Engineering Manual
Engineering Manual
670 series
Engineering Manual
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license
and may be used or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1
Introduction.......................................................................3
Introduction to the engineering manual..............................................3
About the complete set of manuals for an IED..............................3
About the engineering manual.......................................................4
Intended audience.........................................................................4
Related documents........................................................................5
Revision notes...............................................................................6
Section 2
Section 3
Engineering process.......................................................11
Workflow...........................................................................................11
Section 4
Setting up a project........................................................15
PCM600 operates on projects..........................................................15
Installing Connectivity packages......................................................15
Setting up communication between PCM600 and the IED...............17
Managing projects in PCM600.........................................................21
Building a plant structure..................................................................22
IEC 61850 naming conventions to identify an IED......................23
Inserting an IED................................................................................25
Setting IED IP address in the project...........................................36
Section 5
Section 6
670 series
Engineering Manual
Table of contents
Section 7
Section 8
Section 9
Section 10 Glossary.........................................................................89
670 series
Engineering Manual
Section 1
Introduction
Section 1
Introduction
1.1
1.1.1
Decommissioning
deinstalling & disposal
Maintenance
Operation
Commissioning
Installing
Engineering
Engineeringmanual
Installation and
Commissioning manual
Operators manual
Application manual
Technical reference
manual
IEC09000744-1-en.vsd
IEC09000744 V1 EN
670 series
Engineering Manual
Section 1
Introduction
a reference during periodic testing. The manual covers procedures for mechanical
and electrical installation, energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in the chronological order (indicated by chapter/section
numbers) in which the protection IED should be installed and commissioned.
The Operators Manual (OM) contains instructions on how to operate the
protection IED during normal service once it has been commissioned. The
operators manual can be used to find out how to handle disturbances or how to
view calculated and measured network data in order to determine the cause of a fault.
The Engineering Manual (EM) contains instructions on how to engineer the IEDs
using the different tools in PCM600. The manual provides instructions on how to
set up a PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and DNP3.
1.1.2
1.1.3
The chapter Engineering tool set gives an introduction to the IED protection
and control manager PCM600.
The chapter Engineering process describes the IED engineering workflow
using PCM600.
The chapter Setting up a project describes the set up of a typical project in
PCM600.
The chapter Protection and control engineering describes how different tools
in PCM600 are used to configure protection and control functionality.
The chapter Local HMI engineering describes the engineering process of the
LHMI.
The chapter IEC 61850 communication engineering describes the engineering
process to create an IEC 61850 communication configuration.
The chapter DNP3 communication engineering describes how to use the
DNP3 communication tool.
Intended audience
General
The engineering manual addresses system and project engineers involved in the
engineering process of a project, and installation and commissioning personnel,
who use technical data during engineering, installation and commissioning, and in
normal service.
670 series
Engineering Manual
Section 1
Introduction
Requirement
The system engineer must have a thorough knowledge of protection and/or control
systems, protection and/or control equipment, protection and/or control functions
and the configured functional logics in the IEDs. The installation and
commissioning personnel must have a basic knowledge of handling electronic
equipment.
1.1.4
Related documents
Identity number
Operators manual
Application manual
Sample specification
SA2005-001281
Identity number
Operators manual
Application manual
Sample specification
SA2005-001282
Identity number
Operators manual
Application manual
Sample specification
SA2005-001280
670 series
Engineering Manual
Section 1
Introduction
Identity number
Operators manual
Application manual
Sample specification
SA2005-001283
Identity number
Operators manual
Application manual
Identity number
Operators manual
Application manual
1MRB520004-BEN
1.1.5
Revision notes
Revision
-
Description
First issue for 670 series version 1.2.
670 series
Engineering Manual
Section 2
Engineering tool set
Section 2
2.1
Introduction
The structure of a monitoring and control system for electrical substations has a
principle structure as shown in Figure 1. It contains a number of IEDs for the
various purposes.
It is recommended to not exceed 60 IEDs in one PCM600 project.
Larger projects can be divided into several PCM600 projects.
HSI
NCC-GW
PCM600
(station-IED1)
(station-IED2)
(tool set)
Station bus
bay
IED 1
bay
IED 2
bay
IED n-1
Station level
Station
Communication
bay
IED n
Bay level
IEC08000101.vsd
IEC08000101 V1 EN
Figure 1:
All three parts require specific engineering and configuration. PCM600 is used to
do the complete engineering and configuration activities needed for bay level IEDs.
Product type and version specific engineering data needed by PCM600 for
protection, control and communication engineering of a particular bay IED is given
in an IED connectivity package.
670 series
Engineering Manual
Section 2
Engineering tool set
PCM600 communicates with the bay IEDs via an Ethernet connection. The
connection allows to reading and writing all configuration data needed for proper
operation from or to the IED. The IEDs have communication interfaces for
protocols and media used for station communication. Bay IED IEC 61850 station
communication files can be exported from PCM600 to station engineering tools for
engineering of station communication between bay IEDs and station IEDs.
A PC with PCM600 can be connected to any 670 series IED within a station using
the Ethernet connection.
The Ethernet connection can then later also be used for service and maintenance
purposes. The connection is also used to handle disturbance records from
protection IEDs using the IEC 61850 file transfer.
The IEDs of today are designed on the concept of the IEC 61850 standard. This is
mainly given for the organization of functions represented by an equivalent logical
node in the IEC 61850 standard. The mapping between the logical node data model
in the IED, following the structure and rules in part 7 of the IEC 61850 standard,
and the function blocks in an IED configuration is given in the IEC 61850
communication protocol manual.
The concept is also used for DNP3 protocol. The signals used or delivered by a
function block are automatically generated and available for station
communication. This concept allows a very efficient cost saving signal engineering.
The engineering of the used communication protocols is a separate task and an
addition to the engineering of protection and control functions.
