunciator
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
41
2.16
Optional Modules
The MS-9200 supports option modules, using connectors J6, J11, J12 and J16 on the main board. There are
five optional modules available for the MS-9200; the RTM-8F Relay/transmitter Module, PIM-24 Printer/PC
Interface Module, the UDACT-F Universal Digital Alarm Communicator Transmitter, the DIM-485 LCD-40
Display Interface Module and the ZDM-16F 16 zone LED Module. Jumper JP4 must be cut before installation of the RTM-8F optional module to enable module placement supervision. Note that devices connected
to the standard EIA-485 connector, the optional EIA-232 connector, the optional EIA-485 connector (via the
PIM-24 or DIM-485) or SLC Loop may be protected from voltage transients by using one of the compatible
surge suppressors listed in Table G-1 of the appendix.
J6 accepts RTM-8F
Comm
unicators
Communicators
UDACT-F Universal Digital Alarm Communicator
Transmitter
Transmits system status to UL Listed Central Station Receivers
via the public switched telephone network. It is capable of
reporting up to 56 software zones or up to 198 addressable
points. The UDACT-F may be mounted directly to the MS-9200
main circuit board, or remotely in a UBS-1F (as shown) or ABS8RF enclosure. The MS-9200 requires software P/N 73580 or
higher to support the UDACT-F. For additional information,
refer to the UDACT-F Manual P/N 50050.
UBS-1F Enclosure
42
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
3/4" Nylon
Standoffs
Rev. B1
7/28/97
P/N 50428:B1
43
+24 VDC
Nonresettable
Power (TB4)
Solid
Earth
Ground
Connection
Future Use
Ferrite
Cores
P/N 29090
Shield
MS-9200
Cabinet
UDACT-F in ABS-8RF
(shown with cover removed)
MS-9200
Notes:
1) This arrangement allows use of the UDACT-F simultaneously with the RTM-8F module.
2) Ferrite cores are recommended for all applications.
3) Recommended wire is 12 AWG to 18 AWG twisted/shielded pair.
4) If shielded wire is used, connect only one end of shield:
a) shield may be connected to cabinet (earth ground) at fire alarm panel, or
b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT-F. NOTE: The shield
end that is not connected should be insulated to prevent accidental grounding. Do not
connect both ends of shield under any circumstance since a ground fault may result.
5) Conduit is recommended for external wire runs. Consult local building codes.
6) Connect Ground Strap (supplied with ABS-8RF enclosure) from Earth Ground terminal on
UDACT-F to a solid building earth ground. Conduit alone will not provide a reliable earth ground.
7) UDACT-F may be located up to 6,000 feet away from the host control panel.
8) Refer to Specifications Section for power requirements.
9) UDACT-F TB1 Terminals 6 and 7 are for future use.
44
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Capabilities
The ACM-8RF Module provides eight Form-C relays with contacts rated for 5 amps.
When installed with an MS-9200 Fire Alarm Control Panel (FACP), the ACM-8RF Relay
Control Modules provide relay activation for each of the 56 possible FACP zones plus
special functions. Options exist to allow for alarm only or alarm and trouble activations
per zone. Output activation for general alarm, general trouble, general supervisory,
NAC fault, AC fail, walktest start and battery trouble are also available. Refer to the
ACM-8RF Manual Appendix for information on setting module switches for addressing
and relay functions.
The ACM-8RF is installed on the standard EIA-485 communication bus and wiring is
supervised by the FACP. Power for the module must be power-limited and may be
provided by the FACP or by a UL listed power supply such as the FCPS-24F. Up to 32
ACM-8RF Relay Control Modules may be placed onto the EIA-485 communication bus
(if no other devices are installed on the bus). Removable terminal blocks are provided
for ease of wiring installation and servicing. Refer to the ACM-8RF Manual for UL
power-limited wiring requirements and switch SW4 receive/transmit selection options.
ABS-8RF Enclosure
The ACM-8RF module can be mounted remotely in an ABS-8RF annunciator surface-mount backbox.
CAUTION!
CAUTION!: It is vitally important that, following relay programming, all relays be tested for correct activation by
triggering zones and/or special functions at the FACP. It should also be noted :
ACM-8RF relays will activate during the Alarm Pre-signal Sequence.
ACM-8RF relays will not activate during the Alarm Verification Retard and Reset periods.
ACM-8RF
Nonresettable 24 VDC
Power Out
TB4 - 3(+) & 4(-)
EIA-485
TB5 - 1(+) & 2(-)
MS-9200
Rev. B1
7/28/97
P/N 50428:B1
45
RTM-8F Option
Module
Standoffs
use metal
screw and
standoff here
insert here
RTM-8F
Main Circuit Board
46
Document # 50428
7/28/97
P/N 50428:B1
Power
Limited
Zone 1
Zone 2
Zone 3
Zone 4
Switch
Settings
Zone 5
Disconnected
Zone 6
Zone 7
Normal
Zone 8
Metal Standoff
Transmitter Output
(-) normal
(+) normal
J1 (on back of board)
Transmitter Output
Document # 50428
Rev. B1
1N4004
7/28/97
P/N 50428:B1
47
2.17
A remote serial printer may be permanently connected to provide a hard-copy printout of program entries, history
file and walktest data. The Printer/PC Interface Module Part Number PIM-24 provides an EIA-232 conversion to
adapt to most 40 and 80 column printers and most IBM PC/XT/AT or compatible computers including laptops and
personal computers. (This option is not available simultaneously with use of the DIM-485/LCD-40).
CAUTION: DO NOT connect a printer or PC to the MS-9200 Fire Alarm Control Panel if a ground fault exists on
the panel. Circuit damage may result.
PROGRAMMING
Refer to System Edit in the Programming/Read Status Section of this manual for printer programming instructions.
INSTALLATION
Remote printers and PCs require a separate 240 VAC, 50Hz primary power. Also required is the PIM-24 which
includes the Printer/PC Interface Module, interface cable prewired to a DB9F connector as shown in Figure 2.30
and a DB25 adapter. Connect the Printer/PC Interface board to J11 on the MS-9200 main circuit board and the
attached cable to the serial EIA-232 port on the printer or PC. Use the DB25 adapter if a nine pin connector is not
available on your printer or PC. Note that a ground fault may occur on the MS-9200 panel, dependent upon the
printer used, when this connection is made. For this reason, it is important that there be no preexisting ground fault
on the panel. Consult the factory for recommended printers.
PRINTER CONFIGURATION
The PIM-24 is required. Also refer to the documentation supplied with your printer. Set the printers options as
listed in the table which follows.
Typical Printer Settings
COMMUNIC. SETUP:
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:
LARGE
7
EVEN
1 STOP
2400
PC CONFIGURATION
Kit PK-9200 includes the MS-9200 Programming Utility software on 3-1/2"
floppy disk P/N 75298, the Instruction Manual P/N 15677 and the PIM-24
(Printer/PC Interface Module with cable and DB9F/25 connectors).
48
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1=PROGRAMMING
2=RD STATUS 3=AC/BAT
1 = Programming: Programming the system may only be accomplished by an authorized user. Before
attempting to program the system, place the SW1 Write Protect switch in the down position. SW1 is located
on the lower right side of the MS-9200 main circuit board (see page 6). If the switch is in the up 'Write
Protect' position while attempting to enter the Programming Mode, the LCD will display the following:
WRITE PROTECT!!!
