Control Inst
Control Inst
FIRST LE1TER
Measured or
Inilialing
Variable
A
Readoulo,
Passive
Funclion
Modijier
User'scooice
Voltage (EMF)
F
G
F1ow rate
User', choice
User',cboic.
Control
Conductivity
(electrical)
Density (mass)
or specitX:
Modi]ier
Alarrn
Analysis
Burner flame
Output
Function
Differential
gravity
Primary element
Ratio (fraction)
Glas.
Gaging
(dimensiooal)
Hand (manually
initiated)
Current
(electrical)
Power
Time or time
High
Indicat.
Controlstation
scheduIe
L
Level
Moisture or
humidity
User's cboice
User's cboic.
Oritice
(restriction)
Pressure or
Paint (test
connection)
Middle or inter-
mediate
User's cboice
vacuum
Q
Quantity or
event
Radioactiviy
Speed or
Low
Light (pilot)
Integrate
User'schoice
User's cboice
or
totalize
Recordor pnn!
Switch
SafelY
frequency
Transmit
Temperature
MuItivariable
Viscosity
w
x
Weight or force
Well
Unclassified
Unclassified
Multifunction
Multifunction
Multifunction
Valve, damper,
or louver
Unclassified
User's cboice
Relay or compute
Position
Drive, actuate
or unclassified
final control
element
Unclassified
FEEDBACK PROCESSCONTROL
lated variable) and out of (the controlled variable) the processo The
closed-loop control system achieves this balance by measuring the demand and regulating the supply to maintain the desired balance over
time.
The basic idea of a feedback controlloop is most easily understood
by imagining what an operator would bave to do if automatic control
did Dot exist. Figure 1-8 shows a common application of automatic
control found in many industrial plants: a beat exchanger that uses
steam to beat cold water. In manual operation, the amount of steam
entering the beat exchanger depends on the air pressure to the valve,
which is set on the manual regulator. To control the temperature manually, the operator would watch the indicated temperature, and by comparing it with thedesired temperature, would open or close the valve to
admit more or less steam. When the temperature had reached the desired value, the operator would simply hold that output to the valve to
keep the temperature constant. Under automatic control, the temperatufe controller performs the same function. The measurement signat to
the controller from the temperature transmitter is continuously compared to the set-point signat entered into the controller. Based on a
comparlson of the signats, the automatic controller can tell whether
the measurement signat is above or below the set point and move the
valve accordingly until the measurement (temperature) comes to its
final value.
The simple feedback controlloop shown in Figure 1-9 illustrates
the four major elements of any feedback controlloop.
13
+
~;~OL~:'-=- --.or
I MEASUREMENT
SUPPLV-*
FINAL ACTUATOR
CONTROLLED
VARIABLE
14 FEEDBACK PROCESSCONTROL
Controlling
the Process
INTRODUCTIONTO PROCESSCONTROL 15
CONTROLLER
SPAN OF
MEASUREMENT
--rINLET FLOW
Lr
,-',
,,"
[[],
=
". ,'~~~""'-1
...,...,-
~}f~
-"..,"~ 2--=~.;:
-~-=-~_.=~.
f
OUTLET
_E/
I
100
I
50
I
O
FLOW
,:--=('i
~--=~
~I
16 FEEDBACK PROCESSCONTROL
level in a tank at midscale. As the level in the tank rises, the fioat acts to
reduce the fiow rate coming in. Thus, the higher the lquid level, the
more the fiow will be reduced. In the same way, as the level falls, the
fioat will open the valve to add more lquid to the tank. The response of
this system is shown graphically. As the level moves from O to 100
percent, the valve moves from fully open to fully closed. The function
of an automatic controller is to produce this kind of opposing response
over varying ranges. In addition, other responses are available to control the process more efficiently.
Selecting
Controller
Action
17
U psets
There are three conditions that require different ftows to maintain the
level in the tank. First, if the position of the output hand valve is
opened slightly, more ftow leaves the tank, causing the level to fall.
This is a change in demand, and to restore balance, the inlet ftow valve
must be opened to supply a greater ftow rate. A second type of unbalanced condition is a change in the set point. Maintaining any other level
besides midscale in the tank causes a different ftow out. This change in
demand requires a different input valve position. The third type of
up set is a change in the supply. If the pressure output of the pump
increases, even though the inlet valve remains in the same position, the
increased pressure causes a greater ftow, which at first causes the level
to begin to rise. Sensingthe increased measurement, the level controller must close the val ve on the inlet to hold the level at a constant value.
In the same way, any controller applied to the beat exchanger shown in
Figure 1-1 must balance the supply ofheat added by the steam with the
beat removed by the water. The temperature remains constant if the
ftow of beat in equals the ftow of beat out.
Process
Characteristics
and Controllability
The automatic controller uses changes in the position of the final actuator to control the measurement signal, moving the actuator to oppose any change it sees in the measurement signal. The controllability
of any process depends on the efficiency of the measurement signal
response to these changes in the controller output. For proper control,
the measurement should begin to respond quickly, but then Dot change
too rapidly. Because of the tremendous number of applications of automatic control, characterizing a process by what it does, or by industry, is an almost hopeless task. However, all processes can be described by the relationship between their inputs and outputs. Figure
1-11 illustrates the temperature response of the beat exchanger when
the control valve is opened by manually increasing the controller output signal.
At first, there is no immediate response at the temperature indication. Then the temperature begins to change, steeply at first, then approaching a final, constant level. The process can be characterized by
the two elements of its response. The first element is the dead time, or
the time before the measurement begins to respond. In this example, a
delay arises because the beat in the steam must be conducted to the
18 FEEDBACK PROCESSCONTROL
STEAM FLOW
(MANUAL)
I
OUTLET
WATER
TEMPERATURE
L~,I"/"""'
TIME
water before it can affect the temperature, and then to the transmitter
before the change can be seen. Dead time is a function of the physical
dimensions of a process and such things as belt speeds and mixing
rates. Second, the capacity of a process is the material or energy that
must enter or leave the process to change the measurements-for example, the gallons necessary to change level, the Btu's necessary to
change temperature, or the standard cubic feet of gas necessary to
change pressure. The measure of a capacity is its response to a step
input. Specifically, the size of a capacity is measured by its time constant, which is defined as the time necessary to complete 63 percent of
its total response. The time constant is a function of the size of the
process and the rate of material or energy transfer. For this example,
the larger the tank and the smaller the ftow rate of the steam, the longer
the time constant. These numbers can be as short as a few seconds, or
as long as several hours. Combined with dead time, they define the time
it takes the measurement signal to respond to changes in the valve
position. A process will begin to respond quickly, but then not change
too rapidly, if its dead time is small and its capacity is large. In short,
the larger the time constant of capacity compared to the dead time, the
better the controllability of the processo
Controli er Responses
-..TIME
19
has been made, severa! types o responses are used to control a processoThese are (1) on/otI, two-position, control, (2) proportional action, (3) integral action (reset), and (4) derivative action.
On/off Control
MEASUREMENT
100
% SIGNAL TO
VALVE
20 FEEDBACK PROCESSCONTROL
Action
INTRODucnON TO PROCESSCONTROL 21
% OUTPUT
22 FEEDBACK PROCESSCONTROL
deviates from set paint. Each line on the graph represents a particular
adjustment of the proportional band. Two basic properties of proportional control can be observed from this graph:
1. For every value of proportional band, whenever the measurement
equals the set paint, the normal output is 50 percent.
2. Each value of the proportional band defines a unique relationship
between measurement and output. For every measurement value
there is a specific output value. For example, using the 100percent
proportional band line, whenever the measurement is 25 percent
above the set paint, the output from the controller must be 25
percent. The output from the controller can be 25 percent only if
the measurement is 25 percent above the set paint. In the same
way, whenever the output from the controller is 25 percent, the
measurement will be 25 percent above the set paint. In short, there
is one specific output value for every measurement value.
For any process controlloop, only one value of the proportional
band is the best. As the proportional band is reduced, the controller
response to any change in measurementbecomes increasingly greater.
At some paint, depending on the characteristic of each particular process, the response in the controller will be large enough to drive the
measurement back so far in the opposite direction as to cause constant
cycling of the measurement. This proportional band value, known as
the ultimate proportional band, is a lmit on the adjustment of the
controller in that loop. On the other hand, if too wide a proportional
band is used, the controller response to any change in measurement is
too small and the measurement is Dot controlled as tightly as possible.
The determination of the proper proportional band for any application
is part of the tuning procedure for that loop. Proper adjustment of the
proportional band can be observed by the response ofthe measurement
to an upset. Figure 1-16shows several examples ofvarying the proportional band for the beat exchanger.
Ideally, the proper proportional band will produce one-quarter amplitude damping, in which each hal cycle is one-half the amplitude of
the previous hal cycle. The proportional band that will cause onequarter wave damping will be smaller, thereby yielding tighter control
over the measured variable, as the dead time in the process decreases
and the capacity increases.
One consequence of the application of proportional control to the
basic controlloop is offset. Offset means that the controller will maintain the measurement at avalue different from the set paint. This is
most easily seen in Figure 1-10. Note that ifthe load valve is opened,
INTRODUCTIONTO PROCESSCONTROL 23
WATER FLOW
(LOAO)
i
I
1~
TEMPERATURE
-j/'\/,~"-",,,
I
,-~
TOOWIOE
CHANGE IN
UEMANO
B
C
TOO NARROW
CORRECT
TIME
ftow will increase through the valve and the val ve would bave to open.
But note that, because of the proportional action of the linkage, the
increased open position can be achieved only at a lowered level. Stated
another way, in order to restore balance between the ftow in and the
ftow out, the level must stabilize at avalue below the set point. This
difference, which will be maintained by the control loop, is called
offset, and is characteristic of the application of proportional-only control to feedback loops. The acceptability ofproportional-only control
depends on whether this offset can be tolerated. Since the error necessary to produce any output decreases with the proportional band, the
narrower the proportional band, the less the offset. For large capacity,
small dead time applications accepting a very narrow proportional
band, proportional-only control will probably be satisfactory, since the
measurement will remain within a small percentage band around the set
point.
If it is essential that there be no steady state difference between
measurement and set point under all load conditions, an additional
function must be added to the controller. This function is called integral
action (an older term is reset).
Integral
Action
(Reset)
24 FEEDBACK PROCESSCONTROL
% MEASUREMENT
L_-
SET
paiNT
I
I
I
...riME
Fig. l-I?
exists. This function, then, causes the output to change until the proper
output is achieved in order to hold the measurement at the set paint at
various loads. This response is added to the proportional response of
the controller as shown in Figure 1-17. The step change in the measurement first causes a proportional response, and then an integral
response, which is added to the proportional. The more integral action
there is in the controller, the more quickly the output changes due to
the integral response. The integral adjustment determines how rapidly
the output changesas a function oftime. Among the various controllers
manufactured, the amount of integral action is measured in one of two
ways-either in minutes per repeat, or the number of repeats per minute. For controllers measuring integral action in minutes per repeat,
the integral time is the amount of time necessary for the integral mode
to repeat the open-loop response caused by proportional mode, for a
step change in error. Thus, for these controllers, the smaller the integral number, the greater the action of the integral mode. On controllers
that measure integral action in repeats per minute, the adjustment indicates how many repeats of the proportional action are generated by the
integral mode in one minute. Table 12-1 (p. 300) relates the controller
adjustments from one manufacturer to another. Thus, for these controllers, the higher the integral number, the greater the integral action.
Integral time is shown in Figure l-IS. The proper amount of integral
action depends on how fast the measurement can respond to the additional valve trave 1 it causes. The controller must nat drive the valve
faster than the dead time in the process allows the measurement to
respond, or the valve will reach its lmits before the measurement can
be brought back to the set paint. The valve will then remain in its
extreme position until the measurement crosses the set paint, whereupon the controller will drive the valve to its opposite extreme, where it
INTRpDUCTION TO PROCESSCONTROL 25
% MEASUREMENT
~
,
:+-RT
% OUTPUT
(I/D)
SET paiNT
-+1
::::::""J--r-
b~I~
I
I
a. b
TIME
will remain until the measurementcrosses the set point in the opposite
direction. The result will be an integral cycle in which the valve travels
from one extreme to another as the measurementoscillates around the
set point. When integral action is applied in controllers on batch processes, where the measurement is away from the set point for long
periods between batches, the integral may drive the output to its maximum, resulting in "integral wind-up." When the next batch is started,
the output will Dot corne off its maximum until the measurement
crosses the set point, causing large overshoots. This problem can be
prevented by including a "batch function" in the controller, a function
specifically designed to prevent "wind-up."
Derivative
Action
...TIME
26 FEEDBACK PROCESSCONTROL
% MEASUREMENT
-_J==~
--~
"~!
-t__J-
% OUTPUT
(IlO)
+TIME J...
~
Fig. 1-19. Two derivative responses.
tive response. The derivative holds this output as long as the measurement is changing. As soon as the measurementstops changing, regardless owhether it is at the set point, above or below it, the response due
to derivative action will cease. Among all brands o controllers, derivative response is commonly measured in minutes, as shown in Figure
1-20. The derivative time in minutes is the time that the open-loop,
proportional-plus-derivative response, is ahead o the response due to
proportional action alone. Thus, the greater the derivative number, the
greater the derivative response. Changes in the error are the result o
changes in either the set point or the measurement, or both. To avoid a
large output spike caused by step changes in the set point, most modem controllers apply derivative action only to ehanges in the measurement. Derivative action in controllers helps to control processes with
especially large time constants. Derivative action is unnecessary on
""
% MEASUREMENT
,,
DT""
I
:.:::~J
% OUTPUT
r-
::::::::::~'
.f"
PROPORTIONAL ONLY
PROPORTIONAL + DERIVATIVE
INTRODUCTIONTO PROCESSCONTROL 27
the Controller
28 FEEDBACK PROCESSCONTROL
INTRODUCTIONTO PROCESSCONTROL 29
Conclusion
30 FEEDBACK PROCESSCONTROL
Questions
INTR9DUCTION TO PROCESSCONTROL 31
Gain
Rate
Integral
Controller, on/otI
e. Valve
Desiredvalue
Manipulatedvariable
Error
appearsin an instrumentdiagram.It
c. Frequencyconverter
d. Final control element
c. 50 percent
b. 100percent
d. Impossibleto define
1-13. If in a proportional-plus-integral
controller measurement
is away from
the set point for a long period,the controller's output will be:
32 FEEDBACK PROCESSCONTROL
d. 100percent
1-14. In the modemcontroller,derivative actionis appliedonly to the:
8. Error
c. Setpoint
b. Measurement
d. Integral circuit
1-15. The functionof the integral(reset)modeis to:
8. Opposechangein measurement
b. Automaticallyadjustthe controller's gain
c. Eliminate offset
d. Stabilizethe controlloop
Process/Pressure Measuring
Process/Pressure
Instruments
Instruments
Pressure is a universal
universal processing
processing condition.
condition. It is also
also a condition
oflife
Pressure
conditionoflife
on this planet:
at the
an atmospheric
that
atmospheric ocean
ocean that
on
planet: we live at
the bottom
bottom of an
extends upward
upward for many
miles. This mass
mass of air has
has weight,
weight, and
and this
extends
manymiles.
weight
pressing downward
downward causes
causes atmospheric
atmospheric pressure.
pressure. Water,
Water, a funfunweight pressing
damental
necessityof life, is supplied
most of us
supplied to most
us under
under pressure.
pressure. In
damental necessity
the typical process
process plant,
plant, pressure
pressure influences
influences boiling
boiling point
point temperatemperathe
tures, condensing
temperatures, process
process efficiency,
efficiency, costs,
costs, and
and
tures,
condensingpoint
point temperatures,
other important
important factors.
measurementand
control of pressure,
other
factors. The
The measurement
and control
pressure, or
lack of it-vacuum-in
it-vacuum-in the
plantis critical. Instruments
lack
the typical process
process plant
Instruments
are
How these
are available
available to measure
measure a wide
wide range
range of pressures.
pressures. How
these instruinstruments function
chapter.
ments
function is the subject
subjectof this chapter.
What
Is Pressure?
Pressure?
What Is
Pressure
Pressure is force dividel
divided by the area over which it is applied. Pressure
Pressure
is often defined in terms of
of "head."
"head." For example, assume
assume that we bave
have
a water column 1 foot square
square and 23
23 feet tall. We
We want to find the
pressure in the bottom
boUom ofthe
mar be
ofthe column. The weight ofthe
ofthe column may
calculated by first finding the volume of water. This is the area
of the
area of
33
34
FEEDBACK PROCESSCONTROL
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 35
Units ot Measurement
Every major country has adopted its own favorite units of measurement. The United States has traditionally employed the English system. However, international trade has made it necessaryto standardize
units of measurement throughout the world. Fortunately, during this
standardization, there has be en rationalization ofthe measurementsystem. This has led to the adoption of the System lnternatonal d'Untes
(SI), a metric system of units. The force of common usage is so strong
that the familiar English system will undoubtedly persist for many
years, but the changeover is definitely underway. The time will soon
corne when process industries will deal exclusively with SI units.
Pressure
Measurement
Perhaps the area that has caused the most concern in the change to SI
units is pressure measurement. The new unit of pressure, the pascal, is
unfamiliar even to those who have worked in the older CGS (centimetre, gram, second) metric system. Once it is accepted and understood,
it willlead to a great simplification of pressure measurement Cromthe
extremes of full vacuum to ultrahigh pressure. It will reduce the multiplicity ofunits now common in industry to one standard that is compatible with other measurements and calculations. To understand the pascal and its relationship to other units of pressure measurement, we
must return to a basic understanding of pressure.
As noted previously, pressure is force per unit area.
36 FEEDBACK PROCESSCONTROL
where:
W = weight of the object
m = its mass
G = accelerationdue to gravity
Because gravity on the earth's surface is roughly constant, it has
been easy to talk abolli a weight of 1 pound and a mass of 1 pound
interchangeably. However, in faci, force and mass, as quantities, are as
different as apples and pears, as the astronauts bave observed. A numbec of schemes bave be en devised to overcome ibis problem. For example, a quantity called the pound-force was invented and made equal
to the force on a mass of one pound under a specified acceleration due
to gravity. The very similarity between these two units led to more
confusiott. The pascal, by its definition, removes all these problems.
The Pascal
The SI unit of pressure is defined as the pressure or stress that arises
when a force of one newton (N) is applied uniformly over an area of one
square metre (m2). This pressure has been designated one pascal (Pa).
Thus, Pa = N/m2. This is a small unit, but the kilopascal (KPa),
1,000 pascals, and the megapascal (MPa), one million pascals, permit
easy expression of common pressures. The definition is simple, because gravity has been eliminated. The pascal is exactly the same at
every point, even on the moon, despite changes in gravitational acceleration.
In SI units, the unit offorce is derived from the basic unit for mass,
the kilogram (kg), and the unit of acceleration (metres per second per
second, mls2). The product of mass times acceleration is force and is
Gauge,
PROCESS/PRESSURE
MEASURING INSTRUMENTS 37
After the introduction of SI units, the use of the "bar" (lOSPa) gained
favor, especially in European industry, where it closely resembles the
CGS unit of kg/cm2 (kilograms per square centimetre). At thai time, the
SI unit was called the "newton per square metre." As well as being
quite a mouthful, it was found to be inconveniently small (one N/m2
equals 0.000145psi). The use ofthe millibar in meteorology lent weight
to the acceptance of the bar. However, the use of a multiple like (lOS)in
such an important measurement and the resulting incompatibility of
stress and pressure units led to the adoption ofthe N/m2, giving it a new
name, the pascal (Pa), in October 1971. The kilopascal (kPa), 1,000
pascals, equals 0.145 psi and most common pressures are thus expressed in kPa. The megapascal(mPa) equals 145 psi and is convenient
for expressing high pressures.
Absolute,
and Differential
Pressure
The pascal can be used in exactly the same way as the English or CGS
metric units. The pascal may be regarded as a "measuring gauge," the
size ofwhich has been defined and is constant. This gauge can be used
to measure pressure quantities relative to absolute vacuum. Used in
this way, the results will be in pascal (absolute). The gauge may also be
used to measure pressures relati ve to the prevailing atmospheric
pressure, and the results will be pascal (gauge). Ifthe gauge is used to
measure the difference between pressures, it becomes pascal (differen-
tial).
The use of gauge pressure is extremely important in industry, since
it is a measure ofthe stress within a vesseland the tendency offtuids to
leak auto It is really a special case of differential pressure measurement,
inside versus outside pressure. Where there is any doubt about whether
a pressure is gauge, differential, or absolute, it should be specified in
full. However, it is common practice to shaw gauge pressure without
specifying, and to specify by saying "absolute" or "differential" only
for absolute or differential pressures. The use of "g" as in psig is
disappearing, and the use of "a" as in psia is frowned upon. Neither g
flor a is recognized in SI unit symbols. However, M is recognized for
differential pressure in all units.
38 FEEDBACK PROCESSCONTROL
Understanding
the Effects
of Gravity
at different places:
Melbourne (Australia)
Foxboro (USA)
Soest (The Netherlands)
9.79966 rn/S2
9.80368 rn/S2
9.81276 rn/S2
Hence the difference around the world is approximately :t 0.1 percent from the average. This is oflittle practicat importance in industrial
applications. However, with some transmitters being sold with a rated
accuracy of :t0.25 percent, it is well to consider the effect of a gravityinduced difference of more than hal the tolerance thai can arise if the
transmitter was calibrated in Europe and tested in Australia.
Gravity-Dependent
Units
Units such as psi, kglcm2, inches of water, and inches of mercury (Hg)
are all gravity dependent. The English unit pounds per square inch (psi)
is the pressure generated when the force of gravity acts on a mass of
one pound distributed aveT one square inch. Consider a dead weight
tester and a standard mass of one pound which is transported around
the earth's surface: the pressure at each paint on the earth will vary as
the gravitational acceleration varies. The same applies to units such as
inches of water and inches of mercury. The force at the bottom of each
column is proportional to the height, density, and gravitational acceleration.
Dead weight testers are primary pressure standards. They generate
pressure by applying weight to a piston that is supported by a fluid,
generally oil or air. By selecting the weights and the cross-sectional
aTea of the piston, the pressure generated in any gravity field can be
calculated. Therefore, dead weight testers are gravity dependent. For
accurate laboratory work, the gravity under which the tester was calibrated and that at the place of use must be taken into account. Similarly,
the pressure obtained by a certain height of fluid in a manometer depends on density and gravity. These factors must be corrected for the
PROCESS/PRE:SSURE
MEASURINGINSTRUMENTS 39
Units
While gravity plays no part in the definition of the pascal, it has the
same value wherever it is measured. Units such as pounds-force per
square inch and kilogram-force per square centimetre are also independent of gravity because a specific value of gravitational acceleration
was selected in defining these units.
Under equal gravity conditions, the pound-mass and pound-force
are numerically equal (which is the cause of considerable confusion).
Under nonstandard gravity conditions (the usual case), correction factors are required to compensate for the departure from standard. It
should be noted that the standard value of actual gravity acceleration is
llot recognized as such in the SI unit system, where only the SI unit of
acceleration of one metre per second per second is used. In the future,
only the measured actual gravity at the location of measurement (G)
will be used when gravity plays a part in the system under investigation. The pascal is a truly gravity-independent unit and will be used to
avoid the presently confusing question of whether a stated quantity is
gravity dependent.
Pressure
Standards
Now let us consider the calibration standards that are employed with
pressure-measuringinstruments and the basic instruments that are used
to measure pressure. It mar help to look at the ways in which the
standards for pressure calibration are established. You will recalI that
head is the same as pressure. A measure of head, then, can be a dependable measure of pressure. Perhaps the oldest, simplest, and, in
many respects, one of the most accurate and reliable ways of measuring pressure is the liquid manometer. Figure 2-2 shows a differential
manometer. When only a visual indication is needed and static
pressures are in a range that does Dot constitute a safety hazard, a
transparent tube is satisfactory. When conditions for the visual manometer are unsuitable, a variety of ftoat-type liquid manometers are
often employed.
40 FEEDBACK PROCESSCONTROL
HIGH
PRESSURE
PROCESS/PR;:SSURE
MEASURINGINSTRUMENTS 41
HIGH
PRESSURE
Fig.
42
FEEDBACK PROCESSCONTROL
LIQUID
GLASS
--- WEIGHT
DEAD WEIGHT
TESTER
TO
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 43
INSTRUMENT
UNOER TEST
44 FEEDBACK PROCESSCONTROL
Plant Instruments
That Measure
Pressure
Directly
Thus far in tbis chapter we bave been concemed with the detinition of
pressure, and some of the standards used bave been described. In the
plant, manometers and dead weight testers are used as standards for
comparison and calibration.
The working instruments in the plant usually include simple mechanical pressure gauges, precision pressure recorders and indicators,
and pneumatic and electronic pressure transmitters. A pressure transmitter makes a pressure measurementand generates either a pneumatic
or electrical signal output thai is proportional to the pressure being
sensed. We will discuss transmitters in detaillater in ibis chapter. Now
we will deal with the basic mechanical instruments used for pressure
measurement, how they operate and how they are calibrated. When the
amount of pressure to be measured is very small, the following instruments might be used.
Bell Instrument
Fig.
PROCESS/PRE$SURE
MEASURINGINSTRUMENTS 45
46 FEEDBACK PROCESSCONTROL
tube."
Figure 2-11A shows such a tube. As pressure is applied internally,
the tube straightens out and returns to a cylindrical Corm. The excursion of the tube tip moves linearly with internal pressure and is
converted to pointer position with the mechanism shown. Once the
PROCESS/PRE;SSURE
MEASURINGINSTRUMENTS 47
48 FEEDBACK PROCESSCONTROL
2-11 B.
Liquid
or Steam Pressure
Measurement
ter.
Pulsation Dampener
If the instrument is intended for use with a fluid under pressure and
subject to excessive fluctuations or pulsations, a deadener or damper
should be installed. This will provide a steady reading and prolong the
life of the gauge.
Two other elements that use the Bourdon principIe are the spiral
(Figure 2-12) and helical (Figure 2-13). The spiral and helical are, in
effect, multitube Bourdon tubes. Spirals are commonly used for
Fig.
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 49
2-12. Spiral.
pressure ranges up to o to 200 psi or 1.4 MPa, and helicals are made to
measure pressures as high as Oto 80,000 psi or 550 MPa. The higher the
pressure to be measured, the thicker the walls ofthe tubing Cromwhich
the spiral or helical is constructed. The material used in the construction mar be bronze, beryllium copper, stainless steel, or a special NiSpan C alloy. Spirals and helicals are designed to provide a lever motion of approximately 45 degrees with full pressure applied. If this
motion is to be translated into pen or pointer position, it is common
practice to utilize a four-bar linkage, and this necessitates a special
calibration technique. If, instead of measuring gauge pressure, it is
necessary to read absolute pressure, the reading must make allowances
for the pressure of the atmosphere. This mar be done by utilizing an
absolute double spiral element. In tros element, two spirals are used.
One is evacuated and sealed; the second has the measured pressure
applied.
The evacuated sealed element makes a correction for atmospheric
pressure as read on the second element. Thus, the reading can be in
terms of absolute pressure, which is gauge plus the pressure of the
atmosphere, rather than gauge.
An absolute double spiral element of this type mar be used to
measure pressures up to 100 psi or 700 Kpa absolute. This element is
shown in Figure 2-14.
Metallic
Bellows
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 51
ounces to many pounds per square inch. A bellows will develop many
times the power available from a helical, spiral, or Bourdon tube.
A bellows is typically rated in terms of its equivalent square inch
area. To create a linear relationship between the excursion of the bellows and the applied pressure, it is common practice to bave the bellows work in conjunction with a spring, rather than with the spring
characteristic of the metal within the bellows itself. Each bellows and
spring combination has what is called a spring rate. The springs used
with the bellows are usually either helical or spiral. Typically, the
spring rate of the helical spring is ien times or more thai of the bellows
material itself.
Using a spring with a bellows has several advantages over relying
on the spring characteristics of the bellows alone. The calibration procedure is simplified, since adjustments are made only on the spring.
Initial tension becomes zero adjustment and the number of active turos
becomes span adjustment. A spring constructed of stable material will
exhibit long-term stability thai is essential in any component.
.When a measurement of absolute pressure is to be made, a special
mechanism employing two separate bellows mar be used. It consists of
a measuring bellows and a compensating bellows, a mounting support,
and an output lever assembly (Figure 2-17). The measuring and compensating bellows are fastened to opposite ends of the fixed mounting
support: the free ends of both bellows are attached to a movable plate
mounted between them. The motion of ibis movable plate is a measure
of the difference in pressure between the two bellows.
52 FEEDBACK PROCESSCONTROL
Pressure
Transmitters
Signal Transmissions
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 53
54 FEEDBACK PROCESSCONTROL
The receiver converts the signat into a suitable pen or pointer position.
Because the scale is labeled in proper units, it is possible to read the
measuredpressure.
A typical pneumatic indicator is shown in Figure 2-18 (top) and its
operation mar be visualized by studying Figure 2-18 (bottom, right).
The input signal passes through an adjustable needle valve to provide damping, then continues to the receiver bellows. This bellows,
55
Pressure
Seals
Application
A sealedpressuresystemis usedwith a pressuremeasuringinstrument
to isolate corrosive or viscousproducts, or products that tend to solidify, from the measuringelementand its connectivetubing.
Definition
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 57
58 FEEDBACK PROCESSCONTROL
temperatures.
The Foxboro l3DMP Series pneumatic d/p Cell transmitters with
pressure seals (Figure 2-21) measure differential pressures in ranges of
O to 20 to O to 850 inches of water or O to 5 to O to 205 kPa at static
pressures Cromfull vacuum up to flange ralingo They transmit a proportional 3 to 15 psi or 20 to 100kPa or 4 to 20 mA dc signat to receivers
located up to several hundred yards or melers Cromthe point of measurement.
S9
FiUing Fluids
Ideally, the filling fluid used in a sealed pressure system should be
noncompressible, bave a high-boiling point, a low-freezing point, a low
coefficient of thermal expansion, and low viscosity. It should be noninjurious to the diaphragm and containing parts, and should Dot cause
spoilage in the event ofleakage. Silicone-based liquid is the most popular filling fluid.
The system is evacuated before the filling fluid is introduced. The
system musi be completely filled with fluid and free from any air pockets thai would contract or expand during operation, resulting in erroneous indications at the pen or pointer or in an output signat. The
degree of accuracy of any filled pressure system depends on the perfection of the filling operation.
Calibration
Techniques
The procedure for calibration of a pressure instrument consists of comparing the reading of the instrument being calibrated with a standard.
The instrument under calibration is then adjusted or manipulated to
make it agree with the standard. Success in calibration depends Dot
only on one' s ability to adjust the instrument, but on the quality of the
standard as well.
Field Standards
Field standards must be reasonably convenient to use and must satisfy
the accuracy requirements for the instrument under calibration. A 100inch water column, for example, is extremely accurate but Dot practical
to set up out in the plant. For practical reasons, we find that most field
standards are test ganges.The test gaugeis quite similar, in most cases,
to the regular Bourdon ganges. However, more care has gone into its
design, construction, and calibration, making it very accurate. A good
quality test gauge will be accurate to within ::\:0.25percent of its span.
This is adequate for most field use.
Under some conditions, a manometer mar be used in the field. This
usually occurs when a low-pressure range is to be calibrated and no
other suitable standard is readily available.
Portable Pneumatic Calibrator
All of the ingredients required to perform a calibration bave been combined into a single unit called a portable pneumatic calibrator. This unit
60
FEEDBACK PROCESSCONTROL
Pneumatic
Pressure
Transmitter
0/1"
PROCESS/PRE~SURE
MEASURINGINSTRUMENTS 61
~~
o~
~~
;c
~"
~m
~C
~~z
mO~
,,~~
cm~
z
~2
~~
~'"
~~~;~:~
;
l ,t'i'
" ",'
~, \c:
\\'i",:"
'
62 FEEDBACK PROCESSCONTROL
FLE'~"
Relay
PROCESS/PRE$SURE
MEASURINGINSTRUMENTS 63
INPUT
DIAPHRAGM
SUPPLY
STEM
VALVE
BALL VALVE
OUTPUT
EXHAUST
SPRING
ot Operation
The 11GM Pneumatic Transmitter (Figure 2-24) is a force-balance instrument that measures pressure and transmits it as a proportional 3 to
15 psi pneumatic signal (20 to 100kPa).
The pressure is applied to a bellows, causing the end of the bellows
to exert a force (through a connecting bracket) on the lower end of the
force bar. The metal diaphragm is a fulcrum for the force bar. The force
is transmitted through the ftexure connector to the range rod, which
pivots on the range adjustment wheel.
Any movement of the range rod causes a minute change in the
clearance between the ftapper and nozzle. This produces a change in
the optput pressure from the relay to the feedback bellows until the
force of the feedback bellows balances the pressure on the measure-
64 FEEDBACK PROCESSCONTROL
Pressure Transmitter
PROCESS/PRES:sURE
MEASURINGINSTRUMENTS 65
until the force in the bellows balances the force on the diaphragm
capsule.
The output pressure, which establishes the force-balane, is the
transmitted pneumatic signal, which is proportional to the 'absolute
pressure being measured. This signal is transmitted to a pneumatic
receiver to record, indicate, or control.
Ouestions
2-1. An ordinary commercial Bourdon gauge has a scale of O psi to 250 psi,
and an accuracy of:t 1.percent of span. If the gauge reads 1.75psi, within
what maximum and minimum values will the correct pressure fall?
8. 1.74to 1.76psi
c. 1.76.5to 1.78.5psi
b. 1.72.5to 1.77.5psi
d. 1.79to 1.80psi
2-2.
8.
b.
c.
66 FEEDBACK PROCESSCONTROL
2-3.
a.
b.
c.
d.
Absolutepressuris:
Gaugepressureplus atmosphericpressure
Gaugepressurelessatmosphericpressure
Gaugepressureplus atmosphericpressuredivided by two
Always referencedto a point at the peakof Mt. Washington,NH
PROCESSlPRESSURE
MEASURINGINSTRUMENTS 67
c. No problemis created
d. Readthe peakand minimumand divide by two to obtainthe true
pressure
2-12. A measurement
of absolutepressureis to be madeusinga mechanism
employingtwo separatebellows. Measurementis appliedto one bellowsand
the other:
8. Is sealedat an atmosphericpressureof 14.7psi
b. Is completelyevacuatedand sealed
c. Containsalcoholfor temperaturecompensation
d. Has an activeareatwice that of the measuringbellowsand is sealedat a
pressuretwice atmospheric
2-13. The dangerof havinga high-pressureline carryinga dangerous
chemicalrupture in the control room is:
8. Eliminated by usingspecialduty piping
b. Ignored
c. Eliminated throughthe useof a transmissionsystem
d. Minimized by placingthe line within a protectivebarrier
2-14. The standardpneumatictransmissionsignalmost generallyused in the
United Statesis:
8. 3 to 27 psi
c. 3 to 15psi
b. 10to 50 psi
d. 2 to 12psi
2-15. A sealedpressuresystem:
8. Is similar in someways to a liquid-filled thermometer
b. Sealsthe processmaterialin the instrument
c. Must be usedat a fixed temperature
d. Is alwaysusedwith manualtemperaturecompensation
2-16. A pneumaticrelay:
8. Is a setof electricalcontactspneumaticallyactuated
b. Is a signalbooster
c. Is a pneumaticamplifier
d. Containsa regulatoractuatedby a bellows
2-17. Whenthe clearancebetweenflapper and nozzlechangesby 0.0006
inchesthe output of the transmitterwill changeby:
8. 3 psi
c. 12psi
b. 15psi
d. 6 psi
2-18. An instrumentis to be calibratedto measurea rangeof Oto 6,000psi.
For sucha calibration:
8. oil or lquid shouldbe used
b. Air mustbe used
c. An inert gas suchas nitrogenis required
d. Any sourceof highpressureis acceptable
68 FEEDBACK PROCESSCONTROL
Level Measurement
Measurement Methods
Methods
Level
The
The typical process
process plant
plant contains
contains many
many tanks,
tanks, vessels,
vessels, and
and reservoirs.
reservoirs.
measurement
store or process
process materials.
materials. Accurate
Accurate measurement
Their function
function is to store
of thesecontainers
materialin the tanks
of the contents
contents ofthese
containers is vital. The
The material
tanks is
usually
occasionallyit may
mar consist
consistof solids.
usually liquid, but occasionally
solids.
Initially,
level measurement
measurementappears
presenta simple
Initially, level
appears to present
simple problm.
problem.
However,
closerlook soon
soonreveals
variety of problems
that must
mustbe
However, a closer
reveals a variety
problems that
be
resolved.
materialmay
mar be
very corrosive;
mar tend
resolved. The material
be very
corrosive; it may
tend to solidify; it
mar tend
mar contain
contain solids;
mar create
other
may
tend to vaporize;
vaporize; it may
solids; or it may
create other
difficulties.
difficulties.
The
commonmethods
The common
methods employed
employed for automatic
automatic continuous
continuous liquid
level measurements
level
measurements are
are as
as follows
follows (see
(see also
also Table
Table 3-1):
3-1):
1.
Float-and-eable
1. Float-and-cable
2.
2. Displacement
Displacement(buoyancy)
(buoyancy)
3. Head
Head (pressure)
(pressure)
4. Capacitance
Capacitance
5. Conductance
5.
Conductance
6. Radiation
Radiation(nucleonic)
(nucleonic)
7. Weight
7.
Weight
8. Ultrasonic
8.
Ultrasonic
9. Thermal
9.
Thermal
69
70 FEEDBACK PROCESSCONTROL
Available Upper
Range Values
Open
10 in to 250 ft
0.25 to 75 m
4 in to 250 ft
0.lt075m
2 in to many ft.
50 mm to many metres
5 in to many ft.
0.25 to many metres
6 in to 12 ft
0.15 to 3.6 m
3 in to 50 ft.
75 mm to 15 m
lnches to Feet
mm to m
Depends on Tank Dim.
Open
Open
corrosive or dirty
Clean
Tank
Open
Both
Both
Condition
of Liquid
Open
Any type
Both
Any type
Wide
Both
Any type
Wide
Wide
One or more Points
80th
Nonconductive
80th
80th
Any type
Conductive
Float-and-Cable
A ftoat-and-cable or ftoat-and-tape instrument (Figure 3-1) measures
liquid level by transmitting to a mechanism the rise and fall of a ftoat
thai rides on the surface of the liquido Mechanisms are available to
accommodate level variations ranging from a few inches to many feet.
Float-and-cable devices are used primarily in open tanks, whereas ftoat
level switches mar be designed to operate in a pressurized tank.
