LP-PTG-701002 Inst Spec Rev D
LP-PTG-701002 Inst Spec Rev D
LP-PTG-701002 Inst Spec Rev D
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 2 of 79
REVISIONS
PAGE
A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
REVISIONS
PAGE
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 3 of 79
CONTENTS
1.
SCOPE .....................................................................................................................................................5
2.
3.
REFERENCE DOCUMENTS...................................................................................................................6
3.1
3.2
3.3
3.4
3.5
3.6
3.7
4.
5.
5.7
5.8
5.9
5.10
6.
General ......................................................................................................................................48
Instrument Air Characteristics ...................................................................................................48
Instrument Oil Characteristics ...................................................................................................49
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
6.4
6.5
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 4 of 79
Distribution System....................................................................................................................49
6.4.1
Air distribution ............................................................................................................50
6.4.2
Oil distribution ............................................................................................................50
Return Header to Hydraulic Power Unit ....................................................................................50
7.
8.
8.2
8.3
9.
10.
10.2
11.
12.
13.
PAINTING ..............................................................................................................................................73
14.
LABELLING ...........................................................................................................................................73
14.1
14.2
14.3
15.
16.
ATTACHMENT A
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
1.
Page 5 of 79
SCOPE
This specification defines the main rules to be followed during the Instrument Engineering,
Construction and Commissioning stages for the implementation of the PECIKO VI LP
Compression Project.
These rules are to be considered as minimum requirements; so it is expected from the
CONTRACTOR /VENDOR to submit to the COMPANY, for agreement, all possible
solution that could give technical or economical improvement.
The hereafter rules shall apply to the following tasks:
2.
Detail engineering
Purchase
Inspection
Construction
Pre-Commissioning
Commissioning
GENERAL INFORMATION
The PECIKO VI LP Compression Project scope covers the following facilities:
2.1
Two new LP turbo compression trains including suction scrubbers and associated
suction coolers & discharge air cooler units.
Main Requirements
Instrumentation shall be provided to satisfy the following requirements:
Enable safe and convenient plant start-up, uninterrupted operation and controlled
shutdown,
Provide automatic protective action where deviation of plant variables could result in
a hazard to personnel or equipment,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 6 of 79
Provide information and controls to enable plant and utilities to meet the specified
requirements for safety, product quality, throughput, efficiency and economic
operation,
Provide local indication of plant variables at points, which will allow local adjustment
of control and by-pass valves. Local indication of variables necessary at plant and
equipment during start-up, shutdown or during emergency conditions shall also be
provided,
3.
REFERENCE DOCUMENTS
3.1
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
API RP 521
API RP 526
API RP 527
API RP 551
API RP 552
API RP 554
API RP 555
API STD 670
API 941
API 2000
API 2534
Status : AFC
Doc. Class : 2
Page 7 of 79
API RP 520
Revision : D
Date : May 05, 2008
Cable glands.
Test of valves.
ATEX Directives
European
Directive
94/9/EC
(23/03/94)
on
the
approximation of the laws of the Member States concerning
94/9/EC
(ATEX 100a5/ATEX 1376) equipment and protective systems intended for use in
potentially explosive atmospheres
European Directive 1999/92/EC (16/12/99) on minimum
1999/92/EC
requirements for improving the safety and health protection
(ATEX 1185/ATEX 1376)
of workers potentially at risk from explosive atmospheres
International Electrotechnical Commission (IEC)
Environmental testing Particular attention : Test Ca (Damp
IEC 60068-2-1 to 75
heat, steady state). Test Fd (Random vibration Wide Band).
IEC 60079-0 to 25
Electrical apparatus for explosive gas atmosphere.
Electrical installation in ships: Choice and installation of
IEC 60092-352
cables for low-voltage power systems.
Low-Frequency cables and wires with PVC insulation and
IEC 60189-1 to 7
PVC sheath.
Polyvinyl chloride insulated cables of rated voltage up to
IEC 60227-1 to 7
and including 450/750 V
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
IEC 60245-1 to 8
IEC 60331
IEC 60332
IEC 60529
IEC 60534-8
IEC 60801-1
IEC 61000
IEC 61131-1 to 8
IEC 61508-1 to 7
IEC 61511-1 to 3
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 8 of 79
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 9 of 79
3.2
COMPANY Documents
The following minimum COMPANY specifications shall be applied:
Reference
GS INS 101 Rev. 03
GS INS 104 Rev. 02
GS INS 107 Rev. 01
GS INS 108 Rev. 02
GS INS 110 Rev. 00
GS INS 137 Rev. 01
GS INS 146 Rev. 02
GS INS 900 Rev. 02
GS ENV 001 Rev. 02
GS ELE 001 Rev. 02
GS ELE 031 Rev. 01
GS ELE 051 Rev. 01
GS ELE 311 Rev. 02
GS EXP 101 Rev. 03
GS EXP 103 Rev. 03
GS EXP 105 Rev. 02
GS EXP 107 Rev. 02
GS EXP 205 Rev. 02
GS SAF 216 Rev. 01
GS SAF 261 Rev. 01
GS SAF 312 Rev. 02
GS COR 350 Rev. 04
GS COR 352 Rev. 04
GS PVV 142 Rev. 01
3.3
Title
Instrumentation engineering, supply and construction general
requirements
Design of the generation of instrument air or gas
Design and installation of instrumentation links
Instrumentation for the design of plant rooms and control
rooms
Instrumentation for package units
Design and supply of on/off valve control panels
Design of generation and distribution of hydraulic energy
Instrument hook-up diagrams
Environmental Requirements for Oil and Gas Projects Design
Electrical design criteria
Design of earthing and bonding system
Design and installation of lightning protection
Cable trays and ladders
Pre-Commissioning and Commissioning
Pre-Commissioning and Commissioning Technical Preparation
Pre-Commissioning Execution
Commissioning Execution
Maint. Preparation During a Project Phase Spare Parts
Area Classification
Pressure protection and relief, emergency shutdown and
depressurisation
Guidelines for selecting and installing fire and gas detection
systems
External protection of off-shore and coastal structures and
equipment by painting
Internal protection of equipment by painting
Piping valves vessels
ID-PK6-GE-TSA-075002
ID-PK6-GE-TSA-075003
ID-PK6-GE-TSA-075004
ID-PK6-GE-TSA-075006
Title
Minimum Requirements for Contractor Final
Documentation Specification
Vendor Drawings and Documents Specification
Spare Parts Specification
Packing, Forwarding & Marking Specification
QMS/QC Requirements for Vendors
ID-PK6-GE-PTG-101002
ID-PK6-GE-TSA-071001
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 10 of 79
Reference
ID-PK6-GE-PTG-122001 to 007
Title
P&IDs General Symbols (Sheet 1 to 7)
ID-PK6-GE-PTG-200201
ID-PK6-GE-TSA-205001
ID-PK6-GE-PTG-017009
Equipment List
Equipment Numbering Specification
Equipment Design Conditions Specification
ID-PK6-GE-PTG-286001
Safety Concept
ID-PK6-GE-PTG-501001
ID-PK6-GE-PTG-501003
ID-PK6-GE-JTC-702208
ID-PK6-GE-JTC-702212
ID-PK6-GE-JTC-711302
ID-PK6-GE-JTC-721502
ID-PK6-LP-PTG-280001
ID-PK6-LP-PTG-280002
ID-PK6-LP-PTG-281005
ID-PK6-LP-PTG-281006
ID-PK6-LP-PTG-282002
ID-PK6-LP-PTG-282004
ID-PK6-LP-PTG-282005
ID-PK6-LP-PTG-441001
ID-PK6-LP-PTG-601001
ID-PK6-LP-PTG-601002
ID-PK6-LP-PTG-601009
ID-PK6-LP-PTG-601010
ID-PK6-LP-PTG-602001
ID-PK6-LP-PTG-602002
ID-PK6-LP-PTG-701001
ID-PK6-LP-PTG-701003
ID-PK6-LP-PTG-701004
ID-PK6-LP-PTG-701005
ID-PK6-LP-PTG-701006
ID-PK6-LP-PTG-701007
ID-PK6-LP-PTG-701008
ID-PK6-LP-PTG-701010
ID-PK6-LP-PTG-701020
ID-PK6-GE-JTC-707211
ID-PK6-LP-JTC-283580
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 11 of 79
3.4
Order of Precedence
Except if the local Codes and Regulations are more stringent, the order of precedence
shall be:
data sheets,
particular specifications,
this specification,
Company Documents,
3.5
Depressurisation system,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 12 of 79
3.6
System of Units
ISO system will be used with the following exception.
Flow
Pressure
Liquid
Gas
Air, N2
Nm3/h
General
Vacuum
Differential Pressure
mbar, bar
Temperature
Level
Viscosity
Centipoise (cP)
Length
Analyser
Normal conditions for gas volume are 0C and 1013 mbar abs.
Standard conditions for gas volume are 15,6C and 1013 mbar abs.