PRESS BACKSPACE
In order to program the system, a valid password must first be entered. Once the correct password is
entered, the user may select Autoprogram or Program Editing. After programming is completed, return SW1
to the Write Protect position.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
49
NOTE: There are two programming levels. Program Level 1 is for system configuration in which data relating
to device types, zoning, messages, etc. is entered into the system memory. Program Level 2 is where a
qualified operator can access features such as Disable, Clear History, Walktest, Time Change and Program
Check. For Program Level 2, the SW1 Write Protect switch should remain in the up (Write Protect) position.
2 = Read Status: Entering Read Status allows the user to read the status of any point/zone in the system plus
display or print the history file or print the entire user program. The Read Status feature is NOT password
protected. Read Status is explained in Section IV Operating Instructions.
3 = AC/BAT: Entering AC/BAT allows the user to read the battery voltage and AC line voltage. The AC/BAT feature
is NOT password protected.
BATTERY: 24V
AC LINE: 240V
Section 3.1 on the following page describes initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system. Make certain the SW1 Write Protect switch
is in the down position before attempting any Level 1 Programming functions.
3.0 Initial P
o w er-up
Po
Once wiring of addressable devices to the SLC loop is completed, power up the system. Since the addressable
devices have not yet been programmed, their LEDs will not flash, the System Trouble LED will be on and the LCD
display will alternate between the following two displays:
TROUBLE IN SYSTEM
PROGRAM CORRUPTED
TROUBLE IN SYSTEM
NO DEVICES INSTALL
If the system remains unprogrammed, the piezo will sound after a few minutes. It can be silenced by pressing the
Acknowledge/Step switch, but it will continue to resound until the system is programmed.
50
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
3.1 Programming
Press the ENTER key. The screen below will appear:
1=PROGRAMMING
2=RD STATUS 3=AC/BAT
To enter the programming mode, press '1'. The display will read as follows:
KEY IN 5 DIGIT
PASSWORD, THEN ENTER
Entering the Level 1 password (default 00000) will cause the following screen to appear: (Refer to Section 3.2)
Entering the Level 2 password (default 11111) will cause the following screen to appear: (Refer to Section 3.3)
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
51
Passwords
There are two factory set programming passwords, 00000 and 11111, which will access two different screens as
indicated on the previous page. From either of the screens, access to specific system and device programming
may be obtained. All programming entries are stored in nonvolatile memory. The factory set passwords can be
changed by the user, and a method exists to clear one or both passwords. Note: For Canadian applications, both
passwords must be changed from the factory settings. If an invalid password is entered, the display shows:
'INCORRECT PASSWORD'. To exit from Programming operations at any time, press the Backspace (Left Arrow)
key repeatedly.
3.2.01 Clear
Pressing '0' will clear all general system programming options as defined in Section 3.2.04 and all programmed
addressable devices from the nonvolatile memory of the MS-9200. Before executing the CLEAR command, the
display will prompt the user to press ENTER in order to verify the command before the system actually clears
programming data. CLEAR is a useful command when the unit is first installed, prior to autoprogramming. NOTE:
It is necessary to 'Autoprogram' after using the clear function.
3.2.02 Autoprogram
Pressing '1' enters the AUTOPROGRAMMING mode. The main purpose of autoprogramming is to allow the
installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is
brought on-line, it must be autoprogrammed. Autoprogram is also the only way to add or delete devices.
Once autoprogram is selected, the MS-9200 automatically polls all devices installed/wired to the SLC loop. The
panel communicates with each individual addressable device and displays the type of device at each address
location starting with detectors and then modules.
While autoprogramming the system, the MS-9200 will display the following:
AUTOPROGRAM
PLEASE WAIT
Verification of each device address and type installed on the SLC may now occur. If information is correct press
the ENTER key, if not press the left arrow key to delete. In addition, adjective and noun descriptors plus zone
assignments may be added to the display field per device address. If the Reset key is pressed at this time or the
panel is allowed to timeout (after 10 minutes), a 'System Corrupted' message will appear. Be certain to step
through all devices using the Enter or Left Arrow key.
52
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
The first time that autoprogramming is selected, all points installed on the SLC loop are identified. Default device
type (monitor, smoke detector, control) and software zone assignments for each device are displayed. On any
successive enabling of the autoprogram feature, the LCD will display only the newly installed, deleted or changed
devices on the SLC loop.
Devices which match the program already in memory are not changed and are not shown to the operator. Devices
which do not match the program (not the same address and/or type) are shown to the operator. Devices inadvertently set to the same address are identified, and displayed on the screen.
I. NEW DETECTORS
For each new detector, the Autoprogram feature selects default program values and presents the information to
the user. A typical example:
where: the 'P' in P01 represents the actual type code (photo) of the detector found at address 01. ('I' represents Ion type detector.)
The adjective and noun fields are blank, but may be user programmed.
Z00 is the default zone selection meaning 'general alarm' (main circuit board NAC outputs 1 & 2). See Appendix B for Software Zone Assignment.
After the new detector is displayed, press ENTER to accept the default information shown. Alternately, press
LEFT CURSOR (the triangle to the left of ENTER) to reject the autoprogram information, and not enter it into
memory. In most cases, adjective, noun descriptors and zone assignments will be added by using the following
procedure.
The MS-9200 will lead you through the program editing process. A blinking cursor moves through the fields as
you press the RIGHT CURSOR key (the triangle to the right of ENTER). After moving into other fields, you
may return to a previous field by pressing LEFT CURSOR. Change the blinking fields by pressing the UP
CURSOR key, the DOWN CURSOR or by pressing the appropriate numeric key.
Custom words may be entered via the keypad. The alphanumeric operation of the keypad changes a blinking
letter in the ADJ and NOUN fields.. For example, to enter the letter R, press the 7 key to step through 7, P, R
and S; stop on R; then press the RIGHT CURSOR (not ENTER) to move to the next letter position.
To reduce the number of key presses, the user may also select from a library of stored words. The ADJ field
library provides five character words selected by the UP cursor or DOWN cursor from the list below.
_____
blanks (default)
NORTH
SOUTH
_EAST
_WEST
FRONT
CENTR
_REAR
UPPER
LOWER
_MAIN
FIRST
__2ND
__3RD
__4TH
__5TH
FLR_1
FLR_2
FLR_3
FLR_4
FLR_5
RM___
The ADJECTIVE field may be loaded from the library list above, and then modified letter-by-letter if desired.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
53
Pressing the UP or DOWN cursor keys steps through the library. Once the UP or DOWN keys
are pressed, the blinking cursor moves to the last character of the ADJECTIVE field, assuming
that the user will next want to move beyond this field.
Pressing a key on the 12-key pad changes the letter indicated by the blinking cursor. Any
alphanumeric character may be entered.
Pressing the RIGHT or LEFT cursor key moves the blinking cursor one letter right or left.
When the RIGHT cursor key is pressed with the blinking cursor on the last letter of the ADJECTIVE label, the
cursor will move to the first letter of the NOUN field.
Altering the NOUN field is done in a similar way. Use the UP or DOWN cursor keys to step through the
NOUN library (shown below).
__________
(all blanks - default)
_BASEMENT_
_BOILER_RM
_CLASSROOM
_CLOSET___
_CORRIDOR_
_ELECT._RM
_ELEVATOR_
_ENTRANCE_
_FLOOR____
_GARAGE___
_HALLWAY__
_HVAC-ROOM
_KITCHEN__
_LOBBY____
_OFFICE___
_PATIENT__
_RESTROOM_
_ROOM_____
_STAIRWAY_
_STOREROOM
_WING_____
_ZONE_____
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the
ADJ or NOUN field as follows:
If the Zero is pressed, a '0' is placed in the first letter position.
If the Zero key is then pressed a second time with no intervening key actions, the entire ADJECTIVE field is replaced with the field entered for the previous device programmed, and the cursor
moves to the last character of the field (Recall function). The Recalled ADJECTIVE or NOUN field
may now be changed letter by letter.
