Interface Panel Function PDF
Interface Panel Function PDF
INSTRUCTIONS
FOR INTERFACE PANEL FUNCTION
Upon receipt of the product and prior to initial operation, read these instructions thoroughly, and retain
for future reference.
MOTOMAN INSTRUCTIONS
MOTOMAN- INSTRUCTIONS
DX200 INSTRUCTIONS
DX200 OPERATORS MANUAL (for each purpose)
DX200 MAINTENANCE MANUAL
The DX200 operators manuals above correspond to specific usage. Be sure to use the appropriate manual.
Part Number:
Revision:
165834-1CD
0
MANUAL NO.
HW1481793 0
1/41
165834-1CD
MANDATORY
CAUTION
Some drawings in this manual are shown with the protective covers
or shields removed for clarity. Be sure all covers and shields are
replaced before operating this product.
ii
HW1481793
2/41
165834-1CD
WARNING
CAUTION
NOTE
iii
HW1481793
3/41
165834-1CD
WARNING
Once the emergency stop button is released, clear the cell of all
items which could interfere with the operation of the manipulator.
Then turn the servo power ON.
iv
HW1481793
4/41
165834-1CD
CAUTION
Equipment
Manual Designation
DX200 Controller
DX200
Programming Pendant
Manipulator cable
HW1481793
5/41
165834-1CD
Manual Designation
Character Keys
/Symbol Keys
Axis Keys
/Numeric Keys
Keys pressed
simultaneously
Displays
Registered Trademark
In this manual, names of companies, corporations, or products are
trademarks, registered trademarks, or brand names for each company or
corporation. The indications of (R) and TM are omitted.
vi
HW1481793
6/41
165834-1CD
Table of Contents
Table of Contents
1 Outline of Interface Panel Function................................................................................................. 1-1
2 Display and Operations of Panel Screen ........................................................................................ 2-1
2.1 Interface Panel Display...................................................................................................... 2-1
2.1.1 Panel Screen Display ........................................................................................... 2-1
2.1.2 Panel Screen Operation by Touch Panel ............................................................. 2-2
2.1.3 Panel Screen Operation by PP Keys.................................................................... 2-3
2.1.4 Numeric Display ................................................................................................... 2-3
2.1.5 Input of Numeric Value ......................................................................................... 2-4
2.1.6 Change of Panel Screen ...................................................................................... 2-4
2.1.7 Change of Language on Screen .......................................................................... 2-5
3 Data Setting and Touch Panel I/F Instructions ............................................................................... 3-1
3.1 Setting Procedure .............................................................................................................. 3-2
3.1.1 I/F Panel Setting Data and Display Position......................................................... 3-3
3.1.2 Editing of Setup .................................................................................................... 3-4
3.1.3 Editing of Panel Type ........................................................................................... 3-5
3.1.4 Editing of Panel Color........................................................................................... 3-5
3.1.5 Editing of Panel Name.......................................................................................... 3-6
3.1.6 Editing of Text Color ............................................................................................. 3-6
3.1.7 Editing of Security ................................................................................................ 3-7
3.1.8 Editing of Interlock Enable.................................................................................... 3-8
3.1.9 Editing of Input ..................................................................................................... 3-9
3.1.10 Editing of Group Name ..................................................................................... 3-10
3.1.11 Initialization of Set Data.................................................................................... 3-12
3.2 Details on Interface Panel Setting Items.......................................................................... 3-13
4 Save and Load of Set Data............................................................................................................. 4-1
5 Editing Saved Data ......................................................................................................................... 5-1
vii
HW1481793
7/41
165834-1CD
Table of Contents
6 Parameters...................................................................................................................................... 6-1
6.1 Clearing the Status of Signals............................................................................................ 6-1
6.1.1 Status of General Output Signals at Mode Change.............................................. 6-2
6.1.2 Status of General Output Signals at Power Supply ON........................................ 6-3
6.1.3 Status of Auxiliary Relay Signals at Power Supply ON ........................................ 6-3
6.1.4 Status of I/F Panel Signals at Power Supply ON.................................................. 6-3
6.2 Allocation of General Input Signals to Interface Panel Screens ........................................ 6-4
6.2.1 Notification of the Status of General Input Signals ............................................... 6-4
viii
HW1481793
8/41
165834-1CD
1-1
HW1481793
9/41
165834-1CD
2. Press {I/F Panel} while the Interface panel appears on the screen.
The screen goes back to the previous display.