3.7
AED
AGA
API
ASME
ASTM
ATEX
AWS
BPMIGAS
BDV
BPD
BPS
BS
CCTV
CI
CR
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
CP
DB
DMCMS
ED
EPSC
ESD
ESDV
ER
EWS
FAT
F&G
FGS
FO
FOC
FOS
GA
HART
HMI
HPU
HS
HVAC
ICSS
IE
IEC
IFAT
I/O
ITR
IP
IPE
IR
IS
ISA
ISE
ISO
JB
LCD
LCP
LCS
LED
LEL
MC
MCB
MCT
MOV
MIH
MAC
MCC
MTBF
MTTR
MWS
NEC
NDT
Revision : D
Status : AFC
Doc. Class : 2
Page 13 of 79
Discipline : INS
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
Control Panel
Distribution Board
Data Management and Condition Monitoring System
Explosive Decompression
Engineering Procurement Supply Construction
Emergency Shut-Down
Emergency Shut-Down Valve
Equipment Rack
Engineering Work Station
Factory Acceptance Test
Fire & Gas
Fire and Gas System
Fibre Optic
Fibre Optic Cables
Fibre Optic System
General Alarm
Highway Addressable Remote Transducer
Human Machine Interface
Hydraulic Power Unit
Hand Switch
Heating, Ventilation and Air Conditioning
Integrated Control and Safety System
Instrument Earth
International Electrotechnical Commission
Integrated Factory Acceptance Test
Input / Output
Instrument Technical Room
Ingress Protection
Instrument Protective Earth
Infra Red
Intrinsically Safe
Instrument Society of America
Intrinsically Safe Earth
International Standard Organisation
Junction Box
Liquid Crystal Display
Local Control Panel
Local Control Station
Light Emitting Diode
Low Explosive Level
Marshalling Cabinet
Main Circuit Breaker
Multi-Cable Transit
Motor Operated Valve
Maintenance In Hibit
Manual Alarm Call point
Motor Control Centre
Mean Time Between Failure
Mean Time To Repair
Maintenance Work Station
National Electrical Code
Non Destructive Test
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
NPT
NPTF
OD
OCS
OWS
P&ID
PA/GA
PC
PCS
PLC
PDCS
PSDV
RTD
RFI
SAT
SIL
SOE
SPDT
SS
SSS
TCP/IP
UCP
UPS
V AC
V DC
VDU
VFC
XV
Status : AFC
Doc. Class : 2
Page 14 of 79
Revision : D
Date : May 05, 2008
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
COMPANY
CONTRACTOR
VENDOR
NOTIFIED BODY
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 15 of 79
4.
5.
5.1
Site location: Onshore and offshore to the South of the MAHAKAM river delta, East
Kalimantan (Indonesia).
b)
c)
19,5 C
Temperature max.
35 C
Temperature design
40 C
Relative humidity
mini : 50%
Maxi :100%
In case of HVAC failure, instruments shall run properly up to the design temperature /
humidity considering temperature rising of 5C per hour.
5.2
Materials
Due to the saline effects, the use of aluminium parts (even protected by special coating)
shall be prohibited. Any deviation shall have to be approved by COMPANY.
Materials and assemblies shall be properly chosen in order to avoid galvanic corrosion
(0.3 volts maximum potential difference).
Carbon steel shall never be used without suitable corrosion protective paint (refer to
related section of this document).
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
5.3
Revision : D
Status : AFC
Doc. Class : 2
Page 16 of 79
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 17 of 79
5.4
Interference
All instruments and microprocessor-based system shall meet the following Radio
Frequency Immunity (RFI) requirements that shall be tested at the acceptance test and
performance checkout stage:
TEST
SYSTEM RESPONSE
Test 1
5W hand-held transmitter operated at 1 metre from No effect
each side panel/door, with all doors and covers in
place.
Test 2
As above with all doors open but internal covers and No damage to equipment.
Analogue values shall not change
printed circuit cards in place.
by more than 1 % Full Scale.
No other effects on operation.
TEST 3
As above, with a randomly selected input or output
module per cabinet on an extender card, if
appropriate and with all CPU and memory cards
and their covers in place. Alternatively, with one
input/output module removed.
As test 2.
The transmitters employed for test purposes shall be of the following frequency range: 50
MHz to 500 MHz and 5 W of power.
Basic reference standard is IEC 60801 (part 3) for design and manufacturing
considerations.
The above RFI requirements are to be considered as a minimum.
5.5
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 18 of 79
5.6
5.6.1
Area Classification Code for Petroleum Installations, Model Code for Safe Practice
Part 15, issued by Institute for Petroleum (IP).
Type 0 area
Type 1 area
Type 2 area
Refer to relevant Project document Hazardous Equipment Table document number IDPK6-LP-PTG-282002.
5.6.2
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 19 of 79
flameproof enclosures
"d"
increased safety
"e"
intrinsic safety
"i"
encapsulated
"m"
pressurised enclosures :
"p"
non-sparking
Use of protection mode EExp and EExn shall be limited to specific applications and
submitted to COMPANY for approval.
Within type 0 zone, electrical instrument installation shall be forbidden.
As far as possible, explosion proof protection type shall be used instead of intrinsically
safe.
Within type 1 and 2 zones, the choices to be done between the different protection levels
shall be as follows:
INSTRUMENTS AND ACCESSORIES
Level gauge illuminators (if any)
Junction boxes
All other instruments and accessories
*:
* *:
"i"
n
ZONE 1
d
e
d *
ZONE 2
d
e
d **
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 20 of 79
Particular attention shall be paid to I.S. circuits for which the whole loop must be certified.
CONTRACTOR shall perform the I.S. loop calculation notes and issue them in the loop
calculation note dossier.
For Intrinsically Safe (IS) systems, attention shall be paid to cable routing segregation and
barriers shall be of the galvanic isolation type.
ISA RP 12.6 standard shall be used as reference for installation of IS systems in
hazardous locations.
I.S. multi-core cables shall be allowed provided that the requirements of IEC 60079-11,
are fully satisfied.
In potentially explosive atmospheres only approved and marked equipment is allowed to
be used. All equipment shall be marked according to the European directive 94/9/EC
method.
Marking according to 94/9/EC:
serial number,
year of construction unless it can be clearly identified from the serial number.
CE *
***
EEX * * *
ATEX *
5.7
Certification
5.7.1
General
Each electrical instrument or system installed in hazardous area shall be built according to
IEC recommendations and corresponding national translations and publications (e.g.
UTE/AFNOR in France; VDE in Germany).
For each type of instrument, instrument circuit and enclosure containing instrument
circuits, it shall be obtained from the manufacturers (and before purchasing stage) a copy
of the certificate of conformity to the standards delivered by an agreed Certifying
Authority. Compilation of this information is achieved by the Instrument Certification
Schedule. Particular attention shall be paid to IS circuit for which the whole loop must be
certified. A dossier shall be provided with the calculation note for each IS loop.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
5.7.2
Page 21 of 79
INERIS in France,
LCIE in France,
CESI in Italy,
TV in Germany,
PTB in Germany,
NEMKO in Norway,
CSA in Canada.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 22 of 79
The notified Body shall perform the certification sequence and the main activities as
follows:
perform a visual inspection and tests of the fully assembled and pre-tested cabinet /
panel during the Factory Acceptance Tests period at MANUFACTURER premises,
perform a visual inspection and tests at site when the cabinet / panel is fully
installed, connected and energised,
CONTRACTOR shall have the responsibility to develop and issue the above design
dossier.
CONTRACTOR shall detail and complete the certification scope of work during the
detailed engineering stage.
All above certification activities are fully included in CONTRACTOR scope of work.
5.7.3
test results and certification of the degree of protection (IP code) of the cabinet /
panel,
copy of FM / UL /CSA certificate of compliance for all individual non ATEX certified
components,
residual charge and estimated discharge duration of power supply unit capacitors,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
5.7.4
5.7.5
Cables
Page 23 of 79
Field instrument
Refer to Project specification "On/Off Valve Actuators & Local Stations", document
number ID-PK6-LP-PTG-701007.
5.8
Selection of Instrument
5.8.1
General
All equipment shall comply with the requirements of the specific hazardous area where
they are installed. Specifically all field instruments shall be certified for use in zone 1 as
per ATEX European Directive.
The varieties of different instrument types to be installed on the different sites shall be as
limited as possible to minimise spares and maintenance.
For standardisation purposes, the instrumentation provided on the package shall be of the
same Manufacturer, brand and type as the one, supplied for the Project.
Instruments and accessories of the best reliability/availability and local maintenance
easiness shall be used.
All instruments and accessories shall be brand new.
Instrumentation systems shall be chosen in order to avoid penetration of process fluids in
the control and technical rooms.
All field instruments shall be specified and suitable for the related design equipment
design conditions.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 24 of 79
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 25 of 79
Enclosure protection type shall be classified in accordance with the International Electrotechnical Commission (IEC) Standard 60 529 (IP code).
Local instruments shall generally be supplied with a 2" pipe mounting device except for
pressure gauges, instrument mounted directly on the line and level instruments on vessel
or stand pipe
Instrument electrical entries shall generally be threaded 3/4" NPTF or 1/2 NPTF. Unless
otherwise specified, instrument pneumatic entries shall be threaded 1/4" NPT (if required
larger size could be selected) and process connections shall be threaded 1/2" NPT.
