The example shows a wiring in which the cooling chain of a shipping container is monitored. If
the permitted maximum temperature of -4C is exceeded, a latching relay is set which
addresses an output for a signal lamp; a pulse generator is enabled which sends out a signal
to the Data Log function every 30 seconds so that it records the current temperature present at
the analog amplifier. The excess temperature can be acknowledged with the button at I1.
Parameters
You can specify in the properties which inputs, outputs or functions you want to record as data
log elements. Select the parameters of the required block and click "Add" to add them to the
list of data log elements. You can select up to 32 data log elements.
Page 2 of 7
SIEMENS
Upload data log
From internal memory
Select "Tools; Transfer; Upload Data Log" to upload the data log from the internal LOGO!
memory.
Page 3 of 7
SIEMENS
From SD card
To upload the data log from an SD card, set the base module to "Stop" mode and remove the
card from the 0BA7. Insert the card in the SD card slot on the PC or into a card reader. The
recording is now available on the removable storage device in a .csv file.
Page 4 of 7
SIEMENS
In the next step you decide which file you want to import. Select the path in which you have
previously saved the file.
After acknowledgment with "Open", the Text Import Wizard opens because the data come with
a delimiter. You can make different formatting settings for your log.
In the first step you specify how the data are separated in the original file. Confirm your
settings with "Next".
Page 5 of 7
SIEMENS
In step 2 you specify which characters were used as delimiters. Confirm your settings with
"Next".
In step 3 you can assign data types to the columns. Close the wizard with "Finish".
You will now be prompted where you want to add the new data. Select the required target and
and confirm your selection with "OK".
Page 6 of 7
SIEMENS
The data log is now added with separated columns into the spreadsheet and you can save it
once again.
Page 7 of 7