NOTE
2-1
HW1481793
10/41
165834-1CD
2.1.2
2-2
HW1481793
11/41
165834-1CD
2.1.3
SUPPLEMENT
SUPPLEMENT
Numeric Display
Follow the operations as below to display numeric values on the panel
screen
1. Set the item "PANEL TYPE" in the I/F PANEL SETUP screen to either
"Counter" or "Preset counter".
Numeric value will be displayed in either three-digit number or sixdigit number according to the setting of indicated value.
If the indicated value exceeds the specified number of digits (threedigit or six-digit), an asterisk "*" appears instead of numeric value.
Three-digit display:
Six-digit display:
2-3
HW1481793
12/41
165834-1CD
2.1.5
Six-digit display:
NOTE
2.1.6
2-4
HW1481793
13/41
165834-1CD
2.1.7
SUPPLEMENT
2-5
HW1481793
14/41
165834-1CD
3-1
HW1481793
15/41
165834-1CD
3.1
Setting Procedure
The procedure in the case of setting up the following table is
shown.
Table 3-1: Example of I/F Panel Setting
Items
Set Data
ARRANGE
1A
SETUP
INVAL ID
PANEL TYPE
COUNTER
3 FIGURES
PANEL COLOR
BLACK
PANEL NAME
COUNTER U
COUNTER M
COUNTER D
TEXT COLOR
BLACK
SECURITY
OPERATION
PERMIT
INPUT(DISP)
B VARIABLE
B000
GROUP NAME
MAIN
3-2
HW1481793
16/41
165834-1CD
3.1.1
2. Move the cursor to the position where the item is to be arranged and
press [SELECT].
Using the [PAGE] or the {PAGE} button changes the control group of
the arrangement setting screen and a user can select the position
where the item is to be arranged.
3-3
HW1481793
17/41
165834-1CD
3.1.2
3-4
HW1481793
18/41
165834-1CD
3.1.3
2. Move the cursor to the panel type to be selected and press [SELECT].
3.1.4
2. Move the cursor to the panel color to be selected and press [SELECT].
3-5
HW1481793
19/41
165834-1CD
3.1.5
SUPPLEMENT
3.1.6
2. Move the cursor to the text color to be selected and press [SELECT].
3-6
HW1481793
20/41
165834-1CD
3.1.7
3-7
HW1481793
21/41
165834-1CD
3.1.8
NOTE
3-8
HW1481793
22/41
165834-1CD
3.1.9
2. Move the cursor to the input No. setting area on the right of {INPUT
(DISP)}, and press [SELECT].
Enter the numeric input mode.
3. Enter the input No. with the numeric keypad, and press [ENTER].
3-9
HW1481793
23/41
165834-1CD
3.1.10
SUPPLEMENT
3-10
HW1481793
24/41
165834-1CD
3-11
HW1481793
25/41
165834-1CD
3.1.11
3-12
HW1481793
26/41
165834-1CD
3.2
Items
Explanations
Arrangement
32 positions in total: 1A to 4H
Setup
0: INVALID, 1: VALID
VALID INVALID: the setup status can be changed from Valid to Invalid without
conditions.
INVALID VALID: When the set parameter is OK after checking, the status can be
changed from Invalid to Valid.
The following setting is required for VALID status:
<When Icon type is circle, square, or selector switch>
Input: Signal
Output: none or within the range of general output signals
<When Icon type is counter>
Input: B-variable, I-variable, or register
<When Icon type is preset counter>
Input: B-variable, I-variable, or register
Output: B-variable, I-variable, or register
* If the setting item is edited in the Valid status, the status
becomes Invalid.
Panel Type
Panel Color
Panel Name
Text Color
Security
Interlock Enable
0: Prohibited, 1: Permitted
Input
ID
No.
Output
ID
No.
Contact
OFF: A-contact, ON: B-contact
The setting is invalid when the ID is not set to 1: Signal.