In general, instrument piping shall be of 316L tubing. Compression fittings of the double
ferrule type shall be used unless otherwise specified by way of process media and/or
process conditions. Tubing shall be imperial size for all equipment including packaged
units.
Instrument tubing and fittings shall be made with unpainted 316L stainless steel for
operating temperature up to 50C.
For temperature in excess of 50C, instrument tubing shall be made with painted 316L
stainless steel.
The signal transmission shall be as follows:
-
pneumatic
analogue
digital
Field electrical signals shall be transmitted over individual cables to a junction box then
through multi-core cables to marshalling cabinets inside the Technical Rooms.
As a general rule, where thresholds are derived from an analogue signal for alarm /
shutdown purposes, the transmitters from which the signal is derived, threshold shall be
selected such that no set point falls below 10 % or above 90 % of the signal.
Transmitters and actuators shall be powered, at 24V DC, directly from the control and
safety systems cabinet.
Where the signal is also required in package, UCP local panel loop powered
current/current isolators shall be provided and mounted in the local panel.
All electronic transmitters shall be "Smart" type for standardisation purposes but those
transmitters which are used for critical functions (e.g. ESD, F&G, anti-surge, etc...) shall
have their "Smart" facilities disabled. The "Smart" facilities enable/disable shall be
secured, access protected and performed at the field device only and shall not rely on the
hand held portable calibrator. The transmitters for ESD/F&G application shall be SIL2
certified.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 26 of 79
Electrical interface alarm and trip signals shall use volt free contacts powered by the
receiving system. Control principles are identical to those developed during the previous
phases. PCS Start/Stop shall be done by one volt free contact without relays in the
instrument marshalling cabinets. When the motor is running the contact is maintained
closed, when the motor is stopped is open.
Each process trip function shall have an associated pre-alarm. Pre-alarm and trip
functions shall not be derived from the same instrument.
All field transmitters shall be equipped with integrally mounted permanent digital indicators
measuring the transmitter actual range for maintenance purposes.
In the case of control valve loops an additional indicator shall be provided where required,
such that it is readable from the control valve.
The analogue transmission shall be used for the Emergency Shut Down system and the
Fire and Gas system.
5.8.2
Flow instrument
5.8.2.1
General
Flow measurement equipment shall be classified in one of the following categories:
-
Class 1
Class 2
Class 3
For flow measurement, instrument assemblies made with standard concentric orifice
plates and differential pressure transmitters shall be used as often as possible.
Flow orifice shall not be used where the anticipated turn down ratio exceeds 5:1 for non
fiscal applications. Due consideration is to be given to the maximum pressure drop
dictated by the process.
Flow differential pressure transmitters shall be built as per the relevant section of this
specification. Square Root extraction shall be performed in the Process Control System
(PCS) or Safety Shutdown System (SSS) not in the transmitter.
For Class 3 measurements the full straight piping run mentioned in ISO 5167-1 standard
shall apply. Straight length values with additional uncertainties can be used.
Detailed engineering CONTRACTOR shall be fully responsible to cross check the flow
rate requirements and provide the suitable flow meter range.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 27 of 79
5.8.2.2
General
The complete assembly material (viz. Flange and body, bolting, nuts, Carrier Ring)
excluding orifice plate, shall be as per Piping Material Classes specification,
document number ID-PK6-GE-PTG-501001. Bleed holes shall be provided
wherever it is expected to be used in measurement of two phase flow.
b)
Orifice plate
Standard construction of orifice plates used for class 2 and class 3 measurements
shall be in full accordance with concentric orifices as described in ISO 5167
normalisation, in particular for the following points of interest:
Bore accuracy,
Concentricity of bore,
Surface roughness,
Plate flatness,
Design limitations,
Calculations etc,
Design, installation and calculation of orifice plates for class 1 measurement shall be
as per AGA 3 standard.
The use of other type of flow measuring devices shall be subject to prior COMPANY
approval.
Orifice plate material shall be AISI 316L unless otherwise specified.
The beta ratio (d/D) shall be kept between 0.3 and 0.7.
Normal flowrate shall be in such a way that its value is approximately 70% of the
design flow.
Flowrate to be measured shall be kept between 30% and 90% of the design flow.
Differential pressure to be measured shall be 0-250 mbar as far as possible.
Orifice plates shall be calculated at 110% of the maximum design process.
The following other ranges may be used: 0-50, 0-125 or 0-500 mbar.
Pressure taps shall be flange type only.
Flange tap connections shall be in accordance with ANSI B16.36.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 28 of 79
Except for retractable type, each orifice plate shall be supplied with an engraved
stainless steel tag giving the following information on its upstream side:
Tag number
D and d dimensions in mm
Flange rating
Material
Retractable orifice
Retractable orifices shall have the following characteristics:
Mechanical lifting system allowing easy lifting operation even in the case
of large pressure drops and large sized orifices,
Suitable safe isolation from process (dual chamber isolating door and
double seals),
Each plate shall show the instrument tag number suffixed by a unique letter of
the alphabet and its bore diameter
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 29 of 79
5.8.2.3
General
Ultrasonic, Coriolis, positive displacement, rotameter and turbine type flow meters
shall only be used with acceptance or specification from COMPANY (generally for
accurate or large rangeability measurements).
In case of large range of flow measurement in gases or low viscosity liquids, vortex
flow meter shall be used.
The use of differential pressure instruments using the following principle shall be
forbidden:
Case
Dial
type
material
end connections
Range and
engineering unit
accuracy
Positive displacement flow meters shall be self protected against overspeed, reverse flow and shocks.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 30 of 79
c)
type 1
type 2
insertion type flow meters for pipe sizes bigger than 4"
Output signal for remote indication shall be 4-20mA analogue signal (2 wires).
The flow meter accuracy shall include the turbine accuracy and the accuracy of the
associated converter.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 31 of 79
In this case, the preamplifier should be located close to the turbine meter or located
inside the pick up coil housing.
The frequency to 4-20mA or digital signal conversion shall be incorporated to locally
mounted electronic.
The use of common mode rejection system fitted with a differential amplifier to
be installed in a cabinet in the technical room for use with receivers located in
the control room.
In this case, frequency to 4-20 mA current conversion shall be made in
technical room.
Coriolis flow-meters
Introduction
Typically a Coriolis flow meter includes an inline meter assembly (vibrating tubes
and sensors), and a local electronic transmitter to process raw sensor signal and
transmit data to a control system.
Coriolis flow meter shall be selected according to the specified process conditions
including operating as well as transient conditions such like start-up and shutdown.
Housing material of the meter tube in contact with the fluid shall be selected to suit
external environment and to provide secondary pressure containment. Pressure
containment purge fitting has to be provided.
Housing material shall be 304L stainless steel minimum.
Installation of the Coriolis system shall take into account the maximum distance
between the sensor and the electronic.
The flag mounting position shall be adopted.
Specific tools (e.g. special cable) shall be supplied by VENDOR.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 32 of 79
Sensor
Material selection of the Coriolis flow meter shall be done according to the piping
class, process fluid features and design process conditions and shall account for the
risks of corrosion fatigue associated with the cyclic loads induced by the meter tube
vibrations.
Wetted parts shall be 316L stainless steel minimum.
As a general statement, Coriolis flow meter shall be of flanged end type.
Minimum flanges rating shall be 150 lbs. Flange facing shall be chosen in
accordance with the piping classes.
2 Coriolis flow meter diameter is not allowed due to piping class constraints.
Coriolis flow meter pressure rating shall take into account the design service
temperature according to ASME B 31.3.
Coriolis flow meter must not be used to support the pipe.
An internal temperature measurement shall automatically compensate the sensor
element changes due to the temperature variations.
Electronic
Electrical connection shall be 3/4 NPTF.
Power supply shall be 24V DC (floating earth).
Coriolis flow meter shall be microprocessor based smart type and shall directly
measure the mass flow and the density.
Local visual indicator will be provided and will show:
Flow rate,
Density,
Temperature,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 33 of 79
Mass flow,
Volume flow,
Density,
Temperature,
A gold plated Volt Free Contact (VFC) output to monitor the flow direction or a
Coriolis flow meter overall fault selectable by configuration.
Liquid
0.1% from 10 to 100 % of the maximum flow
Gas
0.5% from 10 to 100 % of the maximum flow
Repeatability
Liquid
0.05% from 10 to 100 % of the maximum flow
Gas
0.25% from 10 to 100 % of the maximum flow
Density
Accuracy
Liquid
0.5 kg/m3
Gas
2 kg/m3
Repeatability
Liquid
0.2 kg/m3
Gas
1 kg/m3
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 34 of 79
Temperature
Accuracy
2 C
Repeatability
0.2 C
Loss pressure drop, accuracy and necessary straight length shall be stated on data
sheet for each process case.
The technical documentation shall clearly show the maximum flow turndown with the
associated accuracy and repeatability.
Environmental influences (e.g. pressure effect) and the relevant corrective action
shall be clearly stated within the technical documentation.
e)
Rotameters
They shall be used with specific COMPANY' s approval only.
Preference shall be given to metal type rotameters; glass tube type being only
allowed if the following conditions are satisfied simultaneously:
Metal type rotameters shall be fitted with magnetic follower systems for indication
and, if needed, transmission.