Float devices bave the advantage of simplicity and are insensitive
to density changes. Their major disadvantage is their limitation to reasonably clean liquids. Thrbulence mar also create measurement problems. The ftoat and cable technique does Dot lend itselfto the transmitter concept as well as do some of the following techniques.
Displacement
(Buoyancy)
72
FEEDBACK PROCESSCONTROL
where:
f
V
Lw
L
B
=
=
=
=
=
73
temperature service. Interface level measurementmar be accomplished by permitting the interface level to vary over the length of the
displacer.
f = V (B) (SG difi)
SG difI = SG lower liquid minus the SG upper liquid
Head or Pressure
74 FEEDBACK PROCESSCONTROL
DETAlL
OF NOTCH
IN BUBBLE PIPE
76 FEEDBACK PROCESSCONTROL
OPEN TANK
Fig. 3-7.
Span = xGL
Suppression= yGL+ zG,
Span = xGL
Suppression= yGL+ zG,
Span = xGL
Elevation =/dG. -yGL
(0.8)
(minus sign indicates thai the higher pressure is applied to the low side
of the cell.)
At times the liquid to be measured possessescharacteristics thai
create special problems. Assume, for example, thai the liquid being
measured will solidify if it is applied to a wet leg and it is virtually
impossible to keep the leg dry. This type of application could use
a pressure repeater. The repeater (Figure 3-8) is mounted above
the maximum level of the liquid, and the liquid level transmitter is
mounted near the bottom ofthe tank. The pressure in the vapor section
is duplicated by the repeater and transmitted to the instrument below,
(Figure 3-9). Thus, the complications of a wet leg are avoided, and a
varying pressure in the tank will Dot atrect the liquid level measurement.
The pressure range thai mar be repeated is O to 100 psi or Oto 700
kPa. The supply pressure musi exceed the pressure to be repeated by
78 FEEDBACK PROCESSCONTROL
(Figure 3-10).
Conductance
Conductivity level sensors consist of two electrodes inserted into the
vessel or tank to be measured. When the level rises high enough to
provide a conductive path from one electrode to the other, a relay (solid
state or coil) is energized. The relay mar be used for either alarm or
control purposes. Conductivity then becomes either point control or an
alarm point. The lquid involved must be a conductor and must Dot be
hazardous if a spark is created. Level by conductivity finds occasional
applications in process plant s (Figure 3-11).
Radiation
LlNE
80 FEEDBACK PROCESSCONTROL
DETECTOR
~~~Jr;~-~~'-==-L__~
\~::::-
--
\~"
\ ::;"""""
\ \'
\\"
\"
INDICATOR
\,
-+
~-g
i~CONVERTER
NUCLEONIC(RADIATION)
Fig. 3-12. Radiationtechnique.
draulic or strain gauge, are used to weigh the vessel and its contents.
The tare weight of the tank is zero adjusted out of the reading, which
will result in a signal proportional to tank contents (Figure 3-13).
One advantage of the weight system is that there is no direct contact with the contents of the tank and the sensor. However, the system
is not economical, and varying densities mar confuse the relationship
between signal and true level.
Ultrasonic
20,000 Hz and a receiver. The time required for the sound waves to
travel to the liquid and back to the receiver is carefully measured. The
time is a measure of level. This technique has excellent reliability and
good accuracy. Furthermore, nothing comes in contact with liquid in
the tank, which minimizes corrosion and contamination. The only generallimitation is economic.
Thermal
Measurement
Methods
for Liquids
and Liquid
Slurries
sity.
The measurement and control of liquid density are critical to a great
number of industrial processes. Although density can be of interest, it
is usually more important as an inference of composition, of concentration of chemicals in solution, or of solids in suspension.
82 FEEDBACK PROCESSCONTROL
Span
Hydrometer
0.1
0.005
0.05
0.05
O.O~
0.05
Displacer
Hydrostatic head
Radiation
Weight oCfixed volume
Vibrating U-Thbe
Condition
oi Liquid
Accuracy
Clean
Clean
:!:1%
Any
Any
Clean
Clean
as % Span
:!:1%
~ to 1%
1%
1%
1-3%
Fig.
lz=ZZarZz=
3-15. Fixed heightofliquid for densitymeasurement.
(3-3)
Vibration
84 FEEDBACK PROCESSCONTROL
Span = H X (G2,- GJ
Zero suppression = H x GI,
(3-4)
detector.
Differential
Pressure Transmitter
There are a variety of system arrangements for hydrostatic head density measurements with d/p Cell transmitters. Although ftange-mounted
d/p Cell transmitters are often preferred, pipe-connected transmitters
can be used on lquids where crystallization or precipitation in stagnant
pockets will noi occur.
These d/p Cell transmitter methods are usually superior to those
using bubble tubes. They can be applied wherever the vessel is high
enough to satisfy the mnimum transmitter span. They are also well
suited for pressure and vacuum applications.
Constant level overftow tanks permit the simplest instrumentation
as shown in Figure 3-16. Only one d/p Cell transmitter is required. With
H as the height of lquid above the transmitter, the equations are still:
Span = H X (G2
Applications with level and/or static pressure variations require compensation. There are three basic arrangements for density measurement
under these conditions. FiTSt, when a seal fluid can be chosen that is
always heavier than the process fluid and will Dot mix with it, the
method shown in Figure 3-17 is adequate. This method is used extensively on hydrocarbons with water in the wet leg.
Fig. 3-16. Constant level, open overftow tanks require only one d/p Cell transmitter for
density measurement.
Fig.
86 FEEDBACK PROCESSCONTROL
y-:'--=(
\
H
DENSITY
~
SIGNA L
A I
=
UQUID
a':iJ-l
PURGE
(SP.GR.=GS)
3-17. In an open or closed tank with varying level and/or pressure. a wet leg can be
filled with seal fluid heavier than the process liquido
For a wet leg fluid o specific gravity Gs. an elevated zero transmitter
musi be used. The equations become:
Span = H x (G2 -GJ,
When no seal or purge lquid can be tolerated, there are ways to provide a "mechanical seal" for the low-pressure leg, or for both legs, if
needed. Figure 3-18 shows the use of a pressure repeater for the upper
connection.
The repeater transmits the total pressure at elevation B to the low
pressure side of the d/p Cell transmitter. In this way, the pressure at
elevation B is subtracted from the pressure at elevation A. Therefore,
the lower transmitter measures density (or H x G, where G is the
specific gravity of the lquid). The equations for the lower transmitter
are:
Span = H X (G2 -GJ
Zero suppression = H x G1
Fig.
whered1
3-18. In an open or closed tank with varying level and/or pressure where seal fluid
or purge is Rot suitable, a pressure repeater can be used.
Questions
88 FEEDBACK PROCESSCONTROL
3-3. A pressurized tank contains a lquid, SG = 1.0, and the level measuring
pressure taps are 100inches apart. A pneumatic differential pressure
transmitter is used to measure level. The leg that connects the top of the tank
to the transmitter is filled with tank lquid. The top tap should be connected
to:
a. The low-pressuretap on the transmitter.
b. The high-pressuretap on the transmitter.
, Either the high- or the low-pressuretap.
d. The high-pressuretap but througha sealchamber.
3.4. In Qu~stion3-3the bottom connectionis madeto the low-pressuretap
on the transmitterand the top is madeto the high-pressure
tap. The signal
output, if the transmitteris calibratedOto 100inches,whenthe tank is full
will be:
a. Topscalevalue
c. O
b. Bottom scalevalue
d. A measureof density
3.5. A plant hasa water tower mountedon top of an 80-footplatform. The
tank is 30 feet high. Whatis the heightof water in the tank if a pressuregauge
on the secondfloor, height 15feet,reads 40 psi.
a. Full
c. 4.74feet
b. 12.42feet
d. 27.42feet
3-6. A displaceris 5 inchesin diameterand 30 incheslong. If it is submerged
to a depthof 20 inchesin lquid sa = 0.8, whatforce will it exert on the top
works?
a. 11.3pounds
c. 35.5pounds
b. 426.3pounds
d. 1.47pounds
3.7. A closed tank level (Sa = 0.83)is measuredwith a differentialpressure
transmitter.The level mar vary from 10to 100inches.The high-pressuretap
is 10inchesabovethe transmitterand a watersealfluid is used.A pressure
repeateris usedfor the top tank pressure.The differentialpressure
transmittershouldbe calibrated:
a. 10to 100inches
b. 10to 84.7inches
c. 8.3 to 74.7inches
d. 8.3 to 98.3inches
3.8. To resistthe corrosiveeffectsof a very unusual,highlyexplosive
chemical,a storagetank is lead-lined.Level measurement
is difficult because
the materialalso solidifiesonce it entersa measuringtap. To measurethe level
with accuracythe bestchoicewould be:
a. Weighthe tank and its contentsand zero out the tare weightof the tank.
b. Use a radioactivelevel measurement.
c. Install a conductivitylevel measurement.
d. Use a thermal conductivitylevel detector.
a. 1.0
c. 0.9
b. 0.83
d. 1.2
Flow Measurement
The process industries by their very nature deal constantly with flowing
fluids, and measurement of these flows is essential to the operation of
the plant. These measurements are indicated, recorded, totalized, and
used for control. Flow measurement is generally the most common
measurement found in the process plant.
Fluid flow measurement is accomplished by:
Ao Displacement
lo Positive displacement meters
20 Metering pumps
Bo Constriction Type, Differential Head
lo Closed conduit or pipe
ao Orifice plate
bo Venturi tube
Co Flow nozzle
do Pitot tube
eo Elbow
fo Target (drag force)
go Variable aTea (rotameter)
20 Open channel
ao Weir
bo Flume
90
FLOWMEASUREMENT 91
C. Velocity Flowmeters
1. Magnetic
2. Turbine
3. Vortex or swirl
4. Ultrasonic
5. Thermal
D. Mass Flowmeters
1. Weighttypes
2. Head and magnetictypes compensatedfor temperature,pressure,
and density
3. Gyroscopeprecisiontypes
4. Centrifugalforce (torque)types
Positive displacementmeters and meteringpumps measurediscrete quantities of flowing fluid. This flow is indicated in terms of an
integrated or totalized flow volume (gallons,cubic feet, litres, cubico
metres, and the like). A typical applicationof this type of flow measurementis custodytransfer, and familiar examplesaredomesticwater
metres and gasolinepumps. The other types of meters listed above
measureflow rate.
lt is flow rate-quantity per time, suchas gallons per minute or
liters per second-which is most generallyused for measurementand
related control applications in the processplant. The most common
rate meter is the constriction or headtype.
Constriction
or Differential
Head Type
+ Z2 = ~p + ~
(VmJ2+ Zl
92 FEEDBACK PROCESSCONTROL
where:
P
Vm
Z
p
G
=
=
=
=
=
If the energy is divided into two forms, static head and dynamic or
velocity head, some of the inferential flow devices can be more easily
studied.
For example, with an orifice plate, the change in cross-sectional
aTeabetween the pipe and the orifice produces a change in flow velocity
(Figure 4-1). The flow increases to pass through the orifice. Since total
energy at the inlet to, and at the throat or, the orifice remains the same
(neglecting losses), the velocity head at the throat must in.crease,causing a corresponding decrease in static head. Therefore, there is a head
difference between a point immedlately ahead of the restriction and a
point within the restriction or downstream from it. The resulting differential head or pressure is a function of velocity that can then be related
to flow. Mechanical flow-measuring instruments use some device or
restriction in a flow line that results in such a differential head.
The following should clarify these relationships. Assume a tank as
shown in Figure 4-2. A flow line enters the tank and replaces the out-
Fig. 4-1. Orifice plate differential producer. The difference in head (pressure) atP, and
P 2is a function of velocity which can be related to ftow.
FLOW MEASUREMENT 93
-+
a=A.J2;
-..Q =AV2-;;h
ftow through the orifice located near the bottom of the tank. If the level
in the tank is H, the velocity of outftow will be:
y2 = 2GB
or
=AV
Substituting the expression for velocity in this equation:
(4-1)
This expression may also be used to calculate the rate offtow past a
point in a pipe. The actual ftow rate will be less than this equation will
V=Y2GH
Q
Q=A\f2Gii
O)
Fig.
94
The orifice plate is the most popular primary device found in most
process plants. Orifice plates are applicable to all clean fluids, but are
Dot generally applicable to fluids containing solids in suspension(dirty
fluids).
A conventional orifice plate consists of a thin circular plate containing a concentric hole (Figure 4-3). Th plate is usually made of stainless
steel but other materials, such as monel, nickel, hastelloy, steel, glass,
and plastics, are occasionally used. The most popular orifice plate is the
sharp-edged type. The upstream face of the plate usually is polished
and the downstream gide is often counterbored to prevent any interference with the flowing fluid. The bore in the plate is held to a tolerance
of a few ten-thousandths of an inch in small sizes and to within a few
thousandths in sizes above 5 inches in diameter.
ln addition to the conventional, sharp-edged, concentric plate,
there are others that bave been designed to handle special situations.
These special types constitute only a small percentage of the total, but
they do occasionally solve a difficult problem.
There are two plates (Figure 4-3) designed to accommodate limited
amounts of suspended solids. The eccentric plate has a bote that is
bored off-center, usually tangent to the bottom of the flow line (inside
periphery of the pipe). The segmentat orifice plate has a segment removed from the lower hal of the orifice plate. ln addition, there are
CONCENTRIC
ECCENTRIC
SEGMENTAL
Reynolds
FLOW MEASUREMENT 95
to drain.
Table 4-1 summarizes application factors to help in deciding
whether the orifice plate can do a particular job.
Another primary device that is frequently found in the process
plant is the Venturi tube shown in Figure 4-4. The Venturi tube produces a large differential with a mnimum permanent pressure loss. It
has the added advantage of being able to measure ftows containing
suspended solids. The most significant disadvantage is its cost which,
when compared with other primary devices, is high.
~~
G
VP
Fig.
96 FEEDBACK PROCESSCONTROL
" t
:
o:
Accuracy (empirical
data)
None
Pressure loss #
, P
Differenlial produced
for given ftow and size
p
E
E
P
P
E
P
F
G
G
E
~
.9"
.s~
".."
.~
~~~~"to"~
~5
"='"
" E
E
EG
None
E
E
GG
F
None
Non.
VP
G
G
F
U
E
F
P
F
F
VP
E
P
F
vapors
First cost
EGG *
F
E
E
U
G
Ease of changing
capacity
E
G
Ease of instalIalion
Excellent
G
F
Good
FairP
Poor
VP
U
/I
Very poor
Unknown
E indicates lowest loss, P highest, etc.
EG
EG
p
E
G
None
E
u
uVP
E
F
G
F
Fig.
FLOW MEASUREMENT 97
4-5. Flownozzleassembly.
Fig.
98 FEEDBACK PROCESSCONTROL
rb
4-7. Targetflowmeter.
FLOW MEASUREMENT 99
Oevices
Secondaryinstrumentsmeasurethe differential produced at the primary devices and convert it into a signal for transmissionor into a
motion for indication, recording, or totalization.
Secondaryinstrumentsinclude the mercury manometer,the socalled mercurylessor diaphragm(beUows)meterand various types of
force-balanceand motion-balancepneumaticand electronictransmitters.
In the past the mercury manometer was an extremely popular secondary device, but the high price and danger of mercury bave all but
eliminated it from everyday use. However, a few mercury manometers
are still employed for ftow rate measurements in gas pipelines. The
bellows or diaphragm secondary devices are popular when a direct
indication or record is desired. The most popular secondary device is
the force-balance transmitter. The reasons for this popularity are virtually unlinited adjustability, no harm from extensive overrange, and
the a vailability of a standard signal that can be fed into a recorder, a
controller, or other instruments that may be combined to form a sys-
tem.
Still another detail is the mounting of the secondary device (locations are shown in Figure 4-8). With liquid ftow, the secondary device is
LIQUID FLOW
GAS FLOW
STEAM FLOW
below the pipeline being measured to ensure that the connecting lines
attached to the sicle of the pipe remain liquid filled. With steam, the
lines should always remain filled with condensate; but with gas, the
secondary device is mounted above the ftow line to drain away any
liquid that mar be present.
When any primary device is installed in a pipeline, the accuracy
will be improved if as much straight run as possible precedes il.
Straight run beyond the primary device is of far less concem.
Still another important consideration is the location of the pressure
taps. With nozzles, Venturi, Dall and Pitot tubes, and elbows, the
pressure tap locations are established. For orifice plates, however, a
variety of tap locations are used. These are ftange, corner, vena contracta, or D and D/2, along with full ftow or pipe taps. Figure 4-9
describes these tap locations, and Figure 4-10 shows the importance of
tap location. In general, ftange taps are preferred except when physical
limitations make pipe taps advantageous. Corner taps require a special
ftange and vena contracta tap locations relate to orifice openings.
Corner taps are advantageous for pipe sizes under 2 inches.
Figure 4-11 describes the permanent head loss caused by the primary device selected.
Relating
The two basic formulas bave already been introduced. In the English
system, G = 32 feet per second squared, and in the metric system,
G = 980 centimetres per second squared. The height (h) would be expressed in feet in the English system and centimetres in the metric
Fig. 4-11. Pennanent head los s in a ditferential producer may be plotted as a percent of
measured ditferential for the several types of primary devices. These values must be
interpreted according to the acceptable head loss limit for any particular application.
will take a long time to complete. For tros reason the sample calculations that follow will use the English system.
In Equation 4-1, V is in fe et per second; the acceleration due to
gravity (G) is in feet per second squared; H is the height in feet of a
column of the fluid caused by the differential pressure across a primary
device. To express this equation in terms of an equivalent differential
(h), in inches of water, H is replaced by (h/12)G) where G is the
specific gravity of the fluid at flowing temperature.
Substituting V into Equation 4-1:
(4-2)
where:
Q = Volumetric flow (cubic feet per second)
A = Cross-sectional aTea of the orifice or throat of the primary
device (square feet)
h = Differential across the primary device (inches of water)
G, = Specific gravity of the fluid (dimensionless)
G = Acceleration due to gravity (a constant: 32.17feet per second2)
For lquids, it is more useful to express Q in gallons per minute.
AIso, it is convenient to express the area of the orifice or throat interms
of its diameter (d in inches). Substituting in Equation 4-2:
x~
(4-3)
= 5.667
SD2
fE::
V G;
Gi
(4-6)
which simplifiesto:
Q = 5.667 SIJ2 YG;l
GI
Pb" T;G
Ratio
0.100
0.125
0.150
0.175
0.200
0.225
0.250
0.275
0.300
0.325
0.350
0.375
0.400
0.425
0.450
0.475
0.500
0.525
0.550
0.575
Square-Edged
Orifice, Flange
Corner or
Radius Taps
Ful/-Flow
Quadrant-
2\-2& 8D
Nozz/e
and
Lo-Loss
Dall
Taps
Venturi
Tub.
Tube
(PipJ
0.005990
0.006100
0.009364
0.009591
0.01349
0.01389
Edged
Orifice
0.01839
0.01902
0.02402
0.02499
0.0305
0.03044
0.03183
0.0390
0.03760
0.03957
0.0484
0.04558
0.04826
0.0587
0.05432
0.05796
0.08858
0.06390
0.06874
0.1041
0.07429
0.08068
0.1210
0.1048
0.08559
0.09390
0.1392
0.1198
0.09776
0.1085
0.1588
0.1356
0.1170
0.1267
0.1109
0.1247
0.1800
0.1527
0.1335
0.1443
0.1251
0.1426
0.2026
0.1705
0.1500
0.1635
0.1404
0.1625
0.2270
0.1900
0.1665
0.1844
0.1568
0.1845
0.2530
0.2098
0.1830
0.207
0.1745
0.2090
0.2810
0.2312
0.2044
0.232
0.1937
0.2362
0.3110
0.2539
0.2258
0.260
0.0700
0.0824
0.0959
0.1106
0.2144
0.2664
0.3433
0.2783
0.2472
0.292
O.(X)()
0.2369
0.3002
0.3781
0.3041
0.2685
0.326
0.625
0.650
0.675
0.700
0.725
0.750
0.775
0.800
0.820
0.2614
0.3377
0.4159
0.3318
0.2956
0.364
0.2879
0.3796
0.4568
0.3617
0.3228
0.3171
0.4262
0.5016
0.3939
0.3499
0.3488
0.4782
0.5509
0.4289
0.3770
0.3838
0.6054
0.4846
0.4100
0.4222
0.6667
0.5111
0.4430
O.4646
0.5598
0.4840
0.5113
0.6153
0.5250
0.6666
0.5635
(4-10)
Equation 4,.10is applicable to gas ftow only when the pressure
differential is small enough so that gas density does Dot change significantly. A simple rule ofthumb is that the maximum differential in inches
of water should Dot exceed the absolute operating pressure in psi absolut.~. For example, if the gas operating pressure is 22 psi absolute, at a
particular installation, and the maximum differential is 20 inches of
water, Equation 4-10 can be used.
Flow rate 'measurements for gas and steam are more difficult to
make with accuracy than those for liquido The reason is changes in
specific gravity, weight, temperature, pressure, and so on, that mar
occur under operating conditions.
These changes will bave an effect on measurement accuracy and
under certain conditions mar be difficult to predict. An abbreviated set
of tables for the formulas given are included in this book. If more
accuracy is required, more exact equations, along with detailed tables,
such as those found in Principies and Practice oi Flow Meter Engineering
by Spink, should be used.
Another method of performing these ftow calculations is to use a
ftow slide rule. The ftow slide role has the table values incorporated
into its scales. If the tables given are used, the resulting accuracy
should be as good as the flow slide rule.
Now several sample problems are given to demonstrate the procedure followed for each type of calculation. Additional problems are
given at the end of tros chapter.
SAMPLEPROBLEMJ A 4-inch schedule 40 pipe carries water that is
measured by a concentric, sharp-edged, orifice plate, d = 2.000 inches,
with flange taps. The differential is measured with an electronic differential pressure transmitter. The transmitter is calibrated Oto 100inches
of water pressure and has an output of 4 to 20 mA dc. If the signal Crom
the transmitter is 18.4 mA dc, find the flow rate.
S/ep 1. Convert the electrical signal to differential pressure.
18.4 -4
20 -4
S =
0.475
0.1404
0.4968
0.5000
0.1568
(0.5000
0.4968 -0.475
-0.475 )
S = 0.1547
Step5. Substitute in Equation 4-7:
SAMPLEPROBLEM
2 An elbow is used as a primary device. The taps are
made at 45 degrees. The line is a 6-inch schedule 40 pipe. What is
the water flow rate if the effective radius of curvature is 9 inches
and a differential pressure of 35 inches of water pressure is produced.
= 172.66 .yj"5 =
,021.47gpm
SAMPLEPROBLEM
3 Dry-saturated steam is measured with a ftow nozzle. The d/D is 0.45 and the line size is a S-inch schedule SOpipe. The
static pressure is 335 psi. Calculate the ftow rate at a differential
pressure of 200 inches of water in pounds per hour.
W(pounds per hr.) = 359SD2V:y;
(4-8)
s = 0.2026
D = 7.625 inches (Table A-4)
Yf = 0.754 pounds per cubic feet
W(pounds per hour) = 359 x 0.2026 x 7.6252\1200 x 0.754
= 4,228.77x 12.28
W = 51,929 pounds per hour
SAMPLEPROBLEM
4 A 6-inch schedule 40 pipe (1D-6.065) carries fuel
gas with a specific gravity of 0.88. The line pressure is 25 psi. Plowing
temperature is 60oPand the ftow is measured with an orifice plate with
ftange taps. The maximum ftow rate is 2,000,000standard cubic feet per
day. Pind the diameter of the hole to be bored in the concentric orifice
plate if 20 inches of water pressure is full-scale differential.
2,000,000
= 7' 727 x S x. 6 0652 V120(25
+-~
24
(460
+ 6~
.2144
.2218
.2369
.600
~ =
D
( .2218
.2369
-.2144
-.2144
d = (.583)(6.065)
= 3.536 inches
Fig.
4-12. Variablearea(rotarneter)flowmeter.
surements common in' the typical process plant. Open-channel measurements utilize head meter techniques.
Primary
Devices
welrs.
V-notch weirs are essentially plates (usually metal) that contain a
V-shaped notch (Figure 4-13). The angle of the V can vary, but the
formulas given are for the most common angles 30, 60, and 90 degrees.
V-notch weirs are employed for lower ftow rates than those that would
be measured by a rectangular weir.
In weir measurement (Figure 4-15) the nappe, or profi1e of water
over the weir, must be completely aerated if good accuracy is to be
obtained. All weirs then produce some head loss as the lquid falls free.
If head loss is a problem, a ftume might be a better choice.
Flumes, a further development of the basic weir concept, are designed primarily to reduce the head loss that is experienced with the
CIPPOLETTI
WEIR~S>2H
ECTANGULAR
WEIR-j
MAX
I
: 4~
_L)2H
MAX
PREFERABLY
ANO
>4H
MAX
I
0>3H
MAX
C\PPOLETTI
WEIR
GPM
70000
50000
100
40000
80
30000
60
50
20000
40
30
10000
8000
6000
5000
10
4000
3000
6
5
2000
3
1000
800
600
500
1.0
400
De
300
0.6
05
0.4
200
0.3
100
80
60
50
OI
40
0.08
30
006
0.05
20
0.04
FLOW
0.03
10
0.02
8
FLOW
6
5
001
0008
0.006
0005
0004
0003
0.002
weir.
AERATION'UNDE.
NAPPE
.k.
,..~~--~~~:::::: ~~:.:--::::~
i o
t7::::::;:::~~~t=:=f:~:::::::--i
l CO"".~.,.....c"O" .. TH.OAT...TION!l/.".'N.'.cr' ON c~1
Lc
f ~~~--~:
~.
..PLAN
'. "
.1
M
,\
\\
:~+
.1-0
.1.
Ir:--
'-'0-.,,
;1
'LOW
,
l
oi;;;.
""
,o
.";;,,
''-
SECTION
o-o
~
:..:.;
c;...
.,
'" ~< '"",:,
~'""
~~~--c
~-c..,
":";oC~.i~~~~@a~
, \oi
~~~t;
a~~=~~:",-c-co",
~~~:,
ci ci ci ci ci ci ci":":"";";
;... ~
;. .., .., .., .., .., .., .., .., .., .., ..,
~ ~
-"""""""""""""""'"
.1~ ...
~ ri:
'"
G)
Q: .:
:;
oc:
~~
~~
~
'"'
~ r;:
'"
~
lo.
cE
'"
~
.9
~
e
=
e
~
t, .t
to.t
'2
~
=
~
'Q
.5
~ .t
e
'~
.!,
~ ...
~
'Q
~
'"
=
NN''~"""":'ob~=~~
~~~~~~~:!:!:!:f:f
e
=
.;!;:-::i
-::i.;!-::.;!
~-'c-~-;'-;';'~;'
~ .;
~"!I!J;)ION
sn!~ ..un;) qloowS
--.N
-..,
'" ~
...
oS
'C
Li:
Qj
:c
.., .., .., .., .., .., .., .., .., ..,
~~~~~~~~~~~~
99~9O999999
N N N ...,J,
...,J,
.
:.:.~..~...
-"'-0-,
= ...g ::-
~.
;:- ::,..,.0--;
O':":'N"'~""""'obd,=
~":-~9~9"'99999
g--NN""",,",.o""~o.
..~.-!!!"~.-!!!
c ;:;:- c '" ~ ;,- ~ ;,- "C>
'9 'i' ";' "f
"f ";' '" -.,.
";'
-NN
b.b
..
'~
..,.
o. o. o. o. o. o. o. o. o.
~~!~~:,:,~~~~:,
5
,5
o
~.
oS
""
.. to.
~ ;;: :::
.:.!::~;:~~~:':~J.
.~
!~;;;~~~~~~:!~~
~,\,O-9'\'99"'9999
OO'--N""""'-o"'~
113
'!~
GPM
MGO
3000
CFS
4000
2000
3000
2000
1000
800
1000
800
600
500
400
300
200
100
so
60
40
50
600
500
400
300
200
80
100
60
50
30
40
20
30
20
10
8
6
5
4
3
2
10
08
06
O~
10
08
04
03
06
05
0.2
03
04
100
-t++
MGO
80
02
OI
60
50
40
004
20
FLOW
10
8
OI
006
QO~
30
FLOW
CFS
008
008
006
OO~
004
002
I
I
I
2
HEAD-INCHES
L-I
2
HEAD-FEET
I I .I.
6
I
8 10
,.,.,.
,..
I~ 20
60
0.03
80 100
002
FLOW
.456810
2/:3
56
8 IQ
001
FIVE
INCHES IS HINIHUN FLA.L SCALE
HEAD III'H
FDXBORD FLOA' ANO CABLE
HE'ER
Parshallfiume
Flume
size (in.)
3.
Q = 0.992 HI,547
6
Q = 2.06 HI,58
9
Q = 3.07 HI,53
12
Q = 4.00 HI,522
Q = crs; L = crest length (fi); H
Flume
size (in,)
18
Q = 6.00 H',538
24
Q = 8.00 HI,55.
36
Q = 12.00 HI,566
48
Q = 16.00 Hl.578
= head (fi)
Velocity
Flowmeters
Magnetic Flowmeter
The principIe of the magnetic ftowmeter was first stated by Faraday in
1832, but did Dot appear as a practical measurement for the process
plant until the 1950s.Its advantages are no obstruction to ftow, hence
no head loss; it can accommodate solids in suspension; and it has no
pressure connections to plug up. It is very accurate and has a linear
ftow rate to output relationship. Its disadvantages are that measured
material must be lquid; the lquid must bave some electrical conductivity; and it is expensive.
Operation
Operation ofthe magnetic ftowmeter is based on Faraday's well-known
law of electromagnetic induction: The voltage (E) induced in a conductor oflength (D) moving through a magnetic field (H) is proportional
to the velocity (V) of the conductor. The voltage is generated in a plane
that is mutually perpendicular to both the velocity ofthe conductor and
the magnetic field. Stated in mathematical form:
E = CHDV
(4-11)
suspended material. Most industrialliquids can be measured by magnetic flowmeters. Exceptions are someorganic chemicals and most refinery products. Water, acids, bases, slurries, liquids with suspended solids, and industrial wastes are commou applications. The limitation is
the electrical conductivity ofthe liquido The magnetic flowmeter offers
no more restriction to flow than an equivalent length of pipe, Figure
4-21.
Structurally, a magnetic flowmeter consists of either a lined metal
tube, usually stainless steel because of its magnetic properties, or an
unlined nonmetallic tube. Linings for the metal tubes can be polytetrafluoroethylene (Teflon), polyurethane, or some other nonmagnetic,
nonconducting material.
The electrodes are suitably insulated from the metal tube. Nonmetallic fiberglass flow tubes do llot require any lining. The electrodes
most be insulated so that the voltage generated can be measured across
the electrodes. The insulation has no bearing on the actual voltage
generation, bot without the insulator, voltage would bleed off through
the metallic walls of the tube.
The coils are similar in design to the deflection coils used on a
television picture tube. Two coils are used and work together to create
a uniform magnetic field. The coils are generally series-connected, but
mar be parallel-connected if the measured flow velocity is low.
The signal output from the flow tube's electrodes is an altemating
voltage at supply frequency. This 10w-Ievel voltage is generally between 1 mV and 30 mV at full flow rate.
This 10w-Ievel altemating voltage must be measured and converted
either into a record or display or into a dc common denominator transmission signal. This signal, typically 4 mA at zero and 20 mA at full
scale, can be fed into a recorder or controller. The device that can
accomplish tros is a special type of transmitter. This transmitter is
located either directly on the flow tube (Figure 4-22), near it, or within
the control room. The preferred location is as near to the flow tube as
possible; temperature and corrosive conditions are the constraints that
dictate location. In some applications a digital or pulse rate signal output Cromthe transmitter mar be required, and this option is available.
Accuracy
The accuracy of most magnetic ftowmeter systems is 1 percent of fullscale measurement. This includes the accuracy of both the meter itself
and its secondary instrument. Because ibis type of meter is inherently
linear, its accuracy at low-ftow rates exceeds the practical accuracy of
such inferential devices as the Venturi tube. Accuracy of the Venturi is
:tO.75 percent, according to ASME Fluid Meters Report, and thai of
the secondary instrument is abolli :tO.5 percent. At the low end ofthe
measurement scale, secondary instrument readability decreases owing
to the square root relationship. The magnetic ftowmeter can be labora-
rate. Differential pressure changes occur as the vortices are formed and
shed. This pressure variation is used to actuate the sealed sensor at a
frequency proportional to vortex shedding.
Thus, a train of vortices generates an altemating voltage output
with a frequency identical to the frequency of vortex shedding. This
frequency is proportional to the flow velocity.
The voltage signal from the detector (Figure 4-25) is conditioned
and amplified for transmission by electronics located in a housing
mounted integral with the flowmeter body. The final output signal is
available either in pulse fonn with each pulse representing a discrete
quantity of fluid for totalizing or, optionally, as a 4 to 20 mA dc analog
signat for flow rate recording or control.
Turbine
Flowmeter
The turbine meler derives its name from its operating principie. A
turbine wheel (rotor) is set in the path ofthe flowing fluid. As the fluid
enters the open volume between the blades of the rotor, it is deflected
by the angle of the blades and imparts a force causing the rotor to turo.
The speed at which the rotor turos is related, over a specified range,
linearly to flow rate.
Several methods are employed to transmit this motion to a readout
device outside ofthe conduit. In some applications a mechanical device
convers the rotor motion directly to a register. In process applications,
however, the usual method is to use an electrical method. A coil containing a permanent magnet is mounted on the meter body. The turbine
flowmeter (Figure 4-26) consists of a section of metal pipe, a multibladed rotor mounted in the center ofthe straight-through passage,and a
magnetic pickup coil mounted outside the fluid passage. A shaft held in
place by fixed radian vanes supports the rotor assembly. As each blade
tip of the rotor passesthe coil it changesthe flux and produces a pulse.
The total number of pulses indicates the volum e of fluid which has
passed through the meter and the rate of the pulses generated becomes
a measure of flow rate.
Turbine flowmeters are frequently employed as sensors for inline
blending systems.
Turbine flowmeters bave excellent accuracy and good rangeability.
They are limited to clean fluids. They are expensive, but do bave
unique features.
Other Flowmeters
Conclusion
Questions
4-1. Match the head meter primary devices with the application (select asingle
rest answer for each):
Orifice plate ~
r.I. T-.
Hgh-pressure~~~._~recovery
Flow nozzle Venturi tube Pitot tube-
Elbow taps-e.
-c.
b. Air ducts
Sedimentin lquid
d. Economyand accuracyare
important
No straightrun available
4-6. A 2-inch schedule 40 line {lD = 2.067) is used to carry gasoline (SP
GR = 0.75). The ftow rate is measured with an orifice plate (d = 1.034)and
pipe taps are used. At full ftow rate a ditIerential pressure of 50 inches of
water is produced. What is the approximate full ftow rate in gpm?
8. 30 gpm
c. 250 gpm
b. 53 gpm
d. 36 gpm
4-7. Assume an 8-inch schedule 160 pipe (ID = 6.813 inches) carries a full
ftow of 40,000pounds per botir of dry saturated steam. The static pressure is
335 psi. Flange taps are used and the ditIerential pressure across the orifice
plate at full-ftow rate is 1OOinches of water. What is the size of the bare in the
orifice plate?
8. 4.357 inches
c. 2.271 inches
b. 3.645 inches
d. 5.109 inches
4-8. Fuel gas is carried in a 6-inch schedule 40 pipe (ID= 6.065 inches).
Flow rate is measured with an orifice plate using fiange taps and the bare in
the orifice is 3.457 inches. The specific gravity is 0.88, the fiowing temperatur~
is 60F, and the static pressure is 25 psi. Maximum fiow rate creates a
ditIerential of 20 inches of water. What is the approximate fiow rate in
cubic feet per day?
8. 1,500,000SCFD
c. 2,500,000SCFD
b. 2,000,000SCFD
d. 3,000,000SCFD
4-9.
8.
b.
c.
4-10.
8.
b.
c.
d.
4.11. With suspended solids and/or entrapped gas in a fiowing liquid, the
magnetic fiowmeter will:
8. Read high
b. Read low
c. Read the liquid fiow only
d. Read the correct total volume of the mixture
4-12. A turbine fiowmeter produces an output in the form of pulses. The total
number of pulses is:
8. Inversely proportional to fiow
b. Directly proportional to total ftow
c. Proportional to the square root of fiow
d. Proportional to the square of fiow
Temperature
Thermistors
Bimetallic devices
Optical and radiation pyrometers
Temperature-sensitive profitS
Various types of measurement control systems are compared in Table
5-1.
Instrument selection must anticipate overall control requirements.
Low cost often justifies consideration of filled systems for measurements below 1,200oPor 650C. Other advantages of mechanically or
pneumatically transmitted temperature measurements include lowexplosion hazard, simple maintenance requirements, high reliability,
and independence Crom external power. Advantages of electrical systems include higher accuracy and sensitivity, practicality of switching
or scanning several measurement points, larger distances possible between measuring elements and controllers, replacement of components
Table5.1. Comparisonof TemperatureMeasuringSystems
ComparisonFactors
Purchase cost
Long distance transmission
Change or replacement
o components
lnstallation costs
Maintenance
Averaging measurement
Surface measurement
Time constant
(bare bulb and no well)
Temperature difference
Sensitivity
Accuracy
Operating costs
Least
Favorable
Most
Favorable
lntermediate
F
E
p
p
EandP
F
P
T
T
F
P
E
Bo
F
F
R
T
R
E
R
F
F
F
P
F
E
F
R
T
F
P and T
P
Filled Thermal
Systems
MEASUREMENTS
129
Type
Principie
SAMA Class
Liquid
Volumechange
fluids
Lower range limit
Upper range limit
Organic liquido
(Hydro-carbons)
-200"F (- I3IY'C)
+6OO"F(+315C)
40F (25C)
600'F (33IY'C)
Ambient temperature
lA Full
Not required
Compensation
Sensor size
IB Case
Smallest
Medium
Largest
Overrange capabiJity
Sensor elevation elfect
Medium
Least
None
Greatest
None
Barometric pressure
effect (altitude)
None
Slightly (greatest on
smaIl spans)
Scale uniformity
Unifonn
"'.5 to "'1.0% ofopan
Non-Uniform
Uniform
;:0.5to;:I.0%ofspan
upper % of scaIe
;:O.5to;:I.0%of
spon
#1-ClasslIA
#2
Accuracy
Response (d)
#1 Fastest
Vapor (a)
Pressure change
11
Pressure change
III
arganic liquido
Puregases
(Hydro-carbons),
water
-425F
(-2SS"C)
+6OO'F (+3IS0C)
400'F (215C)
-45SOF (-2700C)
+l,4OO'F(+7ro'C)
1200F(700C)
1.000'F (5500C)
IIIB case
#3-Class
Slightly (greatest o
small spans)
lIB
#4 Slowest
Cost
Maximum
CapiIlary
standard
length
Highe.1
Lowest
Medium
30m or 100I
(a) Class 11 systems are supplied as either SAMA Class llA or lIB. In Class llA, sensor is aIways
hotter than tubing or instrument case. In Class lIB, sensor is always cooler than tubing or case.