PCM600 can be used for different purposes throughout the IED life cycle. A set of
special tools is available for different applications.
The applications can be organized in:
This manual is valid for PCM600 supporting the 670 series product ver.1.2.
2.2
670 series
Engineering Manual
Section 2
Engineering tool set
Communication engineering
Service management
670 series
Engineering Manual
Section 2
Engineering tool set
HWT
PST
SMT
GDE
ACT
Communication Management
CMT
SMT
DRH
Service Management
MON
EVT
PCM600
IEC08000100.vsd
IEC08000100 V1 EN
Figure 2:
Additional functionality to manage the project and to organize the user rights:
Organizing users with their rights, profile and password to use the
different tools and activities within the tools.
Defining allowed activities for the user profiles to use tools in PCM600.
Organizing users with their rights, profile and password to read and write
files of the IED.
Defining allowed activities for the user profiles to use the read and write
function.
Once the engineering of the IED is done, the results must be written to the IED.
Conversely some parts of the engineering information can be uploaded from the
IED for various purposes.
The connection between the physical IED and PCM600 is established via an
Ethernet link on the front or rear port on the IED.
10
670 series
Engineering Manual
Section 3
Engineering process
Section 3
Engineering process
3.1
Workflow
Start
Create plant structure
Project
HWT
Save the work
between the
different steps
ACT/
SMT
Parametrization
PST
GDE
Supported
protocols
IEC61850
Export
SCD
IET600
Signal engineering
CMT
Write configuration
to IED
Import
SCD
SMT
IED
WRITE
IED
WRITE
End
End
Write configuration
to IED
IEC08000122.vsd
IEC08000122 V2 EN
Figure 3:
670 series
Engineering Manual
11
Section 3
Engineering process
12
Include and engineer the function blocks for LHMI element groups with
ACT and SMT.
Define the LED behavior with PST.
Configure the LEDs with ACT and SMT.
670 series
Engineering Manual
Section 3
Engineering process
670 series
Engineering Manual
13
14
Section 4
Setting up a project
Section 4
Setting up a project
4.1
4.2
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000392-1-en.vsd
IEC09000392 V1 EN
Figure 4:
4.
5.
6.
16
The Connectivity package manager shows the IEDs that are compatible with
the installed PCM600 version.
Activate the ABB IED Connectivity Package RE_670 Ver. n to use 670 series
products. (n = version number)
Always use the latest version of a connectivity package, see Figure 5. Click Set
Latest in the menu bar.
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000393-2-en.vsd
IEC09000393 V2 EN
Figure 5:
4.3
Direct point-to-point link between PCM600 and the IED front port. The front
port can be seen as a service port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to
enable communication.
The communication procedures are the same in both cases.
1.
2.
3.
4.
670 series
Engineering Manual
17
Section 4
Setting up a project
Setting up IP addresses
The IP address and the corresponding mask must be set via the LHMI for each
available Ethernet interface in the IED. Each Ethernet interface has a default
factory IP address when the IED is delivered. This is not given when an additional
Ethernet interface is installed or an interface is replaced.
The default IP address for the IED front port is 10.1.150.3 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the
local HMI path Main menu/Settings/General settings/Communication/
Ethernet configuration/Front port.
The default IP address for the IED rear port is 192.168.1.10 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the
local HMI path Main menu/Settings/General settings/Communication/
Ethernet configuration/Rear OEM - port AB and Rear OEM - port CD.
The front and rear port IP addresses cannot belong to the same
subnet or communication will fail. It is recommended to change the
IP address of the front port, if the front and rear port are set to the
same subnet.
IED
RJ-45
PCM600
Tx
Tx
Rx
Rx
IEC09000096-1-en.vsd
IEC09000096 V1 EN
Figure 6:
The following description is an example valid for standard PCs using Microsoft
Windows operating system. The example is taken from a Laptop with one Ethernet
interface.
Administrator rights are required to change the PC communication
setup. Some PCs have the feature to automatically detect that Tx
18
670 series
Engineering Manual
Section 4
Setting up a project
signals from the IED are received on the Tx pin on the PC. Thus, a
straight (standard) Ethernet cable can be used.
1.
IEC09000355-1-en.vsd
IEC09000355 V1 EN
Figure 7:
2.
IEC09000356-1-en.vsd
IEC09000356 V1 EN
Figure 8:
3.
670 series
Engineering Manual
Select the TCP/IP protocol from the list of configured components using this
connection and click Properties.
19
Section 4
Setting up a project
IEC09000357-1-en.vsd
IEC09000357 V1 EN
Figure 9:
4.
Select Use the following IP address and define IP address and Subnet mask if
the front port is used and if the IP address is not set to be obtained
automatically by the IED, see Figure 10. The IP address must be different from
the IP address chosen for the IED.
IEC09000658-1-en.vsd
IEC09000658 V1 EN
Figure 10:
5.
6.
20
670 series
Engineering Manual
Section 4
Setting up a project
4.4
Extensions of the exported project file is *.pcmp and those files are only used for
exporting and importing the projects between PCM600s. PCM600 uses the SQL
server and the projects are stored as SQL databases (.mdf files).
It is possible to create new projects from the File menu. Currently
open projects and project tools shall be closed before.
670 series
Engineering Manual
Select File and Open/Manage Project ... to see the projects that are currently
available in the PCMDataBases.
Open Projects on my computer.
Click the icon New Project. To create new project currently open projects and
object tools shall be closed.
The New Project window opens, see Figure 11.
21
Section 4
Setting up a project
en05000609.vsd
IEC05000609 V1 EN
Figure 11:
5.
6.
4.5
Name the project and include a description (optional) and click Create.
PCM600 sets up a new project that will be listed under Projects on my
computer.