Transmission signal shall be as stated in data sheets.
Float limit stops to be provided for over-range protection.
Indications of all rotameters shall be of direct reading type.
Calibration accuracy shall be 2 % of span.
Repeatability shall be 0,25 % of span.
Temperature effect shall be 0,5% of span / 30C variation.
Body ends for rotameters shall be as follows:
top and bottom (or exceptionally side and bottom) flanged connections for
bigger instruments (with flanges in compliance with piping class specification).
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 35 of 79
Metal type rotameters shall have 316 stainless steel tubes unless otherwise
specified.
5.8.3
Level instruments
General
Level sketches showing all level related instruments (transmitters, gauges, switches, etc.)
shall be provided before placing any purchase order.
Nozzle position:
-
Wherever possible the level taps shall be the maximum distance away from the tank
inlet and draw-off nozzles.
Tapping in the bottom of drums shall be avoided. Where the operating conditions
require taps in the bottom, the nozzles shall be extended so that to penetrate of 50
mm inside the drums.
Use of stand pipe shall be allowed for instruments not related to safety system and only
when three or more instruments of a same vessel area are to be connected to the vessel.
For all interface measurements, Displacement transmitters shall be used and stand pipe
should be avoided.
In order to avoid vibration, level instruments shall be installed as close as possible to the
drum.
Level instruments shall be fitted with a drain valve and a vent plug.
5.8.3.1
General
Displacement type level instruments are the preferred method of continuous level
measurement up to a range of 48.
Displacer can be either spring or torque tube type.
Displacement type instruments shall be used for process control, alarm and shutdown
applications.
Displacer length shall be selected to fully utilise the surge capacity of the vessel.
Unless otherwise specified, the surge capacity of a vessel shall be regarded as the
highest level threshold detected on that vessel, plus 20 % of its elevation taken from the
vessel bottom tangent line.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 36 of 79
type
material
power supply
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 37 of 79
5.8.3.2
pneumatic
analogue
digital
connection
process
air
electrical
3/4" NPTF,
hysteresis
repeatability
minimum
span adjustment
zero adjustment
response time
Note:
c)
output signal
air supply
1.4 barg,
output signal
0.2 to 1 barg,
adjustment
hysteresis
repeatability
span adjustment
set point
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 38 of 79
Type
body
gauge cocks :
connections
3/4" stainless steel angle valve with ball check feature offset
type with screwed bonnet, trim to be stainless steel,
process
gauge
vent
drain
:
:
Note: Total visible length and centre to centre length shall be stated on data sheets.
The visible length shall cover:
-
If needed, and when the use of a portable lamp is not convenient to improve visibility of
level into level gauges, electrically power supplied illuminators suitably certified shall be
provided.
Gauge glass shall be used for clean non viscous liquids. Magnetic type gauges with AISI
stainless steel tube may be considered where gauge glasses cannot be used subject to
COMPANYs approval.
5.8.3.3
Level switches
Use of level switches shall require COMPANY's approval.
Level switches shall be float type. Float and mechanism shall be easily removable without
disassembly of connecting pipe work. External chamber shall have side and bottom
connections.
Top mounted type level switches may be used only if external type cannot be used. Top
mounted internal float instruments shall be fitted with stilling well.
Sufficient clearance, above the vessel, shall allow the instrument removal.
Electrical switch contacts will be sealed snap acting gold plated contact micro switches
(SPDT). Mercury bottles switches shall not be used. They shall be rated 1A/24V DC.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 39 of 79
differential
material
Connections :
chamber type
3/4" flanged,
4" flanged.
drain
3/4" flanged.
5.8.4
Pressure instruments
5.8.4.1
Pressure transmitters
They shall be manufactured as per the section Transmitters of this specification.
5.8.4.2
0 to 1-2-3-4-5-6-10-16-25-40-60-100-160-250-400-600-1000 barg,
dual scale (barg and %) shall be used when a pressure gauge is used as mean to
indicate a level,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 40 of 79
accuracy
connection
bottom connection,
1/2" NPT Male for process pressure gauge,
1/4" NPT Male for receiver pressure gauge.
5.8.4.3
accessories
Pressure switches
Use of pressure switches shall require COMPANY's approval.
They shall have internally accessible adjusters for both set point and dead band.
Adjusters shall be provided with range indication.
Sensing element shall be able to withstand at least 1.5 time the design pressure.
One sealed snap acting gold plated contact micro-switch - SPDT - rating : 1A/24V DC
shall be provided. Mercury switch bottle type shall not be used.
-
accuracy
measurement connections
Wetted parts shall be of AISI 316 stainless steel unless otherwise specified.
5.8.5
Temperature instruments
5.8.5.1
General
Platinum resistance type sensors (RTD) shall be the mean of measurement for control
and remote indication wherever the temperature is between -200 and + 500C.
Inert gas expansion type systems shall be allowed for indication on local panels as well as
local control for simple applications.
Bi-metallic dial thermometers may be used for local reading purpose when errors of
indication in excess of 1% of the span are acceptable.
Mercury in glass thermometers should be used for test measurements only.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Status : AFC
Doc. Class : 2
Page 41 of 79
5.8.5.2
Revision : D
Date : May 05, 2008
Thermowells
Thermowells shall be designed strictly in accordance with the 5.6.4 of the general
specification GS-INS-101 Instrumentation Engineering, Procurement and Construction
General Requirements and GS-INS-900 Instrument hook-up diagrams.
Thermowells shall comply with the project specification Piping Material Classes
document number ID-PK6-GE-PTG-501001.
Thermowell shall be made of one piece of metal and shall be AISI 316 stainless steel as a
minimum.
Connections shall be as follows:
-
Process
Element
Thermowells shall be design in conformity with the ASME PTC 19.3 calculations
performed by CONTRACTOR to show that all thermowells are suitable for stress and
frequency due to maximum stream velocity conditions.
A thermowell sizing and calculation summary table shall be issued by CONTRACTOR
during detailed engineering and shall be used for piping nozzles and thermowell pre-sizing
purposes (see Attachment A).
Minimum length shall consider the sum of weldolet height, pipe wall-thickness, minimum
immersed length (1/3 of piping internal diameter).
The maximum operating conditions corresponding to the most stringent operating case
shall be used instead of the line design conditions.
The thermowell Vendor/ Manufacturer shall further validate CONTRACTOR table.
Test wells used for general purposes shall be equipped with screwed plug permanently
attached with stainless steel chain.
5.8.5.3
Type
element
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 42 of 79
5.8.5.4
output signal
analogue
4-20mA - 2 wires,
digital
power supply
material
head
connections
with thermowell :
electrical
accuracy
protection
Accuracy
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Over-range protection
Transmitters
5.8.6.1
General
Status : AFC
Doc. Class : 2
Page 43 of 79
5.8.6
Revision : D
Date : May 05, 2008
Output shall be 4-20 mA with superimposed digital communication signal for smart
transmitter (PCS VENDOR standard protocol preferably or HART protocol).
Standard output shall be 4 to 20 mA (2 wires) for analogue transmitters. Output shall be
0.2 to 1 barg for pneumatic transmitters.
Electronic pressure and differential pressure transmitters shall be of the strain gauge or
capacity type.
Pneumatic pressure and differential pressure transmitter shall be of the force balance type
having diaphragm or bellow type sensing elements and 1/4" NPTF connection for supply
and signal.
Pressure and differential pressure transmitters shall have stainless steel wetted parts
unless if process fluid needs other material.
All pressure transmitters shall be installed with a block and bleed valve assembly.
When dual transmitters (one for safety, one for process control) are used for the same
process measurement, they shall have the same range and span. Process connections
shall be fully independent but shall be as close as possible to allow comparison of
measurements.
5.8.6.2
Transmitter description
Electronic and pneumatic pressure or differential pressure transmitter:
-
type
sensing element
power supply
air supply
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 44 of 79
output signal :
4-20mA through 600 ohms load for electronic transmitters,
0.2 - 1.0 barg for pneumatic transmitters,
4-20 mA with superimposed digital communication signal for smart transmitter,
body
connection :
process
1/2" NPTF
air
electrical
accuracy
hysteresis
and deadband
repeatability
0.1% of
transmitters,
calibration
span
for
electronic
0.2% of
transmitters,
calibration
span
for
pneumatic
span
range
zero elevation
/ suppression
Where pressure thresholds are derived from an analogue signal, the transmitter range
elevation shall be such that no threshold falls down below 10% and goes up above 90% of
the transmitter signal.
-
span/range units :
Pressure
barg, bara
Differential pressure
mbar, bar.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 45 of 79
Note:
For special and limited appliances, a remote diaphragm seal transmitter with remote seal
pressure element of flush type including intermediate flush ring with plugged hole for drain
or vent purpose shall be provided by the VENDOR, subject to COMPANY approval.
The flush diaphragm seals with flushing ring (one piece) shall be mounted directly on 3" or
4 flanges, supplied by others; facing and rating shall be clearly stated on data sheets.
Transmitter, capillary and separator shall be factory mounted and filled with special antifreezing transmission liquid, silicone fluid or equal.
