Measuring and Monitoring Relay CM-PVS: Three-Phase Monitor For Over-And Undervoltage Data Sheet

The document describes the CM-PVS three-phase monitoring relay, which monitors phase sequence, phase loss, and over- and undervoltage, with adjustable thresholds and time delays. It has LED indicators, two output contacts, and is powered from the monitored circuit. The relay is approved to various standards and is available in models for 160-300V or 300-500V supply voltages.

Uploaded by

Mahmood Zizo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
152 views6 pages

Measuring and Monitoring Relay CM-PVS: Three-Phase Monitor For Over-And Undervoltage Data Sheet

The document describes the CM-PVS three-phase monitoring relay, which monitors phase sequence, phase loss, and over- and undervoltage, with adjustable thresholds and time delays. It has LED indicators, two output contacts, and is powered from the monitored circuit. The relay is approved to various standards and is available in models for 160-300V or 300-500V supply voltages.

Uploaded by

Mahmood Zizo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Measuring and monitoring relay CM-PVS

Three-phase monitor for over- and undervoltage


Data sheet

2CDC 251 049 F0004

Features








Three-phase monitoring of phase sequence, phase loss, over- and undervoltage


Adjustable over- and undervoltage threshold
Adjustable ON- and OFF-delay
Dual-frequency measuring input 50/60 Hz
Powered by the measuring circuit
2 c/o contacts
3 LEDs for status indication

Approvals
,

CM-PVS

and

(pending)

Marks
,

 R: green LED supply voltage, relay


 F1: red LED fault signal

Ordering data

 F2: red LED fault signal

Type

Supply voltage

Order code

CM-PVS
CM-PVS

160-300 V AC, 50/60 Hz


300-500 V AC, 50/60 Hz

1SVR 430 794 R1300


1SVR 430 794 R3300

- overvoltage: F1
- undervoltage: F2
- phase loss:
F1 on, F2 flashes
- phase sequence:
F1 and F2 flash alternately
 Threshold adjustment
Umin/Umax
 Time adjustment 0.1-10 s
Phase sequence and phase
loss are signalled without
delay.
 Rotary switch for selecting
the time delay function

Ordering data - Accessories


Description

Order code

Sealable cover
Adapter for screw mounting
Marker

1SVR 430 005 R0100


1SVR 430 029 R0100
1SVR 366 017 R0100

Application
The CM-PVS is a three-phase monitor. It is able to monitor the phase parameters phase sequence, phase
loss, over- and undervoltage.

ON-delay
OFF-delay

Operating mode
Over- and undervoltage monitoring
If all three phases are present with correct voltage, the output relay is energized.
If the voltage to be monitored exceeds or falls below the set threshold value, the output relays are deenergized undelayed or delayed (0.1-10 s), depending on the set time delay.
The fault type is indicated by LEDs.
The output relays re-energize automatically, instantaneously or with delay (0.1-10 s), depending on the set
time delay, as soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of
5%.
Phase sequence and phase loss
Phase sequence and phase loss are indicated and reset without time delay.
Adjustment of time delay
The fault signal can be suppressed or, for better evaluation, stored for the settable delay time of 0.1 to
10 s.
The rotary switch
Switch position
Switch position

/
:

is used to select the delay time function.


In case of a fault, the de-energizing of the output relays and the respective
fault signal are suppressed for the set delay time.

In case of a fault, the output relays de-energize immediately and a fault signal
is issued and stored for the set delay time. This way, also momentary
undervoltage conditions are recognized.

Measuring and monitoring relay CM-PVS


Three-phase monitor for over- and undervoltage
Data sheet
Function diagrams
ON-delayed over- and undervoltage monitoring
(switch position
)
L1, L2, L3
>U
>U-5%
Level
<U+5%
<U
1SVC 110 000 F0074

15/18
15/16
25/28
25/26
F1: red LED
F2: red LED
R: green LED

OFF-delayed over- and undervoltage monitoring


(switch position
)
L1, L2, L3
>U
>U-5%
Level
<U+5%
<U
1SVC 110 000 F0075

15/18
15/16
25/28
25/26
F1: red LED
F2: red LED
R: green LED

Thresholds for over- and undervoltage adjustable:


1SVR 430 794 R1300: Umin = 160-220 V Umax = 220-300 V
1SVR 430 794 R3300: Umin = 300-380 V Umax = 420-500 V

Phase sequence and phase loss, signalled without delay


L1, L2, L3

1SVC 110 000 F0078

Level

15/18
15/16
25/28
25/26
F1: redLED
F2: red LED
R: green LED

1SVC 110 000 F0512-a

Position of connection terminals

L1, L2, L3
15-16/18
25-26/28

Supply voltage =
monitoring voltage
2 c/o - closed-circuit principle

Measuring and monitoring relay CM-PVS


Three-phase monitor for over- and undervoltage
Data sheet
Technical data
Input circuit (= monitoring circuit)

L1, L2, L3

Supply voltage - power consumption

L1, L2, L3
L1, L2, L3

Supply voltage tolerance


Supply voltage frequency
Supply voltage frequency tolerance
Duty time
Monitoring circuit