22
Project = Center
Substation = Name of the substation
Voltage Level = identifies to which grid type or part in the substation the IED
belongs to
Bay = Bay within the voltage level
IED = selection of the IED, which is used in the bay. Several IEDs are possible
within a bay, for example one control IED and two protection IEDs.
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000710-1-en.vsd
IEC09000710 V1 EN
Figure 12:
Once a plant structure is built the name of each level in the structure should be
renamed by the names/identifications used in the grid. Use the right mouse button
to build the plant structure by selecting the elements from the context menu.
Rename the level after insertion, using the Rename possibility or the Object
Properties. Figure 12 shows the start of a project with two IEDs placed but still not
renamed.
To build a plant structure is useful when a complete grid with an
essential number of IEDs has to be built.
Procedure to build a plant structure:
4.5.1
Right-click in the plant structure and select New and Create from Template ...,
or
Right-click in the plant structure and select New, General and select one of the
elements IED Group or Substation.
Click View in the menu bar and select Object Types. Select the needed
elements and drag and drop them into the plant structure. Close the window if
it does not close automatically.
670 series
Engineering Manual
23
Section 4
Setting up a project
PCM600 takes care for these two possibilities. The two possible signal
designations are available per object in the object properties for all hierarchical
levels beginning with the station as highest level.
The technical key is automatically generated based on the rules and type
specifications of IEC 61346 and the extended definitions done for substations by a
technical committee. The technical key is shown in the Object Properties under
SCL Technical Key or Technical Key.
The predefined full path name of the technical key for the IED would be
AA1J1Q01A1.
For all practical engineering purposes (both towards the IED and towards the
61850 engineering process), the user should keep the default SCL technical key. It
is however possible, due to for example company naming policies, to rename the
SCL technical key for the station level, voltage level, bay level and IED level using
the Object properties window as shown in Figure 13.
The renamed full path name of the technical key for the IED would be
DMSTATC1Q1SB1.
24
670 series
Engineering Manual
Section 4
Setting up a project
IEC08000374.vsd
IEC08000374 V1 EN
Figure 13:
4.6
Inserting an IED
The context menu or the Object Types view shows the available 670 series IEDs
possible to insert, on the bay level in the plant structure, according to the installed
connectivity package.
In the plant structure it is possible to:
670 series
Engineering Manual
Online mode: When the IED is already connected to PCM600 and the
communication is established, PCM600 can read the configuration
directly from the physical IED. This is useful when an order specific IED
is used. The order configuration is written to the IED at the factory and
can be accessed by PCM600. The housing type, the used overlay version
for local HMI and the IO boards included in the IED will be read from
the IED directly.
Offline mode: When the physical IED is not available or not connected
to PCM600 the engineering steps are done without any synchronization
25
Section 4
Setting up a project
IEC09000361-1-en.vsd
IEC09000361 V1 EN
Figure 14:
3.
26
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000711-1-en.vsd
IEC09000711 V1 EN
Figure 15:
4.
IEC09000712-1-en.vsd
IEC09000712 V1 EN
Figure 16:
5.
670 series
Engineering Manual
Select the port and insert the IP address of the physical IED to configure, see
Figure 17.
27
Section 4
Setting up a project
IEC09000713-1-en.vsd
IEC09000713 V1 EN
Figure 17:
6.
Cross check that the IED, whose IP address has been inserted, has been
detected online by PCM600, see Figure 14.
The user can not scan data from the IED or proceed further if
the IED is not online or if the IP address is not correct.
7.
28
Click the Scan option to scan/read the IED Type and IED Version for the IED
that is online, see Figure 18.
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000714 V2 EN
Figure 18:
8.
670 series
Engineering Manual
Click next to open the Housing Selection Page and select the housing and
display type of the IED, see Figure 19
29
Section 4
Setting up a project
IEC09000742-1-en.vsd
IEC09000742 V1 EN
Figure 19:
9.
30
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000715 V2 EN
Figure 20:
31
Section 4
Setting up a project
in offline mode is almost similar to that of an online mode; however with offline
mode it is not necessary to type the correct IP address in the Communication port
and IP address dialog.
The version information needs to be selected from the drop down menu as shown
in Figure 21
IEC09000741 V2 EN
Figure 21:
32
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000716-1-en.vsd
IEC09000716 V1 EN
Figure 22:
670 series
Engineering Manual
33
Section 4
Setting up a project
IEC09000717-1-en.vsd
IEC09000717 V1 EN
Figure 23:
3.
4.
34
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000718-1-en.vsd
IEC09000718 V1 EN
Figure 24:
5.
Click Delete Template to delete the template, click Import Template to import
a template from the selection window or click Create to insert the selected IED
to the bay, see Figure 23.
It is possible to insert more than one IED from the Create New
Object from Template window and the selection window
remains open until the user clicks Close.
Inserting a pre-configuration
Pre-configurations in PCM600 are available as *.pcmi files and include all
information that is related to the IED object in PCM600. The pre-configuration is
bound to a specific hardware configuration.
Two alternatives to insert a pre-configuration:
670 series
Engineering Manual
Use the pre-configuration that has been ordered together with the IED.
Create an own configuration, export the configuration as *.pcmi file and use it
to configure other IEDs.
35
Section 4
Setting up a project
Right-click the bay and select Import ... to select the IED template file
(*.pcmi) , see Figure 25.
IEC09000644-1-en.vsd
IEC09000644 V1 EN
Figure 25:
2.
3.
4.
5.
Import the *.pcmi file from the bay level in the plant structure.
Click OK to insert the new IED object in the plant structure.
Modify the configuration in ACT in case of changes.
Write the configuration to the IED.
Ordered default configurations are not locked. The user can use any
of the available default configurations in the IED or as a base for
the own configuration. The only requirement is that all needed
hardware and software options are available.
4.6.1
36
Via the first window of the wizard when including a new IED in a project, see
Figure 26.