Capillary length shall be as short as possible and stated on data sheets.
5.8.7
Receivers
5.8.7.1
General
Receiver instruments for local installation shall suit permanent working operation within
environment as specified in this specification.
Scales shall be as follows:
-
Flow
Level
0-100% linear,
Pressure
Direct reading,
Temperature
Direct reading,
Signal to valves
0-100%.
Instruments will be fitted with a label indicating the process coefficient and the engineering
unit.
5.8.7.2
Field recorder
Case for field recorders shall be of manufacturer standard suitable for offshore service
and fitted with shatter-proof front glasses and mounting accessories for 2" pipe
installation.
-
sensing element
bellow type;
bellow range
0.2 to 1 barg,
Direct process receivers (receiving process pressure, differential pressure and bulb
type temperature signal)
sensing element :
Bourdon cell for differential pressure,
Bulb, capillary and Bourdon tube for temperature,
Bourdon tube (wound helical type) for static pressure.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 46 of 79
Graduations:
-
Flow
Pressure
0-100 % linear,
Temperature
0-100 % linear.
Connections:
5.8.8
air
process
Accuracy
1 % of full scale,
Reading factors
Control Valves
Refer to Project specification Control valves document number ID-PK6-LP-PTG-701006.
5.8.9
5.8.10
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 47 of 79
5.9
5.10
5.10.1
General
On major items of equipment, where operator action is required at the equipment itself, a
detailed display identifying the fault condition shall be given local to the equipment, with a
minimum of unit common alarms provided in the control room.
In these circumstances, acceptance in the control room should not alter the state of any
local alarm light. Any subsequent fault shall reactivate the unit common alarms.
The alarm sequence shall include the first-up facilities to ISA S18.1.
The alarm sequences shall allow two flashing speeds:
-
slow flash
20 5
fast flash
110 30
Alarm logic shall be accomplished by electronic blind alarm sequences installed in racks.
These racks will be integrated within the local cabinets.
5.10.2
Illuminated display
1)
2)
Where annunciators are used, the windows shall be grouped in display boxes with a
maximum of 7 adjacent vertically. A preferred arrangement is 5 x 3.
3)
4)
In the absence of an alarm, the relevant display window shall be dark; a dim light is
not acceptable.
5)
6)
At least one "lamp test" and where appropriate an "accept" and "reset" button shall
be provided for each unit on the relevant panel section. However, more buttons may
be required depending on panel layout.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 48 of 79
7)
Different colours as specified shall be used for indicating lights and display windows
to differentiate the following categories:
-
Trip action
Magenta,
Alarm (action)
Amber,
Status
White.
green,
red.
8)
Red shall be an indication that an electrical circuit is energised, green that it is deenergised.
9)
e.g. PAHH-2415A,
Location
Alarm
VENDOR shall advise maximum number of characters versus height per line.
6.
6.1
General
Air distribution network shall take into account the following considerations:
Plant layout,
Service air shall be totally segregated from the instrument air network.
Note: All pneumatic instruments shall be able to operate with a minimum air pressure of
4.5 bar g at instrument inlet.
6.2
10
4.5
Oil free
< 1 ppm
Temperature C
Dew point C
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 49 of 79
6.3
220
180
150
130
(Also refer to Project specification Hydraulic Power Unit document number ID-PK6-LPPTG-701010).
6.4
Distribution System
For detail of distribution principle refer to specification GS-INS-104 Design of the
generation and distribution of instrument air or gas.
Distribution system shall easily permit future extensions (30% spare) and distribution even
if a part of the plant is stopped.
Except for main feeder, the instrument air sub headers should have the same routing and
supports as the instrument cables routing.
Instrument air / oil supply sub headers shall have the following minimum sizes:
1/2"
for up to 5
1"
1 1/2" for 21 to 50
distributed points,
2"
for 51 to 100
distributed points,
3"
distributed points,
Instrument oil return sub headers shall have the following minimum sizes:
3/4"
for up to 5
1"
return points,
Air instrument network shall have a slope to ensure constant drainage. Low point shall be
equipped with drain valves.
Instrument air network is designed to ensure a Maxi pressure loss of 0,7 bar g @ Max
flow.
Materials used for instrument air/oil distribution shall be in line with related piping class
specification (for all parts located upstream the instrument air or gas feeding manifolds).
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 50 of 79
Feeding manifolds shall be made of stainless steel 316L as well as all parts installed
downstream.
6.4.1
Air distribution
Future take off points fitted with valves shall be installed on the main feeder. Derivations
on main feeders on racks shall be 1" minimum size. Derivation on secondary feeders shall
have 1/2" diameter.
All derivations shall be taken at the upper part of the feeder and shall be isolated by ball
valves.
Local panels containing pneumatic instrumentation shall be provided with a common dual
filter/pressure regulator/pressure gauges assembly.
Filter regulator, fitted with pressure gauge, shall be installed for each air/gas pneumatic
instrument supply. Air set shall be SS 316 L.
Individual instrument air/gas tubing, fittings, and accessories installed downstream the
filter pressure regulator shall have the following characteristics:
Material
Size
For utility balance sizing purpose, a usage factor of 0.1 will be considered for intermittent
consumers, like On / Off actuated valves.
6.4.2
Oil distribution
For oil distribution principle and applicable installation rules, refer to project specification
Hydraulic Power Unit document number ID-PK6-LP-PTG-705010.
6.5
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 51 of 79
External hydraulic return lines to hydraulic reservoir shall be supplied and installed by
CONTRACTOR.
7.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
8.
INSTRUMENT INSTALLATION
8.1
Page 52 of 79
Instruments shall maintain accuracy and repeatability all along their working life,
All mechanical stress exceeding the maximum values given by the instrument
Vendor shall be avoided by means of appropriate choice of mounting principle,
Important:
All instruments shall be mounted close coupled to the process unless otherwise specified.
For instrument mounting, the tubing technology shall be used (according to ASME
B36.10), except for level instruments.
All fittings and accessories (valves, unions, tees, reducers) downstream the piping block
and bleed manifold shall be made of AISI 316 as a minimum requirement with double
ferrule SWAGELOK fittings.
Tubing shall be AISI 316L stainless steel. Tubing shall be imperial sizing.
Choice between socket welded, flanged or NPT screwed connection to piping block and
bleed integrated manifold shall be done taking into account parameters such as pressure,
temperature and fluid type. Refer to Instrument hook up standard for a proper choice
according to piping classes.
Selection of single piping isolation, single or double piping block and bleed integrated
manifolds used for vessel and piping connections shall be done as described on the P&ID
s Instrumentation symbols drawing numbers ID-PK6-GE-PTG-122001 to 007.
Generally double block and bleed integrated manifold shall be used with operating
pressure equal or above 70 bar g.
A particular attention shall be paid to instruments submitted to vibrations (compressors
and/or heavy instruments with flange connections lower than 300 lbs). In such cases,
instruments shall be suitably supported and process nozzles for instrument impulse pipe
shall be bracketed.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 53 of 79
Instruments connected to small size process pipes or pipes made of synthetic material
shall be suitably supported.
Instruments shall be installed on 2 pipe support. The number of 2 pipe supports shall be
limited as far as possible. If process pipe translation is not expected, supporting of
instrument using existing structural beams is preferred.
8.1.1
Flow instruments
a)
Orifice plates
As often as possible, orifice plates shall be mounted on horizontal part of the piping.
If not possible, vertical mounting shall be up flow for liquids and down flow for
gases.
Straight length requirements are given by ISO 5167-1 standard. Bracketed values
with 0.5% additional uncertainty can be used.
Before installation, orifice plate bores shall be carefully inspected for concentric
roundness, sharpness and absence of burns and nicks.
b)
Gas flowmeters
Flowmeters shall be installed above orifice plates, taps will be vertical.
On vertical pipe, impulse pipes to transmitters shall have 15 minimum slope
in order for the condensates to flow back to the process pipe.
Liquid flowmeters
Taps shall be at horizontal position. The transmitter shall be mounted under
the orifice plate. Sufficient clearance shall be made available between
adjacent process lines in order to allow easy installation and handling of block
valves and associated fittings.
If two flowmeters are mounted on the same orifice plate, the four taps of the
flanges shall be used.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Status : AFC
Doc. Class : 2
Page 54 of 79
Revision : D
Date : May 05, 2008
Integrated manifolds
They shall be used for close coupled flowmeters and shall be of the 5 valves
type (2 for isolation, 1 for by-pass purpose, 2 for purge/drains). Integrated
manifolds shall never be used in combination with liquid sealing systems.
c)
Inline flowmeter
Inline flow meter shall be mounted as per VENDOR recommendations. Special
attention shall be paid to orientation of the meter and supporting. Unless there are
specific reasons, coriolis shall be installed in vertical.
8.1.2
Level instrument
Unless otherwise specified, each instrument shall have its own impulse pipes.
Use of stand pipe shall be allowed for instruments not related to emergency shutdown
system and only when three or more instruments of a same vessel area are to be
connected to the vessel.
A level instrument impulse pipe shall never enter at the bottom side of a vessel.
