Siemens - General Fire Detection System Planning
Siemens - General Fire Detection System Planning
Planning guidelines
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Extent of monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4.1
4.2
4.3
4.4
4.5
Choice of detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smoke detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat detectors types D/T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IR flame detectors type S.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual call points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
9
16
18
20
5
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
21
21
24
43
55
68
77
77
77
78
6
6.1
6.2
6.3
6.4
80
80
80
83
84
7
7.1
7.2
7.3
85
85
85
7.4
8
8.1
Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
87
9
9.1
88
88
10
10.1
10.2
90
90
90
11
92
Keyword index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93
86
86
I
Fire & Security Products
Siemens Building Technologies Group
06.2002
II
Fire & Security Products
Siemens Building Technologies Group
06.2002
Foreword
These planning guidelines contain the basic know-how for the planning of sophisticated
fire detection systems. It is an important tool and reference work for the planner of fire
detection systems.
It contains basic information which applies to all fire detectors. As far as possible we have
tried to provide a layout which can be used irrespective of detector type. Specific detector
data is provided where it is needed in depth.
For the new AlgoRex generation of detectors, such specific data are provided in separate documents as setting parameters differs considerably from the setting of previous
generations of detectors.
However, section 5, Number and arrangement of point-type detectors also applies for
AlgoRex detectors.
1
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Extent of monitoring
In principle we should endeavour to provide complete monitoring in all fire compartments.
The monitoring of selected fire compartments (partial monitoring) or selected rooms or
groups of rooms (selective monitoring) should only be applied exceptionally.
With complete monitoring (or within partial monitoring) the following zones must also be
monitored:
Lift, transport, transmission and light shafts in which the nature of the structure or an
accumulation of material poses a fire risk
Cable ducts and shafts if they are accessible, or in close proximity to other sectors
which are not isolated by fire-resistant divisions 1)
Sanitary and heating installation supply shafts if accessible, or in close proximity to other sectors which are not isolated by fire-resistant divisions 1)
Rooms for ventilation and air conditioning installations as well as fresh and used air
ducts
Ducts for chutes for material and refuse and their hoppers
Closets and structures which are large enough for a person to enter
Covered-in loading ramps with protruding roof if they are not at least isolated from the
monitored sector by a fire-resistant 1) division
Storage areas under protruding roofs if they are not at least isolated from the monitored
sector by a fire-resistant 1) division
Areas below galleries
Voids in dropped ceilings and raised floors according to table Fig. 1
Voids above dropped ceilings with evenly distributed openings of 50% of the surface
area should be regarded as a part of the room just below
Zones in rooms which are created by shelves or other fixtures and fittings which reach
to within 30cm of the ceiling
Exceptions to the rules concerning monitoring
Sanitary installation rooms, e.g. washrooms, toilets, providing no combustible stocks
or refuse are stored there, or the enclosing walls are non-combustible
Cable shafts with cable sealing on each floor and which have no electrical switchgear or
safety cut-out installations.
Rooms which are protected by an automatic fire extinguishing system and are at least
fire-resistant isolated should the automatic monitoring of these rooms provide no special advantages
Voids in dropped ceilings and raised floors which according to table Fig. 1 are
constructed as zones without monitoring
According to the situation, (to be determined in each case) the following can be excluded:
Separate, fire-resistant 2) isolated storage tank rooms
Air raid shelters which in peacetime are not used for other purposes
Residential zones, fire-resistant 2) isolated
Cold storage rooms and intense cooling plants 50m2
Separate battery rooms, fire-retardant isolated 1)
1)
Structural divisions are described as fire-retardant if they can withstand a fire for at least 30 minutes.
2)
Structural divisions are described as fire-resistant if they can withstand a fire for at least 90 minutes.
2
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Void features
Inaccessible or
accessible and without fire load
or
sources of ignition
or
few and fire-proof electrical
installations (at least self-extinguishing)
none
Room monitoring
(complete monitoring of void)
Fig. 1
3
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Choice of detector
4.1
General
The specifying of which detector to use and where depends on
the monitoring category or the general monitoring aim of the FDS*
room height
the ambient influences including deceptive phenomena
4.1.1
Monitoring
category
low
to
medium
Application examples
no danger to life
and
unit structure or fire compartment
150m2
and
little fire spread
and/or
danger of smoke logging
and
low concentration of valuable
property
Kitchens
Heating plants
Recreation rooms/lounges
Small garages
Small workshops
possibly small offices
Hotel rooms
Factory rooms
Offices with important
documents
Research laboratories
Staircases
Wards
EDP systems
Museums
Historical buildings
III
Application criteria
II
Fire risk /
consequences
medium
to
large
Fig. 2
large
g
to
very large
Table Monitoring categories, monitoring aims, fire risk, application criteria and
application examples
5
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.1.2
Room height
Rauch
h
3
Radiation
h
2
h
1
Fig. 3
Smoke detectors
The thermodynamics of open fire transport smoke particles, which become diluted in the
larger volume of air, even to very high ceilings.
Allowance for this smoke dilution can be made by employing sensitive smoke detectors.
Smouldering fires lack the thermodynamics to transport the smoke. Such fires are only
detected by detectors on high ceilings when they develop into open fires.
Heat detectors
The hot air currents rising from an open fire cool rapidly with increasing distance from the
fire and increasing room volume. For this reason their limitations in respect of high-ceiling
applications are soon reached.
Flame detectors
Although heat radiation decreases by the square of the distance from the fire location to
the detector, thanks to its high response sensitivity these detectors can also be used in
high rooms.
4.1.3
Suitability table
The table shows an evaluation of the detectors according to their suitability in respect of
the monitoring target (U) and room height (H). The overall suitability is found by multiplying the values U and H.