If the Zero key is pressed again with no other intervening key actions, and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a '0'. If the last character goes from 9 to 0, and the characters to the left of the last
character are also numbers, they are also incremented (overflow).
The above increment function may be repeated with each press of the Zero key.
54
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
SPECIAL FUNCTION
MONITOR
PULL BOX
HEAT DET
SMOKE ZON
WATERFLOW
SUPERVISY
TAMPER_SW
_________
ACK_SW__
SILENC SW
RESET SW
DRILL_
NONE (DEFAULT)
NONE
NONE
NONE
CAUSES NON SILENCEABLE ALARM
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
BECOMES SUPERVISORY POINT (SEE SECTION IV, OPERATION)
NONE (BLANK LABEL)
FUNCTIONS LIKE ACKNOWLEDGE SWITCH
FUNCTIONS LIKE SILENCE SWITCH
FUNCTIONS LIKE RESET SWITCH
FUNCTIONS LIKE DRILL SWITCH
Follow the same procedure as described in Section I New Detectors, for editing of the ADJECTIVE and NOUN
fields.
The default zone selection is Z00 (main circuit board NAC outputs 1 & 2) and may be set to Z01 through Z56 if
desired. See Appendix B Software Zone Assignment.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
55
III.
CONTROL MODULE AUTOPROGRAMMING
A typical control module Autoprogram screen would be:
SPECIAL FUNCTION
2
3
4
5
6
7
CONTROL
BELL CKT
HORN CKT
SOUNDERS
_________
RELAY
STROBES
Select an adjective descriptor from the library list shown in Section I New Detectors. Use the cursor keys as
described in Section I.
Control modules may be assigned to a maximum of three software zones. (See Appendix B). Zone Z00
represents general alarm. All control modules are assigned to Zone Z00 upon initial power up.
3.2.03
Point Edit
While displaying the Program Level One Menu screen (see Section 3.2), pressing '2' allows for editing of the point
(addressable device) descriptor screens. These screens show the device type, the device address, adjective and
noun field descriptors and the software zone locations that the point (addressable device) is assigned to. Point
editing is performed after autoprogramming and may be done at any time, except during an alarm condition. The
display shows:
56
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
3.2.04
System Edit
The System Edit function is selected by pressing '3'. The system edit screen appears as shown below for software
releases prior to P/N 73750. This software does not support the LCD-40 Annunciator:
DEFAULT
(N)one
SELECTION
(Y)120 seconds
(Y)60 seconds1
(Y)10 minutes1
(Y)3 minutes with 15 second Acknowledge1
(N) = None
(T) = Temporal
(C) = California
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F2
(6) = Style 6
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or
silence key has been pressed.
When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation, up to 56 zones, use AFM
Series Annunciators or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.
The system edit screen appears as shown below for software P/N 73750 or greater. This software is required to
support the LCD-40 Annunciator:
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
57
There are nine system function options for software P/N 73750 or greater. The factory default selections and user
option selections are shown below:
FUNCTION
DEFAULT
SELECTION
V = Alarm Verification
I = Silence Inhibit
A = Auto-Silence
P = Pre-signal
C = Bell Code
(N)one
(N)one
(N)one
(N)one
(N)one
(Y)120 seconds
(Y)60 seconds1
(Y)10 minutes1
(Y)3 minutes with 15 second Acknowledge1
(M) = March Time
(T) = Temporal
(C) = California
(Z) = 56 Zones
(ZU) =56 Zones Annunciator with UDACT-F2
(P) = 198 Points
(PU) = 198 Points Annunciator with UDACT-F2
L = LCD-40 installed (requires DIM-485)
P = Printer or local PC installed (requires PIM-24)
(6) = Style 6
(Y)es = Sound onboard piezo every 15 seconds during alarm and
every 2 minutes during trouble after acknowledge or silence key
has been pressed.
A/U = Annunciators
(N)one
with or without UDACT-F
L/P = LCD-40 or
Printer/PC in use
S = SLC loop style
R = Alarm/Trouble
Reminder
(N)one
(4) = Style 4
(N)o
When the UDACT-F has a fault, this entry allows the FACP to display 'DACT Trouble' on the LCD display and printer
hardcopy. The history file will also be updated with this information. For zone annunciation use AFM Series Annunciators
or LDM Series Annunciators. For 198 point annunciation, use the LDM Series Annunciators.
3.2.05
Password Change
While displaying the Program Menu, press '4' to change either of two passwords. One high level password,
defaulted to 00000, allows for point and system programming. A second lower level password, defaulted to
11111, allows for status changes such as: (1) disable points/zones (2) clear history file, (3) walk test enable,
(4) time and date set and (5) program check. Pressing '4' will display:
*,NNNNN, E=LEVEL 1 PW
#,NNNNN, E=LEVEL 2 PW
Select the password to change by typing * or #, then enter the new password. As the new program or status
password is entered it is displayed. When ENTER is pressed, the display reads "PRESS ENTER IF OK,
NNNNN = NEW PROGRAM PW". After ENTER is pressed, the new password is stored in EEPROM memory
and the program returns to the program change screen. If BACKSPACE is entered, the password remains
unchanged and the program returns to the program change screen.
58
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
3.2.06
LOAD
While displaying the Program Menu, program selection '5' sets up the MS-9200 for transfer of its application
database from/to a DOS-based computer. This may be used to save the program that exists in an MS-9200 for
security and future service reasons; or may be used to transfer a program created off-line to the MS-9200. Refer
to Document# 15677 for more information. When the Load option is selected, the following screen will be displayed:
3.3
Prog
vel Tw o
Progrr am Change - Le
Lev
While the MS-9200 system is normal with no active alarms, troubles or supervisories, the screen shown below
will be displayed:
1=PROGRAMMING
2=RD STATUS 3=AC/BAT
KEY IN 5 DIGIT
PASSWORD,THEN ENTER
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
59
Enter the Level 2 password (default = 11111) then press the ENTER key to access Programming Change Level
Two. The screen below will appear:
3.3.01 Disable
Pressing '1' displays the following screen:
DISABLE/ENABLE
PRESS */#, AA, ENTER
Press the * key to display detectors, the # key to display modules, followed by the device address, then the
ENTER key. A typical display is shown below:
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Rev. B1
7/28/97
P/N 50428:B1
61
CHANGE TIME/DATE
10:00 A MON 03/04/96
The first digit of the hours is flashing and may be changed with the numeric pad. The RIGHT CURSOR moves to
the next digit and the UP/DOWN cursor selects (A)M or (P)M and day of the week. Pressing the ENTER key
stores the time and date and returns to the level 2 main screen.
3.3.05 Check
Program selection '5' performs a check on software zone assignments. The MS-9200 looks for output devices
assigned to a software zone that does not contain any input devices (detectors, monitor modules). If multiple
devices fail the check, the UP/DOWN keys are used to step through the list of devices. The user must return to
point editing to correct any errors.
NOTE: The system continues monitoring alarm conditions during all Programming and Read Status operations
with theexception of Walktest.
At the completion of system programming, Switch SW1 (Write Protect switch) should be set to the Write Protect
position to prevent inadvertent changes to programmed features. Slide the switch to the up position to select the
Write Protect feature. See Figure 2.23 for the location of SW1.
62
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
IV OPERATING INSTR
UCTIONS
NSTRUCTIONS
4.0
Control Switches
ACKNOWLEDGE/STEP
The Acknowledge/Step key silences the piezo sounder and changes all flashing LEDs to steady. Only one
press is necessary regardless of the number of new alarms, troubles or supervisory signals. When the
piezo is silenced, an 'ACKNOWLEDGE' message is sent to the printer and the history file. Multiple active
events are scrolled on the display at a three second rate.