670 series
Engineering Manual
Section 4
Setting up a project
IEC09000719-1-en.vsd
IEC09000719 V1 EN
Figure 26:
Via the IP address of the IED in the Object Properties window, see Figure 27.
IEC08000121.vsd
IEC08000121 V1 EN
Figure 27:
Procedure
1.
2.
3.
670 series
Engineering Manual
37
Section 4
Setting up a project
The used alternative depends on the time at which the IP address is available. To
enter the IP address via the IED object properties window allows to changing the
IP address at any time.
38
670 series
Engineering Manual
Section 5
Protection and control engineering
Section 5
5.1
5.1.1
Overview
ACT is used to create the application configuration for an IED. The application
configuration is built up with function blocks.
Function blocks are dedicated for different functionality, for example:
Preprocessing blocks
Control related functions
Protection related functions
Monitoring functions
Communication
For detailed information about function blocks see the technical
reference manual and the application manual.
SMBIs and SMBOs are still available for 670 series in PCM600,
but the user is not constrained to use them anymore. The user can
connect the function blocks inputs and outputs directly to the
hardware channels.
Some function blocks are mapped as logical nodes according to the IEC 61850
standard. Other function blocks are not mapped as logical nodes, for example:
Logical gates
Timers
670 series
Engineering Manual
39
Section 5
Protection and control engineering
5.1.2
Function blocks
Do not use other characters than a-z, A-Z, 0-9 and _ when
setting user defined names for signals and function blocks,
since other characters might not display properly in local HMI.
Also avoid using space character.
40
670 series
Engineering Manual
Section 5
Protection and control engineering
13
11
10
14
15
16
12
17
IEC08000258.vsd
IEC08000258 V1 EN
Figure 28:
Connection(s)
ANSI symbol
Inverted output
5.1.3
670 series
Engineering Manual
41
Section 5
Protection and control engineering
A function block can contain more signals than needed in that application part.
Hide unused signals to get a clear picture.
Signals are located on both sides of the middle position up and down. When there
is space left, move some signals up or down for a better visibility and connection
routing.
Boolean input and output signals may need to be inverted to fulfill the logic. ACT
supports to add the inversion logic to a binary signal.
The input signal on glue logic function blocks can only be inverted
if a glue logic function block with lower execution order in the
same cycle time is available. Similar, the output signal can only be
inverted if a glue logic function block with higher execution order
in the same cycle time is available. Up to two input signals and two
output signals can be inverted for glue logic blocks in the same
cycle time.
Even though current is injected to the IED and the IED is connected
to PCM600 in online mode, the signal value in ACT is shown as zero.
All not mandatory input signals have a default value that will be used when not
connected.
5.1.4
Execution order
Cycle time
Instance number
Each time a new function block is selected these parameters have to be selected
from the drop down lists in ACT. Depending on the function block type not all
three parameters are selectable. The cycle time may be predefined to one value.
The instance number is a counter for the total possible number of function blocks
of that type used within an application configuration.
The Execution Order and Instance Number are a combination that is predefined
within a product. It is possible to select a pair out of the list. Figure 29 shows an
example how the drop down list could look like.
42
670 series
Engineering Manual
Section 5
Protection and control engineering
IEC09000720-1-en.vsd
IEC09000720 V1 EN
Figure 29:
670 series
Engineering Manual
43
Section 5
Protection and control engineering
IEC09000737 V1 EN
Figure 30:
For the same time point, faster cycle times are executed first.
IEC09000615-1-en.vsd
IEC09000615 V1 EN
Figure 31:
A function block type can be defined to be a member of one or several cycle times.
A function block instance can be set only to one cycle time.
44
670 series
Engineering Manual
Section 5
Protection and control engineering
Execution Flow
Execution order
group 1
Execution order
group 2
Execution order
group 3
IEC08000271.vsd
IEC08000271 V1 EN
Figure 32:
5.1.5
Configuration parameters
5.1.6
Connection validation
A connection is only useful and possible between two signals of the same base
attribute type, see Figure 33.
670 series
Engineering Manual
45
Section 5
Protection and control engineering
IEC08000304.vsd
IEC08000304 V1 EN
Figure 33:
5.1.7
Hardware channels
Hardware channels can only be connected to a function block input or output. A
hardware connection can be established in ACT or SMT. When a hardware channel
is connected a graphical symbol appears in ACT, see Figure 34. The connection is
also represented in SMT with a cross mark. Hardware channels are always visible
in SMT.
Supported hardware channels are:
46
670 series
Engineering Manual
Section 5
Protection and control engineering
IEC09000723-1-en.vsd
IEC09000723 V1 EN
Figure 34:
5.1.8
Validation
Validation checks the application configuration on errors about the rules and
restrictions defined for doing a MainApplication on three levels.
During creating the logic while doing a connection or placing a function block.
On demand by starting the validation.
When writing the application configuration into the IED.
670 series
Engineering Manual
A connection between two input signals or two output signals is not possible.
A connection between two different data types is not possible, for example a
binary output to an analog input.
47
Section 5
Protection and control engineering
Validation on demand
To check the validity of an application configuration, click the 'Validate
Configuration' icon in the toolbar. ACT will check the application configuration for
formal correctness. Found problems are qualified in:
Warnings will not prevent writing to the IED. Errors have to be corrected before
writing the application configuration to the IED. An application configuration can
be saved and ACT can be closed with open errors, but not written to the IED, see
Figure 35.
These problems are listed in the Output View under the Tab Application
Configuration. A double-click in the error or warning row will navigate to the
MainApplication>Page>Area where the problems are identified.
