Modbus TCP Scada
Modbus TCP Scada
Contents
1
System Topology............................................................................. 2
5.2
6.2
6.3
6.4
6.5
Runtime Test................................................................................. 21
About Moxa
Moxa is a leading manufacturer of industrial networking, computing, and automation
solutions. With over 25 years of industry experience, Moxa has connected more than 30
million devices worldwide and has a distribution and service network that reaches
customers in more than 70 countries. Moxa delivers lasting business value by empowering
industry with reliable networks and sincere service for automation systems. Information
about Moxas solutions is available at www.moxa.com. You may also contact Moxa by email
at [email protected].
How to Contact Moxa
Tel:
Fax:
+886-2-8919-1230
+886-2-8919-1231
1 Application Description
This application describes how to set up a WinCC system to control and monitor Modbus end
devices whose information is transmitted from MGate MB3000 in an HVAC application project.
The main topic in this application note will learn about WinCC setting, such as:
User interface to display and manage the processes on the controllable device.
For more information on Modbus end devices PowerFlex 4M (Converter) and IAQPoint2
(Meter), refer to the documents Configuring Allen-Brandly ControlLogix PLC with Moxa MGate
5105-MB-EIP.
2 System Topology
The following figure shows a system topology where Modbus end devices, PowerFlex 4M
(Converter) and IAQPoint2 (Meter), are connected to the serial ports on MGate MB3000
through RS-485-2W wiring. MGate MB3000 and PC (with WinCC installed) are on the same
Ethernet subnet. A fan is connected to PowerFlex 4M that outputs electric current to power the
fan.
Page 2 of 22
PowerFlex 4M:
PowerFlex 4M is an adjustable frequency AC drive (converter).
IAQPoint2:
IAQPoint2 is an indoor air quality monitor. It can detect CO2, temperature and humidity
levels.
WinCC
A SCADA system developed by Siemens AG.
Rev.: V7.2.
4 About WinCC
WinCC allows you to visualize the process and configure a graphic user interface. You can
use the user interface to operate and observe the process.
WinCC allows you to:
Observe the process. The process is displayed graphically on a screen. The display is
updated each time a process status changes.
Operate the process. For example, you can configure a setpoint or open a valve using the
user interface.
Monitor the process. An alarm automatically signals in the event of a critical process status.
If, for example, a predefined value is exceeded, a message will appear on the screen.
WinCC Components
The major components of WinCC are the Configuration Software (CS) and Runtime
Software (RT).
The core of the Configuration software is WinCC Explorer that displays the entire project
structure.
The following table lists the major systems in WinCC.
Process unit
Editor
Function
Graphics System
Graphics Designer
Configuring Screens
Signaling system
Alarm Logging
Configuring messages
Archiving system
Tag Logging
Archiving data
Report system
Report Designer
Create layouts
User Administration
User Administrator
Communication
Tag management
Configure communication
Page 3 of 22
When you execute a project in process mode in WinCC Runtime, the project will then be in
Runtime. WinCC Runtime allows you to operate and observe the processes.
WinCC Runtime performs the following tasks:
Archive current Runtime data, such as process values and message events.
5 WinCC Configuration
5.1 Creating a Project
1. Start the WinCC Explorer Program by clicking Start Program Siemens
Automation SIMATIC WinCC WinCC Explorer.
Page 4 of 22
2. In WinCC Explorer, create a new project. Click File New or click the New icon.
3. In the WinCC Explorer dialog box, select Single-user project and click OK.
A Single-user project runs on only one computer. Other computers cannot access
this project. The project runs on the computer that serves as the server for data
processing and as an operating station.
4. In the Create New Project dialog box, enter a name in the Project Name field and
click Create.
Page 5 of 22
One connection
Channels
Channels are specialized communication drivers. Channels enable the
transmission of process values from the automation system to the process tags.
WinCC provides a variety of channels to connect different automation systems.
In WinCC, you can use channels, via which values are transferred to the
automation system from WinCC. You can also control processes via these
channels.
Page 6 of 22
Channel Units
Channels have different channel units for the different communication
networks. A channel unit is used to access a specific type of automation system.
A channel unit serves as an interface with exactly one underlying hardware driver
and therefore to exactly one communication processor in the computer.
Connections
In channel units, you configure connections to the various automation systems.
Each connection describes the interface to a single, defined automation system.
The data exchange takes place via the connections in Runtime.
Tags in WinCC
A tag in WinCC represents either a real value or internal value. Internal values are
calculated or simulated within WinCC.
Process Tags
External tags serve as connection links for the exchange of data between WinCC
and the automation systems. Each external tag in WinCC corresponds to a certain
process value in the memory of one of the connected automation systems.
External tags are therefore referred to as process tags.
Internal tags
WinCC also contains internal tags. These tags are not linked to a process and only
transfer values within WinCC.
Page 7 of 22
2. Click Tag Management Add new driver Modbus TCPIP to add a new channel.
The WinCC Configuration Studio screen displays the Modbus TCP/IP Unit #1
channel that you have added.
Page 8 of 22
Page 9 of 22
4. In the Modbus TCPIP properties screen configure the following fields and click OK:
CPU type: Select Compact, Quantum, Momentum from the drop-down list.
5. Repeat steps 1 to 4 to create another connection named converter and configure the
fields in the Modbus TCPIP properties screen as shown in the following figure.
Page 10 of 22
3. For the meter_tag tag group, add the tag as shown in the following figure.
4. For the converter_tag tag group, add the tag as shown in the following figure.
Page 11 of 22
The value range of the temperature register for meter connection is between 0
and 1000. Based on the following formula, the actual temperature is 0 to 100C:
Actual temperature = Value of temperature register / 10
For the converter_tag group tags, activate linear scaling for the tags as shown in
the following figure.
Dynamic objects: These objects will change depending on the individual process
values.
Controllable objects: These objects allow you to control the process. For example,
you can use the buttons, sliders, or I/O fields to set process parameters
(input/output field).
Update dynamic objects. For example, modifies the length of a bar graph in relation to
a process value.
Respond to operator input. For example, the clicking of a button, or the entry of a text
in an input field.
Page 12 of 22
Page 13 of 22
Meter
Page 14 of 22
Motor
Page 15 of 22
Page 16 of 22
2. In the Linking of the Tag Connection dialog box, click the icon to select the temp
tag Assign temp tag.
Page 17 of 22
Page 18 of 22
Page 19 of 22
Because the byModbus I/O fields are used as script reference, it is not necessary to
display them on the screen. Thus, you can set their Display property to No.
Page 20 of 22
3. Set the START.pdl process picture as the startup screen. Click the Graphics Runtime
tab and click the button to select the START.pdl process picture in the Start
Picture field; then, click OK to finish.
8 Runtime Test
In WinCC Explorer, click the Activate button to start WinCC Runtime.
Page 21 of 22
The system starts Graphics Runtime and the START.pdl process picture is displayed as the
startup screen.
WinCC polls the tags of Modbus TCP and displays the updated values on the screen. For
example, WinCC displays the current temperature and speed values.
To start or stop the PowerFlex 4M converter, click the Start or Stop button.
You also change the value of Modify Speed to control the fan speed.