(b) Narrowest spans vary at elevated temperatures.
(c) Smaller spans available in cryogenic regions.
(d) Actual values depend on range, capillary length, sensor dimensions, and type of instrument used.
Electrical
Systems
MEASUREMENTS
131
Calibration
r -F
oc
RTDs
Nickel
Platinum
SAMA Type 11
SAMA 100 ohm, or
-200 to 315
-320
DIN 43760
-200 to
O to
-210 to
-270 to
-270 to
-270 to
-50 to
-320 to 1,200
32 to 300
Copper
SAMA
Thermocouples Iron-Constantan, ISA Type J
Copper-Constantan, ISA Type T
Chromel-Alumel, ISA Type K
Chromel-Constantan, ISA Type E
Platinum-Platinum Rhodium,
ISA Types R & S
ISA Type B
650
150
760
370
1,260
870
1,480
o to 1,700
to 600
-350
-455
-455
-455
-55
to
to
to
to
to
1,400
700
2,000
1,600
2,700
o to 3,100
<
MEASURING
JUNCTION
THERMOCOUPLE
[JINSTRUMENT
REFERENCE
JUNCTION
percent.
Introduction of intermediate metals into a thermocouple circuit will
Dot affect the emf of the circuit, provided the new junctions remain at
the same temperature as the originaljunction. The algebraic sum ofthe
emf' s in a circuit consisting of any number of dissimilar metals is zero,
if all of the circuit is at a uniform temperature. Repeating the law, if in
any circuit of solid conductors the temperature is uniform from Point 1
through all the conducting material to Point 2, the algebraic sum ofthe
emf' s in the entire circuit is totally independent of the intermediate
material and is the same as if Points 1 and 2 were put in contact. If the
individual metals betweenjunctions ofthe circuit are homogeneous,the
sum ofthe thermal emf's will be zero, provided only that thejunctions
of the metals are all at the same temperature.
The emf in a thermoelectric circuit is independent of the method
employed in forming the functions as long as all the junction is at a
uniform temperature and the two wires make good electrical contact.
The junction mar be made directly, by welding, or by soldering. Furthermore, an instrument for measuring the emf mar be introduced into
a circuit at any point without altering the resultant emf, provided the
junctions that are added to the circuit by introducing the instrument are
all at the same temperature. If the temperatures of the new junctions
are DOt uniform, the effect is that of introducing additional thermocouples into the circuit.
Reference Junction
To make accurate temperature measurements with thermocouples, the
reference junction temperature must remain constant; if it varies, suitable compensation for these variations must be provided.
Should there be an uncompensated variation in the reference junction temperature, there will be a corresponding change in the millivoltage with a resultant error in temperature measurement (Table 5-4).
When used in the laboratory and for other checking and testing
purposes, the thermocouple reference junction can be placed in a vacuum bottle filled with shaved ice saturated with water. This method
provides close temperature control (within a fraction of a degree) and
permits accurate reading.
Table5-4. StandardLimits or Error
Coupleor Wire
Range
Limits
Copper-constantan
-300 to -75F
-75 to +2000F
200 to 700F
-100 to + 530"F
:t2% oCreading
:tl~oF:t~
% oCreading
:t4F
Chromel-alumel
530 to l ,400"F
Oto 530F
530 to 2,300"F
:t~% oCreading
:t4F
Platinumrhodiumplatinum
Oto 1,000F
1,000to 2,700"F
Iron-constantan
:t~% oCreading
:tJoF
:tO.J% oCreading
75
KX
~~ WIRE~[]
THERMOCOUPLE
MEASURING
JUNCTION
EXTENSION
<
INSTRUMENT
CONNECTION
HEAD
REFERENCE
JUNCTION
it.
An industrial installation generally consists of a thermocouple with
its connection head, the necessary length of extension wire, and an
indicating, recording, or controlling instrument with internal and automatic reference junction compensation. The extension wires generally
consist of the same materials as the thermocouple elements, or mar be
composed of other materials and alloy wires that generate essentially
the same millivoltage as the thermocouple for application temperatures
up to approximately 400F or 200C(Figure 5-4). The ISA symbols and
color codes for thermocouple lead wires are given in Table 5-5.
Table 5.5. Extension Wire Type Designations and Standard Limits of Error
[SA
Extension
Type
Wire
Color
Code
TX
Copperconstantan
Ironconstantan
Ironcupronel
Chromelalumel
CopperCuNi alloy
+ (blue)
-(red)
+ (white)
-(red)
+ (green)
-(red)
+ (yellow)
-(red)
+ (black)
-(red)
JX
wx
sx
Limits 01
TemperatureRange
F
Error
-75 to +200
:t 1~F
Oto
400
:t4 F
75 to
400
:6 F
to
400
:t4 F
75 to
400
:10 F
Couple
UsedWith
Copperconstantan
Ironconstantan
Chromelalumel
Chromelalumel
Platinum
Rhodiumplatinum
Fig.
<
MEASUREMENTS
135
A verage Temperatures
To measure the average temperature across a large duct or vessel, or
around a retort, any number of thermocouples mar be used in parallel
connections. The voltage at the instrument, or at the point of parallel
connection, is the average of that developed by the number of thermocouples used. This voltage is equal to the sum of the individual
voltages divided by the number of thermocouples. For accurate measurement, the resistances of aU thermocouples and extension wire
circuits should be identical. Since the resistance of the actual thermocouple wiU vary with temperature, and since the lengths of extension wires mar also vary, the efIect of these variations can be minimized by using swamping resistors. The values of the swamping
resistors should be high in comparison with the change or difIerence in
resistances encountered. A resistor value of 1,500 ohms generaUy
works weU.
In order to prevent the flow of current through a ground loop, the
thermocouples should not be grounded. AU thermocouples must be of
the same type and must be connected by the correct extension wires
(Figures 5-5 and 5-6).
ParaUel connection of thermocouples for average temperature
measurement is advantageous because the instrument construction and
<
PotentiometricRecorder
Figure 5-8 shows a simplified circuit diagram of the Foxboro potentiometric recorder (Figure 5-9). An emf input (Ex) is derived Croma
thermocouple or other measuring element. A constant emf (Ez) is
supplied by a Zener diode regulated power supply. As Ex varies, an
error signal is developed, and the circuit becomes unbalanced.
The error signal is converted to an ac voltage by a field effect
transistor chopper and amplified by the integrated circuit amplifier. The
amplified output drives a two-phase balancing motor. The direction of
rotation depends on whether Ex has become greater or smaller. The
motor moves the wiper contact on the slidewire Rsto a position where
the circuit is rebalanced. The slidewire coritact is mechanically con-nected
to the recorder pen, and both are positioned simultaneously.
With a thermocouple input, a temperature sensitive resistor (Rc)
automatically compensates for referenc junction ambient temperature
variations. This resistor changes the balance of the circuit to cancel
TEMPERATURE,
AND HUMIDITY MEASUREMENTS 139
Detectors
Resistancethermometry is based on the change of electrical conductivitv with temperature.Therefore.a coil of wire can act as a tem-
perature sensor, with 'a direct relationship established between resistance and temperature. Standard curves are available, with certified
accuracies within O.IF or oC. Platinum RTDs used as laboratory standards can be obtained with tolerances well within this lmit, and are
capable of precise temperature measurement up to l,650F or 900C. If
an RTD is adjusted to conform to its curve, it may be interchanged with
other RTDs calibrated according to the same curve.
Fig. 5-12. Simplified circuit diagram of 34B Series nickel RTD transmitter.
the appropriate nickel bulb, the converter has an output that is linear
with temperature. Spans as low as 5F or 3C can easily be achieved.
An adjustable range allows a simple field calibration procedure to
change the temperature input range required for a 3 to 15 psi or 20 to
100kPa output. It also operates on all normal supply voltages.
This transmitter is an electromechanical device consisting of a
solid-state, integrated circuit amplifier and an output transducer. Figure 5-12 isa simplified circuit diagram of the nickel RTD version of the
transmitter. The transd ucer is shown in Figure 5-13.
The RTD is wired into a measurement bridge and excited Croma
regulated direct current power supply. The change in resistance of the
RTD causes a bridge output change that is proportional to temperature.
Negative feedback is obtained Cromthe output current and applied to
the opposite side of the measurement bridge. A change in feedback by
the span adjustment changes the gain of the amplifier and thereby
changes the span of measurement.
MEASUREMENTS
143
changes. This unbalances the bridge and creates an error signal between Points A and B.
As in the potentiometric recorder, the error signal is converted to
art ac voltage by a field-effect transistor chopper and amplified by the
transistorized amplifier. The output drives a two-phase balancing
motor. The direction of rotation depends on the polarity of the error
signal. The motor moves the wiper contact on the slidewire until the
bridge is rebalanced and no error signal exists. The pen and slidewire
contact are mechanically connected and therefore positioned simultaneously.
With all resistance-temperature measurements, the use of threeconductor RTD cable is recommended. The effect of ambient temperatufe variations on the cable is thereby minimized.
If the cable connecting the RTD to the instrument has only two
conductors, these conductors become part of the resistance being measured. The result then is an error that will vary with ambient temperature. Remember, with all resistance temperature measurements,
three-conductor RTD cable is recommended. The purpose of the threeconductor cable is to stretch out the measuring bridge. Note the threeconductor cable in Figure 5-14. One of the conductors is common to
both sides ofthe bridge while the other two connect one to each side of
the bridge. Any change in cable temperature will be canceled as both
sides of the bridge are changed a like amount.
Occasionally RTD sensors use a four-wire cable. This is generally
in conjunction with a Kelvin double bridge. The four-wire method does
an excellent job of reducing temperature effects on the cable. The
improve ment over the three-wire method, however, is minimal. In
practice, an RTD may be used with as much as 500 feet of threeconductor cable without the cable creating a perceptible error.
Thermistors
Thermistors are made of heat-treated metallic oxides, and most thermistors differ from ordinary resistors by having a negative coefficient of
resistance. Thermistors are available with a nearly linear temperature
resistance relationship, and other types are available with a sharp
change in slope at some characteristic temperature.
A thermistor can replace an RTD as a temperature sensor. The
difficulty lies in obtaining units that fit the desired characteristic curve
within acceptable lmits of accuracy. When this is accomplished and
the thermistor is mounted so as to stand up under process conditions, it
performs the same function as the conventional RTD.
One advantage of the thermistor is that it has a greater resistance
change for a given temperature change than that of the conventional
wire RTD. A disadvantage is that the accuracy available, although
good, is slightly inferior to that of the conventional RTD. This presumably accounts for the thermistor's limited application in the process
instrumentationfield.
Radiation pyrometers utilize an optical system to focus energy
radiat~d from a body onto a sensing system. Manual devices are often
l:I~ed;'in which energy at infrared or visible wavelengths is focused on a
tar~t'aridcompared
with the light output of a calibrated optical filamentJ9automated devices, the energy (usually in the infrared band) is
focusedori a series arcar ofthermocouples. This thermopile produces a
millivolt output related to the temperature of the source. Pyrometers
are used where high temperatures are to be measured or where contact
with the object is impossible. Accuracy is influenced by such factors as
reflections, gases present in the radiation path, and surface emissivity
of the body under measurement.
Humidity
Measurements
'-+'2.
"0
MEASUREMENTS
147
.'0
.]
.."
I
l
,
1001
t,
,
,
..
E
~
~
2 00"
~
~
C
E
~~
'
;l
.,~f-.#"
I I
2
C
f-
.fH-~
1--
--'
"- -17' I
--/
-fi
-:eo
-40
-00
00
OEW POINT
40
10
TEMPERATURE
80
100
100
140
.F.
tor.
Moisture determination by this lithium chloride element is based on
the fact that, for every water vapor pressure in contact with a saturated
salt solution, there is an equilibrium temperature at which this solution
neither absorbs noc yields moisture to the surrounding atmosphere.
This equilibrium temperature is shown in Figure 5-16 as the "DEW-
Questions
MEASUREMENTS
149
5-14. A psychrometeris:
a. A hair elementinstrument
b. A "wet and dry bulb" humidity instrument
c. An instrumentthat sensespsychologicaldisturbances
d. An instrumentthat readsdirectly in dew point
5-15. A hygrometeris:
a. Convenientfor measuringspecificgravity
b. An instrumentthat measuresgas weight
c. Any instrumentthat measuresmoisturecontent
d. Anothernamefor psychrometer
5-16. A certainthermocouplehasa specifiedtime constantof 2 seconds.If
the processtemperaturechangesabruptly from 800to 900C,the temperature
readouton the indicatorattachedto the thermocouplearter6 secondselapse
will be approximately:
a. 860C
c. 900C
b.835C
d. 895C
5-17. The air velocity pastthe sensorsof a "wet and dry" bulb instrument
shouldbe:
a. 50 feet per second,minimum
b. 2 metresper second,maximum
c. Approximately4.6 metresper second
d. Any value
5-18. The advantageof usinga three-wirecableto connectan RTD to its
associatedinstrumentis that:
a. Referencejunction errors are eliminated
b. The effectof ambienttemperatureon the cablewill be minimized
c. Potentialfailures will be minimal
d. Resistancein the externalcircuit is reduced
5-19. A thermocoupleinstrumenthas an input resistanceof 50,000ohmsand
is usedwith an IC Type J couple.The leadwire is #18 gauge,120feet long.
What is the approximateerror contributedby the leadwire?
a. :t5.0 percent
c. :t0.05 percent
b. :t0.5 percent
d. :tO.1 percent
5-20. The differencebetweenanRTD calibratedto the NR 226curve and one
calibratedto the NR 227curve is:
a. A differentresistance-to-temperature
relationship
b. Nonexistent
c. Greateraccuracywith the NR 226curve
d. Greateraccuracywith the NR 227curve
Electrical
Conductivity
While dissociation into ions and the resulting iOD concentration bave
been adequate concepts in the past, the fact is that DOt all the ions
present are necessarily effective. Some ofthem mar be "complexed,"
151
that is, "tied up" to'other ions and unavailable for reation. The concept of activity covers this situation. In short, a given compound will
dissociate to some degree, described by the dissociation constant, into
ions, and some portion of these ions will be active, described by the
activity coefficient. However, in many common reactions, the activity
coefficient is so near unity that concentration and activity mar be used
interchangeably. In a growing number of processes, the actual ion activity is different enough Cromthe ion concentration to make it necessary to use the proper term. In general, electrochemical measurements
measure activity rather than concentration, and it is always desirable to
refer to the measurements as ion activity rather than ion concentration.
Electrochemical measurements all rely upon the current-carrying
property of solutions containing ions. Some techniques measure all ions
present (electrolytic conductivity). Others respond mainly to particular
types of ions-hydrogen ions (pH); oxidizing/reducing ions (ORP); selected ions (ion-selective). These will be discussed separately below.
The ability to conduct electricity, or the reciprocal of electrical
resistance, is called conductance.The unit in which it is measured is the
reciprocal ohm, commonly called mho. The conductance of any conductor depends on the nature of the material, the shape of the conducting path, and the temperature. In analytical work, only the nature ofthe
material, in this case the type and activity of the ions present, is important. Thus, the term conductivity, the conductance of a volume of the
material of unit length and area, is generally used. (Conductivity has
largely replaced an earlier term, specific conductance.)
In actual measurement, a conductivity cell of known geometry is
immersed in the material, and the resistance (or conductance) across
the cell is measured. This gives a measurement that can be calibrated
directly in conductivity due to the known shape of the cell. Conductance and conductivity are related as follows: the greater the length
of a material of given conductivity, the higher its resistance (the lower
the tonductance); but the greater the aTeaofthe material, the lower the
resistante (the greater the conductance). That is,
aTea
conductance= conductivity iength
(6-1)
centimeters
squarecentimeters
(6-2)
or,
conductivity = mho. cm-1
It is unfortunately common practice to omit the dimensional unit,
so that conductivity is then referred to as mhos. This practice leads to
confusion with conductance, and should be avoided.
The conductivity of most electrolytes at the concentrations and the
temperature ranges normally encountered fall well below unity. For
this reason, the micromho per centmetre, the millionth part of the mho
per centmetre, is normally used.
In the SI system of units, the siemens replaces the mho. One mho
equals one siemens. In conductivity units, one micro mho per centimetre (J.mho/cm)equals one microsiemen per centmetre (J.S/cm).
However, the actual SI unit is the microsiemens per metre, since the
unit of length in the SI system is the metre rather than the centmetre.
One J.S/cmequals 100 J.S/m.
The conductivity of material of unit length and area which has a
resistance of 1,000ohms is 0.001 mho. cm-Ior 1,000micromho .cm-1
(sometimes called simply 1,000 micromhos).
Since the measurement depends on the geometry ofthe cell used, a
cell constant (F) has been defined to describe this geometry simply:
F = length (cm)
aTea(cm2)
(6.3)
(6-4)
Types
ot Calibration
in Conductivity
156
FEEDBACK PROCESSCONTROl
The sensitive portion of the cells shown i~ Figure 6-3 consists of two
platinum electrodes mounted in an H-shaped structure of Pyrex glass
tubing. The electrodes, located in separate sections of the tubing, are
concentrically mounted platinum rings and are ftush with the inside
surface of the tubing. Fouling or damaging the electrodes is thus minimized, and the cells mar easily be cleaned chemically or with a bottle
brush. The platinum electrodes in these cells are coated with platinum
black to minimize polarization etfects.
The cell shown in Figure 6-4 employs graphite, rathr than metallic
electrodes. The type of graphite used has the same surface properties
with respect to polarization as metallic electrodes. These
cells require no platinization. They are cleaned chemically or by wiping
the surface of the electrode with a cloth or brush.
Conductivity cells (Figure 6-5) are used for detecting impurities in
boiler feedwater, for concentration of black liquor (in a pulp digester
for kraft paper), for determination of washing etfectiveness by measurement ofpulp wash, and in many other applications where the presence and concentration of a known salt, base, or acid must be deter-
mined.
Electrodeless
Conductivity
Measurements
~
~
~.
~
Hydrogen
The
term
pH
solution.
of
It
an
means
is,
at
vary
from
any
in
is
tion
of
the
pH
the
to
hydrogen
degree
amo
unt
ofthat
percent).
of
of
ion.
The
potentiometric
ions
acidity
a
(H+)
or
given
Activity
in
alkalinity
ion
actually
values
measurement
can
ofpH,
measurement
that
as
obeys
explanatech-
to
with
ofthe
of
This
an
measurement
along
activity
activity
1 (100
is
equation.
employed
the
effective
called
chapter,
contains
nique
The
percent)
this
of
a measure
time
Nemst
chapter
a measure
solution.
O (O
discussed
(pH)
therefore,
aqueous
present
the
lon Activity
determine
the
Nemst
equation.
To
aid
further
in
understanding
surement,
of
the
properties
some
a thorough
of
pH
meafundamentals
of
aqueous
,---TOROIO
SECONOARY
!'RI MARY
TOROIO
CELL BORE
~~,
solutions
most
be
understood.
CELL
lonization
or Dissociation
;\)'
.1
:;\
\"'
~
!~~
"",,' -'
ELECTRIC ./
"~~~~
ticles. These charged particles are called ions. Ions travel from one
electrode to the other if a voltage is impressed across electrodes
immersed in the solution.
Positive ions, such as H+, Na+, and so on migrate toward the
cathode, or negative terminal, when a voltage is impressed across the
electrodes. Similarly, negative ions, such as OH-, CI-, S04-2, and so
on, migrate toward the anode, or positive terminal.
The freedom of ions to migrate through a solution is measured as
the electrical conductivity of the solution. Chemical compounds that
produce conducting solutions are called electrolytes. Not all electrolytes completely dissociate into ions. Those that do (strong acids,
strong bases, and salts) are strong electrolytes. Others dissociate, but
produce fewer than one ion for every element or radical in the molecule. These are poor electrical conductors, and, hence, weak electrolytes. All weak acids and weak bases fall into this class.
At a specified temperature, a fixed relationship exists between the
activity of the ions and undissociated molecules. This relationship is
called the dissociation constant (or the ionization constant).
For hydrochloric acid (HCI), the dissociation constant is virtually
infinite, which means that for all practical purposes, the HCI is completely composed of positively charged hydrogen ions and negatively
charged chloride ions. Because of the essentially complete dissociation
into ions, hydrochloric acid is a strong acid:
HCl -+- H+ + Cl-
Sodium hydroxide is, for all practical purposes, completely dissociated and is a strong base.
Conversely, ammonium hydroxide, NH4OH, dissociates very little
into NH4+ ions and OH- ions, and is a weak base.
The OH- iODactivity, or strength, of a base depends on the number
of dissociated OH- ions in the solution. The w\mber available depends,
again, DOtonly on the concentration of the compound in water, but also
on the dissociation constant of the particular compound.
Pure water dissociates into H+ and OH- ions, but is very weak in
the senseused above. That is, very little ofthe HOH breaks up into H+
ions and OH- ions. The number of water molecules dissociated is so
small in comparison to those undissociated that the activity of (HOH)
can be considered 1 (100 percent).
HOH ~ H+ + OHAt 77F or 25C, the dissociation constant or water has been
determined to bave a value or 10-14. The product or the activities
(aH+)(aOH-) is then 10-14.
If the activities or hydrogen ions and hydroxyl ions are the same,
the solution is neutral; the H+ and OH- activities must both be 10-7
mols per litre.
It must be remembered that, no matter what compounds are present in an aqueous solution, the prJduct or the activities or the H+ ions
and the OH- ions is always 10-14at 77F or 25C.
If a strong acid, such as HC1, is added to water, many hydrogen
ions are added. This must reduce the number or hydroxyl ions. For
example, if HCl at 25C is added until the H+ activity becomes 10-2,the
OH- activity must become 10-12.
The pH Scale
(-::
aH
(6-5)
Table 6-1
Temperature oC
-Log
(aH+)(80H-)
14.94
14.00
13.26
12.69
12.26
25
50
75
100
Neutral pH
7.47
7.00
6.63
6.35
6.13
Activity
Mols/Litre
Hydroxyl Jan
Activity
Mols/Litre
10.1
0.00000000000001
1
2
0.01
0.001
0.0001
O.0000 1
0.000000001
0.000001
0.00000001
0.0000001
0.0000001
0.00000001
0.000001
pH
Neutral
9
10
11
12
13
14
0.0000000000001
0.000000001
0.0000000001
0.00000000001
0.000000000001
0.0000000000001
0.00000000000001
0.000000000001
0.0000000000I
0.0000000001
0.00001
0.0001
0.001
0.01
0.1
I
10
Therefore, the activity of hydrogen ions will be greater than 10-1, that
is, 10-6, 10-5,10-4. The pH of an acid solution then, by definition, must
be lower than 7, that is 6, 5, 4.
If the number of OH- exceeds H+ ions, the hydrogen iODactivity
must be less than 10-1, that is, lO-s, 10-9,10-1. Therefore, the pH will
be higher than 7, that is, 8, 9, 10.
Table 6-2 demonstrates that a change of just one pH unit means a
tenfold change in strength ofthe acid or base. The reason for this is that
there is an exponential relationship between pH numbers and hydrogen
iODactivity. With so large a change in acidity or alkalinity taking place
with a change ofjust one pH unit, the need for sensiti ve pH measuring
and control equipment cannot be overemphasized.
Table 6-3 shows the nominal pH values for a number of common
solutions.
Table 6-3
pH
14 ~ Caustic soda 4% (I.ON)
--Calcium hydroxide (sat'd sol.) (Iime)
12 --Caustic soda 0.04% (O.OIN)11
--Ammonia 1.7% (I.ON)
--Ammonia 0.017% (O.OIN)
9 +- Potassium acetate ~.98% (O.lN)
8 +- Sodium bicarbonate 0.84% (O.lN)
6
5 ~ Hydrocyanic acid 0.27% (O.lN)
3 ~ Acetic acid 0.6%
"'
1 +- Hydrochloric acid 0.37% (O.IN)
+- Sulfuric acid 4.9% (I.ON)
O +- Hydrochloric acid 3.7% (I.ON)
-1 +- Hydrochloric acid 37% (lON)
d
-~---~
)LASrIC
ot pH-The
Glass Electrode
(
r--y=
MOISTURE
SEAL
CAl
SILVERSILVER
CHLORIDE
COLUMN
SHIELDED
!LECTRODE
CABLE
GLASS-TO-METAL
SEAL
; "TOTAL GLASS" CONSTRUCTION)
NTERNAL
SOLUTION
,H-SENSITIVE
MEMBRANE
E'
lo
nF
aH+o~ts~de
aH+
mslde
(6-6)
where:
E = potential difference measured
Eo = a constant for a given electrode system at a specified temR =
T =
n =
F =
aH+ =
perature (25C)
the gas law constant
Absolute temperature
charge on iOD(+ 1)
Faraday's number, a constant
hydrogen iODactivity
Electrode
The potential inside the glass is the output o the measuring electrode.
It must be compared to the potential in the solution outside the giassto
determine potential difference and, hence, pH. The sensing o the potential in the solution must be independent o changes in solution composition. Platinum or carbon would act as aRP, or redox-measuring
electrodes. They would be responsive to oxidants or reductants in the
solution. They would Dot yield a true solution potential with solution
composition changes.
Plastlc
Body
Internal
Electrode
Element
AgAgCI
The major potential difference exists in the reference electrode, between the metallic silver and the silver ions in the AgCI solution. It
follows from the Nemst equation:
(6-7)
Because R, n, and F are constants, and aAgoand AAg+ are fixed,
this potential (E) will vary only with the absolute temperature of the
electrode. Since there is a definite chemical relationship between the
ionic silver and the activity of chloride in the KCl electrolyte, the above
expression mar also be written as:
E = Eo -kT
log aCl-
(6-8)
To compensate for ibis temperature sensitivity, another silversilver chloride electrode is inserted into the top of the glass measuring
electrode, the internal conductor element mentioned previously. As the
temperature of the electrode changes, the potentials of the reference
electrode and the conductor element will vary, but will effectively cancel each other, assuming similar values for aAg+ (or aCI-) in each electrode as is usually the case.
ot the pH Electrodes
The high resistance of the giass measuring electrode results in the need
for a millivolt meter with very high internal resistance or sensitivity to
measure the cell output. The pH electrodes mar be compared to a pair
of ftashlight cells in series, but unlike the ftashlight cell, the electrodes
Fig. 6-12. Graph oCpH measurement errors versus pH values at various solution
temperatures due to temperature differences across the measurementelectrode tip.
,;,
005
BASE
001
REAGENT
001
005
AtiO
OI
REAGENT
Fig. 6-15. Typical neutralization curves for unbuffered solutions (strong acid or strong
base) and buffered solutions. Examples of buffered solutions are (I) weak acid and its
sale with the addition of a strong base, and (2) strong acid or base, concentrated, 0.01
M.
Oxidation-Reduction
Potential
For example, a ferrous iODmar lose an electron and become a ferric iOD
(gaining increased positive charge) if a reduction, say, of stannic to
stannous ions (which is the reverse ofthis operation) occurs at the same
time.
This measurement uses electrodes similar to those in pH measurement (except that metal is used instead of glass), but the two types of
measurement should DOtbe confused. The measurement depends on
the oxidizing and reducing chemical properties of reactants (not necessarily oxygen). The inert metal electrode versus the reference electrode
will produce a voltage that is related to the ratio of oxidized to reduced
ions in solution.
This measurement is similar to that of pH in the requirements that
it places on the voltmeter used with it. It is useful for determinations in
waste treatment, bleach production, pulp and paper bleaching, and
others.
The application of ORP measurement or control depends on a
knowledge of what goes on within the particular process reaction. The
ORP measurement can be applied to a reaction only under the following
conditions:
1. There are present in the solution two reacting substances: one that
is being oxidized and one that is being reduced.
2. The speed of reaction, following an addition of one of the substances above, is sufficiently fast for good measurement or control.
3. Contaminating substances are held to a minimum, especially those
capable of causing gide reactions of oxidation or reduction.
4. The pH ofthe solution is controlled in those areas ofthe applicable
curve where variations in pH can affect the ORP measurement.
lon-Selective
Measurement
Certain applications require that the activity of a particular iODin solution be measured. This can be accomplisehd with an electrode designed
to be sensitive to the particular iODwhose concentration is being measured. These electrodes are similar in appearanceto those employed to
Chromatography
cable
Specificity
Sensitivity
Conducting
fluids
Nonconducting
fluids
Maintenance
InstalIation
problems
Cost
Capacitance
Conductivity
pH or
ion-selective
ORP
Poor
Pair
Not
applicable
Good
Poor
Good
Good
Excellent
Excellent
Good
Poor
Excellent
Good
Not
Not
applil
appIiI
Low
Low
Low
Low
High
High
Not
applicable
Medium
Low
Low
Low
Medium
Low
Capacitance
Capacitance is Dot, as applied, an electrochemical measurement. However, a measurement of some characteristic in a nonconducting liquid is
frequently required, and in these applications, capacitance mar provide
the answer.
Electrical capacitance exists between any two conductors separated by an insulator (dielectric). The amount of capacitance depends
on the physical dimensions of the conductors and the dielectric constant of the insulating material. The dielectric constant (K) for a vacllum is 1; all other dielectric materials bave a K greater than 1. For
example, for air, K = 1.00588; for dry paper, K = 2 to 3; for pure
water, K = 80. The Table of Dielectric Constants of Pure Liquids
(NBS Circular 514), available Crom the U.S. Govemment Printing
Office, lists the dielectric constants of nearly all common liquids.
Mixtures of materials bave a composite value of K that can be
directly related to composition. This approach is readily applied to the
determination of water content in materials such as paper and crude oil.
Capacitance is also applicable to level, interface, octane, and other
measurement problems.
In general, the capacitance technique has provided a solution to
many measurement problems that cannot be solved easily by more
conventional means. Table 6-4 compares the application of pH, ORP,
ion-selective, conductivity, and capacitance measurements to process
situations.
References
Conductivity cells. Technical Information Sheet 43-10a. Foxboro, MA., The
Foxboro Company.
Fluoride measuring systems-potable water. Technical Information Sheet
43-21a. Foxboro, MA., The Foxboro Company.
Fundamentals of pH measurement. Technical Infor~{ltion Sheet 1-90a.
Foxboro, MA., The Foxboro Company.
pH e1ectrodesand ho1ders. Technical Information Sheet43-11a. Foxboro,
MA., The Foxboro Company.
Theory and app1icationof oxidation-reduction potentials. Technical
Information Sheet 1-61a. Foxboro, MA., The Foxboro Company.
Pneumatic composition transmitter. Technical Information Sheet 37-1.30a.
Foxboro, MA., The Foxboro Company.
Liptk, B. G. Instrument Engineer's Handbook, Sec. 81, Volume I. Radnor,
PA: Chilton.
Shinskey, F. G. pH and pION Control in Process and Waste Streams.
New York: John E. Wiley and Sons, 1973.
Questions
6-3. pH is a measureor:
a. Effective acidity or alkalinity of a liquid
b. The oxidationor reductionpropertiesof a solution
c. Specificconductanceof an electrolyteor total ionic activity
d. Purity in an aqueoussolution
6.4.
a.
b.
c.
d.
8.
b.
c.
d.
6-6. Capacitancemeasurements
are usuallyappliedto:
8. Conductingliquids
c. Gasmeasurements
b. Nonconductingliquids
d. lonized gases
6.7.
8.
b.
c.
d.
8. A ftowingtype
b. A pressurizedftowing type
c. A nonftowingtype
d. A pressurizednonftowing
type
6-14. The pH of 8 streamis to be monitoredaccurately.It is discoveredthat
the temperatureof this streamvariesfrom 40 to 60F:
8. A measuringsystemwith automatictemperaturecompensation
is
indicated
b. Temperaturecompensationis not necessary
c. A manualtemperaturecompensationwill be adequate
d. The pH rangewill determinethe needfor temperaturecompensation
6-15. The most popularcarriergasusedin gaschromatographs
is:
8. Helium
c. Hydrogen
b. Air
d. Oxygen
SECTION
II PNEUMATIC
AND ELECTRONIC
CONTROL
SYSTEMS
e~r
e=r-c
Fig. 7-1. Algebraic summing point.
and resistance. These factors cause phase changes that will be described in this chapter.
Gain appears in two forms-static and dynamic. Gain is a number
that equals the change in a unit's output divided by the change in input
which caused il.
Gain = AAoutput
input
The static gain of an amplifier is easily computed if, for a given step
change in input, the resulting change in output can be monitored. Case
A in Figure 7-3 shows an amplifier with a static gain of one. In Case B,
the output is magnified when compared with the input by a factor
greater than one. In Case C, the output change is less than the input.
Rere, the input has been multiplied by a number less than one.
The dynamic gain of an amplifier mar be computed by inducing a
giDewave on the input and observing the resulting output. Figure 7-4
illustrates this procedure with an amplifier that has no time lag between
its input and output. If the amplitude of the output is only hali as high as
Case
20%
5%
10% [ 10%
Output change
10%
10%
Static gain
!Q=1
10
22
10=2
Inputchange
1.--1
10-2
the amplitude of the input giDe wave, the amplifier is said to bave a
dynamic gain of 0.5 for the particular frequency of the input wave, for
example, 1 Hz.
By monitoring the output amplitude for many different input frequencies, a series of dynamic gain numbers mar be found. A plot of the
amplitude ratio (gain) as a function of frequency of the input giDewave
is the gain portion of a Bode diagram, or a frequency-response curve
(Figure 7-4). Note that the higher the frequency, the lower the gain.
)(
This is true for nearly all processes and instruments. The frequency
scale is normally a logarithmic scale. Gain or amplitude ratio is also
normally expressed in decibels, where l decibel equals 20 times the
logarithm to the base 10 of the amplitude ratio.
As the frequency becomes lower and lower, and finally approaches
zero, a measure of the amplifier's static gain can be obtained.
Just as the static or dynamic gain of an individual amplifier can be
computed, so can the static or dynamic gain of a process controlloop.
Figure 7-5 shows a temperature controlloop. The static loop gain has
been computed by multiplying the static gains of each of the individual
components of the loop. Likewise, the dynamic loop gain could be
calculated by multiplying the dynamic gains of each element at a particular frequency. Pure dead time has a gain of 1.
Each element in the controlloop contributes gain to the totalloop.
Increasing the size of a control valve or narrowing the span of a transmitter has exactly the same effect as increasing the gain of a controller.
)(
PS! ,
PS!
)(
mches
)( ~
Btu
The
Control
System
RC Networks
Figure 7-7 illustrates the phase shifts that occur when a sine wave is
applied to a network ofresistances and capacitances. Each succeeding
RC combination contributes its own phase shift and attenuation. In
Figure 7-7, bottom, a phase shift of 180degrees (a full half cycle) takes
place. That is, the output (eRa)is 180degrees out of phase with the input
(e applied). The signal has also been attenuated because each resistor
causes a loss in the energy level in the system. This phase change can
lead to instability in a closed-loop system.
Oscillation
In a physical system employing feedback, instability will occur if
energy is fed back in such direction (phase) as to sustain the instability
or oscillation.
Oscillators are often divided into two major categories, those thai
utilize a resonant device and those thai do noto The resonant oscillator
uses a device thai requires a minimum of added energy each cycle to
maintain oscillation. On the other hand, the nonresonant oscillator is
simply an amplifier with some type of phase-shifting network between
output and input. A public address system with the gain so high thai it
howls is a nonresonating type.
I
-"
I
SIMPLIFIEO PHASE SHIFTER
Fig. 7-7. Phase ofsigna! acrossR, R2' andRa is different. At one frequency, the output
signa! can be exact!y 180degrees out of phase with the input signa!, as shown in the
graph.
Academically, both the resonant and nonresonant oscillators follow the same mathematicallaw, but the amplifier gain requirements are
quite different for the two categories. With a nonresonant circuit, oscillation will occur (1) if the feedback is positive (inphase) and (2) if the
gain is unity or greater. These two conditions are necessary for sustained oscillation.
Figure 7-8 shows a simple mechanical oscillator. ln ibis system,
energy stored in the spring is transferred to the weight, back to the
spring, to the weight again, and so on. The oscillations soon die Dut
because some ofthe energy is dissipated in each cycle. lfthe oscillation
is to be continuous, energy musi be added to make up the losses.
ln the bottom part ofthe figure, ibis energy is added by depressing
and releasing the weight. If the energy is to enforce the oscillation, it
musi be in the proper phase with the motion. That is, enforcing energy
musi be added at a time when both the energy and the oscillation are
moving in the same direction.
Figure 7-9 shows a free-running oscillator in which the required
energy is introduced through feedback. This circuit is called a phase
shift oscillator. lt consists of a transistor amplifier and a feedback path
comprised of three resistance-capacitance combinations. This circuit is
important because it is a simple illustration of the manner in which an
ordinary amplifier can be made to oscillate simply by use of feedback.
l@~
Fig. 7-8. At top, the magson the spring received a single downward displacement and
the oscillation is delayed. Below, arter the initial displacement, the magsreceives
periodic small displacements and the oscillation is continuous.
11
186
The transistor amplifier Dot only makes up for circuit losses, but
also contributes a phase shift of 180degrees; that is, the collector is 180
degrees out of phase with the base signal. EachRC element contributes
additional phase shift, depending on the values of the components and
the frequency involved. If each RC combination contribute s a phase
shift of 60 degrees, the three together will result in a 180-degreephase
shift. This, added to the 180-degreephase shift through the amplifier,
results in 360 degrees of phase shift. The feedback signal is now in
phase with the input signal. This inphase feedback produces continuous oscillation.
Since only one frequency will be shifted in phase exactly 360 degrees by the RC networks, the oscillator output is of this one fre-
quency.
The closed-loop control system (Figure 7-6) also has phase-shifting
networks, made up of all process and controller <:omponents,together
with an amplifier capable of contributing sufficient gain to overcome the
system's losses. This closed-loop system contains the same basic ingredients as the phase-shift oscillator. Each resistance-capacitance
combination will shift the phase of the energy flowing around the controlloop in the same manner as in Figure 7-9.
Oscillation (instability) will occur whenever (1) the phase relationships through the vario us resistance-capacitance combinations provide
feedback in proper phase, and (2) the system gain is unity, or greater at
the frequency at which the phase shift is 360 degrees.