160-300 V AC - 20 VA
300-500 V AC - 20 VA
-15 % ... +10 %
50/60 Hz
 10 %
100 %
L1, L2, L3

Monitoring functions
Monitoring ranges min.-max.

overvoltage
undervoltage
over- /undervoltage

Thresholds
Hysteresis related to the threshold value
Monitoring voltage frequency
Max. monitoring time
Measuring error within supply voltage tolerance
Measuring error within temperature range

phase sequence, phase loss,


over- and undervoltage
220-300 V / 420-500 V
160-220 V / 300-380 V
adjustable
fixed 5 %
50/60 Hz  10 %
50 ms
 0.5 %
 0.06 % / C

Timing circuit
ON-delay time
Delay time (ON- and OFF delay)
Tolerance of the adjusted delay time
Timing error within supply voltage tolerance
Timing error within temperature range

200 ms
0.1-10 s adjustable
 10 %
 0.5 %
 0.06 % / C

Indication of operational states

R: green LED, F1, F2: red LED

Supply voltage
Output relays energized
Phase loss
Phase sequence
Overvoltage
Undervoltage

R on
R flashes during timing
F1 on, F2 flashes
F1 and F2 flash alternately
F1 on
F2 on

Output circuits

15-16/18, 25-26/28

Number of contacts
Operating principle (output relays de-energize in case of fault)
Contact material
Rated voltage
acc. to VDE 0110, IEC 60947-1
Min. switching voltage / min. switching current
Max. switching voltage
Rated switching current
AC-12 (resistive) 230 V
acc. to IEC 60947-5-1
AC-15 (inductive) 230 V
DC-12 (resistive) 24 V
DC-13 (inductive) 24 V
Max. lifetime
mechanical
electrical (AC-12, 230 V, 4 A)
Short-circuit proof,
n/c
max. fuse rating
n/o

2 c/o (relays)
closed-circuit principle
AgNi
250 V
24 V / 10 mA
250 V AC, 250 V DC
4A
3A
4A
2A
30 x 106 switching cycles
0,1 x 106 switching cycles
10 A fast, operating class gL
10 A fast, operating class gL

General data
Width of enclosure
Weight
Wire size
Mounting position
Degree of protection
Temperature range
Mounting

stranded with wire end ferule


enclosure
terminals
operation
storage

22,5 mm
ca. 130 g (0,29 lb)
2 x 2,5 mm2 (2 x 14 AWG)
any
IP 50
IP 20
-20 C ... +60 C
-40 C ... +85 C
DIN rail (EN 50022)

Measuring and monitoring relay CM-PVS


Three-phase monitor for over- and undervoltage
Data sheet
Technical data (continued)
Standards
Product standard
Low Voltage Directive
EMC Directive
Electromagnetic Compatibility
Interference immunity
electrostatic discharge (ESD)
electromagnetic field
fast transients (Burst)
powerful impulses (Surge)
HF line emission
Interference emission
Operational reliability
Mechanical resistance
Environmental tests

IEC 255-6, EN 60255-6


73/23/EEC
89/336/EEC
acc. to EN 61000-6-2
acc. to IEC 61000-4-2,
EN 61000-4-2
acc. to IEC 61000-4-3,
EN 61000-4-3
acc. to IEC 61000-4-4,
EN 61000-4-4
acc. to IEC 1000-4-5,
EN 61000-4-5
acc. to IEC 1000-4-6,
EN 61000-4-6
acc. to EN 61000-6-4
acc. to IEC 68-2-6
acc. to IEC 68-2-6
acc. to IEC 68-2-30

6 kV / 8 kV
10 V/m
2 kV / 5 kHz
2 kV symmetric
10 V
4g
6g
24 h cycle, 55 C, 93 % rel. 96 h

Approvals / marks
Approvals

cULus, GL and GOST


CCC (pending)
CE, C-Tick

Marks
Isolation data
Rated insulation voltage between in- and output
acc. to VDE 0110, IEC 60947-1
Impulse voltage resistance Uimp
measuring circuit
output circuits
Test voltage between all isolated circuits
Pollution degree
acc. to VDE 0110, IEC 664, IEC 255-5
Overvoltage category
acc. to VDE 0110, IEC 664, IEC 255-5

600 V
6 kV
4 kV
2.5 kV, 50 Hz, 1 min
III
III

1SVC 110 000 F0184

DC load (resistive)

1SVC 110 000 F0185

AC load (resistive)

1SVC 110 000 F0189

1SVC 110 000 F0188

Load limit curves

Reduction factor F for inductive AC load

Contact life / number of operations


220 V 50 Hz 1 AC, 360 operations/h

Measuring and monitoring relay CM-PVS


Three-phase monitor for over- and undervoltage
Data sheet
Dimensions

2CDC 252 031 F0003

in mm

Dimensions accessories

1SVC 110 000 F0182

1SVC 110 000 F0179

Sealable cover

1SVC 110 000 F0181

in mm

Adapter for screw mounting

Marker

Publication No. 2CDC 112 048 D0201


Printed in the Federal Republik of Germany - Issue 7.2004

ABB STOTZ-KONTAKT GmbH


Eppelheimer Strae 82 69123 Heidelberg, Germany
Postfach 10 16 80
69006 Heidelberg, Germany
Internet
www.abb.de/epr
E-Mail
[email protected]