48
670 series
Engineering Manual
Section 5
Protection and control engineering
IEC09000614-1-en.vsd
IEC09000614 V1 EN
Figure 35:
5.2
670 series
Engineering Manual
49
Section 5
Protection and control engineering
All variables listed and shown in the parameter list can be sorted into two groups:
Configuration parameter or
Setting parameter
Configuration parameter
A configuration parameter specifies an operation mode of an application function
or of the IED. These are basic configurations, which are normally configured only
once and then settled. The IED configures itself at start-up according to the given
configuration parameter values.
Setting parameter
A setting parameter (short form only setting) is a parameter that can be changed
in the IED at runtime.
Setting group
Nearly all settings used by the IED for the protection application functions are
organized in a group of settings. Up to six setting groups can be configured with
different values. The IED supports the selection of a setting group at runtime.
5.3
50
670 series
Engineering Manual
Section 5
Protection and control engineering
Binary
Input
BIM
FBs
IOM BI
HMI
LEDs
LEDs
FBs
BOM
Binary
Output
Analog
Input
GOOSE
Input blocks
IOM BO
TRM
GOOSE Inputs
SMAI
IEC 61850
Hardware
IO interfaces
(X-direction)
Goose_Bin
Intl_AP
Signal Matrix
FBs
(Y-direction)
IEC09000709.vsd
IEC09000709 V1 EN
Figure 36:
A binary input channel can be connected to one or several function block inputs,
see Figure 37. If a binary input channel is connected to several different function
blocks in ACT, the connection will appear as glue logic in SMT.
A binary output channel can only be activated from one function block output. If it
should be activated from more than one function block output, glue logic has to be
used. Glue logic means inserting a logical gate (OR and AND blocks) between the
function blocks and the binary output channel. This can be engineered in SMT.
Connections made in SMT will automatically also be shown in
ACT.
670 series
Engineering Manual
51
Section 5
Protection and control engineering
IEC09000721-1-en.vsd
IEC09000721 V1 EN
Figure 37:
Depending on the IED capability, SMT has a separate sheet for each possible
combination.
The possible sheets are:
52
Binary Inputs
Binary Outputs
Analog Inputs
Functions
GOOSE Receive
670 series
Engineering Manual
Section 6
Local HMI engineering
Section 6
6.1
LED engineering
6.1.1
PST
Set LEDs
SAVE
GDE / ACT
Create the
single line diagram
SAVE
END
IEC09000680-1-en.vsd
IEC09000680 V1 EN
Figure 38:
670 series
Engineering Manual
53
Section 6
Local HMI engineering
PST
The function blocks for LHMI are visible by default for PST and SMT.
Use ACT or SMT to connect start and trip signals from application
functions to LED function blocks.
The operation mode of the LEDs is defined in PST.
LHMICTRL
LEDGEN
54
670 series
Engineering Manual
Section 6
Local HMI engineering
IEC09000656-1-en.vsd
IEC09000656 V1 EN
Figure 39:
The LEDs have a number of different operation modes, see Figure 40:
Follow-S
Follow-F
LatchedReset-S
670 series
Engineering Manual
The same as LatchedAck-F-S but the LED starts with steady state and
flashes after acknowledgment.
LatchedColl-S
The LED latches the signal change OFF-ON and flashes (F) until it is
acknowledged.
When the signal is still ON at the time the signal is acknowledged the
LED changes to steady (S) mode.
When the signal has already changed to OFF before the time it is
acknowledged, the LED turns to OFF.
LatchedAck-S-F
The LED illumination follows the status of the signal. The LED
illuminates flashing (F).
LatchedAck-F-S
The LED illumination follows the status of the signal. The LED
illuminates steady (S).
This mode is used for all LEDs that are used to indicate a disturbance.
The LEDs will stay in the last state after the disturbance run time until
they are reset after a defined time.
The timers are set in PST in the function block LEDGEN.
55
Section 6
Local HMI engineering
IEC09000743 V2 EN
Figure 40:
6.1.2
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
LED
IEC01000228_2_en.vsd
IEC01000228 V2 EN
Figure 41:
Monitoring a signal with a LED is a simple mode, where the LED follows the
signal state. More than one signal per LED can be used when applicable. See
Figure 41 for the valid priority rules. The LED illuminates always in steady state.
56
670 series
Engineering Manual
Section 6
Local HMI engineering
LED
Acknow.
en01000231.vsd
IED500-IEC01000231 V1 EN
Figure 42:
LED
Reset
IEC01000235_2_en.vsd
IEC01000235 V2 EN
Figure 43:
This mode catches a signal change to ON and the LED stays ON until the operator
resets the LEDs for this group.
670 series
Engineering Manual
57
Section 6
Local HMI engineering
If the signal is still ON when a reset LED is done, the LED will illuminated again.
This occurs when the application configuration accesses the signal again in the next
cycle after reset. The thin dashed lines in Figure 43 shows the internal state of the
LED following the signal and reset, when no higher prior signal is given.
The LED illuminates always in steady mode.
= Steady
= Flash
IEC08000400.vsd
IEC08000400 V1 EN
Figure 44:
This mode is useful to monitor signals that are involved in case of a disturbance,
see Figure 44. The signal state after the disturbance allows a fast overview about
the disturbance. To get always the situation of the last occurred disturbance, the
LEDs are reset after a predefined time (tReset). So this is the longest time a
disturbance can be monitored by the LED situation.
In case a second disturbance occurs before the tReset time has elapsed, see Figure
45, the signals that are still ON at the end of tReset will return to ON with the next
application configuration cycle after tReset. To clear these LEDs, a second timer
tMax is used. TMax is started when the first signal of the disturbance changes to
ON. tMax is stopped, when tReset could clear all LEDs.
A disturbance runs for a maximum of some seconds, while tReset can be in the
range of 60 to 90 seconds.