If this rule cannot be satisfied, a 50 mm pipe length shall be extended within the vessel
and adequate cleaning/flushing facility provided.
a)
b)
c)
Level switches
Top mounted level switches shall be used as rarely as possible (if used, a 4" top
flange and a stilling well shall be supplied with the vessel).
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 55 of 79
External level switches shall have side and bottom oriented 3/4" connections. A
drain valve shall be supplied.
d)
Level gauges
Each level gauges shall be fitted with a plugged vent tap and a purge tap fitted with
a full bore isolating valve and plug (if drained product are not collected).
Fluid connections shall be top and bottom in order to permit orientation of the
gauge.
8.1.3
Pressure instruments
General
Pressure instrument taps on pipes shall be 3/4" sized. Different sizes may be
exceptionally taken into account (for mechanical seal for example).
Block and bleed valves shall always be supplied unless if process or safety requirements
forbid it. Two instruments shall never be connected to the same process tapping point.
Manometers mounting accessories shall not cover the safety disks insert. A block and
bleed type integrated manifold shall be installed as standard.
Horizontal process pipe
-
Gas service
The instrument tap shall be located on the process pipe upper generating line.
Liquid service
Impulse pipe shall be horizontal and located at the axis of the process pipe for
transmitters.
Manometers shall have vertical impulse pipe and taps located on the upper
generating line.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 56 of 79
8.1.4
Temperature instruments
Connection of the thermowells to the process pipe shall be done by 1 1/2 minimum
flanged connection (2" nozzles on tanks and vessels), choice being made in line with the
project hook-up standards and the results of the thermowell stress calculation performed
by CONTRACTOR which may lead to larger thermowell diameter and flange.
On horizontal pipes, the thermowell shall be mounted on the upper part of the pipe.
For pipe size lower than 4", a 4" size expanded pipe shall be created. The thermowell
bore shall then be welded on the expanded part of this pipe in order for the sensitive part
of the element to be located near the axis of the process pipe.
Line mounted thermowell flange rating shall be the same as the line rating.
8.1.5
Control valves
Control valve location shall permit easy access and maintenance operations to the valve
body as well as to the positioners or actuators.
Control valve bypass shall include all isolatives, drain and throttling valves as per
COMPANY Standard Arrangement.
8.1.6
Vessels
Pipe
Tank
Connection
to
Instrument
Thermowells
(Notes)
2" flanged
1 1/2 flanged
2" flanged
2" flanged
3/4" flanged
2" flanged
1/2"
1/2"
Pressure transmit.
2" flanged
3/4" flanged
2" flanged
1/2"
1/2"
2" flanged
3/4" flanged
2" flanged
1/2"
1/2"
2" flanged
2" flanged
3/4"
4" flanged
4" flanged
3/4"
2" flanged
2" flanged
1/2"
1/2"
Level gauge
2" flanged
2" flanged
3/4" flanged
1/2"
Level switch
2" flanged
2" flanged
3/4" flanged
3/4"
4" flanged
4" flanged
4" flanged
CONNECTION TO EQUIPMENT
Vent.
and
drain
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 57 of 79
Vessels
Pipe
Tank
Connection
to
Instrument
)Depending on
) piping class
) & diameter
1/2"SW or
1/2"
1/2"
CONNECTION TO EQUIPMENT
Vent.
and
drain
1/2" NPT
Pitot tube
3" flanged
Notes:
8.2
Instrument Accessibility
Each instrument shall be considered as a normal working location and therefore shall be
located in order to satisfy workers safety conditions as well as efficiency.
Instrument accessibility being able to induce heavy consequence on piping or platform
layout, this problem shall be considered as soon as possible during the detailed
engineering stage.
Instrument accessibility shall be shown on piping or platform layout drawings.
It shall be important to distinguish two kinds of working location:
-
A working location shall be considered as permanent when visit frequency is higher than
once a month.
Non permanent working location shall have visit frequency lower than once a month.
For permanent type, the access shall be easy. Platforms are requested, movable ladder
forbidden.
For non permanent type, movable ladder shall be allowed if height is less than 3 meters. If
more 3 meter, scaffolding shall be used.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 58 of 79
control valves,
transmitters,
local controllers,
local converters,
in-line flowmeters,
level gauges,
level switches,
pressure switches,
Fire and Gas detectors (Particular attention must be done for accessibility
(calibration and maintenance operations) to F&G detectors, smoke detectors, IR
barrier)
corrosion probes.
Shall be considered as non permanent working location the following types of instruments:
-
Orifice flanges,
Pressure taps,
Pressure gage,
Thermocouples or resistance,
Thermowell.
8.3
8.3.1
Cable design
Cable design shall be as per Project specification Instrument cables document number
ID-PK6-LP-PTG-705003.
Cables calculation notes shall be performed by CONTRACTOR for all solenoid valves, fire
and gas detection loops, and any lengthy or special cables.
All cables connected to instruments, local control panels, UCP s, control and safety
systems and associated field marshalling cabinets shall be single or multi pair / triple /
quad screen cable types with:
-
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Status : AFC
Doc. Class : 2
Page 59 of 79
8.3.2
Revision : D
Date : May 05, 2008
Cable installation
Cable conduits shall not be used unless specifically approved by COMPANY.
Electronic and signal wiring shall be adequately segregated by using dedicated cable
ladders / trays from power wiring and electrical equipment to minimise electro-magnetic
interference.
Redundant communication cables shall be routed by two different ways.
The following minimum distances shall apply,
for Low Voltage (LV) :
-
110 V
10
600 mm
230 V
50
600 mm
400 V
200 A
600 mm
1000 mm
5.5 kV
800 A
A particular attention shall be paid to protection against interferences related to serial links
and very low level signal cables.
Cable routings shall be segregated as follows :
Service
Very low level
Analogue 4 - 20 mA
Digital
Solenoid valve
Power supply
System communication network
Intrinsically safe
X
X
X
X
X
X
X
X
X
The above table shall be further completed with any additional cable types during detailed
engineering phase.
Instrument cables shall be grouped by service and separated by a 10 cm minimum
distance.
Fibre optic cables (FOC) can share the same routing and cable ladders / trays used for
other instrument cables with the exception of IS cables which have dedicated routing.
FOC shall be separated from other instrument cables with separator by a 10cm minimum
distance.
Telecommunication cables shall be routed on dedicated cable ladders / trays.
Cables carrying different type of signals shall not be run in the same cable trays.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 60 of 79
Cable crossing on the same level is forbidden. Crossing between instrument cable and
power cable runs shall be made at right angles at 0.3 m minimum distance.
All cores shall be connected on terminal blocks including spare cores and unused cores.
More than one core connected within one terminal is forbidden.
All spare cores shall be identified.
External and internal cables shall be installed as per Project specification Cable Trays
and Ladders and Trays document number ID-PK6-LP-PTG-601010.
Cable ladders / trays dimensions shall be adequate to accommodate 30% of spare
cables.
Cables trays/ladders systems shall be of the following types:
-
Outdoor:
Indoor
Cable ladders shall be used for all cable routes 300 mm width.
Cable trays shall be used for cable routes < 300 mm width.
Only one cable layer shall be allowed on cable trays which are used for common routing
to several process/utility units and which are expected to be used for future plant
expansion.
Cable tray and cable ladder segregation shall follow the signal segregation as defined in
section 8.3.2.
Cable clamping strips for fixing cables on cable ladders / trays shall be of coated stainless
steel material
Cable ladder / tray elements shall have limited size and weight for easy handling.
Cable ladder / tray change of direction shall be made at oblique angle and be compatible
with the cable bending radius.
All cutting parts, burrs and sharp edges of ladders / trays shall be removed.
Partition shall be installed on cable ladders / trays, which share cables and air lines.
All cables ladders and trays shall include covers.
Control and technical rooms cable routings shall use dedicated cable ladders / trays as
per the above segregation rules.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 61 of 79
Control and technical room cable entry shall use certified water tight and fire resistant
transits (MCT).
8.3.3
Junction Boxes
Junction boxes shall be made of stainless steel or UV resistant and flame retardant
Glass fibre Reinforced Polyester. The glass fibre reinforced polyester shall be made to
avoid static electricity build up.
For junction box, a minimum protection index is IP 65.
Separate junction boxes shall be used for the following cable segregation:
Type of signal
Electrical
Intrinsically safe
PCS ESD F&G
UCP
Power supply
ESD0
PCS
UCP
ESD
F&G
ESD0
Analogue 4 - 20 mA
Digital
Solenoid valve
CONTRACTOR shall be further completed the above table with any additional signal
types during detailed engineering phase.
All junction boxes (IS or not) shall be EEx "e" (Increased safety) certified.
Only one multicore cable shall be connected to each junction box.
Dedicated JBs shall be allocated to each process system. Mixing of cables for different
process system is not allowed.
All cables shall enter the bottom part of JBs only. No side or top entry is allowed.
Copper gland plate shall be provided for cable gland earthing of non metallic junction
boxes. The gland plate shall be positively earthed.
Gland plate is not required for metallic junction box.
Junction boxes shall be fitted with an extension earth terminal.
All multi-pair/triple cable cores shall be connected on spare terminals within junction
boxes.