Figure 7-10 illustrates a plot of system gain (output/input signalBode diagram) and output/input phase shift versus frequency for a
three-mode controller. The phase shift (expressed in degrees of lead or
o
~
'"o
~
Z
~
c
2
10
"
100
1000
LOGARITHM FREOUENCY-~AOIANS PER SECONO
10000
Fig. 7-10. Bode diagram shows gain of system (top) and phase change (bottom) .at
various frequencies. The gain (output signal/input signal) and phase (output/input) are
measured with the system in open-loop operation.
lag) is plotted linearly against the logarithm of frequency. Note that the
integral is phase lagging and the derivative is phase leading.
The proportional adjustment in the controller adjusts its overall
gain and hence the loop gain. The integral adjustment governs the
low-frequency response, and the derivative adjustment governs the
high-frequency gain of the control mechanism.
In addition to controlling gain, these adjustments also affect the
phase shifts. Thus, an improper setting of any one of the three control
modes can cause the control system to satisfy the two criteria for
oscillation and become unstable,
Stability in the Closed-Loop System
Under normal operating conditions, the control system should produce
stable operation. That is, the controller should retum the system to set
point, in the event o an upset, with mnimum overshoot and oscilla-
tion.
Too much overall gain(too narrow a proportionalband)can cause
controlled.
A high-gain setting is desired because this gives the fastest and
most accurate control action. However, too much gain produces oscillation. The best compromise is to use enough gain to produce a damped
oscillation, as shown in the middle of Figure 7-11 (0.25 damping ratio).
Nonlinearities
Thus far it has been assumed that the capacitances and resistances
found in the process control loop bave a fixed value that does not
change with process conditions. This is not always true in practice.
Frequently, process conditions vary the value of the resistances and
capacitances involved and, as a result, the phase and gain relationships
are in constant transition Crom one value to another. At other times,
these values change, limiting or restricting the natural behavior of the
'-PERIOO~
GAI!
MEASURED DR
CDNTRDLLED
VARIABLE
(CLDSED LODP
SYSTEM)
GAIN',
system. Such changes are often considered as a group and are called
nonlinearities.
A thorough understanding of the operation of the linear system is a
prerequisite to an understanding of the nonlinear type. It is common
practice to assume a system is linear for the purpose of basic control,
and then deal with the nonlinear characteristics as problems anse.
Controllers
and Control
Modes
MEASURED
VARIA BLE
FINAL
OPERATOR
POSITION
riME'"
FINAL
OPERATOR
POSIT/ON
MEASURED
VARIABLE
TIME -+
the measured variable exceeds the upper boundary of the gap, the final
operator is closed and remains closed until the measured variable drops
below the lower boundary. It now opens and remains open until the
measured variable again exceeds the upper boundary. In a process
plant, differential-gap control might be used for controlling noncritical
levels or temperatures.
A time-cycle controller is normally set up so thai when the measured variable equals the desired control point, the final operator will
be open for hal the time cycle, and closed the other hal. As the
measured variable drops below the control point, the final operator will
remain open longer than it is closed.
Two-position control is nearly always the simplest and least expensive form of automatic control. Any of the forms discussed can be
implemented with commercially available mechanical, pneumatic, or
electronic instrumentation. On the other hand, two-position control
mar Dot meet the requirements often demanded by today's sophisticated processes. Now let us investigate a typical on/otI controlloop.
Assume we bave a liquid-Ievel process as shown in Figure 7-13.
Throttling
Control
(7-1)
where:
m = controller output or valve position
Error = difference between set (r) and measurement (c)
or
e=r-c
(7-2)
v=
xH=
TlIne
" to nse
.118.4gal.
= 30
gpm = 30 gpm
gpm
=.
395
mm.
Tirne to fall =
-118.4 gal.
= 1.973min.
-60 gpm
3c. Total tirne = (3.95 + 1.973)min. = 5.92 min.
Solution to no. 2:
3.lD1e
T ' to nse
, = (90118,4
,
-40) gal,
gpm = 2.96 mm.
TlD1e
'
-118.4gal.
'
to "la11 = (O
-50) gpm = 2. 37 mm.
Period oCoscillation = 5.33 min,
Solutionto no. 3:
When Q = Mon + Moll = 90 gpm + O gpm = 45 gpm
2
2
m=
Application
Bias = usually adjusted to p-lacethe valve in its 50 percent open position with zero error.
The term proportional band is simply another way o expressing
gain.
% ProportionalBand =
100
Controller Gain
or
Controller Gain =
100
% Proportional Band
%PB (r -c)
+ 50%
Another approach to visualizing the effect of varying the proportional band is shown in Figure 7-14. Each position in the proportional
band dictates a controller output. The wider the band, the greater the
input signal (set point -measurement) musi change in order to cause the
output to swing from O to 100percent. Manual adjustment of the bias
shifts the proportional band so thai a given input signat will cause a
different output level.
ot Proportional
Control
SET POINT
MINUS
MEASUREMENT
GAIN. 1
OUTPUT
TIME-..
OPEN-LOOP
GAIN RESPONSES
0%
1001
CONTROLLER
OUTPUT
MEA5UREMENT,I
"I.
PROPORTIONAL
BANO
OUTPUT
50%
50
100%
0% CONTROLLER
PROPORTIONAL
BANO
-SET
POINT
OUTPUT
.!~I:,_C2~~R2!;~E~
OUTPUT
BIAS (MANUALLY
EFFECT
-
OF
CHANGES
IN
PROPORTIONAL
SET)
= 50%
BAND
(7-5)
___!_'22-:_C2~~~~~!~
tionately more and more offset will exist. Offset mar be eliminated by
manually adjusting the bias until the measured variable equals the set
point.
Narrow-band proportional-only controllers are often used in noncritical, simple temperature loops, such as in maintaining a temperature
in a tank to prevent boiling or freezing. A low, dynamic gain allows a
narrow band to be used. Controllers of ibis nature are typically fieldmounted and pneumatically operated. Many noncritical, level-control
applications having long time constants also use proportional-only control. Now let us apply proportional-only control to the level problem
shown in Figure 7-15.
Proportional-Plus-lntegral
Control
mc es
%PB
-c)
+ 50%
100(57.1 -c) + 50
58.3 = 75
Solving for c: c = 50.9%
Converting to inches: 0.509 x 70 = 35.6 inches
tionship between rneasurernentand set point. Integral action will continue to shift the proportional band as long as a difference exists between rneasurernentand set point. Integral action has the sarne function
as an operator adjusting the bias in the proportional-only controller.
The width of the proportional band rernains constant, and is shifted in a
MEASUREMENT
CONTROLLER
OUTPUT
TIME-'
~
.=
LOAD
MEASUREMENT
% OF SPAN
50
2~
-~"--""
~;;;;",
'
','~
,
SET paiNT
'~
CHANGE
(7-6)
%PB
= gam
e = error (deviation)R
= integraltime
If rou compare this equation with Equation 7-4, the proportionalonly expression, rou will find the bias term replaced by the integral
term.
Fig.
Derivative
ln controlling
(Rate)
multiple-capacity
often desirable. .
By definition, derivative is the time interval by which derivative
action will advance the effect of proportional action on the final
operator. lt is the time difference required to get to a specified level of
output with proportional-only
action as compared to proportionalplus-derivative action. Figure 7-18 illustrates derivative response to a
camp change; where td equals the controller's derivative time.
Derivative
action occurs whenever the measurement si~nal
changes. On a measurement change, derivative action differentiates the
change and maintains a level as long as the measurement continues to
change at the given rate. Under steady-state conditions, the derivative
acts as a 1 to 1 repeater. lt has no inftuence on a controller's output..By
reacting to a rate of input change, derivative action allows the controller to inject more corrective action than is initially necessary in order to
overcome system inertia. Temperature presents the most common application for derivative. Derivative action should Dot be used on processes that are characterized by predominant dead times, or processes
that bave a high noise content, that is, high-frequenY extraneous signaIs such as are present in the typical ftow application.
MEASUREMENT
,
PROPORTIONAL
-ONLY
ACTION
PROPORTIONAL PLUS
DERIVATIVE ACTION
TIME-
7.18. -Derivative
DERIVATIVE
TIME, td
Selecting
Given:
Proportionalband = 50 percent
Integral time = 3 minutes
Derivative time = 3 minutes
Set point = 45 percent
Measurement= 35 percent
Control action: increase-decrease
So/ution:
1. Error staysconstant,thereforeno output changedue to derivative.
2. No output changedueto proportionalaction. However, the proportional action affectsthe integralresponse.
3. Error = r -c = 45% -35% = 10%
4. R = 3 minutes = time to changean amountequalto the error
5. Becausethe proportionalband = 50%,the output in Step4 is multiplied by
= 2.
5% changein 3/4minute.
the Controller
Now that the variety of available control modes has been described,the
next logical question is: which should be selected to control a
particular process? Table 7-1 relates process characteristics to the
common control modes. Let us apply the chart to the beat exchanger
processo
The beat exchanger acts as a small-capacity process; that is, a
small change in steam can cause a large change in temperature. Accu-
Transfer
Lag
Min
Small
Small
Dead
Time
Capacitance
Reaction Load
Rate
Changes
SelfRegulation
Min
Min
High
Low
Moderate
Slow
High
Slow
Any
Slow
Slow
Must bave
SmaIl
Sma11
Prop. +
Integral
Moderate
Moderate
Moderate
Any
Any
Any
Any
Any
Any
Any
Prop. +
Integral +
Deriv.
Fig. 7-19. The process reaction curve is obtained by imposing a step change at input.
7-1.
7.3.
7-4.
202
Table 7-2.
OFFSET
CA. BEy
~'ES
USE
TO'ERATEO?
P-O."
.s
-'+1
USE
The reaction curve of Figure 7-19 clearly indicates that some derivative action will improve control action. Thus a three-mode controller with proportional, integral, and derivative modes satisfies the needs
of the beat exchanger processoTable 7-2, as applied to this problem,
will yield the same resulto
Ouestions
With adequate gain and inphase feedback. any system will:
8. Drift
c. Increase amplitude
b. Oscillate
d. Degenerate
7-2. The natural frequency at which a closed-loop system will cycle depends
upon:
3. The amplifier gain
b. The attenuation provided by the process
c. The phase shift provided by the resistance-capacitanceand dead time
networks that exist in the system
d. Resonance
8.
b.
c.
d.
c. Linear for the purpose ofinitial consideration but with full knowledge
that this may not be the case
d. Nonlinear for purposes of analysis with rhe exception that the system
may prove to be linear
7-5. A closed-loop control system that employs a three-mode controller:
a. Can oscillate or cycle at only one frequency
b. Can oscillate or cycle at several frequencies. depending on controller
adjustment
c. Will not oscillate because of the stability provided by derivative
d. Will produce only damped oscillations with a 0.25 damping ratio
7-6. We have a closed-loop control system which is cycling. We should:
a. Increase the proportional band
c. Check and adjust both
b. Increase integral action
d. Immediately shut it down
7-7. A proportional controller is being used to control a process. and the
offset between set point and control point must be held to a minimum. This
would dictate that rhe proportional band:
3. Be as narrow as possible
b. Be as wide as possible
c. Be of moderate value
d. Does not relate to the problem
7-H. The system gain ofthe closed-loop control system:
3. Refers to the process gain
b. Refers to the gain of the measurement and control devices
c. Refers to total gain of all components. including measurement, controller, val ve operator, valve, and process
d. Relates only to the gain ofthe controller
7-9. If a closed-loop control system employs a straight proportional
controller and is under good control. offset:
3. Will vary in magnitude
b. Will not exceed one-half of the proportional band width
c. Will exceed the deviation
d. Is repeated with each reset7-10.
Any closed-loop system with inphase feedback and a gain of one or
more will:
a. Degenerate
c. Exhibit a 0.25 damping ratio
b. Cycle or oscillate
d. Produce square waves7-11.
How long will it take for the Otltput to change 5 percent if the
measurement remains constant?
Gil 'l'li :
c. Inphase
d. Phase-reversing
c. Inphase
d. Phase-reversing
7-20. The most common combination of control modes found in the typical
process plant is:
8. Proportional-only
b. Proportional, integral, and derivative
c. Proportional-plus-integral
d. On/off
The Flapper-Nozzle
Unit
Figure 8-1 shows the principIe of the ftapper-nozzIe device. Input air
(reguIated at 20 psi or 138 kPa) is fed to the nozzIe through a reducing
tube. The opening of the nozzIe is Iarger than the tube constriction.
Hence, when the ftapper is moved away from the nozzIe, the pressure
at the nozzIe falls to a Iow vaIue (typicalIy 2 or 3 psi, or 10 or 20 kPa);
when the ftapper is moved cIose to the nozzle, the pressure at the
205
nozzle rises to the supply pressure (20 psi or 138 kPa). Flapper movement of only a few thousandths of an inch (Figure 8-2) produces a
proportional pneumatic signal that mar vary from near zero to the
supply pressure. Some pneumatic control mechanisms use the air at the
nozzle (nozzle pressure) to operate a control valve.
The simple ftapper-nozzle unit shown in Figure 8-1 has several
basic limitations. The output air must all corne through the input constriction if it is used directly to operate a control valve. Hence, the
output pressure can change only slowly, causing sluggish action. Just
as the rate of increase in pressure is limited by the input constriction,
the rate of decrease in pressure is similarly limited by the slow rate of
air passage through the nozzle to the atmosphere.
Fig. 8-2. Flapperneedmove only a fewthousandthsof an inch for full rangeof output
(nozzle)pressure.
The
Fig.
PNEUMATICCONTROLMECHANISMS 207
Amplifier
small ball valve. Because the diaphragm has a large area, small
pressure changes on its surface res uit in a significant force to move the
ball valve. The ball valve, when open, permits the full air supply to
reach the output; when closed, it permits the nozzle pressure to bleed
to atmosphere.
If the ftapper position is changed with respect to the nozzle, the air
pressure acting on the celar diaphragm changes and either opens or
closes the celar ball valve, thus either increasing or decreasingthe ftow
of supply air, which now can ftow directly from the supply to the
output, overcoming the first deficiency (slow action) of the ftapper noz-
zle.
relay is often called a pneumatic amplifier becausea small
8-3. Relay is an arnplifier. That is, small change in nozzle pressure (the input to the
relay) causes a large change in output pressure (to the control valve).
The
Relay or Pneumatic
Amplifier
Flapper-nozzle detectors employed in the set-point transmitter and derivative sections of the Model 130 controller use a different type of
pneumatic amplifier. If the flow or volume output requirements are
small, an aspirating relay mar be employed. The pneumatic amplifier,
shown in Figure 8-4, makes use of the Venturi tube principIe and resembles a small Venturi tube. With a 20 psi supply, the throat pressure
of the Venturi can vary 3 to 15 psi or 20 to 100 kPa for a change in
flapper position with respect to the nozzle of less than 0.001 inch. The
aspirating relay accomplishes ibis with almost perfect linearity and
does Dot require parts thai are subject to wear. This recent develop-
.,.SUPP"
,
TO
FLAPPERtNO'
Fig.
PNEUMAT1CCONTROLMECHANISMS 209
ment offers advantages over conventional pneumatic amplifiers, provided that a high volume output is Dot required.
Proportional Action
If a controller had only the units described thus"far, ~apper-nozzle and
relay, it would only bave on/otI action. On/otI control is satisfactory for
many applications, such as large-capacity processes. However, if
on/otI action does Dot meet the control requirements, as in low-capacity
systems, the ftapper-nozzle unit can easily be converted into astable,
wide-band proportional device by a feedback positioning system that
repositions the moving ftapper.
An example of a proportional action mechanism is the Foxboro
12A pneumatic temperature transmitter (Figure 8-5). This device,
called a "force-balance pneumatic transmitter," develops a 3 to 15 psi
(20 to 100kPa) output signal proportional to the measured temperature.
Thus, it is functionally a proportional controller.
210
Figure 8-6 shows .the principIe of the Model 12A transmitter. The
forces created by the bellows are automatically balanced as follows.
When the temperature sensor is subjected to an increase in temperatufe:
1. The increased temperature expands the gas contained in the sensor
and increases the force exerted by its bellows. This increases the
moment of force, tending to rotate the force bar clockwise.
2. The flapper now approaches the nozzle and the nozzle pressure
increases. This pressure is applied to the pneumatic relay (Figure
8-3), increasing its output and the pressure applied to the feedback
bellows, thus increasing the counterclockwise moment of force
sufficiently to restore the force bar to equilibrium.
The force bar (flapper) is now repositioned slightly closer (less than
0.001 inch) to the nozzle, and the output pressure has reached a new
levellinearly related to the measured temperature.
In the actual unit, two additional forces act on the force bar. One is
thai applied by the zero elevation spring. Adjustment of tbis spring
determines the constant force it adds to thai supplied by the feedback
bellows. This allows a given span of temperature measurement to
be raised or lowered. The other force is applied by the ambienttemperature- and barometric-pressure-compensating bellows. This
force compensates for ambient temperature or atmospheric pressure
changes acting on the gas-filled thermal system, thus minimizing errors
caJlsedby these changes.
The Model 12A temperature transmitter produces an output proportional to measurement and is a proportional control mechanism.
However, a useful general purpose controller should incorporate additional modes, and also bave the ability to adjust the parameters of the
mechanism along with other convenient features. For these reasons the
unit described, although a proportional controller, is used primarily as a
transmitter to send an input signal to a generalpurpose controller (such
as the 130 Series), as shown in Figure 8-7.
Control
Mechanism
Requirements
212
Controller
~
~
unit.
Fig.
PNEUMATICCONTROLMECHANISMS 213
The basic added features are a set bellows, which permits adjustment of the set point; and an integral (R) bellows.
ln the actual Model 130 controller (Figure 8-10), a ftoating disk actsas
the ftapper of the ftapper-nozzle system. The resultant moments offorce
due to the four bellows determine the position of the disk with
0f?5!)@
OUTPUT
b=ooa
obOR
b
B
P
b.40
OUTPUT
: o.
o bM
P
b.lo
4
OUTPUT
8.9. Schematicdevelopmentofproportionalcontroller.
PROPORTIONAL
~
=1
('=I--~ --.
REDUCING
TUBE-
~
~
BAND
DIAL
REVERSING
SWITCH
~.-
NU~~LI:
FORCE BALANCING
FLOATING DISC
-INTEGRAL
BELLDWS
PROPORTIONING BELLOWS --'I
-MEASUREMENT
(B) OR
SET (A) BELLOWS
CONTROLLER ACTION
REVERSING SWITCH
/1
\:
r=
=!
,
r~1
'=--,~_f=
INTEGRAL
RESTRICTOR
respect to the nozzle. Therefore, the relay output pressure varies with
changes in pressure in any ofthe bellows. The mechanism is aligned to
produce a midrange output of9 psi (60 kPa) when the error signal is O.
This is called bias.
The width of the proportional band is adjusted by the position of
the proportional-band-adjusting lever. (The term gain is also used in
place of proportional band. Gain is the reciprocal of proportional
band.) This lever positions the fulcrum abolli which the moments of
force created by the pressure in the four bellows act. These moments of
force tilt the floating disk upward or downward, thereby causing a
change in nozzle pressure. The reguli is an increased or decreased
output pressure Crom the controller. This output pressure, which is
proportional to changes in measurement or set pressure, acts to reposition the control valve, thus influencing the process and bringing abolli a
change in the measurement bellows to establish a new equilibrium in
the system.
PNEUMATICCONTROLMECHANISMS 215
TIME
216
ment bellows in the automatic control unit receives from the derivative
unit at the measurement change shown.
The integral function takes place within the automatic control unit
itself. The integral bellows opposes the feedback bellows; thus, if the
feedback bellows introduces negative feedback, the force created by
the feedback bellows will act like positive feedback; that is, it tends to
move the flapper in the same direction as error. This would lead to
instability if the integral restriction were Dot used. anly very slow
signals (minutes in duration) can affect the integral bellows because of
the very small integral restriction. The integral action occurs only arter
the proportional and rate actions h~ve affected the processoIf an error
remains (such as offset due to load change), the integral action takes
place slowly. Because integral action will continue in the presence of a
continuous error, such as we mar find in a batch process, it can cause
the output to go to an extreme. This is called integral windup.
Integral time is adjusted by setting an adjustable restrictor, or needle valve. The dial on this pneumatic val ve is calibrated in minutes of
integral time.
Figure 8-12 illustrates the Foxboro Model 130controller. The control rnodes-proportional, integral, and derivative-are in the controller shown. The signal level with respect to time mar be changed by
appropriate adjustments of proportional, integral, and derivative
modes. The proportional band adjustment is calibrated from 5 to 500
percent, while the integral and derivative dials are calibrated from 0.01
to 50 minutes. These adjustments are calibrated in "normal" times.
The effective times are somewhat different.
In any controller, some interaction between control actions mar
exist because change in one action (proportional, integral, or derivative) can create change in the others. This unavoidable interaction,
even if small, should be kept in mind when adjusting or tuning a control
ler.
Manual Control
Unit
PNEUMATICCONTROLMECHANISMS 217
Fig. 8-12. Pneumatic Consotrol130M controller. (Top) right sicle cover removed and
manual controls. (Battam) the leCtsicle cover is removed to show pneumatic printed
circuit board.
Transfer
Automatic to Manual
With the transfer switch in the automatic position, the thumbwheel in
the manual control unit is disengaged and the automatic controller's
pneumatic output is fed into the manual control unit bellows. The manual control unit remains balanced at this output. At the time of transfer
to manual, the manual unitinstantfy starts transmitting this same output. Thus, the response record of the transfer from automatic to manual (Figure 8-15) is smooth and bumpless.
Manual to Automatic
The transfer Crom manual to automatic requires the use of an
automatic-balancing unit, which consists of a singie-pivoted diaphragm
with four air pressure compartments. This is shown in schematic Corm
AIR
SWITCH
SUPPLY SIGNAL
OUTPUT
PNEUMATICCONTROLMECHANISMS 219
in Figure 8-16. At the left, the unit is in the automatic position; at the
right, it is in manual. It will act as a simple proportional controller with
a fixed proportional band of approximately 30 percent. The basic probIem in transferring from manual to automatic lies in the fact that the
output of the automatic controller must equal that of the manual unit at
the moment of transfer, and then a change at a predetermined integral
rate is necessaryto bring the measurement to the set paint. The output
ofthe manual station is the control unit' s output. Full air supply is sent
to the three pneumatic switches, closing two and opening one, as
shown in Figure 8-16.
The proportional bellows of the automatic control unit is disconnected from the output of the controller. The integral restrictor is
bypassed, and the integral bellows is disconnected from the proportional bellows. The input signals to the automatic balancing unit shown
represent the automatic control unit proportional bellows pressure in
bellows D, and the manual control output in bellows A. Bellows B is
the balancing pressure and bellows C is the output to the integral bel-
lows.
If either the measurement or the set paint to the automatic control
unit changes, the pressure in the proportional bellows must also
change, because it is operating as a proportional-only control unit.
When the change in pressure in the proportional bellows is sensed by
the balancing unit, the unit' s output will change the pressure in the
controller's integral bellows. This, in turo, will cause the proportional
bellows pressure to change in the opposite direction until it once again
equals the output of the manual control relay, or until the supply
pressure limits are reached.
Any diiference between the set and measurement bellows is thus
balanced by the difference between the integral and proportional bel-
lows.
If the output of the manual control unit changes, a similar action
occurs, forcing the proportional bellows pressure to equal the manual
control unit output.
When transferring from manual to automatic (Figure 8-17), the
output will remain at the level determined by the operator when the
controller is in manual. If the measurement input is equal to the set
paint, the output remains constant until corrective action is required. If
the measurement does Dot equal the set paint at the moment of transfer ,
the output will camp from the level of manual operation to the level
necessary to make the measurement equal to set paint a function of the
controller's integral rate.
220
Set Po nt
The set-point knob is attachedto a pneumatictransmitter, which relates the transmitter's output positionor the set-pointpointer (Figures
8-18and 8-19).The output or the transmitteris applied to the set bellows or the controller. If the automaticcontroller is operating, normal
PNEUMATICCONTROLMECHANISMS 221
changes can be made by turning the set-paint knob. Proportional-plusintegral action will occur. Since the derivative amplifier exists only in
the measurementcircuit, derivative action will nat occur. If it is desired
to bring the process slowly to the new set paint with integral action
only, the controller is simply switched to manual, the set-paint change
is made, and the controller is switched back to automatic. Now the
measurement will approach the new set paint, with integral action only,
and no overshoot will occur.
222
SET paiNT
LTIME-i
TIME-
PNEUMATICCONTROLMECHANISMS 223
LlNEARIZING
ASPIRATOR
RELAY
iC
TO REVERSE
FROMREMOTE
SWITCH AND
SET POINT
AUTOMATIC
SIGNAL
L.A.R.
CONTROL U 1T
.L
'j
LOCAL
I ~.
SETPOINT1n-"1
TRANS
AlS \~~-.
r-rr
II
REMOTE
SET
POINT
RECEIVERI
SET KNOB
The Closed-Loop
Pneumatic
Controlled
System
IIPULATED
224
VARIABLE 1
pneumatic temperature transmitter (Foxboro Model 12A), a forcebalance pneumatic controller (Foxboro 130 Series), a pneumatic (diaphragm) valve actuator, and a control val ve (wide-range V-port).
Figure 8-21 shows an accepted manner of representing a system in
a block diagram. All the elements of the actual system are included.
CONTROLLER
,'
"
iDETECTORM (RELAY)t=l
L-
-INTERNALFEEDBACKLOOPjI
SET
II M~.A_S.u.~.!.NG
II
MEANS
~EXTERNAL
CONTROLLED
FEEDBACK
LOOP
MANIPULATEO
PNEUMATICCONTROLMECHANISMS 225
The Process
The process to be controlled is a shell-and-tube beat exchanger. Lowpressure steam applied to the shell beats water flowing through the
tubes. The exchanger has 33.5 square feet ofheat-transfer surface, and
the time required for the beat exchange to take place across this surface causes the exchanger to bave a delayed response. The response
characteristic is that of a multiple-capacitance, multiple-resi&tance
circuit.
Set Point
OUTPUT
SET KNOB
PNEUMATICCONTROLMECHANISMS 227
to hold air and the connectingtubing offers resistanceto air ftow. The
time constant for a pneumatic operator is typically several seconds
with normallengths of connectingtubing. Adding tubing lengthensthe
time constant.Thus, the valve actuatorcontributestime lag or phase
shift to the controlloop, dependingon the lengthof connectingtubing
used.
Final Control
Element
~SE
PNEUMATICCONTROLMECHANISMS 229
".,3."CON.'.,.
'" ,. 6.
,.
PNEUMATICCONTROLMECHANISMS 231
OUTFLOW
WATER
TEMPERATUREI
Fig. 8-27. Controlled set-point change made in automatic mode (top) and in manual mode,
then switched to automatic (bottom).
Batch Controli er
-Fig.
riME
CuRVE
8-28. (Left) Recovery from sustained deviation; proportional plus integral controller
without batch feature. (Right) With batch feature.
below the set point and the controller's output will be at its maximum
value. Ifthe time oftbis deviation is long enough, the integral circuit of
a conventional controller will also reach ibis value. When process conditions retum to normal, no change in controller output can occur until
the measurementreaches the set point. Figure 8-28, curve A illustrates
ibis control action.
The batch switch eliminates tbis integral circuit saturation and
conditions the integral bellows to permit output to start to change
before the measurement reaches theset point. If the controller output
starts to change before the measurement reaches the set point, overshoot can be prevented and the measurement can retum to the set point
smoothly. Figure 8-28, curve B illustrates tbis control action.
Principie
ot Operation
PNEUMATICCONTROLMECHANISMS 233
This causes the pressure in the circuit to dropo As long as the relay
output pressure is above the trip point, the integral circuit pressure will
drop until there is no longer any pressure in the integral bellows. At this
point, the proportional band throttling range will have shifted completely below the set point as indicated in Figure 8-28B, curve B. During this operation, the controller's output pressure is at 15 psi or 100
kPa (or more) and the valve is wide open. When the batch process is
restarted, the control valve will begin to throttle as soon as the measurement reaches the 15 psi or 100kPa lmit of the proportional band
throttling range. Note that as soon asthe controller output drops below
15 psi or 100kPa, normal integral response is restored. This overcomes
the tendency to overshoot the set point.
Load Bias (Preload)
Due to the time characteristics of certain processes, shifting the proportional band completely below the set point will cause an intolerable
delay in bringing the batch to the set point. In such cases, an adjustable
back pressure mar be applied to the vent port to "bias" the batch
switch. Thus, the pressure in the integral circuit mar be prevented from
dropping below a preselected amount and the proportional band throttling range will shift only partially below the set point. Although this
will allow faster recovery, a slight overshoot will occur if the "bias" is
increased too much. Increasing the bias to 15 psi or 100 kPa would
obviously completely eliminate batch action.
One limitation thai applies to all pneumatic control systems is the
distance thai mar be accommodated between components. The maximum distance depends on two major factors: the pneumatic signal
travels at the speed of sound, and the loop components along with the
tubing all bave capacity and resistance. Thus, an RC time constant
musi exist. Volume boosters often are applied to lengthen ibis working
distance. Unfortunately, a volume booster will do nothing to speed up
signal velocity. A booster will help if a large volume, such as thai found
in a pneumatic valve actuator, is involved.
The distance lmit for pneumatic control systems is approximately
200 feet (60 meters). Iftbis distance factor is ignored, the dynamics ofthe
control system will suffer and reguli in poor control operation. If it
becomes necessary to lengthen these distances substantially, the only
practical solution is to utilize electrical signals thai mar work over an
almost unlimited distance.
Questions
c. Gain
8-2. True or false: In a proportional-onlycontroller,ifthe measurement
equals
the set point the output will equalthe bias.
8-3. True or false: In an integralcontroller,the rate of changeof the output
is proportionalto the error.
8.4. True or false: The largerthe numberon the integraldial the greaterthe
effectof the integralaction.
8-5. True or false: In a batchoperation,if a controllerhaswound up, it is
quite possiblethat the valve may stay in an extremepositionuntil the
measurementactuallygoesbeyondthe set point beforethe valve beginsto
changeits position.
8-6. True or false: What somemanufacturerscall rate others call derivative.
8-7. Indicate all the correctstatements:
8. Gainis the reciprocatof the proportionalband.
b. The proportionalbandis the reciprocatof gain.
PNEUMATICCONTROLMECHANISMS 235
c.
d.
e.
f.
The
The
The
The
point.
b. Remain at 8 psi (55 kPa) as long as the measurement stays where it is.
c. Decrease and continue to decrease to 3 psi (20 kPa).
d. Continue to decrease until the measurementreaches the set point, or if
it does not retum to the set point, decrease to Opsi.
8-9. The range of the temperature measuring system used in conjunction
with a Model 130proportional-only contro1ler is O to 150oP(66C). The output
is 9 psi (60 kPa) when the set point and indicator are both at 75P (24C). If
the proportional band is 200 percent, what is the output when the
measurement is 150oP(66C)?
a. 9 psi (60 kPa)
c. 12 psi (83 kPa)
b. 3 psi (20 kPa)
d. 15 psi (100 kPa)8-10.
If the span of a measuring transmitter in a control system is made
one-half of its value, the proportional-band adjustment in the controller must
be -to
maintain the same quality of control.
a. Cut in half
d. Narrowed
b. Doubled
e. None of the above.
c. Squared
8-11. With a proportional-plus-integral controller, a sustained error will result
in:
a.
b.
c.
d.
e.
Windup
A fixed offset
A temporarynarrowingof the proportionalband
A delay in the process
None of the above
8-13.
a.
b.
c.
d.
If proportional-plus-integral
controlis good,the additionof derivative:
Will anticipatechangesand speedup corrections
Will alwaysimprove control
Will makethe controlleradjustmentseasierto accomplish
May create stability problemsin somesystems
237
Electronic control systems,already widely accepted,are gainingrapidly in popularity for a numberof reasons:
1. Electrical signalsoperateover greatdistanceswithout contributing
time lags.
2. Electrical signals can easily be made compatible with a digital
computer.
3. Electronic units can easily handle multiple-signalinputs.
4. Electronic devices can be designedto be essentiallymaintenance
free.
s. Intrinsic safety techniques bave virtually eliminated electrical
hazards.
6. Generally, electricalsystemsare lessexpensiveto install, take up
less space,and can handle almost all processmeasurements.
7. Electronic devices are more energy efficient than comparable
pneumatic equipment.
Feedwater
Control
Systems
Two ditIerential pressure transmitters (Fig. 9-2) are used, one to measure water flow; the other to measure drum water level.
Referring to Fig. 9-3, in operation the ditIerence in pressure between the high and low gide of the transmitter body is sensed by a twin
diaphragm capsule (1) which transforms the ditIerential pressure into a
force equal to the ditIerential pressure times the etIective area of the
diaphragm. The resultant force is transferred through the C-flexure (2)
to the lower end of the force bar (3). Attached to the force bar is a
cobalt-nickel alloy diaphragm which serves as a fulcrum point for the
force bar and also as a seal to the process in the low-pressure cavity
gide of the transmitter body. As a result of the force generated, the
Fig. 9-1. Peedwater control system. (I) Drum water level (2) Steam ftow from boiler,
via turbine steam pressure. and (3) Water ftow into drum.
force
9-4.
Steam ftow out ofthe drum is measured in terms of steam pressure,
which is measured with a pressure transmitter. The operation of the
pressure transmitter is similar to the operation of the differential
pressure transmitter_,The same feedback technique used in the differential pressure transmitter is employed in the pressure transmitter. The
major difference lies in the size and construction of the sensor.
The pressure transmitter measures the pressure in the first stage of
the power turbine. Since there is a linear relationship between first
stage turbine pressure and steam flow, the output signal from the
pressure transmitter is linear with steam flow out of the boiler,
A variety of electronic differential pressure transmitters are available from a number of manufacturers. Some of these make use of strain
gauge detectors, capacitive detectors, resonant wire detectors, and inductive detectors. Many are motion or open loop devices which are still
capable of accuracies within a fraction of a percent. In the application
of any electronic transmitter, the user must guard against subjecting the
electronics to temperatures which might result in damage. This probIem generally can be avoided by observing the precautions recommended by the manufacturer.
The Controllers
The controllers described befe are the Foxboro SPEC 200 type. The
SPEC 200 is generally a split-architecture system. In this system two
areas may be used, a display area and a oest area. Field equipment,
such as measuring transmitters, electrical valve actuators, and the like,
generally operates on 4 to 20 mA dc. Within the oest, SPEC 200 operates on O to 10 volts.
The display area contains control stations, manual stations, recorders, and indicators to provide the necessary operator displays and
controls. These units are shelf-mounted and contain only the electronic
circuitry required to communicate the display and adjustments necessary for an operator to control and monitor a processo
The nest area contains the analog control, computing, alarm, signal
conditioning, and input and output signal converter units. These units
are in the form of "modules" and "circuit cards." The oest itself is
basically an enclosure provided for the mounting of "modules."
System power is supplied to the oest. This power supply must
deli ver + 15 and -15 V dc for operation of the display and nestmounted instruments. Recorder chart drives and alarm lights require 24
V ac.
When a single location is required, the oest and display areas may
RAONaR,
THIRD EDITION
for
NORMAN
CHILTON COMPANY
A. ANDERSON
PENNSYLVANIA
CONTENTS
Preface
SECTION
I FEEDBACK
1 Introduction
PROCESS
to Process
Control
CONTROL
Types of Processes 5 Processes with More Than One Capacity and Resistance 6 Dead Time 6 Measurement 7 Symbols 1.0 The Feedback
Loop 1.0 Feedback Control 1.4 ControIling the Process 1.4 Selecting
ControIler Action 1.6 Up sets 1.7 Process Characteristics and ControIlability 1.7 Controller Responses 1.8 On/Off Control 1.9 Proportional
Action 20 Integral Action (Reset) 23 Derivative Action 25 Selecting
the ControIler 27 Conclusion 29 Questions 30
2 Process/Pressure
Measuring
Instruments
33
What Is Pressure? 33 Units of Measurement 35 Pressure Measurement 35 The Pascal 36 Bar Versus Pascal 37 Gauge, Absolute, and
Differential Pressure 37 Understanding the Effects of Gravity 38 GravityDependent Units 38 Gravity-Independent Units 39 Pressure Standards 39 Plant Instruments That Measure Pressure Directly 44 Bell
vi
CONTENTS
126
CONTENTS
vii
10 Actuators 259
Valve Actuator 259 Valve Positioner 261
Electrical Signals 263 Plinciple of Operation 265 Electric Motor Actuators 267 Questions 268
viii
CONTENTS
Questions 303
Response 339
Testing a
Conclusion 340
Questions 341
History 360
Advantages 360
Technique 361
Appli-
Conclusion 370
CONTENTS
ix
Input 373
Central Processing
Unit (CPU) 373 Output 374 Types of Memory 374 Core 374
Drum 375
Disk 375
Semiconductor (Solid-State) 376 Operator Com-
Conclu-
Description of Circuit 403 Sequential Control Systems 405 Programmable Controllers 406 Programming Language 406 Programming 408
Logic System Automation 409 System Control Displays 410 Conclusion 411
Questions 411
20 Constructing and Instrumenting Real and Simulated Processes 413
Units and Conversion Tables for Process Control 436 Specific Gravities of
Common Liquids 451
Standard Pipe Dimensions 452 Properties of
Saturated Steam and Saturated Water 453 Resistance Values 454
Velocity and Pressure Drop 455 Thermocouple Temperature 458 Relative Humidity (% saturation) Tables 476
Glossary 480
Answers to Questions 488
Bibliography 491
Index 492
FEEDBACK PROCESSCONTROL
PROCESS
REACTIONCURVE
EC
(a)
EDc
TIME
(b)
TIME
PRESSURE
IN TANK
(cI
SUPPLY
TIME
TEMP.
(dI
TIME
Fig. 1-2. Four types or systems: (a) electric, (b) hydraulic, (c) pneumatic, and (d)
thermal. Each has a single capacity and a single resistance and all bave identical
response characteristics.
regulate a process and certain aspects of process behavior will be discussed in this text. Examples of some completely instrumented process
systems will be given to demonstrate the practical application of the
instrument components.
The physical system to be controlled mar be electrical, thermal,
hydraulic, pneumatic, gaseous,mechanical, or any other physical type.
Figure 1-2 and Table 1-1 compare severa! common systems. All followthe
same basic laws of physics and dynamics.