6
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Monitoring
category
I
II
III
Monitoring
g tar
tar- Suitabilityy rating
g
get of the DFS U = Suitability on the basis
of monitoring target or
monitoring category
H = Suitability on the basis
of room height h
U x H = Detector suitability
Rating:
U x H = 4 very good suitable
2 well suited
1 suitable
0 in
i certain
t i cases
Detection
/must be checked
of:
- unsuitable
open
fire
open
fire
smouldering fire
(desired)
open
fire
Smoke detectors
F-detectors
Sensitivity
R-detectors
Sensitivity
Flame
detectors
Heat detectors
Linear
smoke
detectors
Sensitivity
Rate-of-rise
detectors Sensitivity
Fixed
temperature
detectors
Infrared
flame detectors
Sensitivity
Standard
selectable
Standard
selectable
selectable
cl.1
cl.2
selectable
U Suitability on basis of
monitoring target
U Suitability on basis of
monitoring target
0
**
0
**
0
**
0
**
(1 in combination
with
smoke
detectors)
U Suitability on basis of
monitoring target
(2 in (1 in
combination with
smoke
detectors)
smouldering
fire
H - values
Suitability
value H for
room height
h or mount
mounting height
of flame detector
Room height
4,5m
>4,5 - <6m
>6m - <7,5m
>7,5m - <9m
>9m - <12m
>12m - <16m
>16m - 20m
>20m
Fig. 4
7
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.1.4
Monitoring
g
category
I
Additional requirements
If smoke detectors:
Detection of smokeless fires
Variants
D/T
6
Detection of smokeless and
smoke-forming fires
6
1
3
1
Fig. 5
Legend:
III
A2400
II
frequent combination
possible combination
F
ionization smoke detector
R
scattered light smoke detector
D/T
heat detector
S
IR flame detector
A2400 linear smoke detector
8
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.1.5
Smoke detectors
Heat detectors
Flame detectors
The permissible data can be found in the following tables with detector features.
If, due to impermissible deceptive phenomena, heat and flame detectors
have to be installed in rooms with monitoring category II, often other fire protection measures of a preventive and/or defensive nature are called for (see Fire Protection Planning,
CRP, document e431).
4.1.6
4.1.7
Special investigations
If the prevailing conditions are not covered by these guidelines, or not in sufficient detail,
such as unforseeable fire development, spread of fire phenomena, prevailing deceptive
phenomena etc. special investigations should be carried out, e.g. fire tests. For this purpose, analogue signal measuring detectors of the same type with evaluating and display
equipment are available.
4.2
Smoke detectors
Application:
Where smoke is the fire phenomenon to be expected
Where the smoke detectors are not excluded by the ambient conditions
Detection characteristics:
F-Types:
R-Types:
Linear Types:
9
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.2.1
Operating
principle
Application
Deceptive phenomena
F-Smoke
detector
Type/model
detector
F716i
Special features
F716Vi
F732
F906
F905
F900
F911
As for F910 but intrinsically safe for explosion hazard zones 1+2 acc. to EN 50 020
As for F910 but AFNOR standard (sampling
chamber supervised) no integration
F915
F930
10
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Detector setting in dependence of monitoring category, room criteria and room height
Application features
Monitoring
g category
g y
Fig. 6
Room criteria
<3
3...6
6...12
12...20
1
1
1
2
II
1
1
1
2
III
2
2
3
3
1
2
3
3
Smoke entry small
Smoke entry large
For application in rooms with a room temperature of <0C, response sensitivity must be set
to setting 1.
permissible
ambient tem
perature in
C
Degrees of resistance to
Humidity
max. ap
plication
height above
sea level (m)
IEC protec
tion cat.
cat
(detector /
base)
dry dust
Fibres (heavy
fibre content)
Accumulation of
moist, dirt, grease
transient
max.
-10 ...+60
75C
1500
IP 43
very good
adequate
unsuitable
10m/s
5m/s
(V >6m/s sensitivity increase until false alarm)
-25 ...+80
75C
1500
IP 43
very good
specially
with small
smoke entries
good
critical possibly,
check using test
10m/s
5m/s
(V >7m/s
sensitivity
increase
until false
alarm)
8m/s
(V >10m/s
sensitivity
increase
until false
alarm)
-25 ...+80
75C
3000
(set to sensitivity setting 3)
IP 43
very good
specially
with small
smoke entries
good
critical possibly,
check using test
10m/s
-25 ...+80
75C
3000
(set to sensitivity setting 3)
IP 43
very good
good
adequate
10m/s
continuous
max.
11
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.2.2
Operating
principle
Application
Deceptive phenomena
R-Smoke
detector
Generally suitable for monitoring rooms where mainly pyrolysis smouldering fires are expected e.g. for:
- Electrical installations of all
kinds *
- Bed rooms
- Hotel rooms
- Car parking garages
- Restaurants
- Rooms with high rate of air
exchange
Also suitable for monitoring installations e.g.:
- Switching cabinets
- Air sampling systems
* Mi
Mixed
ed monitoring with
ith
F-types in a ratio of 1 : 1
recommended
Type/model
detector
Special features
R716i
R910
R925
R930
R936
12
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Detector setting in dependence of monitoring category, room criteria and room height
Application features
Monitoring
g category
g y
Fig. 7
Room criteria
<3
3...6
6...12
12...20
1
1
1
2
II
1
1
1
2
III
2
2
3
3
1
2
3
3
Smoke entry small
Smoke entry large
For application in rooms with a room temperature of <0C, response sensitivity must be set
to setting 1.
permissible
ambient tem
perature in C
Humidity
max. applica
tion height
above sea
level (m)
IEC protec
tion cat.
cat (de
tector / base)
-10 ...+60
75C
unlimited
-25 ...+75
75C
unlimited
Degrees of resistance to
dry dust
Fibres (heavy
fibre content)
Accumulation of
moist, dirt, grease
IP 43
good to
adequate
inadequate
unsuitable
no influence
IP 43
good
(compensation circuit)
inadequate
critical *
no influence
transient
max.
continuous
max.