The timer tReset and tMax are configured in PST as part of the function block
LEDGEN
58
670 series
Engineering Manual
Section 6
Local HMI engineering
S1
S2
S3
S4
tMax
tRestart
AutoReset
ManReset
S1LED
S2LED
S3LED
S4LED
Illumination =>
= Steady
= Flash
IEC08000401.vsd
IEC08000401 V1 EN
Figure 45:
6.2
6.2.1
670 series
Engineering Manual
59
Section 6
Local HMI engineering
HMI display
window pages
Symbol library
window
Regard the
squence of pages
IED HMI
display window
IEC08000123.vsd
IEC08000123 V1 EN
Figure 46:
Procedure
1.
2.
3.
60
670 series
Engineering Manual
Section 6
Local HMI engineering
Symbol library
The symbol library window contains some panes that include drawing symbols or
elements to create a single line diagram, measurements and texts on a page. Click
on the name bar of the selected element to open the pane.
The library shows the symbols either in ANSI standard or in IEC standard. The
standard is selected by the drop down list box located on top of the display window.
When changing to the other library standard, GDE closes the library windows,
changes the symbols according to the selected new standard and redraws the single
line diagram in the display window.
Select the different panes and their symbols to become familiar with the available
symbols.
Measurements (Measurands) are presented in one format that explains itself when
selected. Select the format and drop it in the drawing area. Use the object
properties to make adaptations.
670 series
Engineering Manual
Select Dynamic Text and Indication to present the text for the actual value of
the function block, see Figure 47.
Click Select Button to select the value.
61
Section 6
Local HMI engineering
IEC08000127.vsd
IEC08000127 V1 EN
Figure 47:
The standard (IEC or ANSI) for the symbols and the selection of the font size for
the text elements can be changed using the two selector boxes on top of the page
window.
The total size of the presented white area (page) represents the visible part of the
local HMI display without header and foot-line.
The visible display for a single line diagram is organized in a raster of 13 x 8
(columns x rows). Each symbol -presented by 24 x 24 pixels- included by the drag
and drop method must be dropped in a raster box. The icon snap to grid must be
enabled to place a symbol. The description text for an apparatus object can be
placed in all four directions around the symbol. The description is part of the
apparatus object. It is possible to place the symbols not under assistance of Snap to
Grid.
Enable Snap to Grid during single line diagram engineering in GDE
to ensure that the single line diagram is rendered correctly, in the
local HMI display, as drawn in GDE.
Handling text
The raster switches when text is selected in a raster of 45 x 15 (columns x rows).
One raster box is the placeholder for one character. A text element must be placed
in the position of the raster. The name and the unit of a measurement or text
62
670 series
Engineering Manual
Section 6
Local HMI engineering
symbol can be changed either by double click the symbol or via the object property
window.
Select and toggle Show Texts using the IED Fonts to get a view how it will look
like later on the real HMI display.
Place the apparatus or transformer symbols by drag and drop in a raster box.
Place the connections symbols by drag and drop in a raster box.
Click the Link icon to enable direct line drawing.
Center the mouse pointer on the center of a connection point; visible in two
circles at the endpoints of a line, to draw a line.
Click to start and move the mouse pointer to the destination connection point.
Center once again the mouse pointer and click to drop the line.
Draw all line elements that are necessary.
Click Select in the menu bar to finish the line drawing.
start point
end point
en05000598.vsd
IEC05000598 V1 EN
Figure 48:
6.2.2
670 series
Engineering Manual
63
Section 6
Local HMI engineering
IEC09000666-1-en.vsd
IEC09000666 V1 EN
Figure 49:
64
670 series
Engineering Manual
Section 6
Local HMI engineering
The following application function blocks are used to deliver the needed information:
Procedure
1.
2.
3.
4.
670 series
Engineering Manual
Right-click the apparatus symbol and select Select Input Signal. A list of
engineered switch control application function blocks opens, see Figure 50.
Select the switch control application function block that corresponds to the
selected apparatus.
Right-click the measurement symbol and select Select Input Signal. A list of
the engineered measurement application function blocks opens.
Select the measurement application function block that corresponds to the
selected symbol.
65
Section 6
Local HMI engineering
IEC08000125.vsd
IEC08000125 V1 EN
Figure 50:
The number of order in the selection window of the process objects corresponds to
the number given in the PST tree and to the application function block in ACT.
Only those apparatus and measurements are shown that are configured in the
application configuration program.
en05000611.vsd
IEC05000611 V1 EN
Figure 51:
66
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
Section 7
7.1
7.1.1
7.1.2
670 series
Engineering Manual
67
Section 7
IEC 61850 communication engineering
LN
part
FB
AFL
FBs
with
monitoring
and
commands
LN
part
FB
AFL
LN
part
GOOSE
Receive
GOOSE
Send
Commands
Event
handler
Communication handler
IEC 61850 protocol
FB
AFL
GOOSE interf.
FBs
with
monitoring
only
LN
LN
GOOSE
GOOSE
Send
Send
FBs
FBs
GOOSE
GOOSE
Receive
Receive
Event
queue
IEC08000364.vsd
IEC08000364 V1 EN
Figure 52:
IEC 61850 has as a concept for the identification of all signals for communication
that belong to a function by a logical node as a placeholder. All signal information
in command and monitoring direction, which belongs to a function, is available
within the logical node.
Whenever a function block is instantiated in ACT, PCM600 automatically
generates the corresponding logical node data. In Figure 52 this is shown by two
parts per function block. The upper part is the visible function block in ACT and
the lower part is the logical node data for the function block.
7.1.2.1
68
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
Data-set
LN
LN
LN
LN
LN
LN
IED 2
Receive
Receive
Send
Data-set
LN
LN
LN
Receive
Receive
Data-set
LN
IED 1
Send
Receive
Send
Receive
LN
LN
LN
LN
LN
IED 3
en05000830.vsd
IEC05000830 V1 EN
Figure 53:
Figure 53 shows an example with three IEDs where each one communicates with
all the others.