ACKNOWLEDGE also automatically sends a 'SILENCE PIEZO' command to the LCD-40, AFM and LDM
annunciators.
When more than one event exists, the first press of the Acknowledge/Step switch silences the piezo and
changes all flashing LEDs to steady. The second press of the switch stops the scrolling and holds the
event on the display for 1 minute. Subsequent pressing of the switch 'steps' through each active event.
Rev. B1
7/28/97
P/N 50428:B1
ALARM SILENCE
The Alarm Silence switch performs the same functions as ACKNOWLEDGE/STEP. In addition, if an alarm
exists, it turns off all silenceable circuits and causes the ALARM SILENCE LED to turn on. It also sends an
'ALARM SILENCED' message to the printer, the history file and the LCD-40. A subsequent new alarm will
resound the system.
63
SYSTEM RESET
Pressing the System Reset switch turns off all control modules and Notification Appliance Circuits, temporarily turns off resettable power to 4-wire detectors, causes an 'All Systems Normal' message to be displayed on the LCD, and stores 'System Reset' in the printer and history file. It also turns on all LEDs,
piezo, and LCD display segments as long as SYSTEM RESET is held (lamp test). Any alarm or trouble
that exists after System Reset will resound the system.
4.1
LED Indicators
4.2
Normal Operation
With no alarms or troubles in the system, the display message is SYSTEMS ALL NORMAL along with
the current time and date as shown below. To set the time and date, see Section 3.3.04.
64
Polls all devices on SLC loop. Checks for valid reply, alarms, troubles, etc.
Monitors AC input voltage and battery capacity.
Refreshes LCD display and updates time.
Scans keyboard.
Performs detector auto test.
Tests memory.
Updates/Reads EIA-485 communications bus.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
4.3
Troub
le Oper
ation
rouble
Operation
With no alarms, the detection of a trouble in the system will cause the piezo to sound, the System Trouble LED to
flash, and the trouble relay to activate. A message will appear on the LCD display indicating the trouble condition.
The same message is sent to the printer and history file, along with time and date.
Addressab
le Smok
e Detectors
Addressable
Smoke
Detectors: For addressable Ion or Photoelectric smoke detectors, the following is a typical
message that could appear on the LCD display for a detector in trouble.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
65
The information displayed in the first line in the previous example provides the following information:
The type of event - in this example TRBL indicates Device Trouble.
The Specific Device Trouble - the # symbol will be replaced by a digit representing a specific trouble
condition. (Refer to the list of Specific Device Troubles below).
Type of device - in this example MONITOR indicates monitor module.
Point type and address - in this example M01 indicates monitor module assigned to address 01.
The information displayed in the second line in the previous example provides the following information:
<ADJ> - user programmed adjective descriptor from library list or custom entry (five characters max.).
<NOUN> - user programmed noun descriptor from library list or custom entry (ten characters max.).
Zone - zone to which the point is assigned.
The # symbol in the display will be replaced by a digit that represents the Specific Device Troubles as listed below:
1 = Invalid Reply:
An Invalid Reply may be due to: (1) incorrect pulse width received from a module, (2) no answer from a
module due to either a complete device failure or removal from the SLC loop, or (3) an incorrect identification code received, i.e. a monitor module replaced by a control module or vice-versa.
2 = Short Circuit Control Module:
A Short Circuit exists across a control module's Notification Appliance Circuit (NAC).
3 = Open Circuit Monitor/Control Module:
An Open Circuit exists on a control module's Notification Appliance Circuit (NAC) or the monitor
module's Initiating Device Circuit (IDC).
Pressing the Acknowledge switch will cause the piezo to silence and the System Trouble LED to go on steady.
This occurs regardless of the number of troubles, alarms and supervisory events active in the system (block
acknowledge). When Acknowledge is pressed, and at least one new alarm or trouble exists in the system, the
ACKNOWLEDGE message is sent to the printer and history file.
If the trouble clears, either before or after ACKNOWLEDGE, the CLEAR TROUBLE message is sent to the printer.
For example:
CLR TRBL_# SMOKE DET P01 <ADJ><NOUN> ZONE # TIME and DATE
If all troubles clear and there are no supervisory or fire conditions active in the system, the system returns to
normal operation status, and the SYSTEMS ALL NORMAL message is shown on the LCD display and stored in the
history and printer files. Trouble restore occurs even if the troubles were never acknowledged (auto restore).
If ALARM SILENCE is pressed when only troubles exist, it will have the same effect as ACKNOWLEDGE/STEP.
The ALARM SILENCE LED will not be illuminated unless there was also an alarm in the system.
If multiple trouble conditions exist in the system, they will be scrolled on the LCD display automatically at a three
second rate. If a combination of alarms, troubles and/or supervisory conditions occur in the system simultaneously, only the alarms are scrolled on the display. If the ACKNOWLEDGE/STEP key is pressed, the display
stops on the present item for one minute, or until the ACKNOWLEDGE/STEP key is pressed again. As the ACKNOWLEDGE/STEP key is pressed, the MS-9200 displays events in the following priority order:
Alarms, in order of address
Supervisory, in order of address
Troubles, in order of address
66
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
4.4
Alarm Operation
Alarm operation is similar to trouble operation, but with the following differences:
4.5
Supervisory Operation
Supervisory operation is similar to alarm operation, but with the following differences:
4.6
There are two Notification Appliance (bell) Circuits on the MS-9200. For software releases prior to P/N
73750, NAC 1 is programmable and factory defaulted to general alarm, silenceable and March Time coding
operation. NAC 2 is not programmable and is fixed as general alarm, nonsilenceable and may not perform
coded functions.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
67
For software releases 73750 or greater, both NAC 1 and NAC 2 are programmable. Both NACs may be either
silenceable or nonsilenceable and may be programmed as steady or coded operations. Coded operation includes
March Time, Temporal or California types. Refer to Section 4.10 for additional information on coding.
4.7
Control-By-Event Operation
Each addressable detector and monitor module can be assigned to one software alarm zone. Control modules
may be assigned to a maximum of three software zones. A General alarm zone (Z00) may be listed for output
(control) points, but it is not necessary to list Z00 for input points, as this is the default zone. Z00 is not activated
by supervisory points.
When an input device (detector, M300 series modules) alarms and is not disabled, it activates all software
zones assigned to it. An output device (control module or Notification Appliance Circuit) that is not disabled is
turned on when any of the software zones to which it is mapped become active.
4.8
Detector Functions
MAINTENANCE ALERT
Each detector is monitored by the control panel for its maintenance status. If a detector is within 80% of its alarm
threshold for a 24 hour period, a 'maintenance alert' message will be displayed automatically signaling that the
detector needs cleaning.
AUTOMATIC TEST OPERATION
An automatic test of each detector is performed every two hours. The detector's sensing chamber and electronics
are functionally tested for normal, safe operation. A trouble message is displayed upon failure of this test. System
Reset clears this trouble.
TYPE CODE SUPERVISION
The MS-9200 monitors hardware device type codes (CP300, SD300, SD300T, M300, M301, M302, and C304) at slow
intervals. Mismatch of any type code, compared to the system program, will cause a device trouble.
SYSTEM ALARM VERIFICATION
The panel may be programmed to perform alarm verification. Alarm verification applies to detectors only. Refer to
Section 4.12 for a description of the Alarm Verification Timer.