3-13
HW1481793
27/41
165834-1CD
Items
Explanations
11
Group Name
SUPPLEMENT
Shown below is the status of output signals. The status varies depending on which of
"push button" and "push-lock/push-release button" is selected by pressing "circle
indication light", "square indication light 1", or "square indication light 2".
3-14
HW1481793
28/41
165834-1CD
Items
Range
Input
Allocatio
n
Output
Icon Type
Allocation
General input
enable
disable
Circle/Square indication
light
Selector switch
enable
enable
Circle/Square indication
light
Selector switch
External input
enable
disable
Circle/Square indication
light
Selector switch
enable
enable
Circle/Square indication
light
Selector switch
Special input
enable
disable
Circle/Square indication
light
Selector switch
Special output
enable
disable
Circle/Square indication
light
Selector switch
I/F panel
enable
enable
Circle/Square indication
light
Selector switch
Auxiliary relay
enable
disable
Circle/Square indication
light
Selector switch
Control input
enable
disable
Circle/Square indication
light
Selector switch
Pseudo input
enable
disable
Circle/Square indication
light
Selector switch
DL input
enable
disable
Circle/Square indication
light
Selector switch
DL output
enable
enable
Circle/Square indication
light
Selector switch
B-variable
B000 to B099
(100 signals)
enable
Counter
enable
enable
Preset counter
I000 to I099
(100 signals)
enable
Counter
enable
enable
Preset counter
Input allocation:
M000 to M999
(1000 signals)
Output allocation:
M000 to M559
(560 signals)
enable
Counter
enable
enable
Preset counter
2
3
4
I-variable
Register
3-15
HW1481793
29/41
165834-1CD
SUPPLEMENT
NOTE
The table above describes the status of input / output allocation on Interface panel.
Dont refer to this allocation table when allocating input/output signals for Concurrent I/O program.
Items
0,1,2
Icon
Icon Type
Indicates the status of allocated signals.
The light turns on when the status of input signal (indicated
value) is ON, whereas it turns off when OFF.
ON
OFF
3,4,5
OFF
3-16
HW1481793
30/41
165834-1CD
Items
6,7,8
Icon
Icon Type
Indicates the status of allocated signals.
ON
OFF
9,10,
11,12
Selector switch
16,17,
18,19
Counter (3 digits)
Counter (6 digits)
3-17
HW1481793
31/41
165834-1CD
4-1
HW1481793
32/41
165834-1CD
5. Press [ENTER].
The confirmation dialog box is displayed.
4-2
HW1481793
33/41
165834-1CD
5-1
HW1481793
34/41
165834-1CD
5-2
HW1481793
35/41
165834-1CD
CAUTION
Syntax error will occur when inserting line feeds into the data
"Data Example".
Syntax error will occur when the number of commas differs from
the saved data in FD/PC card.
Define capital letters for variables.
Wrong signal range or type instruction will make the attribute
invalid when loading.
Loading for one item is possible as follow;
//IFPANEL 4
///NAME Panel 4, Panel 4
1A,0,0,0,1,NAME1,NAME2,NAME3,1,1,0,11111,0,0,0,0,0,0,0,NA
ME1,NAME2,NAME3,0
5-3
HW1481793
36/41
165834-1CD
6 Parameters
6.1 Clearing the Status of Signals
Parameters
6.1
The possible settings and the timing of status signal settings are as
follows:
Signals
Timing of
setting the
status of
signals
Parameters
Set values
General output
signals
Mode change
S4C0064 to S4C0079
S4C1164 to S4C1179
0: Hold / 1: Clear
General output
signals
Power supply
ON
S2C0235
0: Hold / 1: Clear
Auxiliary relay
signals
Power supply
ON
S4C0080 to S4C0095
0: Clear / 1: Hold
I/F panel
signals
Power supply
ON
S4C0569 to S4C0572
0: Hold / 1: Clear
*Notice that auxiliary relay signals have different set values of parameters
from general output signals or I/F panel signals.
"Hold" and " Clear" of the status of signlas are defined as follows:
"Hold " means to keep the status of the previous one at the time of
when the power supply is turned OFF or the mode is changed.