When a GOOSE message is to be sent is defined by configuring the data set with
the defined trigger option and the GOOSE control block (GoCB). This engineering
process is done in the IET600 station configuration tool. The task involves
configuring lists with the signal, value and quality (data attributes) that belong to
the GOOSE message dataset.
In the opposite direction the standard only defines the IED as a receiver of the
GOOSE message. How the GOOSE input signals are handled must be defined in
the IED application configuration. The SCD file generated by the IET600 (or any
other station configuration tool) contains these GOOSE data sets as input data. The
input data must be connected to a GOOSE receive function block
(GOOSEBINRCV and GOOSEINTLKRCV) in SMT.
7.1.3
670 series
Engineering Manual
69
Section 7
IEC 61850 communication engineering
The CID file contains the information needed to configure just one
specific IED.
7.2
7.2.1
7.2.2
70
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
For more details please refer to the IEC 61850 standards. In the following
description it is assumed that PCM600 together with IET600 is used as system
configuration tool.
A short form of a typical sequence is shown in Figure 54 when a complete station
is exported as a SCD file.
1.
2.
3.
Export SCL files from PCM600. In the scenario in Figure 54 it is a SCD file.
Other SCL file types are possible to export.
Configure horizontal and vertical communication in the IET600 station
configuration tool.
Import SCL files to PCM600 project. In the scenario in Figure 54 it is the
updated SCD file.
Figure 54:
7.3
7.3.1
670 series
Engineering Manual
71
Section 7
IEC 61850 communication engineering
Station
IEC08000415.vsd
IEC08000415 V1 EN
Figure 55:
2.
3.
4.
IEC09000627-1-en.vsd
IEC09000627 V1 EN
Figure 56:
5.
7.3.2
Select Export Private Sections and click Export to export the private sections
to the SCD file. A progress window shows the ongoing export of the station.
Right-click the IED in the plant structure and select Export to open the Export
window.
Select the type of file to export from the Save as type drop down list.
72
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
IEC08000416.vsd
IEC08000416 V1 EN
Figure 57:
3.
4.
IEC08000418.vsd
IEC08000418 V1 EN
Figure 58:
7.4
670 series
Engineering Manual
73
Section 7
IEC 61850 communication engineering
Add and/or reconfigure default data sets. The 670 series pre-configured IED
includes a number of predefined data sets, but it is possible to add additional
data sets and/or reconfigure default data sets according to the requirements.
Note that reporting data sets shall only contain data intended to
be used by clients, for example for event handling.
4.
Configure report control blocks for each data set used for vertical
communication. The 670 series pre-configured IED includes a number of
predefined report control blocks, but it is possible to add additional control
blocks and/or reconfigure default control blocks according to the requirements.
Up to 8 report clients can be configured.
5.
6.
Connect the report control blocks to vertical IED clients. The report control
blocks are connected to the vertical clients in the SCD file for a 670 series preconfigured IED. Check each IED client and configure them to the subnetwork
before connecting report control blocks to the clients.
Create a GOOSE message data set for the sending IED. Define the attribute
content of the data set according to the requirements.
The data set for GOOSE may contain signals on data attribute
level or on FCDA level. The latter is also called structured
GOOSE.
Note that one data must only be included in one GOOSE data set.
7.
8.
9.
Create the GOOSE control block and connect it to the GOOSE message data
set. Be sure to check the parameters for the GOOSE control block and update
as required.
Connect the GOOSE control block to the client IEDs, subscribing for GOOSE.
Export the updated SCD file.
Please see the IET600 user manual for additional information about
vertical and horizontal station communication engineering.
74
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
7.5
7.5.1
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 59:
4.1. Click Ignore Substation Section to not import the "SSD-file" part of the
SCD-file.
4.2. Click Don't import IEDs of unknown type to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
4.3. Click Replace unknown ... can be used when it is known, that the file
includes additional IEDs that are needed. The IED of type Generic IEC
61850 IED is used to integrate these kinds of IEDs in the plant structure
etc.
4.4. Click Ignore PCM Object Type to update the IED object(s) in PCM600
from the IED type(s) in the SCD file, disregarding if the IED type(s) in
the SCD file matches the IED object(s) in PM600 or not.
4.5. Start Import when the file definition has been completed. A progress
window presents the import procedure.
5.
670 series
Engineering Manual
75
Section 7
IEC 61850 communication engineering
5.1. Make connections between the signals that the server is sending and the
GOOSE receive interface function blocks (GOOSEBINRCV and
GOOSEINTLKRCV) on the clients side.
If a client is defined for GOOSE receive then at least one cross
in SMT is required to be able to write the configuration to the
IED.
76
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
IEC09000616-1-en.vsd
IEC09000616 V1 EN
Figure 60:
7.5.2
670 series
Engineering Manual
77
Section 7
IEC 61850 communication engineering
3.1. Ignore Substation Section will not import the "SSD-file" part of the SCDfile.
3.2. Don't import ... protects the existing IEDs in case the SCD file does not
match the original configuration in PCM600.
3.3. Replace unknown ... can be used when it is known that the file includes
additional IEDs which are needed. The IED of type Generic IEC 61850
IED is used to integrate these kinds of IEDs in for example the plant
structure.
3.4. Click Ignore PCM Object Type to update the IED object(s) in PCM600
from the IED type(s) in the SCD file, disregarding if the IED type(s) in
the SCD file matches the IED object(s) in PM600 or not.
3.5. Start Import when the definition has been completed. A progress window
presents the import procedure.
4.
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 61:
7.6
78
670 series
Engineering Manual
Section 7
IEC 61850 communication engineering
1.
2.
IEC09000729-1-en.vsd
IEC09000729 V1 EN
Figure 62:
670 series
Engineering Manual
79
80
Section 8
IEC 60870-5-103 communication engineering
Section 8
8.1
Engineering in PCM600
The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1.