-25 ...+75
75C
unlimited
IP 43
good to
adequate
inadequate
unsuitable
no influence
-25 ...+75
75C
unlimited
IP 43
very good
good
critical *
no influence
13
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.2.3
Operating
principle
Application
Deceptive phenomena
Extinction
smoke detector
Type/model
detector
A2400
Transmitter
A2400S
Receiver
A2400E
Special features
14
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
permissible
ambient tem
perature in C
-10 ...+60
Humidity
max. applica
tion height
above sea
level (m)
IEC protec
tion cat.
cat (de
tector / base)
75C
unlimited
IP 52
Degrees of resistance to
dry dust
Fibres (heavy
fibre content)
Accumulation of
moist, dirt, grease
very good
good
adequate
continuous
max.
no influence
periodic
external
cleaning
15
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.3
Operating
principle
Heat detector
Dual
heat detector
Maximum heat
detector
Application
Deceptive phenomena
D716
Standard, EN 54-5,
category 2
high resistance to corrosion
D900
Standard, EN 54-5,
category 1
high resistance to corrosion
D901
As for D900, but intrinsically safe for explosion hazard zones 1+2, EN 50 020
D915
D920
As for D900, but for higher ambient temperature (EN 54-8, temperature range 1)
D921
As for D920, but intrinsically safe for explosion hazard zones 1+2, EN 50 020
D2417
Standard, EN 54-5,
category 1
with integrated base (Scandinavia)
D2401
The detector contains two measuring systems with different response sensitivity
Type/model
detector
Water vapour
Rapid temperature fluctuation
e.g. large doors leading to
warm adjacent rooms
Special features
System 2 sensitive
Water vapour
D2401 Ex
As for D2401, but intrinsically safe for explosion hazard zones 1+2, EN 50 020
D2409
D2410
T2418
Standard, EN 54-8,
Temperature range 1 (+74 ... +90C)
with integrated base (Scandinavia)
T2416
Standard, EN 54-5,
category 2
with integrated base (Scandinavia)
16
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Degree of resistance to
Permissible
ambient tem
perature in 5C
Humidity
-10 ...+50
75C
-25 ...+50
Dry dust
Fibres (heavy
fibre content)
Accumulation of moist,
dirt, grease, etc.
transient
max.
continuous
max.
very good
very good
75C
very good
very good
-40 ...+50
75C
IP 43
very good
very good
-25 ...+50
95C
IP 65
very good
very good
-25 ...+60
95%
IP 65
very good
very good
-25 ...+270
100% for
sensor +
capillary
tube
IP 65
very good
very good
-40 ...+50
75C
IP 43
very good
very good
-25 ...+50
17
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.4
Operating
principle
IR flame
detector
IR flame
detector
Type/model
detector
Application
Deceptive phenomena
S610
(1-channel
detector)
S2406
(2-channel
detector)
S2406 Ex
S2406 SEx
As for S2406, but intrinsically safe for explosion hazard zones 1+2, EN 50 020
1) Electrical welding only at short distance to
detector
S2406 R
S2406 REx
Special features
18
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Degree of resistance to
permissible
ambient
temperature
in C
Humidity
Accumulation of moist,
dirt, grease, etc.
-20 ...+70
75C
IP 43
No influence
-40 ...+70
95C
IP 65
No influence
transient
max.
continuous
max.
95C
19
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4.5
4.5.1
Operating principle
Application
Type/model unit
Permissible ambient
temperature in C
Humidity
Special features
-25 ...+80
75C
IP 30
AT50
AT51
AT50Mi
AT51Mi
ATAN50
100C
IP 66
Model for wet and very dusty applications and in explosion hazard areas
Application in intrinsically safe areas
20
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.1
General
5.1.1
Smoke
Radiation
Fig. 8
In general, a fire detection system with a decreasing monitoring area per detector becomes more sensitive because the distance between the detector and fire location is
smaller. Beyond a certain size of monitoring area (particularly with smoke detectors) an
increase in the number of detectors produces little gain in sensitivity. We must strive for a
sensible ratio between cost and effectiveness when choosing a suitable monitoring area.
Thus the number and arrangement of automatic detectors depends on:
the type of detector used and its sensitivity
room geometry
ambient conditions
They must be so chosen and arranged so that incipient fires can be detected at an early
stage (see also the section on system test fires).
Each room to be monitored must contain at least one automatic detector. Smoke and
heat detectors are mounted on the ceiling or wherever the fire phenomena to be expected
spread and accumulate. As far as possible, flame detectors require direct line of sight to
every likely fire location and, therefore, are best installed high up in the corners of a room.
21
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
The detector arrangement must be adapted to the prevailing features of the room such as
ceiling construction, room division, (wall recesses etc.) furnishings, fittings etc. Other aspects to be taken into account:
It must be possible for the corresponding fire phenomena (smoke/heat/ radiation) to
reach the detectors
Foreseeable deceptive phenomena
Foreseeable mechanical influences (vibration etc.)
Correct testing and exchanging
Often when positioning detectors it is necessary, for aesthetic or construction reasons, to
make a compromise whereby the maximum prescribed distances or monitoring areas
may be exceeded by up to 10%.
5.1.2
Cross-zoning
When detectors are cross-zoned the permissible monitoring area for the same type of
detector must be reduced in principle by 50%, providing that the alarm signal is only actuated by two linked detector zones. Excluded from this exception is the cross-zoning of
detectors for specific purposes to prevent false alarms, e.g. smoke detectors in parking
garages. Here the detectors must be uniformly and symmetrically distributed through the
two zones.
Zone A
Zone B
Fig. 9
22
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.1.3
Special cases
Special cases which are not covered by the Cerberus guidelines, or not in sufficient detail,
and the causes of which lie in the fire hazard, the type of detector used, room geometry,
room utilization, or the ambient conditions, require individual treatment. It may be necessary to determine the number of detectors and their locations by carrying out fire tests
with measuring detectors and the corresponding measuring equipment.
5.1.4
Symbol
Designation
Symbol
Designation
Fire detector
Heat detector
Flame detector
Response indicator
...
(Mi)
...