4.9
Time Functions
4.10
Shown below are the pulse rate outputs via NAC 1 or NAC 2 when coded operation is selected. Note that software
releases prior to P/N 73750 only allow coding on NAC 1. Releases 73750 or greater allow coded functions on both
NAC 1 and NAC 2.
CONTINUOUS NO PULSE
MARCH TIME PULSES AT 120PPM.
TEMPORAL CODE PULSES TEMPORAL CODE (0.5 sec. On, 0.5 sec. Off, 0.5 sec. On, 0.5 sec. Off,
0.5 sec. On, 1.5 sec. Off).
CALIFORNIA CODE 10 sec. On, 5 sec. Off
68
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
4.11
Presignal
Presignal is used to delay output activation (control modules and NACs) while allowing for visual verification by a
person. Once a detector or monitor module triggers an alarm, the onboard piezo sounds immediately, but the
Notification Appliance (bell) Circuits are not activated for 15 seconds. During this time, if the acknowledge switch
is pressed, the piezo is silenced and the Notification Appliances will not activate for up to 3 minutes. After 3
minutes, the Notification Appliances will activate if the source of the alarm is not cleared. This does not affect
monitor modules programmed as waterflow or supervisory. Presignal operation requires the approval of the local
Authority Having Jurisdiction.
4.12
13 Sec.
120 Sec
RETARD
Alarm Ignored
CONFIRMATION
Rev. B1
7/28/97
P/N 50428:B1
69
4.13
Style 6 Operation
If the SLC is wired and programmed for Style 6, and a single fault occurs, the control panel will detect
the fault and drive both ends of the line, fully recovering from the fault. The panel latches the trouble and displays
it until the System Reset switch is pressed. The display shows STYLE 6 trouble type.
4.14
Read Status
Read Status functions do not require a password. The MS-9200 will continue to provide fire protection while in
read status mode. Read status may be entered while in alarm or trouble. If a new alarm or trouble occurs
during these functions, the Read Status is aborted to prevent confusion.
READ STATUS ENTRY
The operator presses the ENTER key, and the LCD display shows:
1=PROGRAMMING
2=RD STATUS 3=AC/BAT
The operator presses 2, and the display shows:
DISPLAY POINT=*/#, AA
HISTORY=1 PRINT=2
From this display, an operator may select one of three choices:
To DISPLAY POINT status, the type of device to be read must first be identified by pressing the (*) key for
a detector or the (#) key for a module. The two digit device address is keyed in next, followed by the
ENTER key.
To DISPLAY ZONE status, press the (*) key, then press the (*) key again. Next, key-in the zone number
(1-56) and press ENTER. The UP and DOWN cursor keys are used to view the next or previous zone.
To DISPLAY SYSTEM PARAMETERS, press the (*) key then press the (*) key again followed by ENTER.
To DISPLAY BELL CIRCUIT status, press the (*) key, followed by the (#) key, then the digit 1 or 2, then
ENTER.
To display the 500-event HISTORY file on the LCD, press the 1 key, then ENTER. The UP and
DOWN Arrow keys are used to step through the entries in the file.
To PRINT PROGRAM CONTENTS and CURRENT SYSTEM STATUS or HISTORY FILE, press the 2 key,
then ENTER. A new Menu appears which prompts to press 1 to print Program/Status or 2 to print History
file.
During this and all subsequent operations except print operations, a two minute timer is started that
will return to the previous display if no key is pressed. Each key press restarts the two minute timer.
Press of the left CURSOR (backspace) deletes the previous entry. If there is no entry, it will abort the
Read Status operation and return to the previous display. System Reset will also abort the Read
Status.
70
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
DISPLAY POINT
DISPLAY POINT operations display addressable device status on the LCD display. After the
status of the device is displayed, the UP key may be used to display the status of the next highest
addressable device, and the DOWN key to display the status of the previous addressable device.
The sequence of point display is Detector points 01-99, Module points 01-99, NAC bell circuits 0102, System parameters, and Zones 1-56.
A typical Read Status display is as follows:
READ HISTORY:
The MS-9200 has a 500-event history buffer. Stored events include Point Status, System
Troubles, and ACKNOWLEDGE/STEP, ALARM SILENCE, DRILL and SYSTEM RESET key
presses. All events are recorded with the time and date. History events are stored in volatile
memory, therefore, removal of primary AC power and secondary battery power will clear the
history buffer. To clear the History file without removing power, see Section 3.3.02. To view
events in the history file, use the Up and Down arrow keys to step through the events.
PRINT PROGRAM:
All user programmed options including device types, software zone assignments and system
parameters may be printed. The printout also includes current system status. See Section 2.16
for instructions on connecting a printer.
PRINT HISTORY:
The entire 500-event history file may be printed using the PRINT HISTORY feature. Refer to
Section 2.16 for instructions on connecting a printer.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
71
APPENDIX A: SUPPL
Y CALCULA
TIONS
UPPLY
ALCULATIONS
1. The A
C Br
anch Circuit
AC
Branch
The MS-9200 requires connection to a separate dedicated AC branch circuit (240 VAC), which must be
labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the
protected premises. No other equipment may be powered from the fire alarm branch circuit. The branch
circuit wire must run continuously, without any disconnect devices, from the power source to the fire
alarm control panel. Overcurrent protection for this circuit must comply with Article 760 of the National
Electrical Code as well as local codes. Use #14 AWG wire with 600 volt insulation for this branch circuit.
@240 VAC
Use Table A-1 to determine the total amount of current, in AC amps, that must be supplied to the system.
Un i t
Ty p e
Nu m b er
o f Un i t s
MS-9200
R45-24E
Charger
Cu r r en t
Dr aw
(am p s )
To t al
Cu r r en t p er
Dev i c e
1.2
0. 5
To t al AC B r an c h Cu r r en t Req u i r ed
72
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1.2
amps
APPENDIX A
SUPPL
Y CALCULASUPPLY
TIONS
2. The Main P
o w er Supply
Po
The MS-9200 provides regulated power for operating the fire alarm control panel, operating external devices, and operating the standby battery. The power for operating external devices is limited. Use Table A2A (standby or non-alarm) and Table A-2B (alarm) to determine if external loading is within the capabilities
of the MS-9200 power supply.
Concerning smoke detectors: Refer to the manufacturers data sheet packaged with each smoke detector to
find the standby and alarm current draws to use in the tables of this Appendix. Be sure to power detectors
from TB4, Terminals 5 and 6.
# o f Dev i c es
RTM-8F
ACM-8RF
St an d b y
Cu r r en t
(A m p s )
X
0.08
] one max.
0.009
0.030
ZDM-16F
] one max.
0.00005
AFM-16ATX
AFM-32AX
] one max.
0.04
AEM-16ATF
AEM-32AF
0.002
AFM-16ATF
AFM-32AF
0.04
AFM-16AF
0.025
UDACT-F
] one max.
0.04
LDM-32F
0.04
LDM-E32F
0.002
LCD-40
0.054
4-Wire Smoke
Detector
Power Supervision
Relay
0.025
CP300
0.00015
SD300
0.00015
SD300T
0.0002
M300
0.0002
M301
0.0002
M302
0.007
BG-10LX
0.0002
C304
0.0002
I300
0.0004
Su m Co l u m n f o r St an d b y L o ad
Notes:
1)
2)
3)
4)
5)
6)
To t al
Cu r r en t
(A m p s )
0.08
Amps
Rev. B1
7/28/97
P/N 50428:B1
73
@24 VDC
# of
Dev i c es
Cu r r en t
(A m p s )
To t al Cu r r en t
(A m p s )
0.168
RTM-8F
0.1464
ACM-8RF
[ ]
0.15810
ZDM-16F
0.085
AFM-16ATX
AFM-32AX
[ ]
0.0566
AEM-16ATF
AEM-32AF
[ ]
0.0186
AFM-16ATF
AFM-32AF
[ ]
0.0566
AFM-16AF
[ ]
0.0655
UDACT-F
[ ]
0.0757
LDM-32F
[ ]
0.056
LDM-E32F
[ ]
0.018
LCD-40
[ ]
0.054
4-Wire Smoke
Detector
[ ]
_____
Power Supervision
Relay
[ ]
_____
Addressable
Devices
Max.Draw
All Devices
0.2
Notification
Appliances
[ ]
_____
0.168
0.2
Amps9
Refer to next page for battery calculations using Total Standby and Total Alarm Loads.
