Technical Guide
Technical Guide
Technical guide
Manufacturers declaration
The manufacturer
ABB Components AB
SE-771 80 LUDVIKA
Sweden
On-load tap-changers
type UB
with motor-drive mechanisms
types BUE and BUL
Low Voltage Directive 73/23/EEC (modified by Directive 93/68/EEC) concerning the built-in
motor and apparatus in the control circuits.
Certificate of Incorporation:
The machines above must not be put into service until the machinery into which they have been
incorporated have been declared in conformity with the Machinery Directive.
Date
1997-02-10
Signed by
.........................................................................
Olof Heyman
Title
This Technical Guide has been produced to allow transformer manufacturers, and their designers
and engineers, access to all the technical information required to assist them in their selection of
the appropriate on-load tap-changer and motor-drive mechanism. The guide should be used in
conjunction with the Selection Guide and the Design Guides, to allow the optimum selection to be
made.
The technical information pertaining to on-load tap-changers and motor-drive mechanisms
manufactured by ABB Components has been divided and is contained in separate documents,
with one document for each type.
The information provided in this document is intended to be general and does not cover all
possible applications. Any specific application not covered should be referred directly to
ABB Components AB, or its authorized representative.
ABB Components AB makes no warranty or representation and assumes no liability for the
accuracy of the information in this document or for the use of such information. All information in
this document is subject to change without notice.
ABB Components also manufactures the following products:
Transformer bushings
Wall bushings
GIS bushings
Transformer cooling equipment
Table of Contents
General Information _____________
6
6
7
7
7
8
8
9
9
9
9
9
10
10
10
10
11
11
Characteristics
and Technical Data _____________
12
12
12
12
12
12
13
13
14
14
14
14
14
14
14
Design, Installation
and Maintenance _______________
15
On-Load Tap-Changer
Schematic Diagrams ___________________
Drying _______________________________
Painting _____________________________
Weights _____________________________
Oil Filling _____________________________
Installation ___________________________
Maintenance __________________________
Oul Filter Unit ____________________________
Pressure Relay ________________________
General Description _________________
Design ____________________________
Operation _________________________
Function Pressure ___________________
Testing ___________________________
Dimensions, On-Load Tap-Changer
Type UBB ____________________________
Motor-Drive Mechanism ____________________
Design ______________________________
Installation ___________________________
Maintenance __________________________
Dimensions, Drive Shaft System and
Motor-Drive Mechanism _________________
13
14
15
19
19
19
19
19
19
19
20
20
20
20
20
20
21
21
21
21
21
22
General Information
When the on-load tap-changer operates, arcing occurs in
the tap-changer. To avoid contamination of the transformer oil, the tap-changer is housed in its own oil
compartment separated from the transformer oil. All
components that make or break the current during the
operation of the tap-changer are located in the tapchanger compartment. The UB range of on-load tapchangers operates according to the selector switch
principle, that is, the tap selector and diverter switch
functions are combined in one.
The UB type of on-load tap-changer is mounted on the
inside of the transformer tank. Both cover-mounting and
yoke-mounting may be specified. The tap-changer
comes ready for mounting on the inside of the transformer tank, which simplifies installation procedures.
All of the equipment necessary to operate the tapchanger is contained in a cylinder of glass fibre
reinforced plastic, the selector switch housing. Driving is
from a separate motor-drive mechanism, fitted to the
side of the transformer tank, and connected by means of
drive shafts and bevel gears.
L037164
Connection to oil
conservator
Oil valve
Bevel gear
Pressure relay
Top-cover
Position indicator
window
Cylinder
Change-over selector:
Moving contacts
Fixed contacts
Selector switch:
Fixed contacts
Moving contacts
Current collector
terminal
Transition resistor
Shielding rings
Bottom valve
drain screw
Bottom
Design Principles
On-Load Tap-Changer
contact, which consists of two fingers, pressed on the
fixed contact by springs. The moving switching contact
and the transition contacts are made as rollers, which
move over the knife-like fixed contacts. See Fig. 3. The
making and breaking take place between the fixed and
moving switching contacts.
Selector Switch
The selector switch consists of fixed contacts and a
moving contact system.
The fixed contacts are mounted on bushings which are
inserted through the cylinder wall of the selector switch
housing. Each fixed contact has two contact paths on
each side, one for the moving main contact and one for
the moving switching contacts.
The moving contact system for a single-phase consists
of the main contact, the main switching contact and two
transition contacts. The system is built as a rigid unit
rotated by a common insulated drive shaft. In the service
position the load current is carried by the moving main
Fixed contacts
Moving contacts
Transition Resistors
Change-over Selector
The resistors are made from spirally wound wire mounted on insulating bobbins. They are connected between
the moving main contact and the transition contacts.