(Si)
AT50
(Mi)
AT50
(Si)
Control element E90Ci
(E90Ci)
Master element E90Mi
(E90Mi)
23
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2
Smoke detectors
5.2.1
h
3
Room height
(Accumulation of heat)
h
2
h
1
Open
fire
Fig. 11 Decrease in smoke density and smoke distribution with increasing room height
The higher the room, the further away from the ceiling the detector must be mounted. The
smoke which gradually cools as it rises cannot break through the cushion of warm air.
The mounting of point-type smoke detectors on the wall is only effective if the room is of
small dimensions.
Smouldering fires usually have insufficient thermal current to carry smoke to high ceilings.
24
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
h3
Room height
(Accumulation of heat)
h2
h1
Smoldering fire
25
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
open fire
smouldering fire
AM
Small monitoring area because:
- room height ~3m
- the detection of smaller incipient
fires (both open and smouldering
fires) is possible by means of
smoke detectors on the ceiling.
open fire
smouldering fire
AM>
AM>>
Application of smoke detectors with increased 1) response sensitivity as partial compensation for the smoke dilution
in large volumes of air.
Fig. 13 Taking increasing room height into consideration when planning a fire detection
system
1)
The immunity to deceptive phenomena of this smoke detector with increased sensitivity is normally maintained by increasing room height itself, as deceptive phenomena without any appreciable inherent thermal current cannot reach the ceiling.
26
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.2
3
1
AM [m2]
Degree of danger
1 little fire danger
2 moderate fire danger
3 major fire danger
Fig. 14 Monitoring area per smoke detector as a function of room height and degree of
danger
Degree of danger 2 can be chosen for most applications
Degree of danger 1 should only be chosen:
if all danger to life can be eliminated
if no valuable or irreplaceable articles are stored in the room concerned
if the fire risk is low
if other fire protection measures would virtually preclude fire spread
if no smoke logging, in particular involving corrosive fission products, can occur in adjacent areas
Degree of danger 3 is recommended if:
if there is serious danger to life
if valuable and/or irreplaceable articles are stored in the room concerned
if the loss of goods or installations would threaten the existence of the owner of the
premises concerned
if the fire risk is classified as high
27
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.3
>10
<20
0.9
>20
<30
0.8
>30
<40
0.7
>40
<50
0.6
>50
<75
0.5
>75
<100
0.4
>100
0.3
Fig. 15 Reduction of the monitoring area per detector in rooms with an abundant
change of air
AM
AMk
= Monitoring area
= Monitoring area rectified
28
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.4
AM
S
2
A M + s x + s x d
4
s max + 1.2 x
AM
A
d max + sM
Fig. 16 The relationship between the monitoring area and the maximum distance between detectors (s)
Maximum distance detector wall
1
2 s +
1.2 A M
2
For practical reasons the maximum distance detector wall must be measured at right
angles horizontally to the wall and not to the corner of the room (this is why the factor 1.27
is rounded down to 1.2).
29
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Fig. 17 below shows the symmetrical distribution of detectors maintaining the permissible detector spacing and the monitoring area AM.
AM
S/2
s + 1.2 A M
Fig. 17 Distribution of detectors
12m
(s)
6m
(s/2)
8.3m
(d)
A 400m2
4.15m
(d/2)
16.6m
4.15m
(d/2)
6m
(s/2)
24m
30
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.5
15cm
0.5m
0.5m
5.2.6
Stored goods or racks whose distance from the ceiling is less than 0.30m, prevent smoke
spread to such an extent that they must be treated as room dividers (walls).
31
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.7
Roof structures
Roof structures which are connected to the room to be monitored and whose surface
area exceeds 10% of the total ceiling area, or providing this portion of the ceiling is >AM,
must be regarded as separate rooms. Otherwise they need not be taken into account.
Roof structure
Roomheight
4m
min. 10cm
max. 30cm
10% h
Ceiling
unsuitable zone
max s
Floor
32
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.8
Ceiling vents
With ceiling vents (Cupolux, domed vents, dampers etc) detectors must be mounted in
the vicinity of the vents providing the distribution of the vents, the monitoring area and the
maximum distance between detectors permit this.
~40cm
~40cm
33
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.9
Galleries
Basically galleries or similar structures which do not allow smoke to pass should be
treated in the same way. The degree to which smoke can penetrate trellis-work must be
judged on the basis of the section on Grid pattern dropped ceilings.
Detectors must be provided beneath galleries which do not permit smoke penetration,
providing:
b >s
whereby s must be calculated from the monitoring area in relation to room height beneath the gallery.
1/
3
2/
3
If
34
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.10
Void
Grid pattern
Position A
h
Ceiling opening
Position B
Pos. A
Pos. B
50%
yes
no
I
or
II
III
Detector arrangement
>50%
yes or no
50%
yes
no
50 - 70%
yes or no
>70%
yes or no
provided h 4m
x
35
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.11
36
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
~1m2
seal off
Fig. 32 Detector arrangement with fresh air ceiling vents covering a large area
Return air:
Point-type return air ceiling vents (diffusers etc.): Do not mount detectors in front of return
air vents, rather in the turbulence zone.
Fig. 34 Detector arrangement with return air ceiling vents spread over a large area
37
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Return air grille in the wall directly below the ceiling: Detectors must be mounted in front of
the return air grille
Fig. 36 Return air vents in the wall near the floor: In addition to the detectors on the ceiling, monitoring of the return air duct with the air-sampling unit ASD-duct detector unit is recommended
38
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.12
Ventilation ducts
Fresh air duct
In order to prevent smoke-logging when fire breaks out in an air conditioning or ventilation
system (e.g. motor or filter fire) the air-sampling unit ASD-duct (with F smoke detectors)
must obviously be installed immediately after the equipment concerned on the outgoing
side.