Notes:
1) Current limitations of terminals:
TB4, Terminals 1 and 2 = 2.50 Amps.
TB4, Terminals 3 and 4 = 0.300 Amp.
TB4, Terminals 5 and 6 = 0.300 Amp.
TB1 and TB2, Any one circuit = 2.50 Amps.
2) Total current draw of terminals listed above cannot exceed:
3.6 Amps - With Standard Transformer (4000TAE) installed alone.
6.0 Amps - With both Standard Transformer (4000TAE) and optional Transformer (XRM-24E) installed.
Total current from TB4, Terminals 3 and 4, 5 and 6 not to exceed 0.600 amperes.
Total System power is 6.6 amps max.
3) M302 Monitor Module current limit at 90 mA in alarm.
4) All RTM-8F Relays activated.
5) All 16 ZDM-16F LEDs on.
6) All Annunciator LEDs on.
7) UDACT-F actively making phone call to Central Station. If the normally open contact is used, current
consumption increases to 100mA.
8) LDM-32F with LEDs on.
9) This column must not exceed 6.6 amps.
10) All eight ACM-8RF Relays activated on a single module.
74
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
BATTERY CALCULATIONS
Use the Total Standby and Alarm Load Currents calculated in Tables A-2A and A-2B for the following
battery calculation.
Standby Load
Current (Amps)
[
]
Alarm Load
Current (Amps)
[
]
Add Standby and Alarm Load for Required Ampere Hour Batt
NOTE:
1) 7 AH battery can be located in the MS-9200 Backbox.
2) 12 AH and 17 AH batteries require the FireLite BB-17F Battery box.
3) 20 AH to 55 AH batteries require the FireLite R45-24E Charger for housing and charging batteries.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
75
APPENDIX B: SOFTW
ARE ZONES
SOFTWARE
Setup and configuration of an addressable system is quite different than a conventional system. In a
conventional system, assignment of input devices (detectors, pull stations, heat detectors, etc.) to zones
is straight forward. Wiring is direct from clearly marked panel terminals to any device assigned to a particular
zone. Connection of output devices (horns, bells, strobes, etc.) in a conventional system is done by direct wiring
of the output device to terminals marked 'bell'.
With addressable systems, the same pair of wires is used to connect to all addressable input and output devices.
Communications between the panel and all addressable devices takes place over one pair of wires originating from
the panel. Software programming is used to configure the system, versus direct wiring. Zone assignment is
created via software means, hence the term 'software zones'.
Setup of an MS-9200 software zone is straightforward. Any zone may have a minimum of one and a maximum of
99 addressable input devices. Each detector is automatically assigned to a general alarm output. A zone may
also have a minimum of one and a maximum of 99 addressable output devices.
Use the charts on the following pages to help in 'zoning' the system. Note that monitor and control modules make
up one group of 99 addresses. It is critical that addresses of detectors are not duplicated and that monitor and
control addresses are not duplicated.
In the following example, photo detectors (SD300) at addresses 01 and 02, along with a monitor module (M300) at
address 01 and control modules (C304) at addresses 03, 04 and 05 have been assigned to zone 1. Zone 2 consists of ion detectors (CP300) at addresses 03 and 04, monitor module (M301) at address 02 and control modules
(C304) at addresses 03, 06 and 07. Zone 3 consists of two photo detectors (SD300) at addresses 05 and 06 plus
one ion detector (CP300) at address 07 and control modules (C304) at addresses 03, 08 and 09.
This example points out some of the key assignment features of the MS-9200. Addresses of detectors are not
duplicated. Addresses of monitor and control modules are not duplicated. The control module at address 03 is
assigned to the maximum three software zones (provides for floor above and floor below). Detectors and monitor
modules are assigned to one software zone.
Take care to properly plan the installation prior to installing any devices.
76
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
SD300
01
SD300
02
ZONE
01
C304
04
M300
01
C304
05
M301
02
C304
03
CP300
03
ZONE
2
C304
06
CP300
04
C304
07
SD300
05
SD300
06
C304
08
ZONE
3
CP300
07
C304
09
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
77
DETECTOR
78
ADJ
NOUN
(Up
(Up
to
to
ZONE
ADDRESS
DEVICE
TYPE
ZONE
NUMBE
01
SD300
02
SD300
ELEV.
03
CP300
2ND
04
CP300
05
SD300
3RD
FLOOR
06
SD300
MEZZANINE
07
CP300
FIRST
5
Characters)
10
Characters)
HALL
LOBBY
FLOOR
ROOM
MECH.
ADDR
210
ROOM
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
MONITOR/CONTROL
MODULE
ADDRESS
DEVICE
TYPE
ZONE
NUMBER
01
M300
02
M301
03
C304
1,2,3
2ND
FLOOR
53
04
C304
1ST
FLOOR
54
05
C304
HALL
55
06
C304
LOBBY
56
07
C304
MEZZANINE
57
08
C304
3RD
58
09
C304
MECH.
WEST
EAST
EAST
ELEV.
ADDR
HALL
51
STAIRWELL
52
FLOOR
ROOM
59
10
60
11
61
12
62
13
63
14
64
15
65
16
66
17
67
18
68
19
69
20
70
21
71
22
72
23
73
24
74
25
75
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
79
80
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
DETECTOR
ADDRESS
DEVICE
TYPE
ZONE
NUMBE
ADJ
NOUN
(Up
(Up
to
to
ZONE
5
Characters)
10
Characters)
ADD
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
81
MONITOR/CONTROL
ADDRESS
82
DEVICE
TYPE
ZONE
NUMBE
ADJ
NOUN
(Up
(Up
MODULE
to
to
5
Characters)
10
Characters)
ADD
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
1234
EIA-485
24 VDC TB4 Terms
3 (+) and 4 (-)
1234
J11
1234
DIM-485 CONNECTIONS
DIM-485
L CD-40 3
P1 Terminal 2
Terminal 2 - IN (+)
P1 Terminal 1
P1 Terminal 4
Terminal 4 - IN (-)
P1 Terminal 3
P1
(+) EIA-485
IN
(-) EIA-485
(+) (-)
EIA-485
OUT
Notes:
1) The above table shows terminal to terminal wiring between the DIM485 and one LCD-40.
2) If more than one LCD-40 is installed, the wiring to the DIM-485 In (+)
Terminal 2 and In (-) Terminal 4 will be from the Out terminals of the
last installed LCD-40.
3) The LCD-40 must have the two supplied R120 (120 ohm) resistors
installed across the In Terminals 2 & 4 and Out Terminals 1 & 3.
These resistors are required for impedance matching.
4) Refer to the LCD-40 Technical Manual Document #50327 for detailed
wiring information.