INTRoDucnON TO PROCESSCONTROL 5
ot Processes
FEEDBACK PROCESSCONTROL
I~RODUCTION TO PROCESSCONTROL 7
FEEDBACK PROCESSCONTROL
INTRODUCTIONTO PROCESSCONTROL 9
,
/
~
FLOW
\:-..:I TRANSMITTER
~
L!-J
SQUARE ROOT
EXTRACTOR
r:-
~
1:"';\ LEVEL
\!:!I TRANSMITTER
r:
~
MUL TIPlIER
L.LJ
~
~
PRESSURE
TRANSMITTER
~
L.:::...J DIVIDER
r'd:"":':1DERIVATIVE
~
CONTROL ACTION
l1:r"
~
TEMPERATURE
TRANSMITTER
r::-,
BIAS, ADDITION
L..=..J OR SUBTRACTION
r::;-,
~
TIME FUNCTION
CHARACTERIZER
1::\
~
POSITION
TRANSMITTER
rA""l
~
COMPARATOR
DIFFERENCE'
~
~
UNSPECIFIEDOR
NONLINEAR FUNCTION
CHARACTERIZER
~
L!.J
ADDER
SUMMR
O /,LIGHT
PANEL
1';"\
\.!oI
INDICA
t:'\
~
RECORDER
t:;:'\
RELAY
COlL
TOR
rJ1 CONTROL
INTEGRAL (RESEn
ACTION
r:-::l
~
*
A VERAGER
~
~
INTEGRATOR
-11-
rl..
\J
NORMALLYOPEN
PROPORTIONAL
CONTROL ACTION
"*
RELAYCONTACT
QUOTATION
ITEM NUMBER
MOUNTED
FRONT
ON
PANEL
OF
REGULATED
PROCESS
THE
AIR
NORMALLYCLOSED
RELAYCONTACT
~
V
AUTO/MANUAL
TRANSFERSWITCH
A\.
'W
MANUAL SIGNAL
GENERATOR
/::'~
ANALOG SIGNAL
GENERATOR
m
L-:-J
TRANSFEROR
TRIP RELAY
m
~
SOLENOID
ACTUATOR
~
~
ELECTRIC
MOTOR
r;
~
HIGH SIGNAL
SELECTOR
m
~
HIGH SIGNAL
lIMITER
~
~
HIGH SIGNAL
MONITOR
m
LOW SIGNAL
L.::::..J SELECTOR
m
~
LOW SIGNAL
lIMITER
r:-:--l
L!:!-J
LOW SIGNAL
MONITOR
~
~
~
~
~
~
VELOCITY OR
RATE lIMITER
~
ANALOG TO
~DIGITALCONV.
r::-1
RESISTANCE TO
~CURRENTCONV.
I;ViVITHERMOCOUPLETO
~VOLTAGE
~VOLTAGECONV.
L.:::..JCURRENTCONV.
~VOLTAGECONV.
r-viV1 VOLTAGE TO
~VOLTAGECONV.
rp;j1 PNEUMATIC TO
~CURRENTCONV.
~
PNEUMATIC TO
~VOLTAGECONV.
r;;;::\
MOTORIZED
~OPERATOR
r:;:-,
CURRENT TO
~PNEUMATICCONV.
~
~
f";O\ HYDRAUlIC
~OPERATOR
r:::::\
UNSPECIFIED
~OPERATOR
..JA
"'D'"
TO
r::';::"1 RESISTANCE TO
~VOLTAGECONV.
~CURRENTTO
VOL TAGE TO
PNEUMAnCCONV.
PNEUMATIC
OPERATOR
THREE-WAY
SELECTOR VAL VE
ROTARYACnON
(BALLI VALVE
10
FEEDBACK PROCESSCONTROL
The Feedback
Loop
INSTRUMENT
INSTRUMENT
MOUNTED ON
BOARD
LOCALLY
MOUNTED
VARIABLE
INSTRUMENT
MOUNTED
BEHIND
BOARD
NSTRUMENT
FOR TWO
MEASURED
VARIABLES
INTRODUCTIONTO PROCESSCONTROL II
FIRST LE1TER
Measured or
Inilialing
Variable
A
Readoulo,
Passive
Funclion
Modijier
User'scooice
Voltage (EMF)
F
G
F1ow rate
User', choice
User',cboic.
Control
Conductivity
(electrical)
Density (mass)
or specitX:
Modi]ier
Alarrn
Analysis
Burner flame
Output
Function
Differential
gravity
Primary element
Ratio (fraction)
Glas.
Gaging
(dimensiooal)
Hand (manually
initiated)
Current
(electrical)
Power
Time or time
High
Indicat.
Controlstation
scheduIe
L
Level
Moisture or
humidity
User's cboice
User's cboic.
Oritice
(restriction)
Pressure or
Paint (test
connection)
Middle or inter-
mediate
User's cboice
vacuum
Q
Quantity or
event
Radioactiviy
Speed or
Low
Light (pilot)
Integrate
User'schoice
User's cboice
or
totalize
Recordor pnn!
Switch
SafelY
frequency
Transmit
Temperature
MuItivariable
Viscosity
w
x
Weight or force
Well
Unclassified
Unclassified
Multifunction
Multifunction
Multifunction
Valve, damper,
or louver
Unclassified
User's cboice
Relay or compute
Position
Drive, actuate
or unclassified
final control
element
Unclassified
FEEDBACK PROCESSCONTROL
lated variable) and out of (the controlled variable) the processo The
closed-loop control system achieves this balance by measuring the demand and regulating the supply to maintain the desired balance over
time.
The basic idea of a feedback controlloop is most easily understood
by imagining what an operator would bave to do if automatic control
did Dot exist. Figure 1-8 shows a common application of automatic
control found in many industrial plants: a beat exchanger that uses
steam to beat cold water. In manual operation, the amount of steam
entering the beat exchanger depends on the air pressure to the valve,
which is set on the manual regulator. To control the temperature manually, the operator would watch the indicated temperature, and by comparing it with thedesired temperature, would open or close the valve to
admit more or less steam. When the temperature had reached the desired value, the operator would simply hold that output to the valve to
keep the temperature constant. Under automatic control, the temperatufe controller performs the same function. The measurement signat to
the controller from the temperature transmitter is continuously compared to the set-point signat entered into the controller. Based on a
comparlson of the signats, the automatic controller can tell whether
the measurement signat is above or below the set point and move the
valve accordingly until the measurement (temperature) comes to its
final value.
The simple feedback controlloop shown in Figure 1-9 illustrates
the four major elements of any feedback controlloop.
13
+
~;~OL~:'-=- --.or
I MEASUREMENT
SUPPLV-*
FINAL ACTUATOR
CONTROLLED
VARIABLE
14 FEEDBACK PROCESSCONTROL
Controlling
the Process
INTRODUCTIONTO PROCESSCONTROL 15
CONTROLLER
SPAN OF
MEASUREMENT
--rINLET FLOW
Lr
,-',
,,"
[[],
=
". ,'~~~""'-1
...,...,-
~}f~
-"..,"~ 2--=~.;:
-~-=-~_.=~.
f
OUTLET
_E/
I
100
I
50
I
O
FLOW
,:--=('i
~--=~
~I
16 FEEDBACK PROCESSCONTROL
level in a tank at midscale. As the level in the tank rises, the fioat acts to
reduce the fiow rate coming in. Thus, the higher the lquid level, the
more the fiow will be reduced. In the same way, as the level falls, the
fioat will open the valve to add more lquid to the tank. The response of
this system is shown graphically. As the level moves from O to 100
percent, the valve moves from fully open to fully closed. The function
of an automatic controller is to produce this kind of opposing response
over varying ranges. In addition, other responses are available to control the process more efficiently.
Selecting
Controller
Action
17
U psets
There are three conditions that require different ftows to maintain the
level in the tank. First, if the position of the output hand valve is
opened slightly, more ftow leaves the tank, causing the level to fall.
This is a change in demand, and to restore balance, the inlet ftow valve
must be opened to supply a greater ftow rate. A second type of unbalanced condition is a change in the set point. Maintaining any other level
besides midscale in the tank causes a different ftow out. This change in
demand requires a different input valve position. The third type of
up set is a change in the supply. If the pressure output of the pump
increases, even though the inlet valve remains in the same position, the
increased pressure causes a greater ftow, which at first causes the level
to begin to rise. Sensingthe increased measurement, the level controller must close the val ve on the inlet to hold the level at a constant value.
In the same way, any controller applied to the beat exchanger shown in
Figure 1-1 must balance the supply ofheat added by the steam with the
beat removed by the water. The temperature remains constant if the
ftow of beat in equals the ftow of beat out.
Process
Characteristics
and Controllability
The automatic controller uses changes in the position of the final actuator to control the measurement signal, moving the actuator to oppose any change it sees in the measurement signal. The controllability
of any process depends on the efficiency of the measurement signal
response to these changes in the controller output. For proper control,
the measurement should begin to respond quickly, but then Dot change
too rapidly. Because of the tremendous number of applications of automatic control, characterizing a process by what it does, or by industry, is an almost hopeless task. However, all processes can be described by the relationship between their inputs and outputs. Figure
1-11 illustrates the temperature response of the beat exchanger when
the control valve is opened by manually increasing the controller output signal.
At first, there is no immediate response at the temperature indication. Then the temperature begins to change, steeply at first, then approaching a final, constant level. The process can be characterized by
the two elements of its response. The first element is the dead time, or
the time before the measurement begins to respond. In this example, a
delay arises because the beat in the steam must be conducted to the
18 FEEDBACK PROCESSCONTROL
STEAM FLOW
(MANUAL)
I
OUTLET
WATER
TEMPERATURE
L~,I"/"""'
TIME
water before it can affect the temperature, and then to the transmitter
before the change can be seen. Dead time is a function of the physical
dimensions of a process and such things as belt speeds and mixing
rates. Second, the capacity of a process is the material or energy that
must enter or leave the process to change the measurements-for example, the gallons necessary to change level, the Btu's necessary to
change temperature, or the standard cubic feet of gas necessary to
change pressure. The measure of a capacity is its response to a step
input. Specifically, the size of a capacity is measured by its time constant, which is defined as the time necessary to complete 63 percent of
its total response. The time constant is a function of the size of the
process and the rate of material or energy transfer. For this example,
the larger the tank and the smaller the ftow rate of the steam, the longer
the time constant. These numbers can be as short as a few seconds, or
as long as several hours. Combined with dead time, they define the time
it takes the measurement signal to respond to changes in the valve
position. A process will begin to respond quickly, but then not change
too rapidly, if its dead time is small and its capacity is large. In short,
the larger the time constant of capacity compared to the dead time, the
better the controllability of the processo
Controli er Responses
-..TIME
19
has been made, severa! types o responses are used to control a processoThese are (1) on/otI, two-position, control, (2) proportional action, (3) integral action (reset), and (4) derivative action.
On/off Control
MEASUREMENT
100
% SIGNAL TO
VALVE
20 FEEDBACK PROCESSCONTROL
Action
INTRODucnON TO PROCESSCONTROL 21
% OUTPUT
22 FEEDBACK PROCESSCONTROL
deviates from set paint. Each line on the graph represents a particular
adjustment of the proportional band. Two basic properties of proportional control can be observed from this graph:
1. For every value of proportional band, whenever the measurement
equals the set paint, the normal output is 50 percent.
2. Each value of the proportional band defines a unique relationship
between measurement and output. For every measurement value
there is a specific output value. For example, using the 100percent
proportional band line, whenever the measurement is 25 percent
above the set paint, the output from the controller must be 25
percent. The output from the controller can be 25 percent only if
the measurement is 25 percent above the set paint. In the same
way, whenever the output from the controller is 25 percent, the
measurement will be 25 percent above the set paint. In short, there
is one specific output value for every measurement value.
For any process controlloop, only one value of the proportional
band is the best. As the proportional band is reduced, the controller
response to any change in measurementbecomes increasingly greater.
At some paint, depending on the characteristic of each particular process, the response in the controller will be large enough to drive the
measurement back so far in the opposite direction as to cause constant
cycling of the measurement. This proportional band value, known as
the ultimate proportional band, is a lmit on the adjustment of the
controller in that loop. On the other hand, if too wide a proportional
band is used, the controller response to any change in measurement is
too small and the measurement is Dot controlled as tightly as possible.
The determination of the proper proportional band for any application
is part of the tuning procedure for that loop. Proper adjustment of the
proportional band can be observed by the response ofthe measurement
to an upset. Figure 1-16shows several examples ofvarying the proportional band for the beat exchanger.
Ideally, the proper proportional band will produce one-quarter amplitude damping, in which each hal cycle is one-half the amplitude of
the previous hal cycle. The proportional band that will cause onequarter wave damping will be smaller, thereby yielding tighter control
over the measured variable, as the dead time in the process decreases
and the capacity increases.
One consequence of the application of proportional control to the
basic controlloop is offset. Offset means that the controller will maintain the measurement at avalue different from the set paint. This is
most easily seen in Figure 1-10. Note that ifthe load valve is opened,
INTRODUCTIONTO PROCESSCONTROL 23
WATER FLOW
(LOAO)
i
I
1~
TEMPERATURE
-j/'\/,~"-",,,
I
,-~
TOOWIOE
CHANGE IN
UEMANO
B
C
TOO NARROW
CORRECT
TIME
ftow will increase through the valve and the val ve would bave to open.
But note that, because of the proportional action of the linkage, the
increased open position can be achieved only at a lowered level. Stated
another way, in order to restore balance between the ftow in and the
ftow out, the level must stabilize at avalue below the set point. This
difference, which will be maintained by the control loop, is called
offset, and is characteristic of the application of proportional-only control to feedback loops. The acceptability ofproportional-only control
depends on whether this offset can be tolerated. Since the error necessary to produce any output decreases with the proportional band, the
narrower the proportional band, the less the offset. For large capacity,
small dead time applications accepting a very narrow proportional
band, proportional-only control will probably be satisfactory, since the
measurement will remain within a small percentage band around the set
point.
If it is essential that there be no steady state difference between
measurement and set point under all load conditions, an additional
function must be added to the controller. This function is called integral
action (an older term is reset).
Integral
Action
(Reset)
24 FEEDBACK PROCESSCONTROL
% MEASUREMENT
L_-
SET
paiNT
I
I
I
...riME
Fig. l-I?
exists. This function, then, causes the output to change until the proper
output is achieved in order to hold the measurement at the set paint at
various loads. This response is added to the proportional response of
the controller as shown in Figure 1-17. The step change in the measurement first causes a proportional response, and then an integral
response, which is added to the proportional. The more integral action
there is in the controller, the more quickly the output changes due to
the integral response. The integral adjustment determines how rapidly
the output changesas a function oftime. Among the various controllers
manufactured, the amount of integral action is measured in one of two
ways-either in minutes per repeat, or the number of repeats per minute. For controllers measuring integral action in minutes per repeat,
the integral time is the amount of time necessary for the integral mode
to repeat the open-loop response caused by proportional mode, for a
step change in error. Thus, for these controllers, the smaller the integral number, the greater the action of the integral mode. On controllers
that measure integral action in repeats per minute, the adjustment indicates how many repeats of the proportional action are generated by the
integral mode in one minute. Table 12-1 (p. 300) relates the controller
adjustments from one manufacturer to another. Thus, for these controllers, the higher the integral number, the greater the integral action.
Integral time is shown in Figure l-IS. The proper amount of integral
action depends on how fast the measurement can respond to the additional valve trave 1 it causes. The controller must nat drive the valve
faster than the dead time in the process allows the measurement to
respond, or the valve will reach its lmits before the measurement can
be brought back to the set paint. The valve will then remain in its
extreme position until the measurement crosses the set paint, whereupon the controller will drive the valve to its opposite extreme, where it
INTRpDUCTION TO PROCESSCONTROL 25
% MEASUREMENT
~
,
:+-RT
% OUTPUT
(I/D)
SET paiNT
-+1
::::::""J--r-
b~I~
I
I
a. b
TIME
will remain until the measurementcrosses the set point in the opposite
direction. The result will be an integral cycle in which the valve travels
from one extreme to another as the measurementoscillates around the
set point. When integral action is applied in controllers on batch processes, where the measurement is away from the set point for long
periods between batches, the integral may drive the output to its maximum, resulting in "integral wind-up." When the next batch is started,
the output will Dot corne off its maximum until the measurement
crosses the set point, causing large overshoots. This problem can be
prevented by including a "batch function" in the controller, a function
specifically designed to prevent "wind-up."
Derivative
Action
...TIME
26 FEEDBACK PROCESSCONTROL
% MEASUREMENT
-_J==~
--~
"~!
-t__J-
% OUTPUT
(IlO)
+TIME J...
~
Fig. 1-19. Two derivative responses.
tive response. The derivative holds this output as long as the measurement is changing. As soon as the measurementstops changing, regardless owhether it is at the set point, above or below it, the response due
to derivative action will cease. Among all brands o controllers, derivative response is commonly measured in minutes, as shown in Figure
1-20. The derivative time in minutes is the time that the open-loop,
proportional-plus-derivative response, is ahead o the response due to
proportional action alone. Thus, the greater the derivative number, the
greater the derivative response. Changes in the error are the result o
changes in either the set point or the measurement, or both. To avoid a
large output spike caused by step changes in the set point, most modem controllers apply derivative action only to ehanges in the measurement. Derivative action in controllers helps to control processes with
especially large time constants. Derivative action is unnecessary on
""
% MEASUREMENT
,,
DT""
I
:.:::~J
% OUTPUT
r-
::::::::::~'
.f"
PROPORTIONAL ONLY
PROPORTIONAL + DERIVATIVE
INTRODUCTIONTO PROCESSCONTROL 27
the Controller
28 FEEDBACK PROCESSCONTROL
INTRODUCTIONTO PROCESSCONTROL 29
Conclusion
30 FEEDBACK PROCESSCONTROL
Questions
INTR9DUCTION TO PROCESSCONTROL 31
Gain
Rate
Integral
Controller, on/otI
e. Valve
Desiredvalue
Manipulatedvariable
Error
appearsin an instrumentdiagram.It
c. Frequencyconverter
d. Final control element
c. 50 percent
b. 100percent
d. Impossibleto define
1-13. If in a proportional-plus-integral
controller measurement
is away from
the set point for a long period,the controller's output will be:
32 FEEDBACK PROCESSCONTROL
d. 100percent
1-14. In the modemcontroller,derivative actionis appliedonly to the:
8. Error
c. Setpoint
b. Measurement
d. Integral circuit
1-15. The functionof the integral(reset)modeis to:
8. Opposechangein measurement
b. Automaticallyadjustthe controller's gain
c. Eliminate offset
d. Stabilizethe controlloop
Process/Pressure Measuring
Process/Pressure
Instruments
Instruments
Pressure is a universal
universal processing
processing condition.
condition. It is also
also a condition
oflife
Pressure
conditionoflife
on this planet:
at the
an atmospheric
that
atmospheric ocean
ocean that
on
planet: we live at
the bottom
bottom of an
extends upward
upward for many
miles. This mass
mass of air has
has weight,
weight, and
and this
extends
manymiles.
weight
pressing downward
downward causes
causes atmospheric
atmospheric pressure.
pressure. Water,
Water, a funfunweight pressing
damental
necessityof life, is supplied
most of us
supplied to most
us under
under pressure.
pressure. In
damental necessity
the typical process
process plant,
plant, pressure
pressure influences
influences boiling
boiling point
point temperatemperathe
tures, condensing
temperatures, process
process efficiency,
efficiency, costs,
costs, and
and
tures,
condensingpoint
point temperatures,
other important
important factors.
measurementand
control of pressure,
other
factors. The
The measurement
and control
pressure, or
lack of it-vacuum-in
it-vacuum-in the
plantis critical. Instruments
lack
the typical process
process plant
Instruments
are
How these
are available
available to measure
measure a wide
wide range
range of pressures.
pressures. How
these instruinstruments function
chapter.
ments
function is the subject
subjectof this chapter.
What
Is Pressure?
Pressure?
What Is
Pressure
Pressure is force dividel
divided by the area over which it is applied. Pressure
Pressure
is often defined in terms of
of "head."
"head." For example, assume
assume that we bave
have
a water column 1 foot square
square and 23
23 feet tall. We
We want to find the
pressure in the bottom
boUom ofthe
mar be
ofthe column. The weight ofthe
ofthe column may
calculated by first finding the volume of water. This is the area
of the
area of
33
34
FEEDBACK PROCESSCONTROL
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 35
Units ot Measurement
Every major country has adopted its own favorite units of measurement. The United States has traditionally employed the English system. However, international trade has made it necessaryto standardize
units of measurement throughout the world. Fortunately, during this
standardization, there has be en rationalization ofthe measurementsystem. This has led to the adoption of the System lnternatonal d'Untes
(SI), a metric system of units. The force of common usage is so strong
that the familiar English system will undoubtedly persist for many
years, but the changeover is definitely underway. The time will soon
corne when process industries will deal exclusively with SI units.
Pressure
Measurement
Perhaps the area that has caused the most concern in the change to SI
units is pressure measurement. The new unit of pressure, the pascal, is
unfamiliar even to those who have worked in the older CGS (centimetre, gram, second) metric system. Once it is accepted and understood,
it willlead to a great simplification of pressure measurement Cromthe
extremes of full vacuum to ultrahigh pressure. It will reduce the multiplicity ofunits now common in industry to one standard that is compatible with other measurements and calculations. To understand the pascal and its relationship to other units of pressure measurement, we
must return to a basic understanding of pressure.
As noted previously, pressure is force per unit area.
36 FEEDBACK PROCESSCONTROL
where:
W = weight of the object
m = its mass
G = accelerationdue to gravity
Because gravity on the earth's surface is roughly constant, it has
been easy to talk abolli a weight of 1 pound and a mass of 1 pound
interchangeably. However, in faci, force and mass, as quantities, are as
different as apples and pears, as the astronauts bave observed. A numbec of schemes bave be en devised to overcome ibis problem. For example, a quantity called the pound-force was invented and made equal
to the force on a mass of one pound under a specified acceleration due
to gravity. The very similarity between these two units led to more
confusiott. The pascal, by its definition, removes all these problems.
The Pascal
The SI unit of pressure is defined as the pressure or stress that arises
when a force of one newton (N) is applied uniformly over an area of one
square metre (m2). This pressure has been designated one pascal (Pa).
Thus, Pa = N/m2. This is a small unit, but the kilopascal (KPa),
1,000 pascals, and the megapascal (MPa), one million pascals, permit
easy expression of common pressures. The definition is simple, because gravity has been eliminated. The pascal is exactly the same at
every point, even on the moon, despite changes in gravitational acceleration.
In SI units, the unit offorce is derived from the basic unit for mass,
the kilogram (kg), and the unit of acceleration (metres per second per
second, mls2). The product of mass times acceleration is force and is
Gauge,
PROCESS/PRESSURE
MEASURING INSTRUMENTS 37
After the introduction of SI units, the use of the "bar" (lOSPa) gained
favor, especially in European industry, where it closely resembles the
CGS unit of kg/cm2 (kilograms per square centimetre). At thai time, the
SI unit was called the "newton per square metre." As well as being
quite a mouthful, it was found to be inconveniently small (one N/m2
equals 0.000145psi). The use ofthe millibar in meteorology lent weight
to the acceptance of the bar. However, the use of a multiple like (lOS)in
such an important measurement and the resulting incompatibility of
stress and pressure units led to the adoption ofthe N/m2, giving it a new
name, the pascal (Pa), in October 1971. The kilopascal (kPa), 1,000
pascals, equals 0.145 psi and most common pressures are thus expressed in kPa. The megapascal(mPa) equals 145 psi and is convenient
for expressing high pressures.
Absolute,
and Differential
Pressure
The pascal can be used in exactly the same way as the English or CGS
metric units. The pascal may be regarded as a "measuring gauge," the
size ofwhich has been defined and is constant. This gauge can be used
to measure pressure quantities relative to absolute vacuum. Used in
this way, the results will be in pascal (absolute). The gauge may also be
used to measure pressures relati ve to the prevailing atmospheric
pressure, and the results will be pascal (gauge). Ifthe gauge is used to
measure the difference between pressures, it becomes pascal (differen-
tial).
The use of gauge pressure is extremely important in industry, since
it is a measure ofthe stress within a vesseland the tendency offtuids to
leak auto It is really a special case of differential pressure measurement,
inside versus outside pressure. Where there is any doubt about whether
a pressure is gauge, differential, or absolute, it should be specified in
full. However, it is common practice to shaw gauge pressure without
specifying, and to specify by saying "absolute" or "differential" only
for absolute or differential pressures. The use of "g" as in psig is
disappearing, and the use of "a" as in psia is frowned upon. Neither g
flor a is recognized in SI unit symbols. However, M is recognized for
differential pressure in all units.
38 FEEDBACK PROCESSCONTROL
Understanding
the Effects
of Gravity
at different places:
Melbourne (Australia)
Foxboro (USA)
Soest (The Netherlands)
9.79966 rn/S2
9.80368 rn/S2
9.81276 rn/S2
Hence the difference around the world is approximately :t 0.1 percent from the average. This is oflittle practicat importance in industrial
applications. However, with some transmitters being sold with a rated
accuracy of :t0.25 percent, it is well to consider the effect of a gravityinduced difference of more than hal the tolerance thai can arise if the
transmitter was calibrated in Europe and tested in Australia.
Gravity-Dependent
Units
Units such as psi, kglcm2, inches of water, and inches of mercury (Hg)
are all gravity dependent. The English unit pounds per square inch (psi)
is the pressure generated when the force of gravity acts on a mass of
one pound distributed aveT one square inch. Consider a dead weight
tester and a standard mass of one pound which is transported around
the earth's surface: the pressure at each paint on the earth will vary as
the gravitational acceleration varies. The same applies to units such as
inches of water and inches of mercury. The force at the bottom of each
column is proportional to the height, density, and gravitational acceleration.
Dead weight testers are primary pressure standards. They generate
pressure by applying weight to a piston that is supported by a fluid,
generally oil or air. By selecting the weights and the cross-sectional
aTea of the piston, the pressure generated in any gravity field can be
calculated. Therefore, dead weight testers are gravity dependent. For
accurate laboratory work, the gravity under which the tester was calibrated and that at the place of use must be taken into account. Similarly,
the pressure obtained by a certain height of fluid in a manometer depends on density and gravity. These factors must be corrected for the
PROCESS/PRE:SSURE
MEASURINGINSTRUMENTS 39
Units
While gravity plays no part in the definition of the pascal, it has the
same value wherever it is measured. Units such as pounds-force per
square inch and kilogram-force per square centimetre are also independent of gravity because a specific value of gravitational acceleration
was selected in defining these units.
Under equal gravity conditions, the pound-mass and pound-force
are numerically equal (which is the cause of considerable confusion).
Under nonstandard gravity conditions (the usual case), correction factors are required to compensate for the departure from standard. It
should be noted that the standard value of actual gravity acceleration is
llot recognized as such in the SI unit system, where only the SI unit of
acceleration of one metre per second per second is used. In the future,
only the measured actual gravity at the location of measurement (G)
will be used when gravity plays a part in the system under investigation. The pascal is a truly gravity-independent unit and will be used to
avoid the presently confusing question of whether a stated quantity is
gravity dependent.
Pressure
Standards
Now let us consider the calibration standards that are employed with
pressure-measuringinstruments and the basic instruments that are used
to measure pressure. It mar help to look at the ways in which the
standards for pressure calibration are established. You will recalI that
head is the same as pressure. A measure of head, then, can be a dependable measure of pressure. Perhaps the oldest, simplest, and, in
many respects, one of the most accurate and reliable ways of measuring pressure is the liquid manometer. Figure 2-2 shows a differential
manometer. When only a visual indication is needed and static
pressures are in a range that does Dot constitute a safety hazard, a
transparent tube is satisfactory. When conditions for the visual manometer are unsuitable, a variety of ftoat-type liquid manometers are
often employed.
40 FEEDBACK PROCESSCONTROL
HIGH
PRESSURE
PROCESS/PR;:SSURE
MEASURINGINSTRUMENTS 41
HIGH
PRESSURE
Fig.
42
FEEDBACK PROCESSCONTROL
LIQUID
GLASS
--- WEIGHT
DEAD WEIGHT
TESTER
TO
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 43
INSTRUMENT
UNOER TEST
44 FEEDBACK PROCESSCONTROL
Plant Instruments
That Measure
Pressure
Directly
Thus far in tbis chapter we bave been concemed with the detinition of
pressure, and some of the standards used bave been described. In the
plant, manometers and dead weight testers are used as standards for
comparison and calibration.
The working instruments in the plant usually include simple mechanical pressure gauges, precision pressure recorders and indicators,
and pneumatic and electronic pressure transmitters. A pressure transmitter makes a pressure measurementand generates either a pneumatic
or electrical signal output thai is proportional to the pressure being
sensed. We will discuss transmitters in detaillater in ibis chapter. Now
we will deal with the basic mechanical instruments used for pressure
measurement, how they operate and how they are calibrated. When the
amount of pressure to be measured is very small, the following instruments might be used.
Bell Instrument
Fig.
PROCESS/PRE$SURE
MEASURINGINSTRUMENTS 45
46 FEEDBACK PROCESSCONTROL
tube."
Figure 2-11A shows such a tube. As pressure is applied internally,
the tube straightens out and returns to a cylindrical Corm. The excursion of the tube tip moves linearly with internal pressure and is
converted to pointer position with the mechanism shown. Once the
PROCESS/PRE;SSURE
MEASURINGINSTRUMENTS 47
48 FEEDBACK PROCESSCONTROL
2-11 B.
Liquid
or Steam Pressure
Measurement
ter.
Pulsation Dampener
If the instrument is intended for use with a fluid under pressure and
subject to excessive fluctuations or pulsations, a deadener or damper
should be installed. This will provide a steady reading and prolong the
life of the gauge.
Two other elements that use the Bourdon principIe are the spiral
(Figure 2-12) and helical (Figure 2-13). The spiral and helical are, in
effect, multitube Bourdon tubes. Spirals are commonly used for
Fig.
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 49
2-12. Spiral.
pressure ranges up to o to 200 psi or 1.4 MPa, and helicals are made to
measure pressures as high as Oto 80,000 psi or 550 MPa. The higher the
pressure to be measured, the thicker the walls ofthe tubing Cromwhich
the spiral or helical is constructed. The material used in the construction mar be bronze, beryllium copper, stainless steel, or a special NiSpan C alloy. Spirals and helicals are designed to provide a lever motion of approximately 45 degrees with full pressure applied. If this
motion is to be translated into pen or pointer position, it is common
practice to utilize a four-bar linkage, and this necessitates a special
calibration technique. If, instead of measuring gauge pressure, it is
necessary to read absolute pressure, the reading must make allowances
for the pressure of the atmosphere. This mar be done by utilizing an
absolute double spiral element. In tros element, two spirals are used.
One is evacuated and sealed; the second has the measured pressure
applied.
The evacuated sealed element makes a correction for atmospheric
pressure as read on the second element. Thus, the reading can be in
terms of absolute pressure, which is gauge plus the pressure of the
atmosphere, rather than gauge.
An absolute double spiral element of this type mar be used to
measure pressures up to 100 psi or 700 Kpa absolute. This element is
shown in Figure 2-14.
Metallic
Bellows
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 51
ounces to many pounds per square inch. A bellows will develop many
times the power available from a helical, spiral, or Bourdon tube.
A bellows is typically rated in terms of its equivalent square inch
area. To create a linear relationship between the excursion of the bellows and the applied pressure, it is common practice to bave the bellows work in conjunction with a spring, rather than with the spring
characteristic of the metal within the bellows itself. Each bellows and
spring combination has what is called a spring rate. The springs used
with the bellows are usually either helical or spiral. Typically, the
spring rate of the helical spring is ien times or more thai of the bellows
material itself.
Using a spring with a bellows has several advantages over relying
on the spring characteristics of the bellows alone. The calibration procedure is simplified, since adjustments are made only on the spring.
Initial tension becomes zero adjustment and the number of active turos
becomes span adjustment. A spring constructed of stable material will
exhibit long-term stability thai is essential in any component.
.When a measurement of absolute pressure is to be made, a special
mechanism employing two separate bellows mar be used. It consists of
a measuring bellows and a compensating bellows, a mounting support,
and an output lever assembly (Figure 2-17). The measuring and compensating bellows are fastened to opposite ends of the fixed mounting
support: the free ends of both bellows are attached to a movable plate
mounted between them. The motion of ibis movable plate is a measure
of the difference in pressure between the two bellows.
52 FEEDBACK PROCESSCONTROL
Pressure
Transmitters
Signal Transmissions
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 53
54 FEEDBACK PROCESSCONTROL
The receiver converts the signat into a suitable pen or pointer position.
Because the scale is labeled in proper units, it is possible to read the
measuredpressure.
A typical pneumatic indicator is shown in Figure 2-18 (top) and its
operation mar be visualized by studying Figure 2-18 (bottom, right).
The input signal passes through an adjustable needle valve to provide damping, then continues to the receiver bellows. This bellows,
55
Pressure
Seals
Application
A sealedpressuresystemis usedwith a pressuremeasuringinstrument
to isolate corrosive or viscousproducts, or products that tend to solidify, from the measuringelementand its connectivetubing.
Definition
PROCESS/PRESSURE
MEASURINGINSTRUMENTS 57
58 FEEDBACK PROCESSCONTROL
temperatures.
The Foxboro l3DMP Series pneumatic d/p Cell transmitters with
pressure seals (Figure 2-21) measure differential pressures in ranges of
O to 20 to O to 850 inches of water or O to 5 to O to 205 kPa at static
pressures Cromfull vacuum up to flange ralingo They transmit a proportional 3 to 15 psi or 20 to 100kPa or 4 to 20 mA dc signat to receivers
located up to several hundred yards or melers Cromthe point of measurement.
S9
FiUing Fluids
Ideally, the filling fluid used in a sealed pressure system should be
noncompressible, bave a high-boiling point, a low-freezing point, a low
coefficient of thermal expansion, and low viscosity. It should be noninjurious to the diaphragm and containing parts, and should Dot cause
spoilage in the event ofleakage. Silicone-based liquid is the most popular filling fluid.
The system is evacuated before the filling fluid is introduced. The
system musi be completely filled with fluid and free from any air pockets thai would contract or expand during operation, resulting in erroneous indications at the pen or pointer or in an output signat. The
degree of accuracy of any filled pressure system depends on the perfection of the filling operation.
Calibration
Techniques
The procedure for calibration of a pressure instrument consists of comparing the reading of the instrument being calibrated with a standard.
The instrument under calibration is then adjusted or manipulated to
make it agree with the standard. Success in calibration depends Dot
only on one' s ability to adjust the instrument, but on the quality of the
standard as well.
Field Standards
Field standards must be reasonably convenient to use and must satisfy
the accuracy requirements for the instrument under calibration. A 100inch water column, for example, is extremely accurate but Dot practical
to set up out in the plant. For practical reasons, we find that most field
standards are test ganges.The test gaugeis quite similar, in most cases,
to the regular Bourdon ganges. However, more care has gone into its
design, construction, and calibration, making it very accurate. A good
quality test gauge will be accurate to within ::\:0.25percent of its span.
This is adequate for most field use.
Under some conditions, a manometer mar be used in the field. This
usually occurs when a low-pressure range is to be calibrated and no
other suitable standard is readily available.
Portable Pneumatic Calibrator
All of the ingredients required to perform a calibration bave been combined into a single unit called a portable pneumatic calibrator. This unit
60
FEEDBACK PROCESSCONTROL
Pneumatic
Pressure
Transmitter
0/1"
PROCESS/PRE~SURE
MEASURINGINSTRUMENTS 61
~~
o~
~~
;c
~"
~m
~C
~~z
mO~
,,~~
cm~
z
~2
~~
~'"
~~~;~:~
;
l ,t'i'
" ",'
~, \c:
\\'i",:"
'
62 FEEDBACK PROCESSCONTROL
FLE'~"
Relay
PROCESS/PRE$SURE
MEASURINGINSTRUMENTS 63
INPUT
DIAPHRAGM
SUPPLY
STEM
VALVE
BALL VALVE
OUTPUT
EXHAUST
SPRING
ot Operation
The 11GM Pneumatic Transmitter (Figure 2-24) is a force-balance instrument that measures pressure and transmits it as a proportional 3 to
15 psi pneumatic signal (20 to 100kPa).
The pressure is applied to a bellows, causing the end of the bellows
to exert a force (through a connecting bracket) on the lower end of the
force bar. The metal diaphragm is a fulcrum for the force bar. The force
is transmitted through the ftexure connector to the range rod, which
pivots on the range adjustment wheel.
Any movement of the range rod causes a minute change in the
clearance between the ftapper and nozzle. This produces a change in
the optput pressure from the relay to the feedback bellows until the
force of the feedback bellows balances the pressure on the measure-
64 FEEDBACK PROCESSCONTROL
Pressure Transmitter
PROCESS/PRES:sURE
MEASURINGINSTRUMENTS 65
until the force in the bellows balances the force on the diaphragm
capsule.
The output pressure, which establishes the force-balane, is the
transmitted pneumatic signal, which is proportional to the 'absolute
pressure being measured. This signal is transmitted to a pneumatic
receiver to record, indicate, or control.
Ouestions
2-1. An ordinary commercial Bourdon gauge has a scale of O psi to 250 psi,
and an accuracy of:t 1.percent of span. If the gauge reads 1.75psi, within
what maximum and minimum values will the correct pressure fall?
8. 1.74to 1.76psi
c. 1.76.5to 1.78.5psi
b. 1.72.5to 1.77.5psi
d. 1.79to 1.80psi
2-2.
8.
b.
c.
66 FEEDBACK PROCESSCONTROL
2-3.
a.
b.
c.
d.
Absolutepressuris:
Gaugepressureplus atmosphericpressure
Gaugepressurelessatmosphericpressure
Gaugepressureplus atmosphericpressuredivided by two
Always referencedto a point at the peakof Mt. Washington,NH
PROCESSlPRESSURE
MEASURINGINSTRUMENTS 67
c. No problemis created
d. Readthe peakand minimumand divide by two to obtainthe true
pressure
2-12. A measurement
of absolutepressureis to be madeusinga mechanism
employingtwo separatebellows. Measurementis appliedto one bellowsand
the other:
8. Is sealedat an atmosphericpressureof 14.7psi
b. Is completelyevacuatedand sealed
c. Containsalcoholfor temperaturecompensation
d. Has an activeareatwice that of the measuringbellowsand is sealedat a
pressuretwice atmospheric
2-13. The dangerof havinga high-pressureline carryinga dangerous
chemicalrupture in the control room is:
8. Eliminated by usingspecialduty piping
b. Ignored
c. Eliminated throughthe useof a transmissionsystem
d. Minimized by placingthe line within a protectivebarrier
2-14. The standardpneumatictransmissionsignalmost generallyused in the
United Statesis:
8. 3 to 27 psi
c. 3 to 15psi
b. 10to 50 psi
d. 2 to 12psi
2-15. A sealedpressuresystem:
8. Is similar in someways to a liquid-filled thermometer
b. Sealsthe processmaterialin the instrument
c. Must be usedat a fixed temperature
d. Is alwaysusedwith manualtemperaturecompensation
2-16. A pneumaticrelay:
8. Is a setof electricalcontactspneumaticallyactuated
b. Is a signalbooster
c. Is a pneumaticamplifier
d. Containsa regulatoractuatedby a bellows
2-17. Whenthe clearancebetweenflapper and nozzlechangesby 0.0006
inchesthe output of the transmitterwill changeby:
8. 3 psi
c. 12psi
b. 15psi
d. 6 psi
2-18. An instrumentis to be calibratedto measurea rangeof Oto 6,000psi.