Fig. 38 Monitoring of the return air with air-sampling unit ASD-duct in the return air
sectors
39
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Tips on installation:
The distance to duct change of direction or change of cross-sectional area must be
approx. 1.5 times duct circumference
Air sampling tubes should as far as possible be in the centre of the duct
Good accessibility for service work
Recommendation: Provide service hatches immediately next to the ASD-Duct
Minimum duct depth:
The tubes may not be shortened to less than 15 cm. Each tube must have at least 6 air
holes (if necessary drill additional holes). Replace the end plug.
5.2.13
Staircases
In staircases at least one detector must be installed on the top floor ceiling. If other floors
are separated from the top floor by a door, another detector must be mounted on the ceiling in front of this door. In staircases which are >12m high and have no vertical separation, an additional detector must be installed at least on every third floor or every sixth
landing.
Smoke barrier
between basement
and upper floor
40
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.2.14
0,6m
0,5m
5.2.15
Ceiling constructions
The monitoring area and detector arrangement will vary according to the slope of the
ceiling.
For practical reasons the slope of the ceiling is not given in degrees, but as a ratio of
height to length of slope. This factor is called the slope (N)
No slope:
(h = 0)
N + h + 0
b
Fig. 41 Room with ceiling slope N = 0
(see section 5.3 Detectors on flat ceilings)
Slight slope:
N1
N2
b1
b2
h + v 0.2
h + v 0.2
b2
b1
Fig. 42 Ceiling slopes N1 = N2 0.2
41
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Ceilings with N 0.2 are regarded as flat ceilings (see section 5.3 Detectors on flat
ceilings).
If a ceiling (or roof) has surfaces with different slopes, e.g. north light roofs, then the least
steep slope applies providing it is not less than s and therefore can be ignored. If both
parts of the ceiling are steeper than s, then each part can be treated separately.
Moderate slope:
N1
N2
h
h
b1
0, 2 t h + v 0.5
b1
b2
0, 2 t h + v 0.5
b2
Fig. 43 Ceiling slopes N1 = N2 >0,2 0.5 (see section 5.4 Detectors on sloping
ceilings)
Steep slope:
N1
N2
h
h
b1
h + u 0.5
b1
b2
h + u 0.5
b2
Fig. 44 Ceiling slope >0.5 (see section 5.4 Detectors on sloping ceilings)
42
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
N2
h
h
b2
b1
N 2 + h + u 0.2
b2
Fig. 45 Asymmetrical ceiling with N2>0.2
Ceilings with N >0.2 are regarded as sloping ceilings (see section 5.4 Detectors on sloping ceilings).
5.3
5.3.1
3 up to 30cm
20 up to 50cm
6 up to 7.5m
7 up to 40cm
25 up to 60cm
7,5 up to 9m
10 up to 50cm
30 up to 70cm
9 up to 12m
20 up to 80cm
50 up to 100cm
up to 6m
43
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.3.2
3
1
AM [m2]
5.3.3
s + 1, 2 A M
100
80
60
40
20
0
s [m]
0
10
12
14
16
max. detector spacing (s)
5.3.4
Room space A AM
The detector must be mounted on the ceiling so that 1/2 s is not exceeded.
44
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.3.5
Fig. 50 Cutting down on the number of smoke detectors by utilizing smoke accumulation in the room
Symmetrical distribution of detectors
Once the monitoring area AM per detector and therefore the maximum permissible spacing of detectors s is known, the symmetrical distribution of detectors in large rooms is
made as follows:
l
Length: l = 55m
Width: b = 35m
Area: A = 55 x 35m
= 1925m2
Monitoring area: AM
= 100m
45
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Detector distribution
Variant 1:
Begin with the length
Variant 2:
Begin with the width
lengthwise direction l:
width b:
M l + sl + 55 + 4, 58 5
12
2. Effective detector spacing in
lengthwise direction l:
s + l + 55 + 11m
5
Ml
35
Mb + b
s + 12 + 2.9 3
width b:
s b + b + 35 + 11.70m
3
Mb
in the width:
lengthwise:
width b:
length l:
A
s bmax. + sM + 100 + 9.10m
11
l
b
M b + s max.
+ 35 + 3.84 4
9.1
b
Width b:
s b + b + 35 + 8.75m
4
Mb
6. Check:
sl x sb AM
11 x 8.75 = 96.2m2
i.e. <100m2
A
s lmax. + s M + 100 + 8.50m
11, 7
b
l
M l + s max.
+ 55 + 6.5 7
8.45
lb
length l:
s lb + l + 55 + 7.85m
7
Ml
sl x sb AM
11.,7 x 7.85 = 91.8m2
i.e. <100m2
5.3.6
Narrow rooms
In narrow rooms the smoke spread is channelled. Therefore detectors may be spaced
further apart. The monitoring area AM may not be exceeded however.
Providing the room width is s, detector spacing s can be increased as follows:
46
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Monitoring area
AM [m2]
180
160
140
120
s l + 1.6 A M
100
80
60
40
20
0
s [m]
0
10
12
14
16
18
20
Maximum detector spacing (s)
sl
sl
5m
<s
7m
14m
7m
1, 2 80
+ 5.36m + 5.4m
2
i.e. the room width is <s and the lengthwise spacing may not exceed sl.
s l + 1.6 A M + 1.6 80 + 14.3m
Actual detector spacing of 7 or 14m is always slightly below the permissible maximum
detector spacing.
In corridors not wider than 3m, in general detector spacing may be in creased to a maximum of 15m.
7,5m
15m
15m
3m
47
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
15m
15m
5.3.7
Joists
Minimum distance detector joist
Joists obstruct the spread of smoke. The minimum distance joist detector is 0.5m.