Document # 50428
P2
Rev. B1
Earth
Ground Optional
Shield
Connect
n/c
(+) 24 VDC
IN
(-) 24 VDC
(+) (-)
24 VDC
OUT
7/28/97
P/N 50428:B1
83
AEM-16ATF
RIBBON
CABLE
AEM-16ATF
RIBBON
CABLE
16 Zone
Alarm & Trouble
AEM-16ATF
RIBBON
CABLE
16 Zone
Alarm & Trouble
16 Zone
Alarm & Trouble
The above configuration provides: 56 Zones of Alarm and Trouble indication, Remote Acknowledge/Step, Alarm
Silence, Drill, and System Reset keys, System Supervisory, AC fail, and Trouble indications. Use AKS-1F
keyswitch to prevent unauthorized actuation of control switches.
+ - + - + T
B
4
B+
T
B
2
A+ A-
B+
B-
T
B
1
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
OPTION
PRINTER
& UP/DOWN LOAD
J11
MS-9200
T
B
5
T
B
6
B+
A+
B-
A-
RIBBON
CABLE
RIBBON
CABLE
84
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
RIBBON
CABLE
AFM-32AX
+ - + - + T
B
4
B+
A+ A-
B+
B-
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
T
B
1
T
B
2
B+
A+
B-
A-
T
B
6
T
B
5
OPTION
PRINTER
& UP/DOWN LOAD
AEM-32AF
J11
MS-9200
RIBBON CABLE
The configuration shown above provides: 56 Zones of alarm indication, a system Trouble LED, an On Line/ Power
LED, local piezo, and a Local Silence/Acknowledge switch.
AFM-16ATF
+ - + - + T
B
4
B+
A+ A-
B+
B-
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
T
B
1
T
B
2
OPTION
PRINTER
& UP/DOWN LOAD
B+
A+
B-
A-
T
B
6
T
B
5
J11
MS-9200MS-9200
MS-9200
AFM-32AF
+ - + - + T
B
4
B+
T
B
2
A+ A-
B+
B-
T
B
1
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
OPTION
PRINTER
& UP/DOWN LOAD
T
B
5
B+
A+
B-
A-
T
B
6
J11
MS-9200
This configuration provides 32 Alarm LEDs,
On Line/Power LED, System Trouble LED,
and Local Silence/Acknowledge switch.
ONLY ONE PER SYSTEM
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
85
EIA-485
Power
+ - + - + T
B
4
B+
T
B
2
A+ A-
B+
B-
T
B
1
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
OPTION
PRINTER
& UP/DOWN LOAD
T
B
5
B+
A+
B-
A-
T
B
6
J11
ALARM ZONE 1
ALARM ZONE 1
ALARM ZONE 1
ALARM ZONE 2
ALARM ZONE 2
MS-9200
ALARM ZONE 2
ALARM ZONE 3
ALARM ZONE 3
ALARM ZONE 3
ALARM ZONE 4
ALARM ZONE 4
ALARM ZONE 4
ALARM ZONE 5
ALARM ZONE 5
ALARM ZONE 5
ALARM ZONE 6
ALARM ZONE 6
ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 7
ALARM ZONE 7
ALARM ZONE 8
ALARM ZONE 8
ALARM ZONE 8
ALARM ZONE 9
ALARM ZONE 9
ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 11
ALARM ZONE 11
ALARM ZONE 12
ALARM ZONE 12
ALARM ZONE 12
ALARM ZONE 13
ALARM ZONE 13
ALARM ZONE 13
ALARM ZONE 14
ALARM ZONE 14
ALARM ZONE 14
ALARM ZONE 15
ALARM ZONE 15
ALARM ZONE 16
ALARM ZONE 16
SYSTEM TROUBLE
PRESS
TO
SILENCE
SYSTEM TROUBLE
PRESS
TO
SILENCE
ON LINE
ON LINE
AFM-16AF
Receive Only
AFM-16AF
Receive Only
ALARM ZONE 10
ALARM ZONE 15
ALARM ZONE 16
SYSTEM TROUBLE
PRESS
TO
SILENCE
ON LINE
AFM-16AF
Receive/
Transmit
The configuration shown above provides: 16 red Alarm LEDs, System Trouble LED, On Line/Power LED, Local
Silence/Acknowledge switch, and piezo. All AFM-16AF annunciators will show the same information.
86
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
AFM-32AX
AEM-32AF
RIBBON
CABLE
+ - + - + T
B
4
B+
T
B
2
A+ A-
B+
B-
T
B
1
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
OPTION
PRINTER
& UP/DOWN LOAD
T
B
5
B+
A+
B-
A-
T
B
6
J11
MS-9200
Receive Only
No Control Switches
AFM-16ATX
AEM-16ATF
RIBBON
CABLE
AEM-16ATF
AEM-16ATF
RIBBON
CABLE
RIBBON
CABLE
Receive Only
System Switches
Don't Function
AFM-16ATX
AEM-16ATF
RIBBON
CABLE
RIBBON
CABLE
AEM-16ATF
AEM-16ATF
RIBBON
CABLE
Receive/Transmit &
Control Switches
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
87
APPENDIX E: NFP
A STAND
ARD-SPECIFIC
NFPA
ANDARD
REQUIREMENTS
The Fire-Lite MS-9200 has been designed for use in commercial, industrial, and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this Appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
MS-9200 Control Panel containing the main control board, cabinet (backbox and door), main supply
transformer and power supply.
Batteries (refer to Appendix A for Standby Power Requirements).
Initiating Devices - connected to one of the control panel's Initiating Device Circuits.
Notification Appliances - connected to the control panel's Notification Appliance Circuit or via a control
module.
The following additional equipment is needed for compliance with the NFPA 72-1993 standards listed
below:
NFPA 72-1993 Fire Alarm Systems for Central Station Service (Protected Premises Unit) and Remote Station Service
MS-5012for connection to a compatible listed Central Station DACR or Protected Premises Receiving
Unit. This unit must be installed as outlined in Figure E-1.
OR
UDACT-F may be installed as illustrated in Section II.
88
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Figure E-1: NFPA Signaling Systems for Central Station Service (Protected Premises Unit)
This Figure illustrates use of an MS-5012. The UDACT-F may also be used. Refer to Section II for
information on installation.
Secondary
Phone Line
Primary
Phone Line
Modular Cable
P/N MCBL-6
Alarm
TB2
Secondary
Active
J2
Kissoff
J3
Trouble
Primary
Active
5
6
7
8
AC POWER
TROUBLE
ALARM
SUPERVISORY
Supervisory
9
10
RESET
11
MODE
SILENCE
12
13TB3
14
Red
yellow
Black
120 VAC
yellow
HOT
Neutral
12VDC
Battery
2-7AH
Black
Ground
White
Green
B+
T
B
2
A+
A-
B+
B-
T
B
1
A+ A-
NO C NO NC C NO NC C
B-
T
B
3
OPTION
PRINTER
& UP/DOWN LOAD
T
B
5
B+
A+
B-
A-
T
B
6
J11
MS-9200
MS-5012
MS-9200
TB2-1
TB3-5
TB2-2
TB3-3
TB2-3
TB3-8
TB2-4
TB3-6
TB2-9
TB3-2
TB2-10
TB3-1
Alarm
Trouble
Supervisory
NOTES:
1) Reference the MS-5012 Manual for additional information.
2) Program the MS-5012 for slave application.
3) SW2 Trouble/No AC switch located on bottom right of MS-9200 main circuit board, must be positioned in the
down position for this application. This prevents the transmission of a trouble on the loss of AC power.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
89
Municipal Box
Circuit
Gamewell
Model M34-56
Local Energy
Municipal Box
Nonpowerlimited
+
-
Polarities shown in
alarm condition
(Dummy load with a 1N4004 diode
when no connection is made)
Transmitter Output
Note: Refer to Figure 2.4 and Section 2.5.1 for information on UL Power-limited wiring requirements.