"Clear" means to turn the status of signals into OFF regardless of the
previous status at the time of when the power supply is turned OFF
or the mode is changed.
6-1
HW1481793
37/41
165834-1CD
6.1.1
6 Parameters
6.1 Clearing the Status of Signals
Status of General Output Signals at Mode Change
By setting parameters from S4C0064 to S4C0079 and S4C1164 to S4C1179 , it allows to set
the status of general output signals (#10010 to #15127) at the time of when changing mode.
Set Values
S4C0064
#10010 to #10167
S4C0065
#10170 to #10327
S4C0066
#10330 to #10487
S4C0067
#10490 to #10647
S4C0068
#10650 to #10807
S4C0069
#10810 to #10967
(Bit
When a bit specification is
specification) set to "1", the status of
general output signals will
0: Hold,
be cleared at the time of
1: Clear
changing mode.
(Bit specification is to be set
by a series of 8 signals.)
S4C0070
#10970 to #11127
S4C0071
#11130 to #11287
S4C0072
#11290 to #11447
S4C0073
#11450 to #11607
S4C0074
#11610 to #11767
S4C0075
#11770 to #11927
S4C0076
#11930 to #12087
S4C0077
#12090 to #12247
S4C0078
#12250 to #12407
S4C0079
#12410 to #12567
S4C1164
#12570 to #12727
S4C1165
#12730 to #12887
S4C1166
#12890 to #13047
S4C1167
#13050 to #13207
S4C1168
#13210 to #13367
S4C1169
#13370 to #13527
S4C1170
#13530 to #13687
S4C1171
#13690 to #13847
S4C1172
#13850 to #14007
S4C1173
#14010 to #14167
S4C1174
#14170 to #14327
S4C1175
#14330 to #14487
S4C1176
#14490 to #14647
S4C1177
#14650 to #14807
S4C1178
#14810 to #14967
S4C1179
#14970 to #15127
Explanation
(Bit
When a bit specification is
specification) set to "1", the status of
general output signals will
0: Hold,
be cleared at the time of
1: Clear
changing mode.
(Bit specification is to be set
by a series of 8 signals.)
6-2
HW1481793
38/41
165834-1CD
6.1.2
6 Parameters
6.1 Clearing the Status of Signals
Status of General Output Signals at Power Supply ON
By setting parameter S2C0235, it allows to set the status of general output
signals (#10010 to #15127) at the time of when turning the power supply
ON.
6.1.3
#10010 to #15127
S4C083
S4C084
#72570 to #73207
S4C085
#73210 to #73847
S4C086
#73850 to #74487
S4C087
#74490 to #75127
S4C088
#75130 to #75767
S4C089
#75770 to #76407
S4C090
#76410 to #77047
S4C091
#77050 to #77687
S4C092
#77690 to #78327
S4C093
#78330 to #78967
S4C094
#78970 to #79607
S4C095
#79610 to #79997
S4C081
S4C082
6.1.4
Set Values
Explanation
When a bit specification is set
to "1", the status of auxiliary
relay signals will be held at the
time of power supply ON.
(Bit specification is to be set by
a series of 32 signals.)
Set Values
Explanation
S4C569
#60010 to #60167
S4C570
#60170 to #60327
S4C571
#60330 to #60487
(Bit
specification)
0: Hold,
1: Clear
S4C572
#60490 to #60647
6-3
HW1481793
39/41
165834-1CD
6.2
6 Parameters
6.2 Allocation of General Input Signals to Interface Panel Screens
6.2.1
Parameters
Correspo
nding
Panel
Screens
Set Values
Explanation
S4C597
NONE
S4C598
Panel 1
S4C599
Panel 2
S4C600
Panel 3
0: No function
1 to 1024
(Integral number):
General input signal
numbers
S4C601
Panel 4
S4C602
Panel 5
S4C603
Panel 6
S4C604
Panel 7
S4C605
Panel 8
S4C606
Panel 9
S4C607
Panel 10
SUPPLEMENT
6-4
HW1481793
40/41
DX200 OPTIONS
INSTRUCTIONS
FOR INTERFACE PANEL FUNCTION
MANUAL NO.
HW1481793
41/41