Dedicated terminals shall be used for overall and individual cable screen termination in
JB's.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 62 of 79
An insulated earth bus bar shall be used for overall cable screen termination inside the
junction box.
Spare are to be provided as follows:
-
Multi-pair cables :
10 % of spare pairs/triads/quads,
junction boxes
20 % spare terminals,
8.3.5
Cable glands
Glands shall be EEx"e" or EEx"d", certified, acceptable for outdoor use and installation in
Zone 1 or Zone 2 hazardous areas, according to the classification of their location. They
shall be T3 temperature-classified.
Glands shall be double seal compression type and manufactured as per BS 6121, to
provide sealing of inner and outer sheaths and clamping of cables braided armour by a
special ring. They shall be disconnect able / reconnect able without degrading the
tightness.
Cable glands shall be made of brass with 16 micrometers of nickel plating.
Glands shall be NPT threaded.
For EEx"e" enclosure, cable glands shall be metric type and shall enter the enclosure
through a clearance hole with a sealing washer to achieve an IP 65 protection.
Each gland shall be supplied with a flame retardant heatshrink PVC protective sleeve.
Gland grounding of the cable armour shall be in accordance with the applicable code for
the connected equipment.
Cable gland plate arrangement shall allow the removal of one cable gland without
removing any other gland fitted on the same gland plate.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 63 of 79
9.
10.
10.1
10.1.1
Definition
10.1.2
Panel
Cabinet
General
The following general requirements shall be followed for all control panels and cabinets:
-
easy access shall be provided to all equipment and connections in order to facilitate
the installation and maintenance with minimum amount of dismantling or removal of
equipment,
consideration shall be taken to easily hoist and handle control cabinets and panels,
satisfactory ventilation,
front and rear access in line with the room layout requirements,
20 % spare space.
all cables shall enter the control panels and the cabinets from the
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 64 of 79
cables marshalling and field cable termination (separate cabinets per type of control
systems),
PCS equipment,
SSS equipment,
F&G equipment,
electrical distribution,
DMCMS
UCPS
miscellaneous.
Construction
Material
The control panels and cabinets shall be totally enclosed by a galvanised steel sheet, its
thickness shall be as follows:
-
2 mm for doors,
the metal sheets shall be reinforced with steel beams welded together, where
necessary,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 65 of 79
care shall be taken to have the faces of panels flat and smooth,
panels and cabinets shall be fixed to the frame using anti-vibration mountings,
panels and cabinets shall be shipped as single or dual bays but shall never exceed
1200 mm width.
Miscellaneous
The following facilities shall be installed in each control panel/cabinet:
-
internal lighting (at the top of the panel/cabinet) controlled by a door switch,
a normal 230 V AC power socket (Indonesian standard) outlet for instrument supply,
ventilation louvers and filtering units to avoid the creation of local hot spots and
ensure adequate heat dissipation and dust protection. Natural ventilation is
preferred but forced ventilation can be used when necessary.
forced ventilation shall be provided with twin paralleled systems each rated at 100 %
duty with maximum noise level less than 55 dBA at 1 meter. Each system shall be
fed from the cabinet power supply distribution (normal 230 V AC) with dedicated
fuses, MCBs and switches,
each panel and cabinet shall have common alarms (VFC) for power supply, fan
failure, high temperature alarms for reporting to PCS at control room.
control panel / cabinet sealing bottom plate with cable access equipped with brush
edges,
(Refer also to Project specification Instrument Earthing Principle document number IDPK6-LP-PTG-701005).
These bus bars shall be connected by CONTRACTOR to the relevant plant earthing
network.
Cable entries for the earthing cables shall be provided by the supplier of the enclosure.
Control panels particular requirements
Panel frame shall be made of carbon steel. Stiffeners and gussets shall be fitted where
necessary to ensure rigidity and proper support for instruments and other fittings.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 66 of 79
Control panels shall be selected for flawless and truly flat surfaces. All subsequent
machining methods shall be selected and applied in a manner to ensure that distortion
does not occur. Any stiffeners or instrument supports shall be arranged so as to avoid
distortion of the panel surface.
Control room panels shall be of the single (front) access type and fitted with swing frame
(if necessary) for rear access to equipment.
Cabinets particular requirements
With the exception of marshalling and power supply cabinets, all cabinets located in the
instrument technical room shall be from the same manufacturer, model and type and shall
be of 19 inches normalised construction according to IEC 60 297.
Cabinet dimensions shall be 600 mm (or 800 mm) width x 800 mm depth and 2100 mm
high (100 mm plinth).
Instrument technical room cabinets shall be of the front and back access type or
exceptionally of swing frame type (to be approved by COMPANY).
Cabinets/Panels supporting
All cabinets and panels shall be bolted to a supporting plinth (100 mm high) clamped or
bolted to deck frame cabinet steel support to allow for on site installation of anti-vibration
mountings.
Painting
The final colour coating shall be RAL 7035.
The minimum paint system shall be:
-
surface preparation :
Degreasing,
Rinsing,
Phosphatation,
Drying.
1st coat
2nd coat
60 microns.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
10.1.4
Revision : D
Status : AFC
Doc. Class : 2
Page 67 of 79
Wiring
All equipment and termination shall be arranged so as to be readily accessible for fault
finding and maintenance.
Field cables shall be clamped at the bottom of cabinet / panel on clamp rail.
The marshalling cabinets shall be equipped with a double row of terminal blocks to allow
crossing of wires.
Interconnections between all marshalling cabinets, control panels and cabinets shall be
designed such as to minimise the hook up works.
Plug and socket arrangement shall be used between the above cabinets as much as
possible.
Cross wiring and shipping breaks between cabinets included within a single row shall be
avoided.
All interconnecting cables shall be terminated on dedicated terminal blocks. Cables shall
not be terminated directly on the terminal on the input / output cards / signal conditioning
termination panel of the control / safety systems.
Terminal blocks shall be of non-hygroscopic material, and incorporate slipper type
terminal clamps or spade type terminals.
The outgoing terminals shall accept 0.5 - 2.5 mm conductors and shall provide sufficient
termination capacity for all permissible field wiring configurations.
Outgoing wires shall be terminated in Klippon type SAKR terminals or equivalent fitted
with socket screws. The knife edge switch shall be pivoted on the panel equipment side.
Fused terminals shall be used for solenoid valve cabinet wiring and instrument with
external power supply (3 wires type).
Powered outputs shall be terminated on terminal blocks.
All terminal blocks/sockets shall be logically arranged with signal levels suitably
separated. Sufficient slack wire neatly coiled or looped should be allowed at all
termination to allow for remaking, additions and testing.
All terminal blocks/sockets shall be grouped and labelled in functions ; i.e. inputs, outputs,
volt free contact, powered outputs, PLC, etc. in such a way that confusion cannot arise or
field circuits cannot be erroneously connected.
Common conductors are prohibited.
All spare cores shall be connected.
No soldered connection shall be allowed.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 68 of 79
Wiring shall be neatly laced or where practical, laid in rigid plastic trunking, and covered.
Colour coded trunking is not required. Separate trunking shall be provided for signal and
power wiring runs to avoid cross-talk.
Trunking shall be sized so that no more than 40 % of the cross-sectional area is filled with
conductors and shall be located so as not to interfere with access to any equipment and
not to encroach on space allocated for future equipment.
All wiring shall be ferruled for identification at each termination point. Ferrules shall be of
the sleeve type. Clip on or wrap type shall not be used.
Signal wiring shall be 0.5 mm stranded. All other wiring shall be 0.75 mm stranded
minimum, and adequately rated.
Stranded conductors shall have crimped ends for insertion into terminal blocks (only one
conductor per terminal).
All wiring shall have 600 V insulation rating with fire resistance in accordance with IEC 60
331 or PVC flame retardant insulation 600 V in accordance with IEC 60 332 (Part 3-22:
Tests of vertically-mounted bunched wires or cables - Category A.) grade and of insulation
value not less than 10 megohms (M).
Each wire and shield of measuring cable shall be connected on various equipment in the
following order: +, -, shield.
Wiring shall be colour coded as follows:
- power
- IPE
- IE
- ISE
- fire
- gas
- system alarms
- signal, control
- IS control
10.1.5
24 V DC
Red (+ VE) - Black
(- VE)
Green/Yellow
Green
Blue/Yellow
Pink
Yellow
Grey
Black
Blue
230 V AC
Brown (L1) - Red (L2)
10.1.6
Interposing relays
Relays shall be included on loops which interface different control / safety systems for
electrical isolation purposes, interfaces, etc. These relays shall be SIL3 certified for all
SSS outputs.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
10.1.7
Revision : D
Status : AFC
Doc. Class : 2
Page 69 of 79
Lightning protection
Lightning protection shall be as per the Project requirements of Design and Installation of
Lightning Protection, document number ID-PK6-LP-PTG-601009.
10.1.8
Labelling
Equipment numbering shall be as per the Project requirements of Instrument
Identification and Numbering document number ID-PK6-LP-PTG-701020.
Each component shall be identified by its unique equipment number defined by Supplier
and affixed to the front face.
All instruments will be labelled in two ways.
