Regulation and control systems HospEC
Insulation fault detection system IFS
Requirements
Principle sequence of an insulation
fault detection
Any insulation faults that occur in the IT systems are reported
immediately by insulation monitoring devices; the IT system
nonetheless continues operation. Quick location and rectification of the insulation fault must be carried out immediately.
Without switching off the system or disconnecting consumers,
locating and reporting of the concerned outgoing feeder circuit
can be conveniently performed by an insulation fault detection
system. The maintenance and repair effort should thereby be
reduced to a minimum.
The device with insulation monitoring function (UEI-710-V.5/
ILT107-V.4) constantly identifies and monitors the insulation resistance in the IT system. If the insulation resistance drops below a specified value, then the search process is started by the
test signal generator (IFS-710-PSG/integrated in the UEI-710-V.5).
The solution
Corresponding messages are now generated by the insulation
monitoring device and peripheral display devices.
Using our insulation fault detection system (IFS), faulty consumer outgoing feeders are detected automatically without switching off the IT system. This is done without measures taken by
the technical department or medical personnel.
The operator receives detailed information on the faulty power
circuit; messages can be saved for future evaluations.
This feeds a test signal (limited to 1 mA) into the IT system. The
test signal is detected by the insulation fault detection device
(IFS-710-W6) by its integrated converter (per outgoing feeder circuit) the faulty circuit is thus isolated. The test signal generator evaluates the fault detection and transfers the evaluation on
the field bus (CAN).
Communication between all devices occurs over the standard
field bus (CAN).
A message is given with the plain-text display of the cutout
designation or specification of the location of the faulty power
circuit as well as the determined insulation resistance. Timeconsuming manual troubleshooting is thus no longer necessary.
Realisation of the insulation fault detection system with:
Multifunctional change-over and
monitoring device UEI-710-V.5
Insulation fault detection devices IFS-710-W6
or with:
Insulation, load and temperature monitoring
device ILT-107-V.4
Test signal generator for insulation fault detection
IFS-710-PSG
Insulation fault detection devices IFS-710-W6
Display of signals are done for example on the:
Multifunctional change-over and
monitoring device UEI-710-V.5
Insulation, load and
temperature monitoring device ILT-107-V.4
Operating and report terminal for IT systems BMTI5
Display and configuration device ANZ 05
Annunciator and control panel FolioTec
IFS-710-W6
ESA Elektroschaltanlagen Grimma GmbH
Detail of an IT system distribution IPS-ICU-710 with
Insulation fault detection system (IFS)
Broner Ring 30 04668 Grimma Tel.: +49(0)3437 / 9211-0 Fax: +49(0)3437 / 9211-26 Email: [email protected] Web: www.esa-grimma.com
Your benefit
Our products
Quick, automatic location of faulty power circuit during
operation
Multifunctional change-over and monitoring device
UEI-710-V.5
No user intervention necessary
Insulation, load and temperature monitoring device
ILT-107-V.4
No time-consuming manual troubleshooting
Test signal generator for insulation fault detection
IFS-710-PSG
Optimisation of maintenance
Improved system reliability
Insulation fault detection device IFS-710-W6
Reporting and storage of faults
Control equipment system HospEC
Operating and report terminal for IT systems BMTI5
Display and configuration device ANZ 05
Annunciator and control panel FolioTec
Integrated component of the HospEC system
Communication via CAN bus with all devices
from the HospEC system
Connection options to central building control systems
with data interface with standard field bus (CAN)
Technical specifications IFS
Number of measuring channels per IFS-710-W6
Number of measurement channels per IT system
Fault detection time
Test signal limited to
6 (measurement converter integrated)
Maximum 132 (96 with UEI-710-V.5)
About 3 sec.
Maximum 1 mA
Measurement value logging
Communication interface/protocol
Parallel (no multiplex process)
CAN/CAN (2.0) acc. to ISO 11898
Messages on the ILT-107-V.4/UEI-710-V.5
Cutout designation of the location of the faulty power circuit,
insulation resistance
Acoustic message, insulation resistance, freely configurable texts
on site and designation of faulty power circuits
Messages to peripheral display devices (BMTI5, ANZ 05, FolioTec)
IFS
Multifunctional change-over and monitoring
device UEI-710-V.5
UEI-710-V.5
Erste Leitung
1L1
1L2
1L3
Leitung 1
1N
Betrieb
Leitung 2
CAN
Leitung 3
Isolation
Laststrom
Temp.
2L1
2L2
Zweite Leitung
2L3
2N
Abgangsleitung
Al1
Al2
Al3
AN
52
53
Communication via field bus (CAN),
connection to the central building control
system
54
Esc
Normale Versorgung
Keine Fehler
Test
UEI-710-V.5
CAN-Bus
DI1
-
DI2
+
-
24V
+
IT system
2
2
IFS-710-W6
IFS-710-W6
Artikel-Nr.: 0080091
Serien-Nr.: XA01
T1 T2
IFS-710-W6
HospEC
Betrieb
ELEKTROSCHALTANLAGEN GRIMMA GmbH
T2 T3
T4 T5
Broner Ring 30
D-04668 Grimma
Telefon 0 34 37 / 92 11 0
Telefax 0 34 37 / 92 11 26
eMail: [email protected]
Web: www.esa-grimma.de
T5 T6
CAN
Fehlersuche
starten
Insulation fault detection device
IFS-710-W6
CAN
CAN
HospEC
ZUSTANDSMELDUNGEN
STRUNG
WARNUNG
e.g. Annunciator and control panel
FolioTec
BETRIEB
ZUSATZ1
BLTTERN
TEXT
BLTTERN
TEXT
MEN
MEN 1
MEN
MEN
ENTER
LEDTEST
SUMMER
AUS
Med.Gases
IT system
LEITUNG 1
RF
LEITUNG 2
ISOLATION
TEST
BETRIEB
BETRIEB
ISO GUT
AUSFALL
AUSFALL
ISO
FEHLER
EIN
EIN
EIN
STRUNG
Lighting control
AUS
AUS
AUS
EIN
AUS
EIN
AUS
EIN
AUS
EIN
AUS
Lighting control
EIN
AUS
EIN
AUS
EIN
AUS
EIN
AUS
EIN
AUS
EIN
AUS
EIN
AUS
Intensive care, Operating theatres
Schematic diagram of insulation fault detection system IFS with UEI-710-V.5
ESA Elektroschaltanlagen Grimma GmbH
Broner Ring 30 04668 Grimma Tel.: +49(0)3437 / 9211-0 Fax: +49(0)3437 / 9211-26 Email: [email protected] Web: www.esa-grimma.com