For sucha calibration:
8. oil or lquid shouldbe used
b. Air mustbe used
c. An inert gas suchas nitrogenis required
d. Any sourceof highpressureis acceptable
68 FEEDBACK PROCESSCONTROL
Level Measurement
Measurement Methods
Methods
Level
The
The typical process
process plant
plant contains
contains many
many tanks,
tanks, vessels,
vessels, and
and reservoirs.
reservoirs.
measurement
store or process
process materials.
materials. Accurate
Accurate measurement
Their function
function is to store
of thesecontainers
materialin the tanks
of the contents
contents ofthese
containers is vital. The
The material
tanks is
usually
occasionallyit may
mar consist
consistof solids.
usually liquid, but occasionally
solids.
Initially,
level measurement
measurementappears
presenta simple
Initially, level
appears to present
simple problm.
problem.
However,
closerlook soon
soonreveals
variety of problems
that must
mustbe
However, a closer
reveals a variety
problems that
be
resolved.
materialmay
mar be
very corrosive;
mar tend
resolved. The material
be very
corrosive; it may
tend to solidify; it
mar tend
mar contain
contain solids;
mar create
other
may
tend to vaporize;
vaporize; it may
solids; or it may
create other
difficulties.
difficulties.
The
commonmethods
The common
methods employed
employed for automatic
automatic continuous
continuous liquid
level measurements
level
measurements are
are as
as follows
follows (see
(see also
also Table
Table 3-1):
3-1):
1.
Float-and-eable
1. Float-and-cable
2.
2. Displacement
Displacement(buoyancy)
(buoyancy)
3. Head
Head (pressure)
(pressure)
4. Capacitance
Capacitance
5. Conductance
5.
Conductance
6. Radiation
Radiation(nucleonic)
(nucleonic)
7. Weight
7.
Weight
8. Ultrasonic
8.
Ultrasonic
9. Thermal
9.
Thermal
69
70 FEEDBACK PROCESSCONTROL
Available Upper
Range Values
Open
10 in to 250 ft
0.25 to 75 m
4 in to 250 ft
0.lt075m
2 in to many ft.
50 mm to many metres
5 in to many ft.
0.25 to many metres
6 in to 12 ft
0.15 to 3.6 m
3 in to 50 ft.
75 mm to 15 m
lnches to Feet
mm to m
Depends on Tank Dim.
Open
Open
corrosive or dirty
Clean
Tank
Open
Both
Both
Condition
of Liquid
Open
Any type
Both
Any type
Wide
Both
Any type
Wide
Wide
One or more Points
80th
Nonconductive
80th
80th
Any type
Conductive
Float-and-Cable
A ftoat-and-cable or ftoat-and-tape instrument (Figure 3-1) measures
liquid level by transmitting to a mechanism the rise and fall of a ftoat
thai rides on the surface of the liquido Mechanisms are available to
accommodate level variations ranging from a few inches to many feet.
Float-and-cable devices are used primarily in open tanks, whereas ftoat
level switches mar be designed to operate in a pressurized tank.
Float devices bave the advantage of simplicity and are insensitive
to density changes. Their major disadvantage is their limitation to reasonably clean liquids. Thrbulence mar also create measurement problems. The ftoat and cable technique does Dot lend itselfto the transmitter concept as well as do some of the following techniques.
Displacement
(Buoyancy)
72
FEEDBACK PROCESSCONTROL
where:
f
V
Lw
L
B
=
=
=
=
=
73
temperature service. Interface level measurementmar be accomplished by permitting the interface level to vary over the length of the
displacer.
f = V (B) (SG difi)
SG difI = SG lower liquid minus the SG upper liquid
Head or Pressure
74 FEEDBACK PROCESSCONTROL
DETAlL
OF NOTCH
IN BUBBLE PIPE
76 FEEDBACK PROCESSCONTROL
OPEN TANK
Fig. 3-7.
Span = xGL
Suppression= yGL+ zG,
Span = xGL
Suppression= yGL+ zG,
Span = xGL
Elevation =/dG. -yGL
(0.8)
(minus sign indicates thai the higher pressure is applied to the low side
of the cell.)
At times the liquid to be measured possessescharacteristics thai
create special problems. Assume, for example, thai the liquid being
measured will solidify if it is applied to a wet leg and it is virtually
impossible to keep the leg dry. This type of application could use
a pressure repeater. The repeater (Figure 3-8) is mounted above
the maximum level of the liquid, and the liquid level transmitter is
mounted near the bottom ofthe tank. The pressure in the vapor section
is duplicated by the repeater and transmitted to the instrument below,
(Figure 3-9). Thus, the complications of a wet leg are avoided, and a
varying pressure in the tank will Dot atrect the liquid level measurement.
The pressure range thai mar be repeated is O to 100 psi or Oto 700
kPa. The supply pressure musi exceed the pressure to be repeated by
78 FEEDBACK PROCESSCONTROL
(Figure 3-10).
Conductance
Conductivity level sensors consist of two electrodes inserted into the
vessel or tank to be measured. When the level rises high enough to
provide a conductive path from one electrode to the other, a relay (solid
state or coil) is energized. The relay mar be used for either alarm or
control purposes. Conductivity then becomes either point control or an
alarm point. The lquid involved must be a conductor and must Dot be
hazardous if a spark is created. Level by conductivity finds occasional
applications in process plant s (Figure 3-11).
Radiation
LlNE
80 FEEDBACK PROCESSCONTROL
DETECTOR
~~~Jr;~-~~'-==-L__~
\~::::-
--
\~"
\ ::;"""""
\ \'
\\"
\"
INDICATOR
\,
-+
~-g
i~CONVERTER
NUCLEONIC(RADIATION)
Fig. 3-12. Radiationtechnique.
draulic or strain gauge, are used to weigh the vessel and its contents.
The tare weight of the tank is zero adjusted out of the reading, which
will result in a signal proportional to tank contents (Figure 3-13).
One advantage of the weight system is that there is no direct contact with the contents of the tank and the sensor. However, the system
is not economical, and varying densities mar confuse the relationship
between signal and true level.
Ultrasonic
20,000 Hz and a receiver. The time required for the sound waves to
travel to the liquid and back to the receiver is carefully measured. The
time is a measure of level. This technique has excellent reliability and
good accuracy. Furthermore, nothing comes in contact with liquid in
the tank, which minimizes corrosion and contamination. The only generallimitation is economic.
Thermal
Measurement
Methods
for Liquids
and Liquid
Slurries
sity.
The measurement and control of liquid density are critical to a great
number of industrial processes. Although density can be of interest, it
is usually more important as an inference of composition, of concentration of chemicals in solution, or of solids in suspension.
82 FEEDBACK PROCESSCONTROL
Span
Hydrometer
0.1
0.005
0.05
0.05
O.O~
0.05
Displacer
Hydrostatic head
Radiation
Weight oCfixed volume
Vibrating U-Thbe
Condition
oi Liquid
Accuracy
Clean
Clean
:!:1%
Any
Any
Clean
Clean
as % Span
:!:1%
~ to 1%
1%
1%
1-3%
Fig.
lz=ZZarZz=
3-15. Fixed heightofliquid for densitymeasurement.
(3-3)
Vibration
84 FEEDBACK PROCESSCONTROL
Span = H X (G2,- GJ
Zero suppression = H x GI,
(3-4)
detector.
Differential
Pressure Transmitter
There are a variety of system arrangements for hydrostatic head density measurements with d/p Cell transmitters. Although ftange-mounted
d/p Cell transmitters are often preferred, pipe-connected transmitters
can be used on lquids where crystallization or precipitation in stagnant
pockets will noi occur.
These d/p Cell transmitter methods are usually superior to those
using bubble tubes. They can be applied wherever the vessel is high
enough to satisfy the mnimum transmitter span. They are also well
suited for pressure and vacuum applications.
Constant level overftow tanks permit the simplest instrumentation
as shown in Figure 3-16. Only one d/p Cell transmitter is required. With
H as the height of lquid above the transmitter, the equations are still:
Span = H X (G2
Applications with level and/or static pressure variations require compensation. There are three basic arrangements for density measurement
under these conditions. FiTSt, when a seal fluid can be chosen that is
always heavier than the process fluid and will Dot mix with it, the
method shown in Figure 3-17 is adequate. This method is used extensively on hydrocarbons with water in the wet leg.
Fig. 3-16. Constant level, open overftow tanks require only one d/p Cell transmitter for
density measurement.
Fig.
86 FEEDBACK PROCESSCONTROL
y-:'--=(
\
H
DENSITY
~
SIGNA L
A I
=
UQUID
a':iJ-l
PURGE
(SP.GR.=GS)
3-17. In an open or closed tank with varying level and/or pressure. a wet leg can be
filled with seal fluid heavier than the process liquido
For a wet leg fluid o specific gravity Gs. an elevated zero transmitter
musi be used. The equations become:
Span = H x (G2 -GJ,
When no seal or purge lquid can be tolerated, there are ways to provide a "mechanical seal" for the low-pressure leg, or for both legs, if
needed. Figure 3-18 shows the use of a pressure repeater for the upper
connection.
The repeater transmits the total pressure at elevation B to the low
pressure side of the d/p Cell transmitter. In this way, the pressure at
elevation B is subtracted from the pressure at elevation A. Therefore,
the lower transmitter measures density (or H x G, where G is the
specific gravity of the lquid). The equations for the lower transmitter
are:
Span = H X (G2 -GJ
Zero suppression = H x G1
Fig.
whered1
3-18. In an open or closed tank with varying level and/or pressure where seal fluid
or purge is Rot suitable, a pressure repeater can be used.
Questions
88 FEEDBACK PROCESSCONTROL
3-3. A pressurized tank contains a lquid, SG = 1.0, and the level measuring
pressure taps are 100inches apart. A pneumatic differential pressure
transmitter is used to measure level. The leg that connects the top of the tank
to the transmitter is filled with tank lquid. The top tap should be connected
to:
a. The low-pressuretap on the transmitter.
b. The high-pressuretap on the transmitter.
, Either the high- or the low-pressuretap.
d. The high-pressuretap but througha sealchamber.
3.4. In Qu~stion3-3the bottom connectionis madeto the low-pressuretap
on the transmitterand the top is madeto the high-pressure
tap. The signal
output, if the transmitteris calibratedOto 100inches,whenthe tank is full
will be:
a. Topscalevalue
c. O
b. Bottom scalevalue
d. A measureof density
3.5. A plant hasa water tower mountedon top of an 80-footplatform. The
tank is 30 feet high. Whatis the heightof water in the tank if a pressuregauge
on the secondfloor, height 15feet,reads 40 psi.
a. Full
c. 4.74feet
b. 12.42feet
d. 27.42feet
3-6. A displaceris 5 inchesin diameterand 30 incheslong. If it is submerged
to a depthof 20 inchesin lquid sa = 0.8, whatforce will it exert on the top
works?
a. 11.3pounds
c. 35.5pounds
b. 426.3pounds
d. 1.47pounds
3.7. A closed tank level (Sa = 0.83)is measuredwith a differentialpressure
transmitter.The level mar vary from 10to 100inches.The high-pressuretap
is 10inchesabovethe transmitterand a watersealfluid is used.A pressure
repeateris usedfor the top tank pressure.The differentialpressure
transmittershouldbe calibrated:
a. 10to 100inches
b. 10to 84.7inches
c. 8.3 to 74.7inches
d. 8.3 to 98.3inches
3.8. To resistthe corrosiveeffectsof a very unusual,highlyexplosive
chemical,a storagetank is lead-lined.Level measurement
is difficult because
the materialalso solidifiesonce it entersa measuringtap. To measurethe level
with accuracythe bestchoicewould be:
a. Weighthe tank and its contentsand zero out the tare weightof the tank.
b. Use a radioactivelevel measurement.
c. Install a conductivitylevel measurement.
d. Use a thermal conductivitylevel detector.
a. 1.0
c. 0.9
b. 0.83
d. 1.2
Flow Measurement
The process industries by their very nature deal constantly with flowing
fluids, and measurement of these flows is essential to the operation of
the plant. These measurements are indicated, recorded, totalized, and
used for control. Flow measurement is generally the most common
measurement found in the process plant.
Fluid flow measurement is accomplished by:
Ao Displacement
lo Positive displacement meters
20 Metering pumps
Bo Constriction Type, Differential Head
lo Closed conduit or pipe
ao Orifice plate
bo Venturi tube
Co Flow nozzle
do Pitot tube
eo Elbow
fo Target (drag force)
go Variable aTea (rotameter)
20 Open channel
ao Weir
bo Flume
90
FLOWMEASUREMENT 91
C. Velocity Flowmeters
1. Magnetic
2. Turbine
3. Vortex or swirl
4. Ultrasonic
5. Thermal
D. Mass Flowmeters
1. Weighttypes
2. Head and magnetictypes compensatedfor temperature,pressure,
and density
3. Gyroscopeprecisiontypes
4. Centrifugalforce (torque)types
Positive displacementmeters and meteringpumps measurediscrete quantities of flowing fluid. This flow is indicated in terms of an
integrated or totalized flow volume (gallons,cubic feet, litres, cubico
metres, and the like). A typical applicationof this type of flow measurementis custodytransfer, and familiar examplesaredomesticwater
metres and gasolinepumps. The other types of meters listed above
measureflow rate.
lt is flow rate-quantity per time, suchas gallons per minute or
liters per second-which is most generallyused for measurementand
related control applications in the processplant. The most common
rate meter is the constriction or headtype.
Constriction
or Differential
Head Type
+ Z2 = ~p + ~
(VmJ2+ Zl
92 FEEDBACK PROCESSCONTROL
where:
P
Vm
Z
p
G
=
=
=
=
=
If the energy is divided into two forms, static head and dynamic or
velocity head, some of the inferential flow devices can be more easily
studied.
For example, with an orifice plate, the change in cross-sectional
aTeabetween the pipe and the orifice produces a change in flow velocity
(Figure 4-1). The flow increases to pass through the orifice. Since total
energy at the inlet to, and at the throat or, the orifice remains the same
(neglecting losses), the velocity head at the throat must in.crease,causing a corresponding decrease in static head. Therefore, there is a head
difference between a point immedlately ahead of the restriction and a
point within the restriction or downstream from it. The resulting differential head or pressure is a function of velocity that can then be related
to flow. Mechanical flow-measuring instruments use some device or
restriction in a flow line that results in such a differential head.
The following should clarify these relationships. Assume a tank as
shown in Figure 4-2. A flow line enters the tank and replaces the out-
Fig. 4-1. Orifice plate differential producer. The difference in head (pressure) atP, and
P 2is a function of velocity which can be related to ftow.
FLOW MEASUREMENT 93
-+
a=A.J2;
-..Q =AV2-;;h
ftow through the orifice located near the bottom of the tank. If the level
in the tank is H, the velocity of outftow will be:
y2 = 2GB
or
=AV
Substituting the expression for velocity in this equation:
(4-1)
This expression may also be used to calculate the rate offtow past a
point in a pipe. The actual ftow rate will be less than this equation will
V=Y2GH
Q
Q=A\f2Gii
O)
Fig.
94
The orifice plate is the most popular primary device found in most
process plants. Orifice plates are applicable to all clean fluids, but are
Dot generally applicable to fluids containing solids in suspension(dirty
fluids).
A conventional orifice plate consists of a thin circular plate containing a concentric hole (Figure 4-3). Th plate is usually made of stainless
steel but other materials, such as monel, nickel, hastelloy, steel, glass,
and plastics, are occasionally used. The most popular orifice plate is the
sharp-edged type. The upstream face of the plate usually is polished
and the downstream gide is often counterbored to prevent any interference with the flowing fluid. The bore in the plate is held to a tolerance
of a few ten-thousandths of an inch in small sizes and to within a few
thousandths in sizes above 5 inches in diameter.
ln addition to the conventional, sharp-edged, concentric plate,
there are others that bave been designed to handle special situations.
These special types constitute only a small percentage of the total, but
they do occasionally solve a difficult problem.
There are two plates (Figure 4-3) designed to accommodate limited
amounts of suspended solids. The eccentric plate has a bote that is
bored off-center, usually tangent to the bottom of the flow line (inside
periphery of the pipe). The segmentat orifice plate has a segment removed from the lower hal of the orifice plate. ln addition, there are
CONCENTRIC
ECCENTRIC
SEGMENTAL
Reynolds
FLOW MEASUREMENT 95
to drain.
Table 4-1 summarizes application factors to help in deciding
whether the orifice plate can do a particular job.
Another primary device that is frequently found in the process
plant is the Venturi tube shown in Figure 4-4. The Venturi tube produces a large differential with a mnimum permanent pressure loss. It
has the added advantage of being able to measure ftows containing
suspended solids. The most significant disadvantage is its cost which,
when compared with other primary devices, is high.
~~
G
VP
Fig.
96 FEEDBACK PROCESSCONTROL
" t
:
o:
Accuracy (empirical
data)
None
Pressure loss #
, P
Differenlial produced
for given ftow and size
p
E
E
P
P
E
P
F
G
G
E
~
.9"
.s~
".."
.~
~~~~"to"~
~5
"='"
" E
E
EG
None
E
E
GG
F
None
Non.
VP
G
G
F
U
E
F
P
F
F
VP
E
P
F
vapors
First cost
EGG *
F
E
E
U
G
Ease of changing
capacity
E
G
Ease of instalIalion
Excellent
G
F
Good
FairP
Poor
VP
U
/I
Very poor
Unknown
E indicates lowest loss, P highest, etc.
EG
EG
p
E
G
None
E
u
uVP
E
F
G
F
Fig.
FLOW MEASUREMENT 97
4-5. Flownozzleassembly.
Fig.
98 FEEDBACK PROCESSCONTROL
rb
4-7. Targetflowmeter.
FLOW MEASUREMENT 99
Oevices
Secondaryinstrumentsmeasurethe differential produced at the primary devices and convert it into a signal for transmissionor into a
motion for indication, recording, or totalization.
Secondaryinstrumentsinclude the mercury manometer,the socalled mercurylessor diaphragm(beUows)meterand various types of
force-balanceand motion-balancepneumaticand electronictransmitters.
In the past the mercury manometer was an extremely popular secondary device, but the high price and danger of mercury bave all but
eliminated it from everyday use. However, a few mercury manometers
are still employed for ftow rate measurements in gas pipelines. The
bellows or diaphragm secondary devices are popular when a direct
indication or record is desired. The most popular secondary device is
the force-balance transmitter. The reasons for this popularity are virtually unlinited adjustability, no harm from extensive overrange, and
the a vailability of a standard signal that can be fed into a recorder, a
controller, or other instruments that may be combined to form a sys-
tem.
Still another detail is the mounting of the secondary device (locations are shown in Figure 4-8). With liquid ftow, the secondary device is
LIQUID FLOW
GAS FLOW
STEAM FLOW
below the pipeline being measured to ensure that the connecting lines
attached to the sicle of the pipe remain liquid filled. With steam, the
lines should always remain filled with condensate; but with gas, the
secondary device is mounted above the ftow line to drain away any
liquid that mar be present.
When any primary device is installed in a pipeline, the accuracy
will be improved if as much straight run as possible precedes il.
Straight run beyond the primary device is of far less concem.
Still another important consideration is the location of the pressure
taps. With nozzles, Venturi, Dall and Pitot tubes, and elbows, the
pressure tap locations are established. For orifice plates, however, a
variety of tap locations are used. These are ftange, corner, vena contracta, or D and D/2, along with full ftow or pipe taps. Figure 4-9
describes these tap locations, and Figure 4-10 shows the importance of
tap location. In general, ftange taps are preferred except when physical
limitations make pipe taps advantageous. Corner taps require a special
ftange and vena contracta tap locations relate to orifice openings.
Corner taps are advantageous for pipe sizes under 2 inches.
Figure 4-11 describes the permanent head loss caused by the primary device selected.
Relating
The two basic formulas bave already been introduced. In the English
system, G = 32 feet per second squared, and in the metric system,
G = 980 centimetres per second squared. The height (h) would be expressed in feet in the English system and centimetres in the metric
Fig. 4-11. Pennanent head los s in a ditferential producer may be plotted as a percent of
measured ditferential for the several types of primary devices. These values must be
interpreted according to the acceptable head loss limit for any particular application.
will take a long time to complete. For tros reason the sample calculations that follow will use the English system.
In Equation 4-1, V is in fe et per second; the acceleration due to
gravity (G) is in feet per second squared; H is the height in feet of a
column of the fluid caused by the differential pressure across a primary
device. To express this equation in terms of an equivalent differential
(h), in inches of water, H is replaced by (h/12)G) where G is the
specific gravity of the fluid at flowing temperature.
Substituting V into Equation 4-1:
(4-2)
where:
Q = Volumetric flow (cubic feet per second)
A = Cross-sectional aTea of the orifice or throat of the primary
device (square feet)
h = Differential across the primary device (inches of water)
G, = Specific gravity of the fluid (dimensionless)
G = Acceleration due to gravity (a constant: 32.17feet per second2)
For lquids, it is more useful to express Q in gallons per minute.
AIso, it is convenient to express the area of the orifice or throat interms
of its diameter (d in inches). Substituting in Equation 4-2:
x~
(4-3)
= 5.667
SD2
fE::
V G;
Gi
(4-6)
which simplifiesto:
Q = 5.667 SIJ2 YG;l
GI
Pb" T;G
Ratio
0.100
0.125
0.150
0.175
0.200
0.225
0.250
0.275
0.300
0.325
0.350
0.375
0.400
0.425
0.450
0.475
0.500
0.525
0.550
0.575
Square-Edged
Orifice, Flange
Corner or
Radius Taps
Ful/-Flow
Quadrant-
2\-2& 8D
Nozz/e
and
Lo-Loss
Dall
Taps
Venturi
Tub.
Tube
(PipJ
0.005990
0.006100
0.009364
0.009591
0.01349
0.01389
Edged
Orifice
0.01839
0.01902
0.02402
0.02499
0.0305
0.03044
0.03183
0.0390
0.03760
0.03957
0.0484
0.04558
0.04826
0.0587
0.05432
0.05796
0.08858
0.06390
0.06874
0.1041
0.07429
0.08068
0.1210
0.1048
0.08559
0.09390
0.1392
0.1198
0.09776
0.1085
0.1588
0.1356
0.1170
0.1267
0.1109
0.1247
0.1800
0.1527
0.1335
0.1443
0.1251
0.1426
0.2026
0.1705
0.1500
0.1635
0.1404
0.1625
0.2270
0.1900
0.1665
0.1844
0.1568
0.1845
0.2530
0.2098
0.1830
0.207
0.1745
0.2090
0.2810
0.2312
0.2044
0.232
0.1937
0.2362
0.3110
0.2539
0.2258
0.260
0.0700
0.0824
0.0959
0.1106
0.2144
0.2664
0.3433
0.2783
0.2472
0.292
O.(X)()
0.2369
0.3002
0.3781
0.3041
0.2685
0.326
0.625
0.650
0.675
0.700
0.725
0.750
0.775
0.800
0.820
0.2614
0.3377
0.4159
0.3318
0.2956
0.364
0.2879
0.3796
0.4568
0.3617
0.3228
0.3171
0.4262
0.5016
0.3939
0.3499
0.3488
0.4782
0.5509
0.4289
0.3770
0.3838
0.6054
0.4846
0.4100
0.4222
0.6667
0.5111
0.4430
O.4646
0.5598
0.4840
0.5113
0.6153
0.5250
0.6666
0.5635
(4-10)
Equation 4,.10is applicable to gas ftow only when the pressure
differential is small enough so that gas density does Dot change significantly. A simple rule ofthumb is that the maximum differential in inches
of water should Dot exceed the absolute operating pressure in psi absolut.~. For example, if the gas operating pressure is 22 psi absolute, at a
particular installation, and the maximum differential is 20 inches of
water, Equation 4-10 can be used.
Flow rate 'measurements for gas and steam are more difficult to
make with accuracy than those for liquido The reason is changes in
specific gravity, weight, temperature, pressure, and so on, that mar
occur under operating conditions.
These changes will bave an effect on measurement accuracy and
under certain conditions mar be difficult to predict. An abbreviated set
of tables for the formulas given are included in this book. If more
accuracy is required, more exact equations, along with detailed tables,
such as those found in Principies and Practice oi Flow Meter Engineering
by Spink, should be used.
Another method of performing these ftow calculations is to use a
ftow slide rule. The ftow slide role has the table values incorporated
into its scales. If the tables given are used, the resulting accuracy
should be as good as the flow slide rule.
Now several sample problems are given to demonstrate the procedure followed for each type of calculation. Additional problems are
given at the end of tros chapter.
SAMPLEPROBLEMJ A 4-inch schedule 40 pipe carries water that is
measured by a concentric, sharp-edged, orifice plate, d = 2.000 inches,
with flange taps. The differential is measured with an electronic differential pressure transmitter. The transmitter is calibrated Oto 100inches
of water pressure and has an output of 4 to 20 mA dc. If the signal Crom
the transmitter is 18.4 mA dc, find the flow rate.
S/ep 1. Convert the electrical signal to differential pressure.
18.4 -4
20 -4
S =
0.475
0.1404
0.4968
0.5000
0.1568
(0.5000
0.4968 -0.475
-0.475 )
S = 0.1547
Step5. Substitute in Equation 4-7:
SAMPLEPROBLEM
2 An elbow is used as a primary device. The taps are
made at 45 degrees. The line is a 6-inch schedule 40 pipe. What is
the water flow rate if the effective radius of curvature is 9 inches
and a differential pressure of 35 inches of water pressure is produced.
= 172.66 .yj"5 =
,021.47gpm
SAMPLEPROBLEM
3 Dry-saturated steam is measured with a ftow nozzle. The d/D is 0.45 and the line size is a S-inch schedule SOpipe. The
static pressure is 335 psi. Calculate the ftow rate at a differential
pressure of 200 inches of water in pounds per hour.
W(pounds per hr.) = 359SD2V:y;
(4-8)
s = 0.2026
D = 7.625 inches (Table A-4)
Yf = 0.754 pounds per cubic feet
W(pounds per hour) = 359 x 0.2026 x 7.6252\1200 x 0.754
= 4,228.77x 12.28
W = 51,929 pounds per hour
SAMPLEPROBLEM
4 A 6-inch schedule 40 pipe (1D-6.065) carries fuel
gas with a specific gravity of 0.88. The line pressure is 25 psi. Plowing
temperature is 60oPand the ftow is measured with an orifice plate with
ftange taps. The maximum ftow rate is 2,000,000standard cubic feet per
day. Pind the diameter of the hole to be bored in the concentric orifice
plate if 20 inches of water pressure is full-scale differential.
2,000,000
= 7' 727 x S x. 6 0652 V120(25
+-~
24
(460
+ 6~
.2144
.2218
.2369
.600
~ =
D
( .2218
.2369
-.2144
-.2144
d = (.583)(6.065)
= 3.536 inches
Fig.
4-12. Variablearea(rotarneter)flowmeter.
surements common in' the typical process plant. Open-channel measurements utilize head meter techniques.
Primary
Devices
welrs.
V-notch weirs are essentially plates (usually metal) that contain a
V-shaped notch (Figure 4-13). The angle of the V can vary, but the
formulas given are for the most common angles 30, 60, and 90 degrees.
V-notch weirs are employed for lower ftow rates than those that would
be measured by a rectangular weir.
In weir measurement (Figure 4-15) the nappe, or profi1e of water
over the weir, must be completely aerated if good accuracy is to be
obtained. All weirs then produce some head loss as the lquid falls free.
If head loss is a problem, a ftume might be a better choice.
Flumes, a further development of the basic weir concept, are designed primarily to reduce the head loss that is experienced with the
CIPPOLETTI
WEIR~S>2H
ECTANGULAR
WEIR-j
MAX
I
: 4~
_L)2H
MAX
PREFERABLY
ANO
>4H
MAX
I
0>3H
MAX
C\PPOLETTI
WEIR
GPM
70000
50000
100
40000
80
30000
60
50
20000
40
30
10000
8000
6000
5000
10
4000
3000
6
5
2000
3
1000
800
600
500
1.0
400
De
300
0.6
05
0.4
200
0.3
100
80
60
50
OI
40
0.08
30
006
0.05
20
0.04
FLOW
0.03
10
0.02
8
FLOW
6
5
001
0008
0.006
0005
0004
0003
0.002
weir.
AERATION'UNDE.
NAPPE
.k.
,..~~--~~~:::::: ~~:.:--::::~
i o
t7::::::;:::~~~t=:=f:~:::::::--i
l CO"".~.,.....c"O" .. TH.OAT...TION!l/.".'N.'.cr' ON c~1
Lc
f ~~~--~:
~.
..PLAN
'. "
.1
M
,\
\\
:~+
.1-0
.1.
Ir:--
'-'0-.,,
;1
'LOW
,
l
oi;;;.
""
,o
.";;,,
''-
SECTION
o-o
~
:..:.;
c;...
.,
'" ~< '"",:,
~'""
~~~--c
~-c..,
":";oC~.i~~~~@a~
, \oi
~~~t;
a~~=~~:",-c-co",
~~~:,
ci ci ci ci ci ci ci":":"";";
;... ~
;. .., .., .., .., .., .., .., .., .., .., ..,
~ ~
-"""""""""""""""'"
.1~ ...
~ ri:
'"
G)
Q: .:
:;
oc:
~~
~~
~
'"'
~ r;:
'"
~
lo.
cE
'"
~
.9
~
e
=
e
~
t, .t
to.t
'2
~
=
~
'Q
.5
~ .t
e
'~
.!,
~ ...
~
'Q
~
'"
=
NN''~"""":'ob~=~~
~~~~~~~:!:!:!:f:f
e
=
.;!;:-::i
-::i.;!-::.;!
~-'c-~-;'-;';'~;'
~ .;
~"!I!J;)ION
sn!~ ..un;) qloowS
--.N
-..,
'" ~
...
oS
'C
Li:
Qj
:c
.., .., .., .., .., .., .., .., .., ..,
~~~~~~~~~~~~
99~9O999999
N N N ...,J,
...,J,
.
:.:.~..~...
-"'-0-,
= ...g ::-
~.
;:- ::,..,.0--;
O':":'N"'~""""'obd,=
~":-~9~9"'99999
g--NN""",,",.o""~o.
..~.-!!!"~.-!!!
c ;:;:- c '" ~ ;,- ~ ;,- "C>
'9 'i' ";' "f
"f ";' '" -.,.
";'
-NN
b.b
..
'~
..,.
o. o. o. o. o. o. o. o. o.
~~!~~:,:,~~~~:,
5
,5
o
~.
oS
""
.. to.
~ ;;: :::
.:.!::~;:~~~:':~J.
.~
!~;;;~~~~~~:!~~
~,\,O-9'\'99"'9999
OO'--N""""'-o"'~
113
'!~
GPM
MGO
3000
CFS
4000
2000
3000
2000
1000
800
1000
800
600
500
400
300
200
100
so
60
40
50
600
500
400
300
200
80
100
60
50
30
40
20
30
20
10
8
6
5
4
3
2
10
08
06
O~
10
08
04
03
06
05
0.2
03
04
100
-t++
MGO
80
02
OI
60
50
40
004
20
FLOW
10
8
OI
006
QO~
30
FLOW
CFS
008
008
006
OO~
004
002
I
I
I
2
HEAD-INCHES
L-I
2
HEAD-FEET
I I .I.
6
I
8 10
,.,.,.
,..
I~ 20
60
0.03
80 100
002
FLOW
.456810
2/:3
56
8 IQ
001
FIVE
INCHES IS HINIHUN FLA.L SCALE
HEAD III'H
FDXBORD FLOA' ANO CABLE
HE'ER
Parshallfiume
Flume
size (in.)
3.
Q = 0.992 HI,547
6
Q = 2.06 HI,58
9
Q = 3.07 HI,53
12
Q = 4.00 HI,522
Q = crs; L = crest length (fi); H
Flume
size (in,)
18
Q = 6.00 H',538
24
Q = 8.00 HI,55.
36
Q = 12.00 HI,566
48
Q = 16.00 Hl.578
= head (fi)
Velocity
Flowmeters
Magnetic Flowmeter
The principIe of the magnetic ftowmeter was first stated by Faraday in
1832, but did Dot appear as a practical measurement for the process
plant until the 1950s.Its advantages are no obstruction to ftow, hence
no head loss; it can accommodate solids in suspension; and it has no
pressure connections to plug up. It is very accurate and has a linear
ftow rate to output relationship. Its disadvantages are that measured
material must be lquid; the lquid must bave some electrical conductivity; and it is expensive.
Operation
Operation ofthe magnetic ftowmeter is based on Faraday's well-known
law of electromagnetic induction: The voltage (E) induced in a conductor oflength (D) moving through a magnetic field (H) is proportional
to the velocity (V) of the conductor. The voltage is generated in a plane
that is mutually perpendicular to both the velocity ofthe conductor and
the magnetic field. Stated in mathematical form:
E = CHDV
(4-11)
suspended material. Most industrialliquids can be measured by magnetic flowmeters. Exceptions are someorganic chemicals and most refinery products. Water, acids, bases, slurries, liquids with suspended solids, and industrial wastes are commou applications. The limitation is
the electrical conductivity ofthe liquido The magnetic flowmeter offers
no more restriction to flow than an equivalent length of pipe, Figure
4-21.
Structurally, a magnetic flowmeter consists of either a lined metal
tube, usually stainless steel because of its magnetic properties, or an
unlined nonmetallic tube. Linings for the metal tubes can be polytetrafluoroethylene (Teflon), polyurethane, or some other nonmagnetic,
nonconducting material.
The electrodes are suitably insulated from the metal tube. Nonmetallic fiberglass flow tubes do llot require any lining. The electrodes
most be insulated so that the voltage generated can be measured across
the electrodes. The insulation has no bearing on the actual voltage
generation, bot without the insulator, voltage would bleed off through
the metallic walls of the tube.
The coils are similar in design to the deflection coils used on a
television picture tube. Two coils are used and work together to create
a uniform magnetic field. The coils are generally series-connected, but
mar be parallel-connected if the measured flow velocity is low.
The signal output from the flow tube's electrodes is an altemating
voltage at supply frequency. This 10w-Ievel voltage is generally between 1 mV and 30 mV at full flow rate.
This 10w-Ievel altemating voltage must be measured and converted
either into a record or display or into a dc common denominator transmission signal. This signal, typically 4 mA at zero and 20 mA at full
scale, can be fed into a recorder or controller. The device that can
accomplish tros is a special type of transmitter. This transmitter is
located either directly on the flow tube (Figure 4-22), near it, or within
the control room. The preferred location is as near to the flow tube as
possible; temperature and corrosive conditions are the constraints that
dictate location. In some applications a digital or pulse rate signal output Cromthe transmitter mar be required, and this option is available.
Accuracy
The accuracy of most magnetic ftowmeter systems is 1 percent of fullscale measurement. This includes the accuracy of both the meter itself
and its secondary instrument. Because ibis type of meter is inherently
linear, its accuracy at low-ftow rates exceeds the practical accuracy of
such inferential devices as the Venturi tube. Accuracy of the Venturi is
:tO.75 percent, according to ASME Fluid Meters Report, and thai of
the secondary instrument is abolli :tO.5 percent. At the low end ofthe
measurement scale, secondary instrument readability decreases owing
to the square root relationship. The magnetic ftowmeter can be labora-
rate. Differential pressure changes occur as the vortices are formed and
shed. This pressure variation is used to actuate the sealed sensor at a
frequency proportional to vortex shedding.
Thus, a train of vortices generates an altemating voltage output
with a frequency identical to the frequency of vortex shedding. This
frequency is proportional to the flow velocity.
The voltage signal from the detector (Figure 4-25) is conditioned
and amplified for transmission by electronics located in a housing
mounted integral with the flowmeter body. The final output signal is
available either in pulse fonn with each pulse representing a discrete
quantity of fluid for totalizing or, optionally, as a 4 to 20 mA dc analog
signat for flow rate recording or control.
Turbine
Flowmeter
The turbine meler derives its name from its operating principie. A
turbine wheel (rotor) is set in the path ofthe flowing fluid. As the fluid
enters the open volume between the blades of the rotor, it is deflected
by the angle of the blades and imparts a force causing the rotor to turo.
The speed at which the rotor turos is related, over a specified range,
linearly to flow rate.
Several methods are employed to transmit this motion to a readout
device outside ofthe conduit. In some applications a mechanical device
convers the rotor motion directly to a register. In process applications,
however, the usual method is to use an electrical method. A coil containing a permanent magnet is mounted on the meter body. The turbine
flowmeter (Figure 4-26) consists of a section of metal pipe, a multibladed rotor mounted in the center ofthe straight-through passage,and a
magnetic pickup coil mounted outside the fluid passage. A shaft held in
place by fixed radian vanes supports the rotor assembly. As each blade
tip of the rotor passesthe coil it changesthe flux and produces a pulse.
The total number of pulses indicates the volum e of fluid which has
passed through the meter and the rate of the pulses generated becomes
a measure of flow rate.
Turbine flowmeters are frequently employed as sensors for inline
blending systems.
Turbine flowmeters bave excellent accuracy and good rangeability.
They are limited to clean fluids. They are expensive, but do bave
unique features.
Other Flowmeters
Conclusion
Questions
4-1. Match the head meter primary devices with the application (select asingle
rest answer for each):
Orifice plate ~
r.I. T-.
Hgh-pressure~~~._~recovery
Flow nozzle Venturi tube Pitot tube-
Elbow taps-e.
-c.
b. Air ducts
Sedimentin lquid
d. Economyand accuracyare
important
No straightrun available
4-6. A 2-inch schedule 40 line {lD = 2.067) is used to carry gasoline (SP
GR = 0.75). The ftow rate is measured with an orifice plate (d = 1.034)and
pipe taps are used. At full ftow rate a ditIerential pressure of 50 inches of
water is produced. What is the approximate full ftow rate in gpm?
8. 30 gpm
c. 250 gpm
b. 53 gpm
d. 36 gpm
4-7. Assume an 8-inch schedule 160 pipe (ID = 6.813 inches) carries a full
ftow of 40,000pounds per botir of dry saturated steam. The static pressure is
335 psi. Flange taps are used and the ditIerential pressure across the orifice
plate at full-ftow rate is 1OOinches of water. What is the size of the bare in the
orifice plate?