90
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Fire-Lite RS82
Remote Station Receiver UL listed.
Refer to Fire-Lite Alarms, Inc., Instruction
Manual for Remote Station Receiver
Model RS-82.
Polarity
Shown is
Normal Standby
Cut
JP1
Jumper JP2 must be in position
ALARM/TROUBLE REVERSE
POLARITY for use in alarm and
trouble transmission or ALARM
ONLY for alarm transmission
only
JP2 Jumper Settings:
RTM-8F Relay
Transmitter
Module
(not suitable for
transmission of
separate alarm
and trouble
signals to
Remote Station)
Alarm/Trouble Polarity
Reversal Remote Station
Power-limited
+
-
Note: Refer to Figure 2.4 and Section 2.5.1 for information on UL Power-limited wiring requirements.
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
91
TB3
MS-9200 Main Board
Form-C Alarm contact
programmed to activate
on General Alarm.
Form-C Trouble contact
which will automatically
activate on any Trouble
condition.
5
7
1
Form-A relay contact
programmed to activate
on Supervisory condition.
Notes:
1) Connection between MS-9200 and the
transmitter are supervised by the transmitter.
2) This MS-9200/Transmitter arrangement
can be employed for NFPA 72D Proprietary
Protective Signaling System.
92
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
APPENDIX F:
WIRE REQUIREMENTS
T-tapping of the SLC loop wiring is allowed for two wire (Style 4) configuations. The total resistance of any branch
cannot exceed 40 ohms. The total wire length of all combined branches cannot exceed 10,000 feet.
Connecting external system accessories to the MS-9200 main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, wire gauge, and wire run length per each MS-9200
circuit. Reference the chart below to specify wire requirements and limitations for each MS-9200 circuit.
NOTE: If the SLC Loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders (such as MA/SS-24D) instead of more
electronically noisy notification appliances such as electromechanical bells or horns.
WIRE REQUIREMENTS
CIRCUIT CONNECTIONS
CIRCUIT TYPE
CIRCUIT FUNCTION
SLC Loop
(power-limited)
Connects to Addressable
Devices
RECOMMENDED
MA X DISTA NCE
(FEET)
WIRE GUAGE
10,000
8,000
4,875
3,225
12 AWG
14 AWG
16 AWG
18 AWG
1,000
12-18 AWG
WIRE TYPE A ND
L IMITATIONS
EIA-485
(power-limited
Connects to annunciator
modules
6,000
18 AWG
EIA-232
(power-limited)
50
18 AWG minimum
2,500
12-18 AWG
M302
(power-limited)
2,500
12-18 AWG
C304
(power-limited)
12-18 AWG
24 VDC Regulated
Resettable and
Nonresettable
(power-limited)
12-18 AWG
24 VDC
Nonregulated
(power-limited)
12-18 AWG
R45-24E
12 AWG in conduit
20
12-18 AWG
WPW999
WPW995
WPW991
WPW975
When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.
Rev. B1
7/28/97
P/N 50428:B1
93
APPENDIX G: Compatib
le Surge Suppressors
Compatible
Surge supressors are protective devices which are designed to limit surge voltages due to power line fluctuations,
voltage transients or lightning. They can be placed on circuits to reduce the possibility of damage to sensitive
equipment due to unexpected voltage surges. Table G-1 lists the surge suppressors which have been tested with
the MS-9200 and have been found capable of reducing the risk of damage to the corresponding circuits due to
voltage fluctuations.
RS-232
RS-485
DLP-DS1
has 24V relay
F
orm-C contact,
Nor thern
p
Technologies, Inc. rotects one pair
DLP-DS1
has 24V relay
Form-C contact,
protects one pair
DLP-DS1
DLP-43
has 24V relay
protects one pair
Form-C contact,
protects one pair
DLP-42
protects two pair
DLP-42
protects two pair
DLP-42
protects two pair
FA 24
protects one pair
FA 24
FA 24
Not available
protects one pair protects one pair
FAS-1-033HC
protects one pair
PC642C-020
protects two pair
PC642C-008LC
protects two pair
FAS-1-060HC
protects one pair
FAS-2-033HC
protects two pair
PCB1B
protects two pair
PCB1B
protects two pair
FAS-2-060HC
protects two pair
Eclips
Edco
TER-030
protects one pair
TER-060
protects one pair
94
Notification
Appliances
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
SYSTEM
NORMAL
(SYSTEM
TROUBLE)
(UNPROGRAMMED SYSTEM)
Trouble in System
Program Corrupted
Press 'ENTER'
1 = Programming
2 = Read Status
3 = AC/BAT
Write
Protect
Press '2'
Press '1'
Press '3'
Battery: 24V
AC Line: 240V
Press '11111'
Press 'ENTER'
1 = Disable 2 = Clr Hist
3 = Walk 4 = Time 5 = Chek
Press '1'
Disable/
Enable Point
Press '2'
Clear Event
File
Press '3'
Walk test
Press '5'
Program
Check
Press '4'
Time
Press '00000'
Press 'ENTER'
0 = Clr 1 = Auto
2 = Point 3 = Sys
4 = Pword 5 = Load
Press '0'
Press 'ENTER'
Press '2'
Press 'ENTER'
Press '1'
Press 'ENTER'
Autoprogram
Please Wait
ENTER to Clear Program
Backspace to Escape
Press '4'
Press 'ENTER'
Press '3'
Press 'ENTER'
Document # 50428
Rev. B1
7/28/97
Press '5'
Press 'ENTER'
*,NNNNN, E=Level 1 PW
#, NNNNN,E=Level 2 PW
P/N 50428:B1
95
Press '2'
Press *AA
Press 'ENTER'
Press #AA
Press 'ENTER'
EXAMPLE:
NORMAL MONITOR M01
Z##
EXAMPLE:
NORMAL SMOKE DET I01
Z##
Press **AA
Press 'ENTER'
Press **
Press 'ENTER'
Press *#AA
Press ENTER
EXAMPLE:
OFF SOFTWARE ZONE
Z##
EXAMPLE:
OFF BELL CKT
PANEL CIRCUIT
Press '1'
Press 'ENTER'
Program/Status Print
LEGEND
Text inside box actually
appears in LCD display
Text inside oval indicates
key press
Write
Protect
96
Rev. B1
7/28/97
P/N 50428:B1
Press '1'
Press '2'
B01
Z##
Press '2'
Press 'ENTER'
History Print
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
97
98
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
Document # 50428
Rev. B1
7/28/97
P/N 50428:B1
99
Limited Warranty
Fire-Lite warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation
of Fire-Lite is to repair or replace, at its option, free of charge for parts and labor,
any part which is defective in materials or workmanship under normal use and service.
For products not under Fire-Lite manufacturing date-stamp control, the warranty is
eighteen (18) months from date of original purchase by Fire-Lite's distributor unless
the installation instructions or catalog sets forth a shorter period, in which case the
shorter period shall apply. This warranty is void if the product is altered, repaired or
serviced by anyone other than Fire-Lite or its authorized distributors or if there is a
failure to maintain the products and systems in which they operate in a proper and
workable manner. In case of defect, secure a Return Material Authorization form
from our customer service department. Return product, transportation prepaid, to
Fire-Lite, 12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by Fire-Lite with respect to its
products. Fire-Lite does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that Fire-Lite is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.
Fire-Lite GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL Fire-Lite BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
Fire-Lite PRODUCTS. FURTHERMORE, Fire-Lite SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF,
OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by FireLite. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
"Fire-Lite" is a registered trademark.
Technical Publishing