0% found this document useful (0 votes)
366 views6 pages

KXN Series

The document describes the features and functions of a digital temperature controller. It includes: - Multi-input and PID auto-tuning capabilities as well as alarm functions. - Descriptions of the display units and operation modes for process values and set points. - Explanations of main functions like control loop break alarm, auto-tuning, and set data lock. - Details on alarm types, input scaling, control direction, and other parameter settings.

Uploaded by

Rey-an A. Moreno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
366 views6 pages

KXN Series

The document describes the features and functions of a digital temperature controller. It includes: - Multi-input and PID auto-tuning capabilities as well as alarm functions. - Descriptions of the display units and operation modes for process values and set points. - Explanations of main functions like control loop break alarm, auto-tuning, and set data lock. - Details on alarm types, input scaling, control direction, and other parameter settings.

Uploaded by

Rey-an A. Moreno
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

FEATURES

- Multi input
- Set SV value by Digital input (Only for KX4S)
- P. I. D Auto-tuning
- Absolute / Deviation alarm (High/Low/Alarm within range)

Functional Description
Control output (OUT) lamp (RED)
Auto-tuning (AT) lamp (RED)
Set-value (SV) display unit (RED)
Process-value (PV) display unit (RED)

- User can select decimal point


- Select control direction (Reverse / Forward action)
- Loop Break Alarm (LBA) function
- Input correction

control system in consecutive order.


Cautions for LBA Function
LBA function will be activated when PID computed value is 0% or
100%. Therefore the time (from trouble occurrence to LBA activation)
equals to the time PID computed value becomes 0% or 100% plus
LBA setup time.
LBA function is not activated while AutoTuning function is being
operated
LBA function might be operated even though there are no troubles in
the control system because LBA is influenced by disturbances(other
heat sources, etc)
In case LBA setup time is short or control object does not match,
LBA might be ON/OFF or LBA might be not ON. In this case, please
set LBA setup time slightly longer.

Loop break alarm (LBA) (RED)

Auto-Tuning(AT) Function

High alarm (ALH) lamp (RED)


Low alarm (ALL) lamp (RED)

Set-value increment Key


Set-value decrement Key
Setting digit shift Key
Set Key

Main Functions
Control Loop Break Alarm (LBA function)
How to set
Usually set the Set-Value of LBA more two times than the Integral Time (I).
Also LBA can also be set by Auto-Tuning function. In this case, the SetValue is more two times than Integral Time (I) automatically.
Description of Operation
LBA function starts to measure time from the moment when PID
computed value (Output On time/cycle) becomes 0% or 100%. LBA
On/Off will be determined according to the changes of Process Value
under LBA setup time.
When 100% P.I.D computed value continues more than LBA setup
time, LBA will be ON if Process Value(PV) does not rise more than 2 .
(In case of forward action, LBA will be ON if PV does not drop more
than 2 .)

Auto-Tuning function measures, computes and sets the optimum P.I.D


or ARW Constant automatically. It can be used anytime after power is
on, while temperature is rising or when control is stabilized.
After finishing setup of P.I.D, ARW and others, perform Auto-Tuning.
Press
key and
key at the same time. Then Auto-Tuning begins
to function and AT indication lamp flashes.
When Auto-Tuning ends, AT indication lamp stops flashing
automatically. Press
key in consecutive order if you want to check
the auto-tuned values.
When changing the constants set by Auto-Tuning automatically,
change each constant according to each parameter setup method.
If you want to stop Auto-Tuning while Auto-Tuning is being operated,
press again
key and
key at the same time. Then Auto-Tuning
will be finished and AT indication lamp stops flashing. In this case
each constant of P.I.D and ARW are not changed. (Maintaining the
values before starting Auto-Tuning)
When changing SV(Set Value) during Auto-Tuning, Auto-Tuning will
be finished and P.I.D control before Auto-Tuning will be started.

Set Data Lock Function


Set date lock function prevents the changes of setup values by front
key or Auto-Tuning activation. It can be used to prevent malfunction
after setup is finished. Set Data Lock is displaying LoC by pressing
key and Lock function can be ON,OFF according to the below
parameter setup method.
0000: Set Data Lock function is OFF
0001: Set Date Lock function is ON, SV (Set Value) can be changed only.
Others: All set data and Auto-Tuning function will be locked.
Checking each setting is possible during data lock.

When 0% P.I.D computed value continues more than LBA setup


time, LBA will be ON if Process Value(PV) does not drop more than 2 .
(In case of forward action, LBA will be ON if PV does not rise more
than 2 .)

Alarm Funtion
Each alarm could be set as below table
( : Set-value (SV)
: alarm set-value)
Deviation alarm

When LBA Works


LBA function works under the following conditions
Trouble of controlled objects : Heater Break, No Power Supply,
Incorrect Wiring, etc.
Sensor trouble : Sensor disconnected, shorted, etc.
Actuator trouble: Burnt relay contact, incorrect wiring, relay contact
not open or closed etc.
Output circuit trouble: Internally burnt relay contact in the unit, relay
contact not on or off, etc.
Input circuit trouble: PV does not changed even though input is changed.
But causes of the above troubles cannot be identified, check the

High & Low alarm

Band alarm

Hysteresis

Absolute alarm

Alarm Delay Time


High & Low alarm

Delay time of High alarm and low alarm can set from SL14 and SL15.
If user set it, alarm will be available after passing delayd time.
(Cancellation of alarm has nothing to do with delay time)

Alarm with in range

Anti-Reset Windup (ARW)

Alarm within range : It operates in ALH Relay only

Set anti-reset windup from A parameter to prevent over - integral.


