Vent Sizing

This document provides calculations for inbreathing and outbreathing of air for an insulated storage tank. It includes: 1) An inbreathing calculation for a 450m3 tank being pumped out at 30m3/hr, with an insulation factor of 1 and C factor of 6.5, resulting in 497.909773 Nm3/hr of inbreathing air. 2) An outbreathing calculation for the same 450m3 tank being pumped out at 90m3/hr, with an insulation factor of 1 and Y factor of 0.32 based on its latitude, resulting in 168.1702 Nm3/hr of outbreathing air. 3) Tables

Uploaded by

Prashant Malve
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (2 votes)
876 views

Vent Sizing

This document provides calculations for inbreathing and outbreathing of air for an insulated storage tank. It includes: 1) An inbreathing calculation for a 450m3 tank being pumped out at 30m3/hr, with an insulation factor of 1 and C factor of 6.5, resulting in 497.909773 Nm3/hr of inbreathing air. 2) An outbreathing calculation for the same 450m3 tank being pumped out at 90m3/hr, with an insulation factor of 1 and Y factor of 0.32 based on its latitude, resulting in 168.1702 Nm3/hr of outbreathing air. 3) Tables

Uploaded by

Prashant Malve
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

inbreathing Calculation

Volume Of Tank
Pump Outlet Flow
Insulation Factor
C factor
Total inbreating air

Air Velocity
sizing of Vent

450 m3
30 m3/hr
1
6.5
497.909773 Nm3/hr

15 m/sec
0.00922055 m2
0.108351

Tank Capacity

ank Capacity

Latitude

Table 1 : C-factor for Inbreathing


Vapor Pressure
Hexane
or similar
Average Storage Temperature
< 25
>=25

Below 42o

6.5

42 to 58

2.5

Above 58o

Vin,air = Vpe + CVtk0.7 Ri


where
Vin,air = Total inbreathing in Nm3/h (Air)
Vpe = Pump-out or emptying in m3/h
Vtk = Tank capacity in m3
Ri = Insulation reduction factor

eathing
Vapor Pressure
Higher than hexane
or unknown
e Storage Temperature (oC)
< 25
>=25
6.5

6.5

Outbreathing Calculation
Volume Of Tank
Pump outlet Flow

Insulation Factor

C factor

Total Outbreathing air

450 m3
90 m3/hr

0.32

168.1702 Nm3/hr

Table 2 : Y-factor for Outbreathing


Latitude

Y-factor

Below 42o

0.32

42o to 58o

0.25

Above 58o

0.2

Vout,air = Vpf + YVtk0.9 Ri


where
Vout,air = Total Outbreathing in Nm3/h (Air)
Vpf = Pump-out or filling in m3/h
Vtk = Tank capacity in m3
Ri = Insulation reduction factor
Y = Factor subject to latitude (see Table 2)