Measuring and Monitoring Relay CM-PVS: Three-Phase Monitor For Over-And Undervoltage Data Sheet
Measuring and Monitoring Relay CM-PVS: Three-Phase Monitor For Over-And Undervoltage Data Sheet
Features
Approvals
,
CM-PVS
and
(pending)
Marks
,
Ordering data
Type
Supply voltage
Order code
CM-PVS
CM-PVS
- overvoltage: F1
- undervoltage: F2
- phase loss:
F1 on, F2 flashes
- phase sequence:
F1 and F2 flash alternately
Threshold adjustment
Umin/Umax
Time adjustment 0.1-10 s
Phase sequence and phase
loss are signalled without
delay.
Rotary switch for selecting
the time delay function
Order code
Sealable cover
Adapter for screw mounting
Marker
Application
The CM-PVS is a three-phase monitor. It is able to monitor the phase parameters phase sequence, phase
loss, over- and undervoltage.
ON-delay
OFF-delay
Operating mode
Over- and undervoltage monitoring
If all three phases are present with correct voltage, the output relay is energized.
If the voltage to be monitored exceeds or falls below the set threshold value, the output relays are deenergized undelayed or delayed (0.1-10 s), depending on the set time delay.
The fault type is indicated by LEDs.
The output relays re-energize automatically, instantaneously or with delay (0.1-10 s), depending on the set
time delay, as soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of
5%.
Phase sequence and phase loss
Phase sequence and phase loss are indicated and reset without time delay.
Adjustment of time delay
The fault signal can be suppressed or, for better evaluation, stored for the settable delay time of 0.1 to
10 s.
The rotary switch
Switch position
Switch position
/
:
In case of a fault, the output relays de-energize immediately and a fault signal
is issued and stored for the set delay time. This way, also momentary
undervoltage conditions are recognized.
15/18
15/16
25/28
25/26
F1: red LED
F2: red LED
R: green LED
15/18
15/16
25/28
25/26
F1: red LED
F2: red LED
R: green LED
Level
15/18
15/16
25/28
25/26
F1: redLED
F2: red LED
R: green LED
L1, L2, L3
15-16/18
25-26/28
Supply voltage =
monitoring voltage
2 c/o - closed-circuit principle
L1, L2, L3
L1, L2, L3
L1, L2, L3
160-300 V AC - 20 VA
300-500 V AC - 20 VA
-15 % ... +10 %
50/60 Hz
10 %
100 %
L1, L2, L3
Monitoring functions
Monitoring ranges min.-max.
overvoltage
undervoltage
over- /undervoltage
Thresholds
Hysteresis related to the threshold value
Monitoring voltage frequency
Max. monitoring time
Measuring error within supply voltage tolerance
Measuring error within temperature range
Timing circuit
ON-delay time
Delay time (ON- and OFF delay)
Tolerance of the adjusted delay time
Timing error within supply voltage tolerance
Timing error within temperature range
200 ms
0.1-10 s adjustable
10 %
0.5 %
0.06 % / C
Supply voltage
Output relays energized
Phase loss
Phase sequence
Overvoltage
Undervoltage
R on
R flashes during timing
F1 on, F2 flashes
F1 and F2 flash alternately
F1 on
F2 on
Output circuits
15-16/18, 25-26/28
Number of contacts
Operating principle (output relays de-energize in case of fault)
Contact material
Rated voltage
acc. to VDE 0110, IEC 60947-1
Min. switching voltage / min. switching current
Max. switching voltage
Rated switching current
AC-12 (resistive) 230 V
acc. to IEC 60947-5-1
AC-15 (inductive) 230 V
DC-12 (resistive) 24 V
DC-13 (inductive) 24 V
Max. lifetime
mechanical
electrical (AC-12, 230 V, 4 A)
Short-circuit proof,
n/c
max. fuse rating
n/o
2 c/o (relays)
closed-circuit principle
AgNi
250 V
24 V / 10 mA
250 V AC, 250 V DC
4A
3A
4A
2A
30 x 106 switching cycles
0,1 x 106 switching cycles
10 A fast, operating class gL
10 A fast, operating class gL
General data
Width of enclosure
Weight
Wire size
Mounting position
Degree of protection
Temperature range
Mounting
22,5 mm
ca. 130 g (0,29 lb)
2 x 2,5 mm2 (2 x 14 AWG)
any
IP 50
IP 20
-20 C ... +60 C
-40 C ... +85 C
DIN rail (EN 50022)
6 kV / 8 kV
10 V/m
2 kV / 5 kHz
2 kV symmetric
10 V
4g
6g
24 h cycle, 55 C, 93 % rel. 96 h
Approvals / marks
Approvals
Marks
Isolation data
Rated insulation voltage between in- and output
acc. to VDE 0110, IEC 60947-1
Impulse voltage resistance Uimp
measuring circuit
output circuits
Test voltage between all isolated circuits
Pollution degree
acc. to VDE 0110, IEC 664, IEC 255-5
Overvoltage category
acc. to VDE 0110, IEC 664, IEC 255-5
600 V
6 kV
4 kV
2.5 kV, 50 Hz, 1 min
III
III
DC load (resistive)
AC load (resistive)
in mm
Dimensions accessories
Sealable cover
in mm
Marker