8. 4.357 inches
c. 2.271 inches
b. 3.645 inches
d. 5.109 inches
4-8. Fuel gas is carried in a 6-inch schedule 40 pipe (ID= 6.065 inches).
Flow rate is measured with an orifice plate using fiange taps and the bare in
the orifice is 3.457 inches. The specific gravity is 0.88, the fiowing temperatur~
is 60F, and the static pressure is 25 psi. Maximum fiow rate creates a
ditIerential of 20 inches of water. What is the approximate fiow rate in
cubic feet per day?
8. 1,500,000SCFD
c. 2,500,000SCFD
b. 2,000,000SCFD
d. 3,000,000SCFD
4-9.
8.
b.
c.
4-10.
8.
b.
c.
d.
4.11. With suspended solids and/or entrapped gas in a fiowing liquid, the
magnetic fiowmeter will:
8. Read high
b. Read low
c. Read the liquid fiow only
d. Read the correct total volume of the mixture
4-12. A turbine fiowmeter produces an output in the form of pulses. The total
number of pulses is:
8. Inversely proportional to fiow
b. Directly proportional to total ftow
c. Proportional to the square root of fiow
d. Proportional to the square of fiow
Temperature
Thermistors
Bimetallic devices
Optical and radiation pyrometers
Temperature-sensitive profitS
Various types of measurement control systems are compared in Table
5-1.
Instrument selection must anticipate overall control requirements.
Low cost often justifies consideration of filled systems for measurements below 1,200oPor 650C. Other advantages of mechanically or
pneumatically transmitted temperature measurements include lowexplosion hazard, simple maintenance requirements, high reliability,
and independence Crom external power. Advantages of electrical systems include higher accuracy and sensitivity, practicality of switching
or scanning several measurement points, larger distances possible between measuring elements and controllers, replacement of components
Table5.1. Comparisonof TemperatureMeasuringSystems
ComparisonFactors
Purchase cost
Long distance transmission
Change or replacement
o components
lnstallation costs
Maintenance
Averaging measurement
Surface measurement
Time constant
(bare bulb and no well)
Temperature difference
Sensitivity
Accuracy
Operating costs
Least
Favorable
Most
Favorable
lntermediate
F
E
p
p
EandP
F
P
T
T
F
P
E
Bo
F
F
R
T
R
E
R
F
F
F
P
F
E
F
R
T
F
P and T
P
Filled Thermal
Systems
MEASUREMENTS
129
Type
Principie
SAMA Class
Liquid
Volumechange
fluids
Lower range limit
Upper range limit
Organic liquido
(Hydro-carbons)
-200"F (- I3IY'C)
+6OO"F(+315C)
40F (25C)
600'F (33IY'C)
Ambient temperature
lA Full
Not required
Compensation
Sensor size
IB Case
Smallest
Medium
Largest
Overrange capabiJity
Sensor elevation elfect
Medium
Least
None
Greatest
None
Barometric pressure
effect (altitude)
None
Slightly (greatest on
smaIl spans)
Scale uniformity
Unifonn
"'.5 to "'1.0% ofopan
Non-Uniform
Uniform
;:0.5to;:I.0%ofspan
upper % of scaIe
;:O.5to;:I.0%of
spon
#1-ClasslIA
#2
Accuracy
Response (d)
#1 Fastest
Vapor (a)
Pressure change
11
Pressure change
III
arganic liquido
Puregases
(Hydro-carbons),
water
-425F
(-2SS"C)
+6OO'F (+3IS0C)
400'F (215C)
-45SOF (-2700C)
+l,4OO'F(+7ro'C)
1200F(700C)
1.000'F (5500C)
IIIB case
#3-Class
Slightly (greatest o
small spans)
lIB
#4 Slowest
Cost
Maximum
CapiIlary
standard
length
Highe.1
Lowest
Medium
30m or 100I
(a) Class 11 systems are supplied as either SAMA Class llA or lIB. In Class llA, sensor is aIways
hotter than tubing or instrument case. In Class lIB, sensor is always cooler than tubing or case.
(b) Narrowest spans vary at elevated temperatures.
(c) Smaller spans available in cryogenic regions.
(d) Actual values depend on range, capillary length, sensor dimensions, and type of instrument used.
Electrical
Systems
MEASUREMENTS
131
Calibration
r -F
oc
RTDs
Nickel
Platinum
SAMA Type 11
SAMA 100 ohm, or
-200 to 315
-320
DIN 43760
-200 to
O to
-210 to
-270 to
-270 to
-270 to
-50 to
-320 to 1,200
32 to 300
Copper
SAMA
Thermocouples Iron-Constantan, ISA Type J
Copper-Constantan, ISA Type T
Chromel-Alumel, ISA Type K
Chromel-Constantan, ISA Type E
Platinum-Platinum Rhodium,
ISA Types R & S
ISA Type B
650
150
760
370
1,260
870
1,480
o to 1,700
to 600
-350
-455
-455
-455
-55
to
to
to
to
to
1,400
700
2,000
1,600
2,700
o to 3,100
<
MEASURING
JUNCTION
THERMOCOUPLE
[JINSTRUMENT
REFERENCE
JUNCTION
percent.
Introduction of intermediate metals into a thermocouple circuit will
Dot affect the emf of the circuit, provided the new junctions remain at
the same temperature as the originaljunction. The algebraic sum ofthe
emf' s in a circuit consisting of any number of dissimilar metals is zero,
if all of the circuit is at a uniform temperature. Repeating the law, if in
any circuit of solid conductors the temperature is uniform from Point 1
through all the conducting material to Point 2, the algebraic sum ofthe
emf' s in the entire circuit is totally independent of the intermediate
material and is the same as if Points 1 and 2 were put in contact. If the
individual metals betweenjunctions ofthe circuit are homogeneous,the
sum ofthe thermal emf's will be zero, provided only that thejunctions
of the metals are all at the same temperature.
The emf in a thermoelectric circuit is independent of the method
employed in forming the functions as long as all the junction is at a
uniform temperature and the two wires make good electrical contact.
The junction mar be made directly, by welding, or by soldering. Furthermore, an instrument for measuring the emf mar be introduced into
a circuit at any point without altering the resultant emf, provided the
junctions that are added to the circuit by introducing the instrument are
all at the same temperature. If the temperatures of the new junctions
are DOt uniform, the effect is that of introducing additional thermocouples into the circuit.
Reference Junction
To make accurate temperature measurements with thermocouples, the
reference junction temperature must remain constant; if it varies, suitable compensation for these variations must be provided.
Should there be an uncompensated variation in the reference junction temperature, there will be a corresponding change in the millivoltage with a resultant error in temperature measurement (Table 5-4).
When used in the laboratory and for other checking and testing
purposes, the thermocouple reference junction can be placed in a vacuum bottle filled with shaved ice saturated with water. This method
provides close temperature control (within a fraction of a degree) and
permits accurate reading.
Table5-4. StandardLimits or Error
Coupleor Wire
Range
Limits
Copper-constantan
-300 to -75F
-75 to +2000F
200 to 700F
-100 to + 530"F
:t2% oCreading
:tl~oF:t~
% oCreading
:t4F
Chromel-alumel
530 to l ,400"F
Oto 530F
530 to 2,300"F
:t~% oCreading
:t4F
Platinumrhodiumplatinum
Oto 1,000F
1,000to 2,700"F
Iron-constantan
:t~% oCreading
:tJoF
:tO.J% oCreading
75
KX
~~ WIRE~[]
THERMOCOUPLE
MEASURING
JUNCTION
EXTENSION
<
INSTRUMENT
CONNECTION
HEAD
REFERENCE
JUNCTION
it.
An industrial installation generally consists of a thermocouple with
its connection head, the necessary length of extension wire, and an
indicating, recording, or controlling instrument with internal and automatic reference junction compensation. The extension wires generally
consist of the same materials as the thermocouple elements, or mar be
composed of other materials and alloy wires that generate essentially
the same millivoltage as the thermocouple for application temperatures
up to approximately 400F or 200C(Figure 5-4). The ISA symbols and
color codes for thermocouple lead wires are given in Table 5-5.
Table 5.5. Extension Wire Type Designations and Standard Limits of Error
[SA
Extension
Type
Wire
Color
Code
TX
Copperconstantan
Ironconstantan
Ironcupronel
Chromelalumel
CopperCuNi alloy
+ (blue)
-(red)
+ (white)
-(red)
+ (green)
-(red)
+ (yellow)
-(red)
+ (black)
-(red)
JX
wx
sx
Limits 01
TemperatureRange
F
Error
-75 to +200
:t 1~F
Oto
400
:t4 F
75 to
400
:6 F
to
400
:t4 F
75 to
400
:10 F
Couple
UsedWith
Copperconstantan
Ironconstantan
Chromelalumel
Chromelalumel
Platinum
Rhodiumplatinum
Fig.
<
MEASUREMENTS
135
A verage Temperatures
To measure the average temperature across a large duct or vessel, or
around a retort, any number of thermocouples mar be used in parallel
connections. The voltage at the instrument, or at the point of parallel
connection, is the average of that developed by the number of thermocouples used. This voltage is equal to the sum of the individual
voltages divided by the number of thermocouples. For accurate measurement, the resistances of aU thermocouples and extension wire
circuits should be identical. Since the resistance of the actual thermocouple wiU vary with temperature, and since the lengths of extension wires mar also vary, the efIect of these variations can be minimized by using swamping resistors. The values of the swamping
resistors should be high in comparison with the change or difIerence in
resistances encountered. A resistor value of 1,500 ohms generaUy
works weU.
In order to prevent the flow of current through a ground loop, the
thermocouples should not be grounded. AU thermocouples must be of
the same type and must be connected by the correct extension wires
(Figures 5-5 and 5-6).
ParaUel connection of thermocouples for average temperature
measurement is advantageous because the instrument construction and
<
PotentiometricRecorder
Figure 5-8 shows a simplified circuit diagram of the Foxboro potentiometric recorder (Figure 5-9). An emf input (Ex) is derived Croma
thermocouple or other measuring element. A constant emf (Ez) is
supplied by a Zener diode regulated power supply. As Ex varies, an
error signal is developed, and the circuit becomes unbalanced.
The error signal is converted to an ac voltage by a field effect
transistor chopper and amplified by the integrated circuit amplifier. The
amplified output drives a two-phase balancing motor. The direction of
rotation depends on whether Ex has become greater or smaller. The
motor moves the wiper contact on the slidewire Rsto a position where
the circuit is rebalanced. The slidewire coritact is mechanically con-nected
to the recorder pen, and both are positioned simultaneously.
With a thermocouple input, a temperature sensitive resistor (Rc)
automatically compensates for referenc junction ambient temperature
variations. This resistor changes the balance of the circuit to cancel
TEMPERATURE,
AND HUMIDITY MEASUREMENTS 139
Detectors
Resistancethermometry is based on the change of electrical conductivitv with temperature.Therefore.a coil of wire can act as a tem-
perature sensor, with 'a direct relationship established between resistance and temperature. Standard curves are available, with certified
accuracies within O.IF or oC. Platinum RTDs used as laboratory standards can be obtained with tolerances well within this lmit, and are
capable of precise temperature measurement up to l,650F or 900C. If
an RTD is adjusted to conform to its curve, it may be interchanged with
other RTDs calibrated according to the same curve.
Fig. 5-12. Simplified circuit diagram of 34B Series nickel RTD transmitter.
the appropriate nickel bulb, the converter has an output that is linear
with temperature. Spans as low as 5F or 3C can easily be achieved.
An adjustable range allows a simple field calibration procedure to
change the temperature input range required for a 3 to 15 psi or 20 to
100kPa output. It also operates on all normal supply voltages.
This transmitter is an electromechanical device consisting of a
solid-state, integrated circuit amplifier and an output transducer. Figure 5-12 isa simplified circuit diagram of the nickel RTD version of the
transmitter. The transd ucer is shown in Figure 5-13.
The RTD is wired into a measurement bridge and excited Croma
regulated direct current power supply. The change in resistance of the
RTD causes a bridge output change that is proportional to temperature.
Negative feedback is obtained Cromthe output current and applied to
the opposite side of the measurement bridge. A change in feedback by
the span adjustment changes the gain of the amplifier and thereby
changes the span of measurement.
MEASUREMENTS
143
changes. This unbalances the bridge and creates an error signal between Points A and B.
As in the potentiometric recorder, the error signal is converted to
art ac voltage by a field-effect transistor chopper and amplified by the
transistorized amplifier. The output drives a two-phase balancing
motor. The direction of rotation depends on the polarity of the error
signal. The motor moves the wiper contact on the slidewire until the
bridge is rebalanced and no error signal exists. The pen and slidewire
contact are mechanically connected and therefore positioned simultaneously.
With all resistance-temperature measurements, the use of threeconductor RTD cable is recommended. The effect of ambient temperatufe variations on the cable is thereby minimized.
If the cable connecting the RTD to the instrument has only two
conductors, these conductors become part of the resistance being measured. The result then is an error that will vary with ambient temperature. Remember, with all resistance temperature measurements,
three-conductor RTD cable is recommended. The purpose of the threeconductor cable is to stretch out the measuring bridge. Note the threeconductor cable in Figure 5-14. One of the conductors is common to
both sides ofthe bridge while the other two connect one to each side of
the bridge. Any change in cable temperature will be canceled as both
sides of the bridge are changed a like amount.
Occasionally RTD sensors use a four-wire cable. This is generally
in conjunction with a Kelvin double bridge. The four-wire method does
an excellent job of reducing temperature effects on the cable. The
improve ment over the three-wire method, however, is minimal. In
practice, an RTD may be used with as much as 500 feet of threeconductor cable without the cable creating a perceptible error.
Thermistors
Thermistors are made of heat-treated metallic oxides, and most thermistors differ from ordinary resistors by having a negative coefficient of
resistance. Thermistors are available with a nearly linear temperature
resistance relationship, and other types are available with a sharp
change in slope at some characteristic temperature.
A thermistor can replace an RTD as a temperature sensor. The
difficulty lies in obtaining units that fit the desired characteristic curve
within acceptable lmits of accuracy. When this is accomplished and
the thermistor is mounted so as to stand up under process conditions, it
performs the same function as the conventional RTD.
One advantage of the thermistor is that it has a greater resistance
change for a given temperature change than that of the conventional
wire RTD. A disadvantage is that the accuracy available, although
good, is slightly inferior to that of the conventional RTD. This presumably accounts for the thermistor's limited application in the process
instrumentationfield.
Radiation pyrometers utilize an optical system to focus energy
radiat~d from a body onto a sensing system. Manual devices are often
l:I~ed;'in which energy at infrared or visible wavelengths is focused on a
tar~t'aridcompared
with the light output of a calibrated optical filamentJ9automated devices, the energy (usually in the infrared band) is
focusedori a series arcar ofthermocouples. This thermopile produces a
millivolt output related to the temperature of the source. Pyrometers
are used where high temperatures are to be measured or where contact
with the object is impossible. Accuracy is influenced by such factors as
reflections, gases present in the radiation path, and surface emissivity
of the body under measurement.
Humidity
Measurements
'-+'2.
"0
MEASUREMENTS
147
.'0
.]
.."
I
l
,
1001
t,
,
,
..
E
~
~
2 00"
~
~
C
E
~~
'
;l
.,~f-.#"
I I
2
C
f-
.fH-~
1--
--'
"- -17' I
--/
-fi
-:eo
-40
-00
00
OEW POINT
40
10
TEMPERATURE
80
100
100
140
.F.
tor.
Moisture determination by this lithium chloride element is based on
the fact that, for every water vapor pressure in contact with a saturated
salt solution, there is an equilibrium temperature at which this solution
neither absorbs noc yields moisture to the surrounding atmosphere.
This equilibrium temperature is shown in Figure 5-16 as the "DEW-
Questions
MEASUREMENTS
149
5-14. A psychrometeris:
a. A hair elementinstrument
b. A "wet and dry bulb" humidity instrument
c. An instrumentthat sensespsychologicaldisturbances
d. An instrumentthat readsdirectly in dew point
5-15. A hygrometeris:
a. Convenientfor measuringspecificgravity
b. An instrumentthat measuresgas weight
c. Any instrumentthat measuresmoisturecontent
d. Anothernamefor psychrometer
5-16. A certainthermocouplehasa specifiedtime constantof 2 seconds.If
the processtemperaturechangesabruptly from 800to 900C,the temperature
readouton the indicatorattachedto the thermocouplearter6 secondselapse
will be approximately:
a. 860C
c. 900C
b.835C
d. 895C
5-17. The air velocity pastthe sensorsof a "wet and dry" bulb instrument
shouldbe:
a. 50 feet per second,minimum
b. 2 metresper second,maximum
c. Approximately4.6 metresper second
d. Any value
5-18. The advantageof usinga three-wirecableto connectan RTD to its
associatedinstrumentis that:
a. Referencejunction errors are eliminated
b. The effectof ambienttemperatureon the cablewill be minimized
c. Potentialfailures will be minimal
d. Resistancein the externalcircuit is reduced
5-19. A thermocoupleinstrumenthas an input resistanceof 50,000ohmsand
is usedwith an IC Type J couple.The leadwire is #18 gauge,120feet long.
What is the approximateerror contributedby the leadwire?
a. :t5.0 percent
c. :t0.05 percent
b. :t0.5 percent
d. :tO.1 percent
5-20. The differencebetweenanRTD calibratedto the NR 226curve and one
calibratedto the NR 227curve is:
a. A differentresistance-to-temperature
relationship
b. Nonexistent
c. Greateraccuracywith the NR 226curve
d. Greateraccuracywith the NR 227curve
Electrical
Conductivity
While dissociation into ions and the resulting iOD concentration bave
been adequate concepts in the past, the fact is that DOt all the ions
present are necessarily effective. Some ofthem mar be "complexed,"
151
that is, "tied up" to'other ions and unavailable for reation. The concept of activity covers this situation. In short, a given compound will
dissociate to some degree, described by the dissociation constant, into
ions, and some portion of these ions will be active, described by the
activity coefficient. However, in many common reactions, the activity
coefficient is so near unity that concentration and activity mar be used
interchangeably. In a growing number of processes, the actual ion activity is different enough Cromthe ion concentration to make it necessary to use the proper term. In general, electrochemical measurements
measure activity rather than concentration, and it is always desirable to
refer to the measurements as ion activity rather than ion concentration.
Electrochemical measurements all rely upon the current-carrying
property of solutions containing ions. Some techniques measure all ions
present (electrolytic conductivity). Others respond mainly to particular
types of ions-hydrogen ions (pH); oxidizing/reducing ions (ORP); selected ions (ion-selective). These will be discussed separately below.
The ability to conduct electricity, or the reciprocal of electrical
resistance, is called conductance.The unit in which it is measured is the
reciprocal ohm, commonly called mho. The conductance of any conductor depends on the nature of the material, the shape of the conducting path, and the temperature. In analytical work, only the nature ofthe
material, in this case the type and activity of the ions present, is important. Thus, the term conductivity, the conductance of a volume of the
material of unit length and area, is generally used. (Conductivity has
largely replaced an earlier term, specific conductance.)
In actual measurement, a conductivity cell of known geometry is
immersed in the material, and the resistance (or conductance) across
the cell is measured. This gives a measurement that can be calibrated
directly in conductivity due to the known shape of the cell. Conductance and conductivity are related as follows: the greater the length
of a material of given conductivity, the higher its resistance (the lower
the tonductance); but the greater the aTeaofthe material, the lower the
resistante (the greater the conductance). That is,
aTea
conductance= conductivity iength
(6-1)
centimeters
squarecentimeters
(6-2)
or,
conductivity = mho. cm-1
It is unfortunately common practice to omit the dimensional unit,
so that conductivity is then referred to as mhos. This practice leads to
confusion with conductance, and should be avoided.
The conductivity of most electrolytes at the concentrations and the
temperature ranges normally encountered fall well below unity. For
this reason, the micromho per centmetre, the millionth part of the mho
per centmetre, is normally used.
In the SI system of units, the siemens replaces the mho. One mho
equals one siemens. In conductivity units, one micro mho per centimetre (J.mho/cm)equals one microsiemen per centmetre (J.S/cm).
However, the actual SI unit is the microsiemens per metre, since the
unit of length in the SI system is the metre rather than the centmetre.
One J.S/cmequals 100 J.S/m.
The conductivity of material of unit length and area which has a
resistance of 1,000ohms is 0.001 mho. cm-Ior 1,000micromho .cm-1
(sometimes called simply 1,000 micromhos).
Since the measurement depends on the geometry ofthe cell used, a
cell constant (F) has been defined to describe this geometry simply:
F = length (cm)
aTea(cm2)
(6.3)
(6-4)
Types
ot Calibration
in Conductivity
156
FEEDBACK PROCESSCONTROl
The sensitive portion of the cells shown i~ Figure 6-3 consists of two
platinum electrodes mounted in an H-shaped structure of Pyrex glass
tubing. The electrodes, located in separate sections of the tubing, are
concentrically mounted platinum rings and are ftush with the inside
surface of the tubing. Fouling or damaging the electrodes is thus minimized, and the cells mar easily be cleaned chemically or with a bottle
brush. The platinum electrodes in these cells are coated with platinum
black to minimize polarization etfects.
The cell shown in Figure 6-4 employs graphite, rathr than metallic
electrodes. The type of graphite used has the same surface properties
with respect to polarization as metallic electrodes. These
cells require no platinization. They are cleaned chemically or by wiping
the surface of the electrode with a cloth or brush.
Conductivity cells (Figure 6-5) are used for detecting impurities in
boiler feedwater, for concentration of black liquor (in a pulp digester
for kraft paper), for determination of washing etfectiveness by measurement ofpulp wash, and in many other applications where the presence and concentration of a known salt, base, or acid must be deter-
mined.
Electrodeless
Conductivity
Measurements
~
~
~.
~
Hydrogen
The
term
pH
solution.
of
It
an
means
is,
at
vary
from
any
in
is
tion
of
the
pH
the
to
hydrogen
degree
amo
unt
ofthat
percent).
of
of
ion.
The
potentiometric
ions
acidity
a
(H+)
or
given
Activity
in
alkalinity
ion
actually
values
measurement
can
ofpH,
measurement
that
as
obeys
explanatech-
to
with
ofthe
of
This
an
measurement
along
activity
activity
1 (100
is
equation.
employed
the
effective
called
chapter,
contains
nique
The
percent)
this
of
a measure
time
Nemst
chapter
a measure
solution.
O (O
discussed
(pH)
therefore,
aqueous
present
the
lon Activity
determine
the
Nemst
equation.
To
aid
further
in
understanding
surement,
of
the
properties
some
a thorough
of
pH
meafundamentals
of
aqueous
,---TOROIO
SECONOARY
!'RI MARY
TOROIO
CELL BORE
~~,
solutions
most
be
understood.
CELL
lonization
or Dissociation
;\)'
.1
:;\
\"'
~
!~~
"",,' -'
ELECTRIC ./
"~~~~
ticles. These charged particles are called ions. Ions travel from one
electrode to the other if a voltage is impressed across electrodes
immersed in the solution.
Positive ions, such as H+, Na+, and so on migrate toward the
cathode, or negative terminal, when a voltage is impressed across the
electrodes. Similarly, negative ions, such as OH-, CI-, S04-2, and so
on, migrate toward the anode, or positive terminal.
The freedom of ions to migrate through a solution is measured as
the electrical conductivity of the solution. Chemical compounds that
produce conducting solutions are called electrolytes. Not all electrolytes completely dissociate into ions. Those that do (strong acids,
strong bases, and salts) are strong electrolytes. Others dissociate, but
produce fewer than one ion for every element or radical in the molecule. These are poor electrical conductors, and, hence, weak electrolytes. All weak acids and weak bases fall into this class.
At a specified temperature, a fixed relationship exists between the
activity of the ions and undissociated molecules. This relationship is
called the dissociation constant (or the ionization constant).
For hydrochloric acid (HCI), the dissociation constant is virtually
infinite, which means that for all practical purposes, the HCI is completely composed of positively charged hydrogen ions and negatively
charged chloride ions. Because of the essentially complete dissociation
into ions, hydrochloric acid is a strong acid:
HCl -+- H+ + Cl-
Sodium hydroxide is, for all practical purposes, completely dissociated and is a strong base.
Conversely, ammonium hydroxide, NH4OH, dissociates very little
into NH4+ ions and OH- ions, and is a weak base.
The OH- iODactivity, or strength, of a base depends on the number
of dissociated OH- ions in the solution. The w\mber available depends,
again, DOtonly on the concentration of the compound in water, but also
on the dissociation constant of the particular compound.
Pure water dissociates into H+ and OH- ions, but is very weak in
the senseused above. That is, very little ofthe HOH breaks up into H+
ions and OH- ions. The number of water molecules dissociated is so
small in comparison to those undissociated that the activity of (HOH)
can be considered 1 (100 percent).
HOH ~ H+ + OHAt 77F or 25C, the dissociation constant or water has been
determined to bave a value or 10-14. The product or the activities
(aH+)(aOH-) is then 10-14.
If the activities or hydrogen ions and hydroxyl ions are the same,
the solution is neutral; the H+ and OH- activities must both be 10-7
mols per litre.
It must be remembered that, no matter what compounds are present in an aqueous solution, the prJduct or the activities or the H+ ions
and the OH- ions is always 10-14at 77F or 25C.
If a strong acid, such as HC1, is added to water, many hydrogen
ions are added. This must reduce the number or hydroxyl ions. For
example, if HCl at 25C is added until the H+ activity becomes 10-2,the
OH- activity must become 10-12.
The pH Scale
(-::
aH
(6-5)
Table 6-1
Temperature oC
-Log
(aH+)(80H-)
14.94
14.00
13.26
12.69
12.26
25
50
75
100
Neutral pH
7.47
7.00
6.63
6.35
6.13
Activity
Mols/Litre
Hydroxyl Jan
Activity
Mols/Litre
10.1
0.00000000000001
1
2
0.01
0.001
0.0001
O.0000 1
0.000000001
0.000001
0.00000001
0.0000001
0.0000001
0.00000001
0.000001
pH
Neutral
9
10
11
12
13
14
0.0000000000001
0.000000001
0.0000000001
0.00000000001
0.000000000001
0.0000000000001
0.00000000000001
0.000000000001
0.0000000000I
0.0000000001
0.00001
0.0001
0.001
0.01
0.1
I
10
Therefore, the activity of hydrogen ions will be greater than 10-1, that
is, 10-6, 10-5,10-4. The pH of an acid solution then, by definition, must
be lower than 7, that is 6, 5, 4.
If the number of OH- exceeds H+ ions, the hydrogen iODactivity
must be less than 10-1, that is, lO-s, 10-9,10-1. Therefore, the pH will
be higher than 7, that is, 8, 9, 10.
Table 6-2 demonstrates that a change of just one pH unit means a
tenfold change in strength ofthe acid or base. The reason for this is that
there is an exponential relationship between pH numbers and hydrogen
iODactivity. With so large a change in acidity or alkalinity taking place
with a change ofjust one pH unit, the need for sensiti ve pH measuring
and control equipment cannot be overemphasized.
Table 6-3 shows the nominal pH values for a number of common
solutions.
Table 6-3
pH
14 ~ Caustic soda 4% (I.ON)
--Calcium hydroxide (sat'd sol.) (Iime)
12 --Caustic soda 0.04% (O.OIN)11
--Ammonia 1.7% (I.ON)
--Ammonia 0.017% (O.OIN)
9 +- Potassium acetate ~.98% (O.lN)
8 +- Sodium bicarbonate 0.84% (O.lN)
6
5 ~ Hydrocyanic acid 0.27% (O.lN)
3 ~ Acetic acid 0.6%
"'
1 +- Hydrochloric acid 0.37% (O.IN)
+- Sulfuric acid 4.9% (I.ON)
O +- Hydrochloric acid 3.7% (I.ON)
-1 +- Hydrochloric acid 37% (lON)
d
-~---~
)LASrIC
ot pH-The
Glass Electrode
(
r--y=
MOISTURE
SEAL
CAl
SILVERSILVER
CHLORIDE
COLUMN
SHIELDED
!LECTRODE
CABLE
GLASS-TO-METAL
SEAL
; "TOTAL GLASS" CONSTRUCTION)
NTERNAL
SOLUTION
,H-SENSITIVE
MEMBRANE
E'
lo
nF
aH+o~ts~de
aH+
mslde
(6-6)
where:
E = potential difference measured
Eo = a constant for a given electrode system at a specified temR =
T =
n =
F =
aH+ =
perature (25C)
the gas law constant
Absolute temperature
charge on iOD(+ 1)
Faraday's number, a constant
hydrogen iODactivity
Electrode
The potential inside the glass is the output o the measuring electrode.
It must be compared to the potential in the solution outside the giassto
determine potential difference and, hence, pH. The sensing o the potential in the solution must be independent o changes in solution composition. Platinum or carbon would act as aRP, or redox-measuring
electrodes. They would be responsive to oxidants or reductants in the
solution. They would Dot yield a true solution potential with solution
composition changes.
Plastlc
Body
Internal
Electrode
Element
AgAgCI
The major potential difference exists in the reference electrode, between the metallic silver and the silver ions in the AgCI solution. It
follows from the Nemst equation:
(6-7)
Because R, n, and F are constants, and aAgoand AAg+ are fixed,
this potential (E) will vary only with the absolute temperature of the
electrode. Since there is a definite chemical relationship between the
ionic silver and the activity of chloride in the KCl electrolyte, the above
expression mar also be written as:
E = Eo -kT
log aCl-
(6-8)
To compensate for ibis temperature sensitivity, another silversilver chloride electrode is inserted into the top of the glass measuring
electrode, the internal conductor element mentioned previously. As the
temperature of the electrode changes, the potentials of the reference
electrode and the conductor element will vary, but will effectively cancel each other, assuming similar values for aAg+ (or aCI-) in each electrode as is usually the case.
ot the pH Electrodes
The high resistance of the giass measuring electrode results in the need
for a millivolt meter with very high internal resistance or sensitivity to
measure the cell output. The pH electrodes mar be compared to a pair
of ftashlight cells in series, but unlike the ftashlight cell, the electrodes
Fig. 6-12. Graph oCpH measurement errors versus pH values at various solution
temperatures due to temperature differences across the measurementelectrode tip.
,;,
005
BASE
001
REAGENT
001
005
AtiO
OI
REAGENT
Fig. 6-15. Typical neutralization curves for unbuffered solutions (strong acid or strong
base) and buffered solutions. Examples of buffered solutions are (I) weak acid and its
sale with the addition of a strong base, and (2) strong acid or base, concentrated, 0.01
M.
Oxidation-Reduction
Potential
For example, a ferrous iODmar lose an electron and become a ferric iOD
(gaining increased positive charge) if a reduction, say, of stannic to
stannous ions (which is the reverse ofthis operation) occurs at the same
time.
This measurement uses electrodes similar to those in pH measurement (except that metal is used instead of glass), but the two types of
measurement should DOtbe confused. The measurement depends on
the oxidizing and reducing chemical properties of reactants (not necessarily oxygen). The inert metal electrode versus the reference electrode
will produce a voltage that is related to the ratio of oxidized to reduced
ions in solution.
This measurement is similar to that of pH in the requirements that
it places on the voltmeter used with it. It is useful for determinations in
waste treatment, bleach production, pulp and paper bleaching, and
others.
The application of ORP measurement or control depends on a
knowledge of what goes on within the particular process reaction. The
ORP measurement can be applied to a reaction only under the following
conditions:
1. There are present in the solution two reacting substances: one that
is being oxidized and one that is being reduced.
2. The speed of reaction, following an addition of one of the substances above, is sufficiently fast for good measurement or control.
3. Contaminating substances are held to a minimum, especially those
capable of causing gide reactions of oxidation or reduction.
4. The pH ofthe solution is controlled in those areas ofthe applicable
curve where variations in pH can affect the ORP measurement.
lon-Selective
Measurement
Certain applications require that the activity of a particular iODin solution be measured. This can be accomplisehd with an electrode designed
to be sensitive to the particular iODwhose concentration is being measured. These electrodes are similar in appearanceto those employed to
Chromatography
cable
Specificity
Sensitivity
Conducting
fluids
Nonconducting
fluids
Maintenance
InstalIation
problems
Cost
Capacitance
Conductivity
pH or
ion-selective
ORP
Poor
Pair
Not
applicable
Good
Poor
Good
Good
Excellent
Excellent
Good
Poor
Excellent
Good
Not
Not
applil
appIiI
Low
Low
Low
Low
High
High
Not
applicable
Medium
Low
Low
Low
Medium
Low
Capacitance
Capacitance is Dot, as applied, an electrochemical measurement. However, a measurement of some characteristic in a nonconducting liquid is
frequently required, and in these applications, capacitance mar provide
the answer.
Electrical capacitance exists between any two conductors separated by an insulator (dielectric). The amount of capacitance depends
on the physical dimensions of the conductors and the dielectric constant of the insulating material. The dielectric constant (K) for a vacllum is 1; all other dielectric materials bave a K greater than 1. For
example, for air, K = 1.00588; for dry paper, K = 2 to 3; for pure
water, K = 80. The Table of Dielectric Constants of Pure Liquids
(NBS Circular 514), available Crom the U.S. Govemment Printing
Office, lists the dielectric constants of nearly all common liquids.
Mixtures of materials bave a composite value of K that can be
directly related to composition. This approach is readily applied to the
determination of water content in materials such as paper and crude oil.
Capacitance is also applicable to level, interface, octane, and other
measurement problems.
In general, the capacitance technique has provided a solution to
many measurement problems that cannot be solved easily by more
conventional means. Table 6-4 compares the application of pH, ORP,
ion-selective, conductivity, and capacitance measurements to process
situations.
References
Conductivity cells. Technical Information Sheet 43-10a. Foxboro, MA., The
Foxboro Company.
Fluoride measuring systems-potable water. Technical Information Sheet
43-21a. Foxboro, MA., The Foxboro Company.
Fundamentals of pH measurement. Technical Infor~{ltion Sheet 1-90a.
Foxboro, MA., The Foxboro Company.
pH e1ectrodesand ho1ders. Technical Information Sheet43-11a. Foxboro,
MA., The Foxboro Company.
Theory and app1icationof oxidation-reduction potentials. Technical
Information Sheet 1-61a. Foxboro, MA., The Foxboro Company.
Pneumatic composition transmitter. Technical Information Sheet 37-1.30a.
Foxboro, MA., The Foxboro Company.
Liptk, B. G. Instrument Engineer's Handbook, Sec. 81, Volume I. Radnor,
PA: Chilton.
Shinskey, F. G. pH and pION Control in Process and Waste Streams.
New York: John E. Wiley and Sons, 1973.
Questions
6-3. pH is a measureor:
a. Effective acidity or alkalinity of a liquid
b. The oxidationor reductionpropertiesof a solution
c. Specificconductanceof an electrolyteor total ionic activity
d. Purity in an aqueoussolution
6.4.
a.
b.
c.
d.
8.
b.
c.
d.
6-6. Capacitancemeasurements
are usuallyappliedto:
8. Conductingliquids
c. Gasmeasurements
b. Nonconductingliquids
d. lonized gases
6.7.
8.
b.
c.
d.
8. A ftowingtype
b. A pressurizedftowing type
c. A nonftowingtype
d. A pressurizednonftowing
type
6-14. The pH of 8 streamis to be monitoredaccurately.It is discoveredthat
the temperatureof this streamvariesfrom 40 to 60F:
8. A measuringsystemwith automatictemperaturecompensation
is
indicated
b. Temperaturecompensationis not necessary
c. A manualtemperaturecompensationwill be adequate
d. The pH rangewill determinethe needfor temperaturecompensation
6-15. The most popularcarriergasusedin gaschromatographs
is:
8. Helium
c. Hydrogen
b. Air
d. Oxygen
SECTION
II PNEUMATIC
AND ELECTRONIC
CONTROL
SYSTEMS
e~r
e=r-c
Fig. 7-1. Algebraic summing point.
and resistance. These factors cause phase changes that will be described in this chapter.
Gain appears in two forms-static and dynamic. Gain is a number
that equals the change in a unit's output divided by the change in input
which caused il.
Gain = AAoutput
input
The static gain of an amplifier is easily computed if, for a given step
change in input, the resulting change in output can be monitored. Case
A in Figure 7-3 shows an amplifier with a static gain of one. In Case B,
the output is magnified when compared with the input by a factor
greater than one. In Case C, the output change is less than the input.
Rere, the input has been multiplied by a number less than one.
The dynamic gain of an amplifier mar be computed by inducing a
giDewave on the input and observing the resulting output. Figure 7-4
illustrates this procedure with an amplifier that has no time lag between
its input and output. If the amplitude of the output is only hali as high as
Case
20%
5%
10% [ 10%
Output change
10%
10%
Static gain
!Q=1
10
22
10=2
Inputchange
1.--1
10-2
the amplitude of the input giDe wave, the amplifier is said to bave a
dynamic gain of 0.5 for the particular frequency of the input wave, for
example, 1 Hz.
By monitoring the output amplitude for many different input frequencies, a series of dynamic gain numbers mar be found. A plot of the
amplitude ratio (gain) as a function of frequency of the input giDewave
is the gain portion of a Bode diagram, or a frequency-response curve
(Figure 7-4). Note that the higher the frequency, the lower the gain.
)(
This is true for nearly all processes and instruments. The frequency
scale is normally a logarithmic scale. Gain or amplitude ratio is also
normally expressed in decibels, where l decibel equals 20 times the
logarithm to the base 10 of the amplitude ratio.
As the frequency becomes lower and lower, and finally approaches
zero, a measure of the amplifier's static gain can be obtained.
Just as the static or dynamic gain of an individual amplifier can be
computed, so can the static or dynamic gain of a process controlloop.
Figure 7-5 shows a temperature controlloop. The static loop gain has
been computed by multiplying the static gains of each of the individual
components of the loop. Likewise, the dynamic loop gain could be
calculated by multiplying the dynamic gains of each element at a particular frequency. Pure dead time has a gain of 1.
Each element in the controlloop contributes gain to the totalloop.
Increasing the size of a control valve or narrowing the span of a transmitter has exactly the same effect as increasing the gain of a controller.
)(
PS! ,
PS!
)(
mches
)( ~
Btu
The
Control
System
RC Networks
Figure 7-7 illustrates the phase shifts that occur when a sine wave is
applied to a network ofresistances and capacitances. Each succeeding
RC combination contributes its own phase shift and attenuation. In
Figure 7-7, bottom, a phase shift of 180degrees (a full half cycle) takes
place. That is, the output (eRa)is 180degrees out of phase with the input
(e applied). The signal has also been attenuated because each resistor
causes a loss in the energy level in the system. This phase change can
lead to instability in a closed-loop system.