Fixed contacts
Moving contacts
Geneva Gear
The Geneva gear principle is used to change a rotary
motion into a stepping motion. Drive is transmitted via a
shaft system and bevel gears from the motor-drive
mechanism. A spring energy accumulator actuates the
Geneva gear. The Geneva gear operates the selector
switch and the change-over selector. The Geneva gear
is also used to lock the moving contact system into
position. The gearing mechanism is maintenance-free.
Oil Conservator
Bevel gear
Vertical drive-shaft
and protection cover
On-Load Tap-Changer
Hand crank
Motor-Drive Mechanism
Motor-Drive Mechanism
The motor-drive mechanism provides the drive to allow
the tap-changer to operate. As the name implies, drive is
provided from a motor through a series of gears and out
through a drive shaft. Several features are incorporated
within the mechanism to promote long service intervals
and reliability.
Special Applications
Type BUL
Accessories
Type BUE
For a list of accessories available for both the TapChanger and the motor-drive mechanisms, see the
Selection Guide or consult ABB Components.
L37166
L37167
Principles of Operation
On-Load Tap-Changer
Switching Sequence
The switching sequence is designated the symmetrical
flag cycle. This means that the main switching contact of
the selector switch breaks before the transition resistors
are connected across the regulating step. This ensures
maximum reliability when the switch operates with overloads.
At rated load the breaking takes place at the first current
zero after contact separation, which means an average
arcing time of approximately 6 milliseconds at 50 Hz.
The total time for a complete sequence is approximately
50 milliseconds. The tap change operation time of the
motor-drive mechanism is approximately 5 seconds per
step.
Fig. 8c.
The transition contact M1 has made on the fixed contact
2. The load current is divided between the transition contacts M1 and M2. The circulating current is limited by the
resistors.
Selector Switch
The switching sequence when switching from position 1
to position 2 is shown in the diagrams of Fig. 8 below.
The moving contact H is shown as one contact but
consists in fact of two, the main contact and the main
switching contact. The main contact opens before and
closes after the main switching contact.
Fig. 8d.
The transition contact M2 has broken at the fixed contact 1. The transition resistor and the transition contact
M1 carry the load current.
Fig. 8a.
Position 1. The main contact H is carrying the load
current. The transition contacts M1 and M2 are open,
resting in the spaces between the fixed contacts.
Fig. 8e.
Position 2. The main switching contact H has made on
the fixed contact 2. The transition contact M1 has opened at the fixed contact 2. The main contact H is carrying
the load current.
Fig. 8b.
The transition contact M2 has made on the fixed contact
1, and the main switching contact H has broken. The
transition resistor and the transition contact M2 carry the
load current.
10
10 loops
SELECTOR SWITCH
CURRENT
COLLECTOR
TERMINAL
H Main contact
M1, M2 Transition contacts
Fig. 9b.
11
Type Designation
UBB..
XXX/YYY
Type
Type of Switching
L Linear
R Plus/Minus
D Coarse/Fine
Type of Connection
N Three-Phase Star Point
T Three-Phase Fully Insulated
Impulse Withstand Voltage To Earth
200 kV, 350 kV
o Check of assembly
o Mechanical test
o Sequence test
o Auxiliary circuits
insulation test
o Vacuum test
o Final inspection
Rating Plate
14 positions
27 positions
27 positions
1500
1000
500
100
200
300
400
500
Rated throughcurrent (A)
fm_00252
Number of
operations
Contact Life
The predicted contact life of the fixed and moving
contacts of the selector switch, is shown as a function of
the rated through-current in Fig. 12. The values are
calculated from the results of the service duty test. For
step voltages equal to or below 40 V at 50 Hz and equal
to or below 50 V at 60 Hz the predicted contact life is
always 500 000 operations.
500 000
Mechanical Life
200 000
100 000
150A
300 000
100
1)
Insulation levels kV
to earth
between phases
fully insulated 1)
20070
350140
200
300
400
500A
Rated through current
200/...
350/...
80 %
400 000
lnsulation Levels
UBB
On-load tap-changer type
300600A
80 %
20070
350140
Type of
switching
Linear
Number of
positions
a2
Between the first
and the last
contacts
(Figs. 1315)
10
12
14
20060
18060
17060
Plus/Minus 9, 1519
11, 2123
13, 2527
20060
18060
17060
Coarse/Fine
20060
18060
17060
1519
2123
2527
b1
In selector
switch
25060
25060
d1
In change-over
selector
BIL 200
BIL 350
25060
350140
Occasional Overloading
8000
Table 2.
Tie-in Resistors
Oil Temperature
The temperature of the oil surrounding the on-load tapchanger shall be between -25 and +105 oC for normal
operation, as illustrated in Fig. 16. The range can be
extended to -40 oC provided that the viscosity of the
tap-changer oil is between 2-800 mm 2/s (= cst).
o
C
1)
+115
2)
+105
Rated Through-Current
The rated through-current of the tap-changer is the
current which the tap-changer is capable of transferring
from one tapping to the other at the relevant rated step
voltage, and which can be carried continuously whilst
meeting the technical data in this document.
3)
1) No operations allowed
2) Emergency overloading.