50cm
48
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
h Joist height
h Room height
AU
AM
49
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Ratio
Ratio
AU
AM
h
h
-0.05 *
0.06-0.1
0.16-0.2
0.21-0.25
0.26-0.3
- 0.1
0.9
P1
0.9
P2
0.9
P2
0.8
P2
0.8
P2
0.8
P2
0.11 - 0.2
0.9
P1
0.9
P3
0.8
P3
0.7
P4
0.6
P4
0.6
P5
0.21 - 0.3
0,9
P1
0.8
P4
0.7
P4
0.6
P4
0.5
P4
0.5
P7
0.31 - 0.4
0.9
P4
0.8
P4
0.8
P4
0.7
P4
0.6
P5
0.5
P7
0.41 - 0.5
1,0
P4
0.9
P4
0.8
P5
0.8
P5
0.7
P5
0.6
P7
0.51 - 0.6
1.0
P1
0.9
P5
0.9
P5
0.8
P5
0.8
P5
0.7
P7
0.61 - 0.7
1.0
P1
0.9
P5
0.9
P5
0.9
P5
0.8
P7
0.8
P7
0.71 - 0.8
1.0
P1
1.0
P6
1.0
P7
0.9
P7
0.9
P7
0.9
P7
0.81 - 0.9
1.0
P6
1.0
P6
1.0
P7
1.0
P7
1.0
P7
0.9
P7
0.9
>0.3
Treat as room
division, ii.e.
division
e the
joist forms a
wall
AU = Inter-joist area
AM = Monitoring area
*
K
P
0.11-0.15
h =
h =
Joist height
Room height
P2
P3
On joist
P4 On joist, provided the width of the inter-joist area is s; otherwise in the centre of
each 2nd inter-joist area. If, as a result, detector spacing is exceeded, detectors must be
arranged in a staggered (chess board) pattern in every 2nd inter-joist area, whereby a
reduction of up to 15% of the number of detectors required is permissible.
P5 On joist provided the width of the inter-joist area is s; otherwise install one detector in each inter-joist area.
P6 One detector in the centre of each inter-joist area, provided that s can be maintained; otherwise arrange the required number of detectors on the joists.
P7 Install one detector in the centre of each inter-joist area, provided that the increased
maximum detector spacing ( 1.6 A Mk ) is not exceeded; otherwise arrange the required
number of detectors on the joists.
Application example for calculating the reduced monitoring area AMk
Room height
4m
Joist depth
1m
AU 24m2
Calculate
AMk
50
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Solution:
1. Calculate the ratio
h + 1 + 0.25
4
h
2. Calculate the ratio
AU
+ 24 + 0.3
80
AM
Ratio
Ratio
AU
AM
h
h
-0.05 *
- 0.1
0.06-0.1
0.16-0.2
0.21-0.25
0.26-0.3
0.9
P1
0.9
P2
0.9
P2
0.8
P2
0.8
P2
0.8
P2
P1
0.9
P3
0.8
P3
0.7
P4
0.6
P4
0.6
P5
0.11 - 0.2
0.21 - 0.3
0.9
P1
0.8
P4
0.7
P4
0.6
P4
0.5
P4
0.5
P7
0.31 - 0.4
0.9
P4
0.8
P4
0.8
P4
0.7
P4
0.6
P5
0.5
P7
0.41 - 0.5
1.0
P4
0.9
P4
0.8
P5
0.8
P5
0.7
P5
0.6
P7
0.51 - 0.6
1.0
P1
0.9
P5
0.9
P5
0.8
P5
0.8
P5
0.7
P7
0.61 - 0.7
1.0
P1
0.9
P5
0.9
P5
0.9
P5
0.8
P7
0.8
P7
0.71 - 0.8
1.0
P1
1.0
P6
1.0
P7
0.9
P7
0.9
P7
0.9
P7
0.81 - 0.9
1.0
P6
1.0
P6
1.0
P7
1.0
P7
1.0
P7
0.9
P7
0.9
>0,3
Treat as room
division, ii.e.
division
e the
joists forms a
wall
AU = Inter-joist area
AM = Monitoring area
*
K
P
0.11-0.15
h =
h =
Joist height
Room height
51
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
s + 1.2 A Mk
100
80
60
40
20
0
s [m]
0
10
12
14
16
Max. detector spacing (s)
s l + 1.6 A Mk
100
80
60
40
20
0
s [m]
0
10
12
14
16
18
20
Increased detector spacing
52
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Example:
AM 100m2 / AU 120m2
8m
8m
8m
8m
4m
6m
24m
12m
6m
4m
40m
Fig. 63 Example of detector arrangement on ceilings with joists (AU >0.9 AM)
Width of inter-joist area <s s
h/h 0.1
Distribute as for flat ceilings, however, maintain minimum space between detector and
joist of 0.5m.
h/h >0.1
Maximum detector spacing is increased in the longitudinal direction because smoke
spread is promoted in this direction.
s l + 1.6 A Mk
The required number of detectors (M = A/AM) is so arranged that each inter-joist area
contains at least one detector. Take advantage of increased detector spacing in the longitudinal direction!
Example: AM 100m2
15m
7.5m
25m
7.5m
30m
53
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
The required number of detectors (M = A/AM) are distributed on the joists so that s or s is
not exceeded.
31.9m
2.9m
Example: AM 100m2
35m
26.1m
2.9m
Example: AM 100m2
35m
54
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.4
5.4.1
Smoke channelling
Sloping ceilings tend to channel smoke towards the ridge where we find the heaviest concentration of smoke. For this reason the basic area to be monitored AM and detector
spacing are increased.
5.4.2
3
1
10 20
2
40
60
1
80
AM [m2]
100
120
140
160
132 - 147
180
200
55
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.4.3
Room height in m
(RH)
up to 50 cm/m
(N 0.5)
distance a
from 50 cm/m
(N 0.5)
distance a
up to 6
3 up to 30cm
20 up to 50cm
6 up to 7.5
7 up to 40cm
25 up to 60cm
7,5 up to 9
10 up to 50cm
30 up to 70cm
9 up to 12
20 up to 80cm
50 up to 100cm
h
h
N + h2
b
h
h
b1
Fig. 71
b2
56
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.4.4
z + 0.75 A Mk
100
80
60
40
20
0
z [m]
0
9 10
Fig. 72 Reference figure z for determining the required number of rows of detectors
Fig. 75 allows us to determine the number and spacing of rows of detectors using the
reference figure z.