A = In case of Auto (0) control.

Up Scale and Down Scale


If a measured value exceeds the high setting range limit due to
upscale, etc., measured-value display stars flashing.
Further, if it exceeds the high input display range limit, the measuredvalue(PV) display unit flashes overscale display
If a measured-value becomes below the low setting range limit due to
downscale, etc., measured-value display starts flashing Futher, if it
becomes below the low input display range limit, the measuredvalue(PV) display unit flashes under-scale display

Set value

Rising time is slow


A = User setting (Set value manually)
Comparatively overshoot is big
Temperature

Model Number when Power is On


Option
Output
04: None
R: Relay
S: Voltage pulse 05: Transmission
06: LBA
C: Current
07: Transmission
+ LBA

Model
K9 : KX9N
K7 : KX7N
K4 : KX4N
KS : KX4S
K3 : KX3N
K2 : KX2N

Comparatively overshoot is not big.

Temperature

Set value

Rising time is rapid


If ARW value is too small or too big, overshoot or undershoot will
happen. Please use same value as P (Proportional band)

Select Set Value (Only for KX4S)


- Set SV1 or SV2 by Digital input
Digital input is OFF (SV2=OFF)
Display SV1, start control according to the SV1.

Version
ex) V 0.1: Version 0.1

Control Direction
Control action can select from SL9
0 : Reverse action for heating control
1 : Forward action for cooling control

Digital input is ON (SV2=ON)


Display SV2, start control according to the SV2.

Input Filter
Input filter time can select from SL11. When PV value becomes
unstable due to effects of noise, the filter helps to eliminate the
unstable status (If select [0], Input filter is off)

Input Scale
In case of DCV input, its a setup range of input range
Example, SL1=0000 (1 - 5V DCV), SL12=100.0, SL13=0.0, Input
scale is as follows.
Input voltage

1V

3V

5V

Display

0.0

50.0

100.0

Operation

Model and Suffix Code

PV / SV Set Mode
PV display
unit

Model

SV display
unit

KX N

Description

Displays process-value.
Process-value
Set-value (SV) Set-value (SV) can be set
(PV)

1 : Set-value (SV) is a control target, It is settable within the input


range.
Parameter Setting Mode
press the
key continuously for 3 sec.
Process value
(PV) display unit

1
1

Name

Initial
value

Set-value 1 -50
Set-value 2 -50
High alarm 1,300
Low alarm

-50

Set
value
Within
Input
range
Within
Input
range
Within
Input
range
Within
Input
range

Proportional
band

20

0~100 %
of F.S

Anti-reset
windup

20

0~100 %
of F.S

Integral time 240 sec 0~3600


sec

Derivative
time

3600
60 sec 0~sec

Full scalelimit 1,300

Under scale
-50
limit
0
Set data lock

KX2N

W)48

(H)96

(D)100

KX3N

(W)96

(H)48

(D)100

KX4N

(W)48

(H)48

(D)100

KX4S

(W)48

(H)48

(D)72

KX7N

(W)72

(H)72

(D)100

KX9N

(W)96

(H)96

(D)100

Size

Control output

(11pin socket type)

Relay Output

Voltage pulse output (12 V d.c)

Current output (4 - 20

Control target value 2

Alarm 1 contact (ALM) * Only for KX4N, KX4S

Alarm 2 contacts (ALL+ALH) * Exception: KX4S

Alarm 3 contacts(ALL+ALH+LBA) * Exception: KX4N, KX4S

Displays high alarm set-value

Alarm output
Displays Low alarm set-value
Set when proportional control is
performed. Control becomes
ON/OFF action with P set to 0 or
0.0 .
Prevents overshoot and/or
undeshoot caused by integral
action effect. Integral action is
turned OFF with ARW set to 0
Eliminates offset occurring in
Proportional control. Integral
action is turns OFF with this
action set to 0
Prevents ripples by predicting
output change and Improves
control stability. Derivative
action turns OFF with this
action set to 0
Indicates control loop break
alarm setting.
Displays manipulated output
cycle (sec.)

Control loop
0~7200
break alarm 480 sec sec
Proportioning
1~100
3
sec
cycle
Hysteresis
0~100 % Displays hysteresis Set-Value
of F.S for main output
(ON/OFF action) 1
2

Digital Temperatrue Contoller

Description
Control target value.

Contents

Suffix code

Within
Input range
Within
Input range

Transmitting output signal


corresponds to the full scale limit.
Transmitting output signal
corresponds to the under scale limit.

0~3

Turns the set data lock ON/OFF

1 is only for the KX4S (It is not displayed in other models)


2 is an option (If the model does not have transmitting
output, 2 is not displayed)(KX4S and KX7N can not select
transmitting output)
3 : Initial value will be changed according to contol output
(Relay output : 20 sec, SSR : 2 sec)

Option

transmission output (4 - 20
* Exception : KX4S, KX7N

None

A 100 - 240 V a.c


Power supply
D 24 V d.c

* Exception KX4S

KX4N with Alarm1 contact supports transmission output

Dimension & Panel Cutout


KX2N (48 X 96)

KX3N (96 X 48)

KX4N / KX4S (48 X 48)

KX7N (72 X 72)

KX9N (96 X 96)

Unit : (