The on-load tap-changer will not
restrict the occasional overloading
of the transformer according to the
standards in section Occasional
Overloading above.
3) Normal operating range.
0
4) When operating within this range,
no overload is allowed.
-25
4)
-40
5)
fm_00215
14
Linear
Plus/minus
Coarse/Fine
8
9
4
9
4
9
8 Regulating steps
Number of loops
Tap positions (electrical)
9 Regulating steps
Number of loops
Tap positions (electrical)
9
10
15
Linear
Plus/minus
Coarse/Fine
10 Regulating steps
Number of Loops
Tap Positions (Electrical)
10
11
5
11
5
11
6
13
6
13
11 Regulating steps
Number of loops
Tap positions (electrical)
11
12
12 Regulating steps
Number of loops
Tap positions (electrical)
12
13
13 Regulating steps
Number of loops
Tap positions (electrical)
13
14
16
Plus/minus
Coarse/Fine
14 Regulating steps
Number of loops
Tap positions (electrical)
8
15
7
15
8
17
8
17
10
19
9
19
10
21
10
21
16 Regulating steps
Number of loops
Tap positions (electrical)
18 Regulating steps
Number of loops
Tap positions (electrical)
20 Regulating steps
Number of loops
Tap positions (electrical)
17
Plus/minus
Coarse/Fine
22 Regulating steps
Number of loops
Tap positions (electrical)
12
23
11
23
12
25
12
25
14
27
13
27
24 Regulating steps
Number of loops
Tap positions (electrical)
26 Regulating steps
Number of loops
Tap positions (electrical)
18
Drying
Maintenance
The tap-changer can be dried together with the transformer according to one of the following processes:
alternating hot-air and vacuum or vapour-phase at a
maximum temperature of 135 oC (275 oF) and a maximum pressure difference of 100 kPa between the tapchanger and the transformer.
Painting
Weights
Table 3 contains the weights of all the models in the UB
range of on-load tap-changers. The motor-drive
mechanism and the drive shaft system are not included
in the overall weight.
On-load tap-changer
Type designation
Approx. weight in kg
Tap-changer
Required
without oil
oil
Ordering Alternatives
Total
Pipe
UBBLN XXX/YYY
UBBRN XXX/YYY
UBBDN XXX/YYY
140
UBBLT XXX/YYY
UBBRT XXX/YYY
UBBDT XXX/YYY
155
100
240
Standard
Valve R
125
280
Pressure relay
Table 3. Weights
Motor-drive mechanism (BUL):
Motor-drive mechanism (BUE):
Drive shaft system:
Draining
For assembly of pipe and valve on the transformer
75 kg
130 kg
Approx. 10 kg
Oil Filling
Pressure relay
Oil filtering
Pipe for connection to oil-filter, suction side
Installation
fm_00257
19
Pressure Relay
Switching contact
30
54
67
ABB Components
~200
~35
Adjusting nut
Spring
Piston
,,
,,
110
One single-pole
switching contact
Connection for
test equipment
R 1/8
~155
15
32
11
Two single-pole
switching contacts
NO NC C NO NC C
64 66 65 61 63 62
NO NC C
61 63 62
fm_00213
Fig. 17.
General Description
Operation
Design
Function Pressure
Breaking capacity
Resistive Inductive
load
load
Withstand voltage
between open
contacts
110 V DC
0.8 A
0.2 A
L < 40 ms
R
125 V DC
0.6 A
0.15 A
220 V DC
0.4 A
0.1 A
L < 40 ms
R
L < 40 ms 2 kV, 50 Hz, 1 min
R
125 V AC
5A
250 V AC
2.5 A
Table 4.
20
Motor-Drive Mechanism
Design
To oil conservator
132
Installation
The motor-drive mechanism is fitted to the outside of the
transformer tank, and connected to the tap-changer (or
tap-changers) by drive shafts and bevel gears.
For correct installation procedure, consult the
appropriate Installation and Commissioning Guide.
H (see table 5)
Maintenance
The motor-drive mechanism should be inspected at
regular intervals and at the same time as the tapchanger is inspected.
For the correct inspection and maintenance procedures,
consult the appropriate Maintenance Guide.
600
394
On-load tap-changer
Type Designation
Dimension H
mm
UBBLN XXX/YYY
UBBRN XXX/YYY
UBBDN XXX/YYY
1193
UBBLT XXX/YYY
UBBRT XXX/YYY
UBBDT XXX/YYY
1489
21
AA
o
> 500 mm
1)
R67.50.5
45
70
921
96
36
775
825
115
75
> 525 mm 1)
M10 (4x)
426
318
BUE 1
BUL
268
366
338
263
12
5 o 2)
)
o2
140
168
192
22
Notes:
23
ABB Components AB
Visiting address: Lyviksvgen 10
Postal address: SE-771 80 Ludvika, SWEDEN
Tel.+46 240 78 20 00
Fax +46 240 121 57
E-mail: [email protected]
www.abb.com