5.4.5
N1
N2
b1
N1 +
h 1
b1
N2 +
h 2
b2
b2
N2
h2
h2
N1
b2
h1
b1
h
h
Joist ratio
h
h
57
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
The number and arrangement of rows of detectors parallel to the ridge is determined taking into account the slope of the ceiling N1 and N2 and the comparison of the two parts of
the building width b1 and b2 with the reference figure z.
With very narrow buildings, the ratio room height to joist depth is taken into consideration
as an additional criterion.
In Table Fig. 75 the various criteria for the comparison are shown horizontally and vertically. At the point of their intersection which meets the conditions for the comparison, we
can read off the corresponding number and arrangement of detector rows.
b1 / b2
1/3
1/3
0
8 [m]
2/5
2/5
0
10 [m]
1/2
1/2
0
10
11
12 [m]
2/3
2/3
0
10
11
12
13
14
15
16 [m]
1/1
1/1
0
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 [m]
58
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Application example:
z = 9m
See detector
arrangement
Flat ceilings
with joists
h1
9m
h 0, 3
h
5m
(
)
15m
4m
N 1 + 0, 83
4m
b 1)b 2 u z
2
b1, b2
z
5m
+ 0, 33
15m
5m
N2 +
15m
b2
6m
b1
b1, z
b2 z
1/2b2 z
1/3b2 z
b2>z, 2/3b2 z
1/2b2 z
2/5b2 z
1/3b2 z
2/3b2>z, 1/2b2 z
1/3b2 z
1/2b2>z, 2/5b2 z
2/3b1 z
1/2b1 z
2/5b1 z
1/3b1 z
Key:
N1 <0,5 N2 <0,5
N1 >0,5 N2 >0,5
N1 <0,5 N2 >0,5
N1 >0,5 N2 <0,5
1/3b2 z
+
_
Yes
No
1/
2
1/
3
1/
5
4m
b1 z
7.5m
b2
15m
7.5m
b1
6m
b1
b2
Fig. 75 Determining the required rows of detectors parallel to the ridge and their distribution over two parts of the
building width b1 or b2
59
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.4.6
b
The minimum number of detectors M is calculated with
A/AM. The result is then rounded up to the nearest figure.
1/2x
The greatest possible detector spacing x at the ridge depends on the monitoring area A and full building width b
and may not exceed 2z.
b1
b2
1/2x
1
Detector spacing x is: x + 2
M
Fig. 77 Longitudinal detector arrangement with 2 rows of detectors with no row of detectors in the ridge
60
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
b1
b2
Detectors required M
1-3
3*
4-5
6-8
9 - 11
11
12 - 14
14
15 - 17
17
18 - 20
20
etc.
etc.
1/2x
x
x
l
x
x
x
My
Mx
My
61
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
4 rows of detectors with no row of detectors in the ridge (result from Fig. 75)
b2
b1
1/2x
My
My
My
My
1
Detector spacing x is: x + 4
M
62
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
b1
b2
Detectors required M
1-5
5*
6-7
8 - 13
12
14 - 18
17
19 - 24
22
25 - 29
27
etc.
etc.
1/2x
x
x
l
x
x
My2
My1
Mx
My1
My2
63
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.4.7
b1
b2
The minimum number of detectors is calculated with A/AM. The result is then rounded up to the nearest uneven number.
1/2x
x
x
l
x
x
Mx
The number of detectors Mx in the ridge is: Mx + M * 1
2
The number of in the lateral row is: My = Mx + 1
Detector spacing is: x + 1
My
Fig. 81 Longitudinal arrangement of detectors with 2 rows of detectors with a row of detectors in the ridge
64
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
3 rows of detectors with a row of detectors in the ridge (result from Fig. 75)
b1
b2
The minimum number of detectors M is calculated with A/AM. For a practical arrangement the result must be corrected according to the following
table:
Result
Detectors required M
1-3
3*
5-7
8 - 10
10
11 - 13
13
14 - 16
16
17 - 19
19
etc.
etc.
1/2x
x
x
l
x
x
Mx
My1
My2
The number of detectors Mx in the ridge and in the outer lateral row My2 is each: Mx + My 2 M * 1
3
The number of detectors My in the lateral row is: My1 = Mx + 1
Detector spacing x is: x +
1
My 1
Fig. 82 Longitudinal arrangement of detectors with 3 rows of detectors with row of detectors in ridge
65
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
3 rows of detectors with no row of detectors in the ridge (result from Fig. 75)
b1
b2
1/2x
66
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
b1
b2
The minimum number of detectors M is calculated with A/AM. For a practical detector arrangement the result must be corrected acc. to the following
table:
Result
1-4
5-6
7 - 10
11 - 15
16 - 19
20 - 24
25 - 28
etc.
Detectors required M
4*
6
10
14
18
22
26
etc.
x
x
My1
Mx
My1
My
The number of detectors Mx in the ridge and in the outer lateral row are each: Mx + My 2 M * 2
4
The number of detectors My on the two inner lateral rows is: My1 = Mx + 1
Detector spacing x is: x +
1
My 1
<1/4s
67
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5
Heat detectors
5.5.1
5.5.2
N1
(h = 0)
N2
h
h
h
h
b
b1
N + h
b
N 1 + h
b1
b2
N 2 + h
b2
= flat ceiling
= moderately sloping ceiling
= steeply sloping ceiling
68
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.3
Heat channelling
With sloping ceilings, heat travels across the slope of the ceiling to the highest point. This
creates a concentration of heat in the ridge. For this reason the basic monitoring area AM
and detector spacing are increased.
5.5.4
0.2
>0.5
AM
AM
AM
30m2
30m2
7.80m
30m2
9.20m
30m2
10.60m
>30m2
20m2
6.60m
30m2
9.20m
40m2
12.00m
Fig. 89 Table Monitoring areas and detector spacing for heat detectors
* If a ceiling (or roof) has surfaces with varying slopes, e.g. north light roofs, then the one with the least slope is
determinative provided it is not shorter than 1/2s and therefore can be ignored. If both halves of the ceiling are
1/2s, then each half can be calculated separately.