Nameplates shall be manufactured from AISI 316 stainless steel and nameplate
characters shall be 20 mm high, boldly engraved and filed black. All accessories, screw or
rivet shall be in stainless steel.
Laminated engraved nameplates with white plate and black letters shall be used for
cabinets located in technical room and for all components located inside the cabinet.
For F&G system and safety shutdown system, the plate shall be with a red background
with white letters.
Each power and earthing connections shall be permanently and durably labelled.
10.2
free standing units shall be designed with base frame work and plinth or with legs,
and shall have a minimum of four bolt down points. On all cabinets, free-standing or
wall mounted, removable lifting eyes are required on top, each one strong enough to
support the fully equipped panel during handling, shipping or placing operations,
VENDOR shall install all instruments, display units, switches, air header and tubing,
electrical terminal boards/blocks, wiring system supports and ancillary fittings,
suitably mounted and supported, ensuring good accessibility of all items for
maintenance and/or inspection,
Instruments on the front face which require adjustment or which have dials that must
be easily inspected, shall be fitted between a height of 1.0 m and 1.8 m with no part
lower or higher,
the construction of each unit shall be designed to prevent the ingress of dust and/or
moisture in quantities which could be harmful to the contained equipment. The
degree of protection required will be IP 65 unless stated otherwise,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 70 of 79
where doubt exists on weather tight enclosure of instruments fitted to the front face,
a front cover and/or canopy which enable compliance with weather proofing
requirements and still provide visibility of dials, annunciators and access shall be
provided,
VENDOR shall group the connections to the cabinet into the following categories:
process, pneumatic, hydraulic, electric power, electric control wiring and intrinsically
safe connections.
Material
Local control panels/cabinets shall be made of AISI 316 stainless steel for all parts except
for internal parts forming secondary structures which may be of AISI 304. Plastics may be
used, subject to COMPANY's approval, for minor supports and electric cable trunking.
Aluminium shall not be used unless specifically approved by COMPANY.
Panels/cabinets layout and arrangement shall provide segregation of the following groups
of equipment:
-
Electrical
The design and installation shall conform to the requirements of the applicable I.E.C.
Recommendations.
VENDOR shall supply all sundries and install and wire all electrical, instrumentation and
accessories. The panel/cabinet shall be complete and ready for site connections to power,
ground, and in/outgoing field connections.
Electrical components shall not be mounted in or on the section allocated to instruments
in contact with process fluids.
Wiring shall be on cable trays, in trunking, or on vertical wire racks designed so as to
produce a neat and accessible layout, properly supported.
Miscellaneous
The following shall be installed in each unit:
-
an internal lighting,
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 71 of 79
Dedicated terminal block and gland plates shall be provided for incoming and outgoing
field cables, including future cable requirements, and shall be prepared for gland and
cable sizes as per specifications.
Cable clamps shall be supplied for the support of field and inter-connecting cables.
20% spare terminals are required for all entries into terminal boxes, gland plates and
clamps. Similar spare capacity shall be provided in the cable trunking.
Painting shall be performed as per COMPANY General Specification GS-COR-350
External protection of structures and equipment by painting.
11.
INSTRUMENT EARTHING
(Refer also to Project specification Instrument Earthing Principles document number IDPK6-LP-PTG-705005).
Field instrument cases and junction boxes cable gland plates shall be earthed using a
6mm conductor between earth tag on instrument or junction box and earth lug on
supporting steelwork.
Supporting steelwork for instruments/junction boxes shall be connected to platform earth
system using a 35mm conductor.
Cable armour shall be earthed at both ends of cable.
Cables screens shall be earthed at one point only (in instrument room cabinets or panels),
except for analogue cable overall screens which are grounded both end to IE.
Continuity of screens shall be maintained from field instruments throughout cable run to
the technical room or control room.
Individual and overall cable screen shall be connected to dedicated screen terminals
inside junction boxes, and directly to a dedicated common IE bus bar inside the panels
and cabinets.
Overall screen of digital signal cables shall be connected to an insulated instrument earth
bar inside the junction boxes and directly to a dedicated common IE bus bar inside the
panels and cabinets.
Earthing of screens within instrument room shall be performed in the marshalling cabinets
at the appropriate earth bar.
Impedance from any instrument earth bar to earth shall be less than 0.5 Ohm.
Connection between technical room/control room earth bars and platform earthing system
shall use 70mm conductors.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 72 of 79
Overall screen of multi pair cables between marshalling cabinets and systems cabinets or
panels shall be insulated and isolated from earth at marshalling cabinet and earthed at
systems cabinets or panels.
In panels or cabinets, following earth connections shall be segregated and shall use
dedicated earth bars connected to the platform / plant relevant earthing network:
-
All panels or cabinets shall be fitted with three above earth bars.
The dedicated earth bars shall be connected to the equipotential bonding system of
general earth grid and internal loops in accordance with Project specifications Design of
Earthing and Bonding systems document number ID-PK6-LP-PTG-601002 and Design
and Installation of Lightning Protection document number ID-PK6-LP-PTG-601009.
12.
INSTRUMENT HOUSING
For specific cases (e.g. transmitters for gas metering) instrument housing may be
required.
Instrument housings shall be made of flame retardant antistatic high density reinforced
polyester or equal (with shatterproof front glass if the instrument is an indicator).
Good thermal insulation is required.
Housing shall be supplied fully equipped with internal mounting brackets for transmitter
installation and with external mounting brackets for hook up facilities on a 2 inches pipe
support.
The housing dimensions shall be suitable for normal operation and maintenance.
The housings shall be provided with quick opening hatch.
All metallic parts shall be corrosion proof (stainless steel).
Instrument housings shall be designed and installed in order to be easily removed, for
repair or maintenance purpose.
Earthing of metallic type housings shall be performed as per Project specification
Instrument Earthing Principles document number ID-PK6-LP-PTG-701005.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
13.
Page 73 of 79
PAINTING
Special care shall be taken to protect surfaces like sight glasses, instruments labels,
instrument windows, control valve stems and positioner levers against paint during pipes
and structure painting operations.
All mounting devices and accessories, like instruments brackets and supports for cable
trays, junction boxes frames, shall be painted according to COMPANY General
Specification GS-COR-350 External protection of off-shore and coastal structures and
equipment by painting.
14.
LABELLING
14.1
Instrument Symbolisation
The instrument symbolisation applicable for the project is defined on drawings "P&ID
General Symbol Sheets 1 to 7" drawing numbers ID-PK6-LP-PTG-122001 to 007.
14.2
14.3
Labels
All labels shall be manufactured with materials giving full guarantee concerning long
service within aggressive environment.
All instruments and tubing connections shall have rigid stainless steel tag stamped with
the assigned project tag numbers.
In addition, instrument nameplates laminated type shall be engraved and installed on
support close to the instrument:
-
Red with white letters for instrument used for Safety Shutdown System.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 74 of 79
All field instruments shall also be identified with a permanent label showing the instrument
tag number which will be installed on the instrument support.
Cables shall be labelled with tamped stainless steel or polypropylene markers attached to
the cables by stainless steel collars.
Cable identification markers shall be fitted at each following location:
15.
material,
scale,
operating range,
labelling,
painting,
accessibility,
calibration certificates.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Revision : D
Status : AFC
Doc. Class : 2
Page 75 of 79
Instrument manufacturers shall test and calibrate each instrument at factory against
the specification and data sheet requirements.
Each instrument shall have a calibration certificate which shall include :
measure
threshold
20% of the supply for transmitters, local controllers or panel controllers and
other non listed items,
100% of the supply for flow orifices and non standard control valves.
If a defective item is found, a new sample shall be controlled and if a new defective
item is found, the whole set shall be rejected.
All rejected items shall be replaced by satisfactory ones at VENDORs cost, without
delivery time delay.
-
wiring checking,
earthing checking,
The Site Acceptance Tests (SAT) shall be performed as per the requirements of the
relevant pre-commissioning and commissioning specifications.
for integrated system such as the Process Control System, SSS, etc., the related
acceptance tests and check-out are fully described in the relevant specifications.
Refer to these documents for further information.
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
16.
Revision : D
Status : AFC
Doc. Class : 2
Page 76 of 79
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-701002
SPECIFICATION
Document type: SPE
System/Subsystem :
Discipline : INS
Status : AFC
Doc. Class : 2
Page 77 of 79
ATTACHMENT A
Revision : D
Date : May 05, 2008
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Document number
ID-PK6-LP-PTG-7010002
Revision : D
Document type :
SPE
System/Subsystem :
Discipline :
INS
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.
Status : AFC
Page 78 of 79
Document number
ID-PK6-LP-PTG-7010002
Revision : D
Document type :
SPE
System/Subsystem :
Discipline :
INS
Status : AFC
Page 79 of 79
COMMENTS TABULATION
Page Of
document
48
Comment nb
Company Comment
Comment # 1
50
Comment # 1
Implemented
(Y/N)
N
Explanation
Minimum air pressure of
4.5 bar g at instrument
inlet in this document, in
order to be in line with
document of Equipment
Design Condition Doc.
No : ID-PK6-GE-PTG017009, para. 6.2
This document is the property of COMPANY. It must not be stored, reproduced or disclosed to others without written authorisation from the Company.