Oscillation
In a physical system employing feedback, instability will occur if
energy is fed back in such direction (phase) as to sustain the instability
or oscillation.
Oscillators are often divided into two major categories, those thai
utilize a resonant device and those thai do noto The resonant oscillator
uses a device thai requires a minimum of added energy each cycle to
maintain oscillation. On the other hand, the nonresonant oscillator is
simply an amplifier with some type of phase-shifting network between
output and input. A public address system with the gain so high thai it
howls is a nonresonating type.
I
-"
I
SIMPLIFIEO PHASE SHIFTER
Fig. 7-7. Phase ofsigna! acrossR, R2' andRa is different. At one frequency, the output
signa! can be exact!y 180degrees out of phase with the input signa!, as shown in the
graph.
Academically, both the resonant and nonresonant oscillators follow the same mathematicallaw, but the amplifier gain requirements are
quite different for the two categories. With a nonresonant circuit, oscillation will occur (1) if the feedback is positive (inphase) and (2) if the
gain is unity or greater. These two conditions are necessary for sustained oscillation.
Figure 7-8 shows a simple mechanical oscillator. ln ibis system,
energy stored in the spring is transferred to the weight, back to the
spring, to the weight again, and so on. The oscillations soon die Dut
because some ofthe energy is dissipated in each cycle. lfthe oscillation
is to be continuous, energy musi be added to make up the losses.
ln the bottom part ofthe figure, ibis energy is added by depressing
and releasing the weight. If the energy is to enforce the oscillation, it
musi be in the proper phase with the motion. That is, enforcing energy
musi be added at a time when both the energy and the oscillation are
moving in the same direction.
Figure 7-9 shows a free-running oscillator in which the required
energy is introduced through feedback. This circuit is called a phase
shift oscillator. lt consists of a transistor amplifier and a feedback path
comprised of three resistance-capacitance combinations. This circuit is
important because it is a simple illustration of the manner in which an
ordinary amplifier can be made to oscillate simply by use of feedback.
l@~
Fig. 7-8. At top, the magson the spring received a single downward displacement and
the oscillation is delayed. Below, arter the initial displacement, the magsreceives
periodic small displacements and the oscillation is continuous.
11
186
The transistor amplifier Dot only makes up for circuit losses, but
also contributes a phase shift of 180degrees; that is, the collector is 180
degrees out of phase with the base signal. EachRC element contributes
additional phase shift, depending on the values of the components and
the frequency involved. If each RC combination contribute s a phase
shift of 60 degrees, the three together will result in a 180-degreephase
shift. This, added to the 180-degreephase shift through the amplifier,
results in 360 degrees of phase shift. The feedback signal is now in
phase with the input signal. This inphase feedback produces continuous oscillation.
Since only one frequency will be shifted in phase exactly 360 degrees by the RC networks, the oscillator output is of this one fre-
quency.
The closed-loop control system (Figure 7-6) also has phase-shifting
networks, made up of all process and controller <:omponents,together
with an amplifier capable of contributing sufficient gain to overcome the
system's losses. This closed-loop system contains the same basic ingredients as the phase-shift oscillator. Each resistance-capacitance
combination will shift the phase of the energy flowing around the controlloop in the same manner as in Figure 7-9.
Oscillation (instability) will occur whenever (1) the phase relationships through the vario us resistance-capacitance combinations provide
feedback in proper phase, and (2) the system gain is unity, or greater at
the frequency at which the phase shift is 360 degrees.
Figure 7-10 illustrates a plot of system gain (output/input signalBode diagram) and output/input phase shift versus frequency for a
three-mode controller. The phase shift (expressed in degrees of lead or
o
~
'"o
~
Z
~
c
2
10
"
100
1000
LOGARITHM FREOUENCY-~AOIANS PER SECONO
10000
Fig. 7-10. Bode diagram shows gain of system (top) and phase change (bottom) .at
various frequencies. The gain (output signal/input signal) and phase (output/input) are
measured with the system in open-loop operation.
lag) is plotted linearly against the logarithm of frequency. Note that the
integral is phase lagging and the derivative is phase leading.
The proportional adjustment in the controller adjusts its overall
gain and hence the loop gain. The integral adjustment governs the
low-frequency response, and the derivative adjustment governs the
high-frequency gain of the control mechanism.
In addition to controlling gain, these adjustments also affect the
phase shifts. Thus, an improper setting of any one of the three control
modes can cause the control system to satisfy the two criteria for
oscillation and become unstable,
Stability in the Closed-Loop System
Under normal operating conditions, the control system should produce
stable operation. That is, the controller should retum the system to set
point, in the event o an upset, with mnimum overshoot and oscilla-
tion.
Too much overall gain(too narrow a proportionalband)can cause
controlled.
A high-gain setting is desired because this gives the fastest and
most accurate control action. However, too much gain produces oscillation. The best compromise is to use enough gain to produce a damped
oscillation, as shown in the middle of Figure 7-11 (0.25 damping ratio).
Nonlinearities
Thus far it has been assumed that the capacitances and resistances
found in the process control loop bave a fixed value that does not
change with process conditions. This is not always true in practice.
Frequently, process conditions vary the value of the resistances and
capacitances involved and, as a result, the phase and gain relationships
are in constant transition Crom one value to another. At other times,
these values change, limiting or restricting the natural behavior of the
'-PERIOO~
GAI!
MEASURED DR
CDNTRDLLED
VARIABLE
(CLDSED LODP
SYSTEM)
GAIN',
system. Such changes are often considered as a group and are called
nonlinearities.
A thorough understanding of the operation of the linear system is a
prerequisite to an understanding of the nonlinear type. It is common
practice to assume a system is linear for the purpose of basic control,
and then deal with the nonlinear characteristics as problems anse.
Controllers
and Control
Modes
MEASURED
VARIA BLE
FINAL
OPERATOR
POSITION
riME'"
FINAL
OPERATOR
POSIT/ON
MEASURED
VARIABLE
TIME -+
the measured variable exceeds the upper boundary of the gap, the final
operator is closed and remains closed until the measured variable drops
below the lower boundary. It now opens and remains open until the
measured variable again exceeds the upper boundary. In a process
plant, differential-gap control might be used for controlling noncritical
levels or temperatures.
A time-cycle controller is normally set up so thai when the measured variable equals the desired control point, the final operator will
be open for hal the time cycle, and closed the other hal. As the
measured variable drops below the control point, the final operator will
remain open longer than it is closed.
Two-position control is nearly always the simplest and least expensive form of automatic control. Any of the forms discussed can be
implemented with commercially available mechanical, pneumatic, or
electronic instrumentation. On the other hand, two-position control
mar Dot meet the requirements often demanded by today's sophisticated processes. Now let us investigate a typical on/otI controlloop.
Assume we bave a liquid-Ievel process as shown in Figure 7-13.
Throttling
Control
(7-1)
where:
m = controller output or valve position
Error = difference between set (r) and measurement (c)
or
e=r-c
(7-2)
v=
xH=
TlIne
" to nse
.118.4gal.
= 30
gpm = 30 gpm
gpm
=.
395
mm.
Tirne to fall =
-118.4 gal.
= 1.973min.
-60 gpm
3c. Total tirne = (3.95 + 1.973)min. = 5.92 min.
Solution to no. 2:
3.lD1e
T ' to nse
, = (90118,4
,
-40) gal,
gpm = 2.96 mm.
TlD1e
'
-118.4gal.
'
to "la11 = (O
-50) gpm = 2. 37 mm.
Period oCoscillation = 5.33 min,
Solutionto no. 3:
When Q = Mon + Moll = 90 gpm + O gpm = 45 gpm
2
2
m=
Application
Bias = usually adjusted to p-lacethe valve in its 50 percent open position with zero error.
The term proportional band is simply another way o expressing
gain.
% ProportionalBand =
100
Controller Gain
or
Controller Gain =
100
% Proportional Band
%PB (r -c)
+ 50%
Another approach to visualizing the effect of varying the proportional band is shown in Figure 7-14. Each position in the proportional
band dictates a controller output. The wider the band, the greater the
input signal (set point -measurement) musi change in order to cause the
output to swing from O to 100percent. Manual adjustment of the bias
shifts the proportional band so thai a given input signat will cause a
different output level.
ot Proportional
Control
SET POINT
MINUS
MEASUREMENT
GAIN. 1
OUTPUT
TIME-..
OPEN-LOOP
GAIN RESPONSES
0%
1001
CONTROLLER
OUTPUT
MEA5UREMENT,I
"I.
PROPORTIONAL
BANO
OUTPUT
50%
50
100%
0% CONTROLLER
PROPORTIONAL
BANO
-SET
POINT
OUTPUT
.!~I:,_C2~~R2!;~E~
OUTPUT
BIAS (MANUALLY
EFFECT
-
OF
CHANGES
IN
PROPORTIONAL
SET)
= 50%
BAND
(7-5)
___!_'22-:_C2~~~~~!~
tionately more and more offset will exist. Offset mar be eliminated by
manually adjusting the bias until the measured variable equals the set
point.
Narrow-band proportional-only controllers are often used in noncritical, simple temperature loops, such as in maintaining a temperature
in a tank to prevent boiling or freezing. A low, dynamic gain allows a
narrow band to be used. Controllers of ibis nature are typically fieldmounted and pneumatically operated. Many noncritical, level-control
applications having long time constants also use proportional-only control. Now let us apply proportional-only control to the level problem
shown in Figure 7-15.
Proportional-Plus-lntegral
Control
mc es
%PB
-c)
+ 50%
100(57.1 -c) + 50
58.3 = 75
Solving for c: c = 50.9%
Converting to inches: 0.509 x 70 = 35.6 inches
tionship between rneasurernentand set point. Integral action will continue to shift the proportional band as long as a difference exists between rneasurernentand set point. Integral action has the sarne function
as an operator adjusting the bias in the proportional-only controller.
The width of the proportional band rernains constant, and is shifted in a
MEASUREMENT
CONTROLLER
OUTPUT
TIME-'
~
.=
LOAD
MEASUREMENT
% OF SPAN
50
2~
-~"--""
~;;;;",
'
','~
,
SET paiNT
'~
CHANGE
(7-6)
%PB
= gam
e = error (deviation)R
= integraltime
If rou compare this equation with Equation 7-4, the proportionalonly expression, rou will find the bias term replaced by the integral
term.
Fig.
Derivative
ln controlling
(Rate)
multiple-capacity
often desirable. .
By definition, derivative is the time interval by which derivative
action will advance the effect of proportional action on the final
operator. lt is the time difference required to get to a specified level of
output with proportional-only
action as compared to proportionalplus-derivative action. Figure 7-18 illustrates derivative response to a
camp change; where td equals the controller's derivative time.
Derivative
action occurs whenever the measurement si~nal
changes. On a measurement change, derivative action differentiates the
change and maintains a level as long as the measurement continues to
change at the given rate. Under steady-state conditions, the derivative
acts as a 1 to 1 repeater. lt has no inftuence on a controller's output..By
reacting to a rate of input change, derivative action allows the controller to inject more corrective action than is initially necessary in order to
overcome system inertia. Temperature presents the most common application for derivative. Derivative action should Dot be used on processes that are characterized by predominant dead times, or processes
that bave a high noise content, that is, high-frequenY extraneous signaIs such as are present in the typical ftow application.
MEASUREMENT
,
PROPORTIONAL
-ONLY
ACTION
PROPORTIONAL PLUS
DERIVATIVE ACTION
TIME-
7.18. -Derivative
DERIVATIVE
TIME, td
Selecting
Given:
Proportionalband = 50 percent
Integral time = 3 minutes
Derivative time = 3 minutes
Set point = 45 percent
Measurement= 35 percent
Control action: increase-decrease
So/ution:
1. Error staysconstant,thereforeno output changedue to derivative.
2. No output changedueto proportionalaction. However, the proportional action affectsthe integralresponse.
3. Error = r -c = 45% -35% = 10%
4. R = 3 minutes = time to changean amountequalto the error
5. Becausethe proportionalband = 50%,the output in Step4 is multiplied by
= 2.
5% changein 3/4minute.
the Controller
Now that the variety of available control modes has been described,the
next logical question is: which should be selected to control a
particular process? Table 7-1 relates process characteristics to the
common control modes. Let us apply the chart to the beat exchanger
processo
The beat exchanger acts as a small-capacity process; that is, a
small change in steam can cause a large change in temperature. Accu-
Transfer
Lag
Min
Small
Small
Dead
Time
Capacitance
Reaction Load
Rate
Changes
SelfRegulation
Min
Min
High
Low
Moderate
Slow
High
Slow
Any
Slow
Slow
Must bave
SmaIl
Sma11
Prop. +
Integral
Moderate
Moderate
Moderate
Any
Any
Any
Any
Any
Any
Any
Prop. +
Integral +
Deriv.
Fig. 7-19. The process reaction curve is obtained by imposing a step change at input.
7-1.
7.3.
7-4.
202
Table 7-2.
OFFSET
CA. BEy
~'ES
USE
TO'ERATEO?
P-O."
.s
-'+1
USE
The reaction curve of Figure 7-19 clearly indicates that some derivative action will improve control action. Thus a three-mode controller with proportional, integral, and derivative modes satisfies the needs
of the beat exchanger processoTable 7-2, as applied to this problem,
will yield the same resulto
Ouestions
With adequate gain and inphase feedback. any system will:
8. Drift
c. Increase amplitude
b. Oscillate
d. Degenerate
7-2. The natural frequency at which a closed-loop system will cycle depends
upon:
3. The amplifier gain
b. The attenuation provided by the process
c. The phase shift provided by the resistance-capacitanceand dead time
networks that exist in the system
d. Resonance
8.
b.
c.
d.
c. Linear for the purpose ofinitial consideration but with full knowledge
that this may not be the case
d. Nonlinear for purposes of analysis with rhe exception that the system
may prove to be linear
7-5. A closed-loop control system that employs a three-mode controller:
a. Can oscillate or cycle at only one frequency
b. Can oscillate or cycle at several frequencies. depending on controller
adjustment
c. Will not oscillate because of the stability provided by derivative
d. Will produce only damped oscillations with a 0.25 damping ratio
7-6. We have a closed-loop control system which is cycling. We should:
a. Increase the proportional band
c. Check and adjust both
b. Increase integral action
d. Immediately shut it down
7-7. A proportional controller is being used to control a process. and the
offset between set point and control point must be held to a minimum. This
would dictate that rhe proportional band:
3. Be as narrow as possible
b. Be as wide as possible
c. Be of moderate value
d. Does not relate to the problem
7-H. The system gain ofthe closed-loop control system:
3. Refers to the process gain
b. Refers to the gain of the measurement and control devices
c. Refers to total gain of all components. including measurement, controller, val ve operator, valve, and process
d. Relates only to the gain ofthe controller
7-9. If a closed-loop control system employs a straight proportional
controller and is under good control. offset:
3. Will vary in magnitude
b. Will not exceed one-half of the proportional band width
c. Will exceed the deviation
d. Is repeated with each reset7-10.
Any closed-loop system with inphase feedback and a gain of one or
more will:
a. Degenerate
c. Exhibit a 0.25 damping ratio
b. Cycle or oscillate
d. Produce square waves7-11.
How long will it take for the Otltput to change 5 percent if the
measurement remains constant?
Gil 'l'li :
c. Inphase
d. Phase-reversing
c. Inphase
d. Phase-reversing
7-20. The most common combination of control modes found in the typical
process plant is:
8. Proportional-only
b. Proportional, integral, and derivative
c. Proportional-plus-integral
d. On/off
The Flapper-Nozzle
Unit
Figure 8-1 shows the principIe of the ftapper-nozzIe device. Input air
(reguIated at 20 psi or 138 kPa) is fed to the nozzIe through a reducing
tube. The opening of the nozzIe is Iarger than the tube constriction.
Hence, when the ftapper is moved away from the nozzIe, the pressure
at the nozzIe falls to a Iow vaIue (typicalIy 2 or 3 psi, or 10 or 20 kPa);
when the ftapper is moved cIose to the nozzle, the pressure at the
205
nozzle rises to the supply pressure (20 psi or 138 kPa). Flapper movement of only a few thousandths of an inch (Figure 8-2) produces a
proportional pneumatic signal that mar vary from near zero to the
supply pressure. Some pneumatic control mechanisms use the air at the
nozzle (nozzle pressure) to operate a control valve.
The simple ftapper-nozzle unit shown in Figure 8-1 has several
basic limitations. The output air must all corne through the input constriction if it is used directly to operate a control valve. Hence, the
output pressure can change only slowly, causing sluggish action. Just
as the rate of increase in pressure is limited by the input constriction,
the rate of decrease in pressure is similarly limited by the slow rate of
air passage through the nozzle to the atmosphere.
Fig. 8-2. Flapperneedmove only a fewthousandthsof an inch for full rangeof output
(nozzle)pressure.
The
Fig.
PNEUMATICCONTROLMECHANISMS 207
Amplifier
small ball valve. Because the diaphragm has a large area, small
pressure changes on its surface res uit in a significant force to move the
ball valve. The ball valve, when open, permits the full air supply to
reach the output; when closed, it permits the nozzle pressure to bleed
to atmosphere.
If the ftapper position is changed with respect to the nozzle, the air
pressure acting on the celar diaphragm changes and either opens or
closes the celar ball valve, thus either increasing or decreasingthe ftow
of supply air, which now can ftow directly from the supply to the
output, overcoming the first deficiency (slow action) of the ftapper noz-
zle.
relay is often called a pneumatic amplifier becausea small
8-3. Relay is an arnplifier. That is, small change in nozzle pressure (the input to the
relay) causes a large change in output pressure (to the control valve).
The
Relay or Pneumatic
Amplifier
Flapper-nozzle detectors employed in the set-point transmitter and derivative sections of the Model 130 controller use a different type of
pneumatic amplifier. If the flow or volume output requirements are
small, an aspirating relay mar be employed. The pneumatic amplifier,
shown in Figure 8-4, makes use of the Venturi tube principIe and resembles a small Venturi tube. With a 20 psi supply, the throat pressure
of the Venturi can vary 3 to 15 psi or 20 to 100 kPa for a change in
flapper position with respect to the nozzle of less than 0.001 inch. The
aspirating relay accomplishes ibis with almost perfect linearity and
does Dot require parts thai are subject to wear. This recent develop-
.,.SUPP"
,
TO
FLAPPERtNO'
Fig.
PNEUMAT1CCONTROLMECHANISMS 209
ment offers advantages over conventional pneumatic amplifiers, provided that a high volume output is Dot required.
Proportional Action
If a controller had only the units described thus"far, ~apper-nozzle and
relay, it would only bave on/otI action. On/otI control is satisfactory for
many applications, such as large-capacity processes. However, if
on/otI action does Dot meet the control requirements, as in low-capacity
systems, the ftapper-nozzle unit can easily be converted into astable,
wide-band proportional device by a feedback positioning system that
repositions the moving ftapper.
An example of a proportional action mechanism is the Foxboro
12A pneumatic temperature transmitter (Figure 8-5). This device,
called a "force-balance pneumatic transmitter," develops a 3 to 15 psi
(20 to 100kPa) output signal proportional to the measured temperature.
Thus, it is functionally a proportional controller.
210
Figure 8-6 shows .the principIe of the Model 12A transmitter. The
forces created by the bellows are automatically balanced as follows.
When the temperature sensor is subjected to an increase in temperatufe:
1. The increased temperature expands the gas contained in the sensor
and increases the force exerted by its bellows. This increases the
moment of force, tending to rotate the force bar clockwise.
2. The flapper now approaches the nozzle and the nozzle pressure
increases. This pressure is applied to the pneumatic relay (Figure
8-3), increasing its output and the pressure applied to the feedback
bellows, thus increasing the counterclockwise moment of force
sufficiently to restore the force bar to equilibrium.
The force bar (flapper) is now repositioned slightly closer (less than
0.001 inch) to the nozzle, and the output pressure has reached a new
levellinearly related to the measured temperature.
In the actual unit, two additional forces act on the force bar. One is
thai applied by the zero elevation spring. Adjustment of tbis spring
determines the constant force it adds to thai supplied by the feedback
bellows. This allows a given span of temperature measurement to
be raised or lowered. The other force is applied by the ambienttemperature- and barometric-pressure-compensating bellows. This
force compensates for ambient temperature or atmospheric pressure
changes acting on the gas-filled thermal system, thus minimizing errors
caJlsedby these changes.
The Model 12A temperature transmitter produces an output proportional to measurement and is a proportional control mechanism.
However, a useful general purpose controller should incorporate additional modes, and also bave the ability to adjust the parameters of the
mechanism along with other convenient features. For these reasons the
unit described, although a proportional controller, is used primarily as a
transmitter to send an input signal to a generalpurpose controller (such
as the 130 Series), as shown in Figure 8-7.
Control
Mechanism
Requirements
212
Controller
~
~
unit.
Fig.
PNEUMATICCONTROLMECHANISMS 213
The basic added features are a set bellows, which permits adjustment of the set point; and an integral (R) bellows.
ln the actual Model 130 controller (Figure 8-10), a ftoating disk actsas
the ftapper of the ftapper-nozzle system. The resultant moments offorce
due to the four bellows determine the position of the disk with
0f?5!)@
OUTPUT
b=ooa
obOR
b
B
P
b.40
OUTPUT
: o.
o bM
P
b.lo
4
OUTPUT
8.9. Schematicdevelopmentofproportionalcontroller.
PROPORTIONAL
~
=1
('=I--~ --.
REDUCING
TUBE-
~
~
BAND
DIAL
REVERSING
SWITCH
~.-
NU~~LI:
FORCE BALANCING
FLOATING DISC
-INTEGRAL
BELLDWS
PROPORTIONING BELLOWS --'I
-MEASUREMENT
(B) OR
SET (A) BELLOWS
CONTROLLER ACTION
REVERSING SWITCH
/1
\:
r=
=!
,
r~1
'=--,~_f=
INTEGRAL
RESTRICTOR
respect to the nozzle. Therefore, the relay output pressure varies with
changes in pressure in any ofthe bellows. The mechanism is aligned to
produce a midrange output of9 psi (60 kPa) when the error signal is O.
This is called bias.
The width of the proportional band is adjusted by the position of
the proportional-band-adjusting lever. (The term gain is also used in
place of proportional band. Gain is the reciprocal of proportional
band.) This lever positions the fulcrum abolli which the moments of
force created by the pressure in the four bellows act. These moments of
force tilt the floating disk upward or downward, thereby causing a
change in nozzle pressure. The reguli is an increased or decreased
output pressure Crom the controller. This output pressure, which is
proportional to changes in measurement or set pressure, acts to reposition the control valve, thus influencing the process and bringing abolli a
change in the measurement bellows to establish a new equilibrium in
the system.
PNEUMATICCONTROLMECHANISMS 215
TIME
216
ment bellows in the automatic control unit receives from the derivative
unit at the measurement change shown.
The integral function takes place within the automatic control unit
itself. The integral bellows opposes the feedback bellows; thus, if the
feedback bellows introduces negative feedback, the force created by
the feedback bellows will act like positive feedback; that is, it tends to
move the flapper in the same direction as error. This would lead to
instability if the integral restriction were Dot used. anly very slow
signals (minutes in duration) can affect the integral bellows because of
the very small integral restriction. The integral action occurs only arter
the proportional and rate actions h~ve affected the processoIf an error
remains (such as offset due to load change), the integral action takes
place slowly. Because integral action will continue in the presence of a
continuous error, such as we mar find in a batch process, it can cause
the output to go to an extreme. This is called integral windup.
Integral time is adjusted by setting an adjustable restrictor, or needle valve. The dial on this pneumatic val ve is calibrated in minutes of
integral time.
Figure 8-12 illustrates the Foxboro Model 130controller. The control rnodes-proportional, integral, and derivative-are in the controller shown. The signal level with respect to time mar be changed by
appropriate adjustments of proportional, integral, and derivative
modes. The proportional band adjustment is calibrated from 5 to 500
percent, while the integral and derivative dials are calibrated from 0.01
to 50 minutes. These adjustments are calibrated in "normal" times.
The effective times are somewhat different.
In any controller, some interaction between control actions mar
exist because change in one action (proportional, integral, or derivative) can create change in the others. This unavoidable interaction,
even if small, should be kept in mind when adjusting or tuning a control
ler.
Manual Control
Unit
PNEUMATICCONTROLMECHANISMS 217
Fig. 8-12. Pneumatic Consotrol130M controller. (Top) right sicle cover removed and
manual controls. (Battam) the leCtsicle cover is removed to show pneumatic printed
circuit board.
Transfer
Automatic to Manual
With the transfer switch in the automatic position, the thumbwheel in
the manual control unit is disengaged and the automatic controller's
pneumatic output is fed into the manual control unit bellows. The manual control unit remains balanced at this output. At the time of transfer
to manual, the manual unitinstantfy starts transmitting this same output. Thus, the response record of the transfer from automatic to manual (Figure 8-15) is smooth and bumpless.
Manual to Automatic
The transfer Crom manual to automatic requires the use of an
automatic-balancing unit, which consists of a singie-pivoted diaphragm
with four air pressure compartments. This is shown in schematic Corm
AIR
SWITCH
SUPPLY SIGNAL
OUTPUT
PNEUMATICCONTROLMECHANISMS 219
in Figure 8-16. At the left, the unit is in the automatic position; at the
right, it is in manual. It will act as a simple proportional controller with
a fixed proportional band of approximately 30 percent. The basic probIem in transferring from manual to automatic lies in the fact that the
output of the automatic controller must equal that of the manual unit at
the moment of transfer, and then a change at a predetermined integral
rate is necessaryto bring the measurement to the set paint. The output
ofthe manual station is the control unit' s output. Full air supply is sent
to the three pneumatic switches, closing two and opening one, as
shown in Figure 8-16.
The proportional bellows of the automatic control unit is disconnected from the output of the controller. The integral restrictor is
bypassed, and the integral bellows is disconnected from the proportional bellows. The input signals to the automatic balancing unit shown
represent the automatic control unit proportional bellows pressure in
bellows D, and the manual control output in bellows A. Bellows B is
the balancing pressure and bellows C is the output to the integral bel-
lows.
If either the measurement or the set paint to the automatic control
unit changes, the pressure in the proportional bellows must also
change, because it is operating as a proportional-only control unit.
When the change in pressure in the proportional bellows is sensed by
the balancing unit, the unit' s output will change the pressure in the
controller's integral bellows. This, in turo, will cause the proportional
bellows pressure to change in the opposite direction until it once again
equals the output of the manual control relay, or until the supply
pressure limits are reached.
Any diiference between the set and measurement bellows is thus
balanced by the difference between the integral and proportional bel-
lows.
If the output of the manual control unit changes, a similar action
occurs, forcing the proportional bellows pressure to equal the manual
control unit output.
When transferring from manual to automatic (Figure 8-17), the
output will remain at the level determined by the operator when the
controller is in manual. If the measurement input is equal to the set
paint, the output remains constant until corrective action is required. If
the measurement does Dot equal the set paint at the moment of transfer ,
the output will camp from the level of manual operation to the level
necessary to make the measurement equal to set paint a function of the
controller's integral rate.
220
Set Po nt
The set-point knob is attachedto a pneumatictransmitter, which relates the transmitter's output positionor the set-pointpointer (Figures
8-18and 8-19).The output or the transmitteris applied to the set bellows or the controller. If the automaticcontroller is operating, normal
PNEUMATICCONTROLMECHANISMS 221
changes can be made by turning the set-paint knob. Proportional-plusintegral action will occur. Since the derivative amplifier exists only in
the measurementcircuit, derivative action will nat occur. If it is desired
to bring the process slowly to the new set paint with integral action
only, the controller is simply switched to manual, the set-paint change
is made, and the controller is switched back to automatic. Now the
measurement will approach the new set paint, with integral action only,
and no overshoot will occur.
222
SET paiNT
LTIME-i
TIME-
PNEUMATICCONTROLMECHANISMS 223
LlNEARIZING
ASPIRATOR
RELAY
iC
TO REVERSE
FROMREMOTE
SWITCH AND
SET POINT
AUTOMATIC
SIGNAL
L.A.R.
CONTROL U 1T
.L
'j
LOCAL
I ~.
SETPOINT1n-"1
TRANS
AlS \~~-.
r-rr
II
REMOTE
SET
POINT
RECEIVERI
SET KNOB
The Closed-Loop
Pneumatic
Controlled
System
IIPULATED
224
VARIABLE 1
pneumatic temperature transmitter (Foxboro Model 12A), a forcebalance pneumatic controller (Foxboro 130 Series), a pneumatic (diaphragm) valve actuator, and a control val ve (wide-range V-port).
Figure 8-21 shows an accepted manner of representing a system in
a block diagram. All the elements of the actual system are included.
CONTROLLER
,'
"
iDETECTORM (RELAY)t=l
L-
-INTERNALFEEDBACKLOOPjI
SET
II M~.A_S.u.~.!.NG
II
MEANS
~EXTERNAL
CONTROLLED
FEEDBACK
LOOP
MANIPULATEO
PNEUMATICCONTROLMECHANISMS 225
The Process
The process to be controlled is a shell-and-tube beat exchanger. Lowpressure steam applied to the shell beats water flowing through the
tubes. The exchanger has 33.5 square feet ofheat-transfer surface, and
the time required for the beat exchange to take place across this surface causes the exchanger to bave a delayed response. The response
characteristic is that of a multiple-capacitance, multiple-resi&tance
circuit.
Set Point
OUTPUT
SET KNOB
PNEUMATICCONTROLMECHANISMS 227
to hold air and the connectingtubing offers resistanceto air ftow. The
time constant for a pneumatic operator is typically several seconds
with normallengths of connectingtubing. Adding tubing lengthensthe
time constant.Thus, the valve actuatorcontributestime lag or phase
shift to the controlloop, dependingon the lengthof connectingtubing
used.
Final Control
Element
~SE
PNEUMATICCONTROLMECHANISMS 229
".,3."CON.'.,.
'" ,. 6.
,.
PNEUMATICCONTROLMECHANISMS 231
OUTFLOW
WATER
TEMPERATUREI
Fig. 8-27. Controlled set-point change made in automatic mode (top) and in manual mode,
then switched to automatic (bottom).
Batch Controli er
-Fig.
riME
CuRVE
8-28. (Left) Recovery from sustained deviation; proportional plus integral controller
without batch feature. (Right) With batch feature.
below the set point and the controller's output will be at its maximum
value. Ifthe time oftbis deviation is long enough, the integral circuit of
a conventional controller will also reach ibis value. When process conditions retum to normal, no change in controller output can occur until
the measurementreaches the set point. Figure 8-28, curve A illustrates
ibis control action.
The batch switch eliminates tbis integral circuit saturation and
conditions the integral bellows to permit output to start to change
before the measurement reaches theset point. If the controller output
starts to change before the measurement reaches the set point, overshoot can be prevented and the measurement can retum to the set point
smoothly. Figure 8-28, curve B illustrates tbis control action.
Principie
ot Operation
PNEUMATICCONTROLMECHANISMS 233
This causes the pressure in the circuit to dropo As long as the relay
output pressure is above the trip point, the integral circuit pressure will
drop until there is no longer any pressure in the integral bellows. At this
point, the proportional band throttling range will have shifted completely below the set point as indicated in Figure 8-28B, curve B. During this operation, the controller's output pressure is at 15 psi or 100
kPa (or more) and the valve is wide open. When the batch process is
restarted, the control valve will begin to throttle as soon as the measurement reaches the 15 psi or 100kPa lmit of the proportional band
throttling range. Note that as soon asthe controller output drops below
15 psi or 100kPa, normal integral response is restored. This overcomes
the tendency to overshoot the set point.
Load Bias (Preload)
Due to the time characteristics of certain processes, shifting the proportional band completely below the set point will cause an intolerable
delay in bringing the batch to the set point. In such cases, an adjustable
back pressure mar be applied to the vent port to "bias" the batch
switch. Thus, the pressure in the integral circuit mar be prevented from
dropping below a preselected amount and the proportional band throttling range will shift only partially below the set point. Although this
will allow faster recovery, a slight overshoot will occur if the "bias" is
increased too much. Increasing the bias to 15 psi or 100 kPa would
obviously completely eliminate batch action.
One limitation thai applies to all pneumatic control systems is the
distance thai mar be accommodated between components. The maximum distance depends on two major factors: the pneumatic signal
travels at the speed of sound, and the loop components along with the
tubing all bave capacity and resistance. Thus, an RC time constant
musi exist. Volume boosters often are applied to lengthen ibis working
distance. Unfortunately, a volume booster will do nothing to speed up
signal velocity. A booster will help if a large volume, such as thai found
in a pneumatic valve actuator, is involved.
The distance lmit for pneumatic control systems is approximately
200 feet (60 meters). Iftbis distance factor is ignored, the dynamics ofthe
control system will suffer and reguli in poor control operation. If it
becomes necessary to lengthen these distances substantially, the only
practical solution is to utilize electrical signals thai mar work over an
almost unlimited distance.
Questions
c. Gain
8-2. True or false: In a proportional-onlycontroller,ifthe measurement
equals
the set point the output will equalthe bias.
8-3. True or false: In an integralcontroller,the rate of changeof the output
is proportionalto the error.
8.4. True or false: The largerthe numberon the integraldial the greaterthe
effectof the integralaction.
8-5. True or false: In a batchoperation,if a controllerhaswound up, it is
quite possiblethat the valve may stay in an extremepositionuntil the
measurementactuallygoesbeyondthe set point beforethe valve beginsto
changeits position.
8-6. True or false: What somemanufacturerscall rate others call derivative.
8-7. Indicate all the correctstatements:
8. Gainis the reciprocatof the proportionalband.
b. The proportionalbandis the reciprocatof gain.
PNEUMATICCONTROLMECHANISMS 235
c.
d.
e.
f.
The
The
The
The
point.
b. Remain at 8 psi (55 kPa) as long as the measurement stays where it is.
c. Decrease and continue to decrease to 3 psi (20 kPa).
d. Continue to decrease until the measurementreaches the set point, or if
it does not retum to the set point, decrease to Opsi.
8-9. The range of the temperature measuring system used in conjunction
with a Model 130proportional-only contro1ler is O to 150oP(66C). The output
is 9 psi (60 kPa) when the set point and indicator are both at 75P (24C). If
the proportional band is 200 percent, what is the output when the
measurement is 150oP(66C)?
a. 9 psi (60 kPa)
c. 12 psi (83 kPa)
b. 3 psi (20 kPa)
d. 15 psi (100 kPa)8-10.
If the span of a measuring transmitter in a control system is made
one-half of its value, the proportional-band adjustment in the controller must
be -to
maintain the same quality of control.
a. Cut in half
d. Narrowed
b. Doubled
e. None of the above.
c. Squared
8-11. With a proportional-plus-integral controller, a sustained error will result
in:
a.
b.
c.
d.
e.
Windup
A fixed offset
A temporarynarrowingof the proportionalband
A delay in the process
None of the above
8-13.
a.
b.
c.
d.
If proportional-plus-integral
controlis good,the additionof derivative:
Will anticipatechangesand speedup corrections
Will alwaysimprove control
Will makethe controlleradjustmentseasierto accomplish
May create stability problemsin somesystems
237
Electronic control systems,already widely accepted,are gainingrapidly in popularity for a numberof reasons:
1. Electrical signalsoperateover greatdistanceswithout contributing
time lags.
2. Electrical signals can easily be made compatible with a digital
computer.
3. Electronic units can easily handle multiple-signalinputs.
4. Electronic devices can be designedto be essentiallymaintenance
free.
s. Intrinsic safety techniques bave virtually eliminated electrical
hazards.
6. Generally, electricalsystemsare lessexpensiveto install, take up
less space,and can handle almost all processmeasurements.
7. Electronic devices are more energy efficient than comparable
pneumatic equipment.
Feedwater
Control
Systems
Two ditIerential pressure transmitters (Fig. 9-2) are used, one to measure water flow; the other to measure drum water level.
Referring to Fig. 9-3, in operation the ditIerence in pressure between the high and low gide of the transmitter body is sensed by a twin
diaphragm capsule (1) which transforms the ditIerential pressure into a
force equal to the ditIerential pressure times the etIective area of the
diaphragm. The resultant force is transferred through the C-flexure (2)
to the lower end of the force bar (3). Attached to the force bar is a
cobalt-nickel alloy diaphragm which serves as a fulcrum point for the
force bar and also as a seal to the process in the low-pressure cavity
gide of the transmitter body. As a result of the force generated, the
Fig. 9-1. Peedwater control system. (I) Drum water level (2) Steam ftow from boiler,
via turbine steam pressure. and (3) Water ftow into drum.
force
9-4.
Steam ftow out ofthe drum is measured in terms of steam pressure,
which is measured with a pressure transmitter. The operation of the
pressure transmitter is similar to the operation of the differential
pressure transmitter_,The same feedback technique used in the differential pressure transmitter is employed in the pressure transmitter. The
major difference lies in the size and construction of the sensor.
The pressure transmitter measures the pressure in the first stage of
the power turbine. Since there is a linear relationship between first
stage turbine pressure and steam flow, the output signal from the
pressure transmitter is linear with steam flow out of the boiler,
A variety of electronic differential pressure transmitters are available from a number of manufacturers. Some of these make use of strain
gauge detectors, capacitive detectors, resonant wire detectors, and inductive detectors. Many are motion or open loop devices which are still
capable of accuracies within a fraction of a percent. In the application
of any electronic transmitter, the user must guard against subjecting the
electronics to temperatures which might result in damage. This probIem generally can be avoided by observing the precautions recommended by the manufacturer.
The Controllers
The controllers described befe are the Foxboro SPEC 200 type. The
SPEC 200 is generally a split-architecture system. In this system two
areas may be used, a display area and a oest area. Field equipment,
such as measuring transmitters, electrical valve actuators, and the like,
generally operates on 4 to 20 mA dc. Within the oest, SPEC 200 operates on O to 10 volts.
The display area contains control stations, manual stations, recorders, and indicators to provide the necessary operator displays and
controls. These units are shelf-mounted and contain only the electronic
circuitry required to communicate the display and adjustments necessary for an operator to control and monitor a processo
The nest area contains the analog control, computing, alarm, signal
conditioning, and input and output signal converter units. These units
are in the form of "modules" and "circuit cards." The oest itself is
basically an enclosure provided for the mounting of "modules."
System power is supplied to the oest. This power supply must
deli ver + 15 and -15 V dc for operation of the display and nestmounted instruments. Recorder chart drives and alarm lights require 24
V ac.
When a single location is required, the oest and display areas may