2.
3.
4.
See the Communication protocol manual for IEC 60870-5-103 for more
information about the IEC 60870-5-103 implementation in .
The COM05 module is equipped with an optical serial and RS485
serial communication interface. IEC60870-5-103 can be
communicated from either of these serial interfaces. The user must
select in PST which interface to use.
670 series
Engineering Manual
81
82
Section 9
DNP3 communication engineering
Section 9
9.1
9.2
670 series
Engineering Manual
83
Section 9
DNP3 communication engineering
1.
2.
3.
Save the actual project configuration in PCM600 to make all signals visible for
CMT.
Right-click the IED in the plant structure and select Communication
Management to start the Communication management tool.
Select the DNP3 protocol from the new window and click OK. Figure 63
presents the design of the two container windows, which open after the
selection of DNP3.
IEC09000722-1-en.vsd
IEC09000722 V1 EN
Figure 63:
2.
3.
84
Press the blue arrow button to insert the selected signals into the configuration.
Press the green double arrow button to insert all signals into the configuration,
see Figure 64.
670 series
Engineering Manual
Section 9
DNP3 communication engineering
IEC08000361.vsd
IEC08000361 V1 EN
Figure 64:
4.
5.
Click the drop down list Signal Type: to select the other signal types for this
channel.
Repeat to move signals for all signal types and save the selection.
Content changes in the DNP3 container are marked with a star at
the end of the name, see Figure 65. The star indicates that changes
in the container have to be saved before leaving CMT.
IEC08000339.vsd
IEC08000339 V1 EN
Figure 65:
9.3
670 series
Engineering Manual
Click the two inner arrows to sort signals to another index sequence, or select
Set Index ... from the context menu to move one or a set of signals to another
array, see Figure 66.
85
Section 9
DNP3 communication engineering
IEC08000336.vsd
IEC08000336 V1 EN
Figure 66:
2.
The selection window shows the number of signals selected, see Figure 67.
IEC08000363.vsd
IEC08000363 V1 EN
Figure 67:
3.
Define the Starting index for this group and click OK.
Click in the class field of the signal to change the class configuration.
The Select Class window opens.
Make the selection according to the definitions in the project and click OK to
close the window and get the new configuration, see Figure 68.
IEC08000338.vsd
IEC08000338 V1 EN
Figure 68:
86
670 series
Engineering Manual
Section 9
DNP3 communication engineering
9.3.1
670 series
Engineering Manual
Click in the Class field of the signal. A new window Select Class opens where
the user classifies the signal.
Select the signal classes and choose between None and 0 to 3 according to the
project demands.
Click OK to set the signal classification.
Write to IED.
87
88
Section 10
Glossary
Section 10
670 series
Engineering Manual
Glossary
AC
Alternating current
ACT
A/D converter
ADBS
ADM
ANSI
AR
Autoreclosing
ArgNegRes
Setting parameter/ZD/
ArgDir
Setting parameter/ZD/
ASCT
ASD
AWG
BBP
Busbar protection
BFP
BIM
BOM
BR
BS
British standard
BSR
BST
C37.94
CAN
CB
Circuit breaker
CBM
CCITT
CCM
CCVT
Section 10
Glossary
Class C
CMPPS
CO cycle
Close-open cycle
Co-directional
COMTRADE
90
CPU
CR
Carrier receive
CRC
CS
Carrier send
CT
Current transformer
CVT
DAR
Delayed auto-reclosing
DARPA
DBDL
DBLL
DC
Direct current
DFT
DIP-switch
DLLB
DNP
DR
Disturbance recorder
DRAM
DRH
DSP
DTT
EHV network
EIA
EMC
EMF
Section 10
Glossary
670 series
Engineering Manual
EMI
EnFP
ESD
Electrostatic discharge
FOX 20
FOX 512/515
Access multiplexer
FOX 6Plus
G.703
GCM
GDE
GI
GIS
GOOSE
GPS
GTM
HDLC protocol
HFBR connector
type
HMI
HSAR
HV
High voltage
HVDC
IDBS
IEC
IEC 60044-6
IEC 60870-5-103
IEC 61850
IEEE
IEEE 802.12
Section 10
Glossary
92
IEEE P1386.1
IED
I-GIS
IOM
Instance
IP
IP 20
IP 40
IP 54
IRF
IRIG-B:
ITU
LAN
LIB 520
LCD
LDCM
LDD
LED
LNT
LON
MCB
MCM
Section 10
Glossary
670 series
Engineering Manual
MIM
Milli-ampere module
MPM
MVB
NCC
NUM
Numerical module
OCO cycle
Open-close-open cycle
OCP
Overcurrent protection
OEM
OLTC
OV
Over voltage
Overreach
PCI
PCM
PCM600
PC-MIP
PISA
PMC
POTT
Process bus
PSM
PST
PT ratio
PUTT
RASC
RCA
REVAL
Evaluation software
RFPP
RFPE
RISC
Section 10
Glossary
94
RMS value
RS422
RS485
RTC
RTU
SA
Substation Automation
SC
SCS
SCT
SLM
SMA connector
SMT
SMS
SNTP
SPA
SRY
ST
Starpoint
SVC
TC
Trip coil
TCS
TCP
TCP/IP
670 series
Engineering Manual
Section 10
Glossary
670 series
Engineering Manual
TEF
TNC connector
Underreach
U/I-PISA
UTC
UV
Undervoltage
WEI
VT
Voltage transformer
X.21
3IO
3UO
95
96
97
ABB AB
Substation Automation Products
SE-721 59 Vsters, Sweden
Phone
+46 (0) 21 32 50 00
Fax
+46 (0) 21 14 69 18
www.abb.com/substationautomation
Contact us