5.5.5
69
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.6
0.15m
0.5m
0.5m
5.5.7
70
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.8
5.5.9
Ceiling ventilation
With ceiling ventilation (Cupolex, mushroom vents etc.) detectors may be installed
near the vents provided this is permitted by the arrangement of the vents, the area to be
monitored and the maximum detector spacing.
~0.4m
~0.4m
71
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.10
Galleries
Basically, galleries or similar structures which suppress the influence of heat flow should
be treated in the same way. The permeability of the flow of heat through trellis constructions must be assessed as under the section Grid pattern dropped ceilings (5.5.13).
Detectors must be provided beneath galleries without heat flow permeability provided:
b >1/4s
whereby the monitoring area s must be based on the room height beneath the gallery.
1/
3
2/
3
h + t 0.1
h
h + is u 0.1 and b u 1
h
detectors must always be provided beneath the gallery. The monitoring area must be calculated according to the room height beneath the gallery.
72
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.11
~1m2
abdichten
5.5.12
10m
10m
73
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.5.13
Void
Position B
Position A
h
Ceiling opening
Grid pattern
>50%
yes or no
yes or no
yes or no
yes
no
no
yes
no
yes
nein
yes
yes or no
<25%
yyes or no
yyes or no
no
yes
5.5.14
Size of opening
Detector arrangement
Pos. A
Pos. B
X
X
X
X
Joists
Joists must be taken into account according to room height and depth of joist.
9
8
7
6
5
4
3
2
1
0
Joists need
not to be
taken into
account
0.1
0.2
0.3
0.4
0.5
0.6
Detectors to be installed
in each inter-joist area
0.7 0.8
Joists in m
74
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
If they have to be taken into account refer to the following table Fig. 101:
20m2
>12m2
8 - 12m2
6 - 8m2
4 - 6m2
<4m2
IJA*
2. IJA
3. IJA
4. IJA
5. IJA
30m2
>18m2
12 - 18m2
9 - 12m2
6 - 9m2
<6m2
IJA
2. IJA
3. IJA
4. IJA
5. IJA
Heat
detector
Fig. 101 Detector arrangement where joists have to be taken into account
5.5.15
<s
s<b2s
min. 0.5m
s<b2s
1/
3
1/
6
1/
6
s<b2s
1/
3
5/
12
5/
12
1/
6
s<b2s
Fig. 103 Arrangement of detector rows with a ceiling slope of N from 0.2 up to 0.5
For ceilings with varying slopes, the row of detectors in the ridge is installed on the least
steep slope. The greater the variation in slope, the more the row of detectors must be
offset.
75
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
0.2 - 0.5m
Fig. 104 Detector arrangement in the ridge with varying slope of ceiling
For north light roofs, detectors can be mounted as for roofs with joists where the roof
structures are less than 1/4s provided h + 0.3 . h The monitoring area AM must in this
h
case be calculated as for a flat ceiling.
76
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.6
5.7
5.8
77
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
5.9
5.9.1
40m
<40m
40m
40m
>40m
78
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Fig. 106 Locations of manual call points in rooms with increased fire danger
Zones of manual call points without mechanical self hold may not be operated via intermediate alarm memories.
5.9.2
Mounting height
In general manual call points should be mounted at a height of 1.5 to 1.7m from the floor.
This prevents unwanted operation (e.g. confusion with light switches in the dark).
They may be mounted at a lower height when built into hose cabinets or control desks.
1.50 - 1.70m
79
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
6.1
Terminology
A detector zone is a group of detectors connected in one detection line, for which an
indicator (fire location indicator) is provided at the control unit.
The detection line is the monitored electrical transmission line which connects the fire
detectors to the control unit.
6.2
6.2.1
Attic
Location
Attic
Upper floor
Upper floor
Ground floor
Ground floor
80
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Zone
Attic
Zone
Ground floor
south
Fire wall
Zone
upper floor
Zone
Ground floor
north
Zone
Staircase
Fig. 109 Sub-division of the entire monitoring area into detector zones
A number of rooms should only be combined in one detector zone
if the rooms are adjoining, if there are not more than five rooms
or
if the rooms are adjoining, if their entrances are easy to supervise and if easily visible
external response indicators are mounted in the vicinity of the entrances to signal a fire
in the room concerned.
Control unit
Fig. 110 One detector zone for max. 5 adjacent rooms, external response indicator is unnecessary
Control unit
Fig. 111 One detector zone for more than 5 adjacent rooms, external response indicator
necessary
Normally flame detectors form detector zones of their own because these detectors often
monitor large areas.
81
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Detectors installed in raised floors, dropped ceilings, cable, air conditioning and ventilation systems, should form a special zone of their own, or it must be possible to determine
in a simple way, e.g. using external response indicators, in which area detectors have
responded.
Zone
Room
External response indicators
on the wall (or under glass
panel in raised floor)
External response
indicators under glass
(or external response
indicators on the wall)
Zone
Floor void
Zone
Room and ceiling void
all external response
indicators on the wall
Fig. 112 Formation of detector zones in areas which are not immediately visible
6.2.2
82
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Zone A
F
Upper floor
Fire department
access
F
Basement floor
Zone B
Fig. 113 Formation of zones of manual call points in staircases with more than two basement levels
6.2.3
6.3
6.3.1
Restrictions on application
In order that a fire can be located quickly and clearly no more than 25 automatic detectors
or 10 manual call points may be connected in one detector zone.
6.3.2
83
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
6.4
MAT
MAT
220V / 50Hz
Fig. 115 Switching off of slave detectors with addressable detector system MS9i
84
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
7.1
7.2
Fire department
access
CZ..
CT..
Display and
operating terminal
CT..
Display and
operating terminal
Fig. 116 Example of a fire detection system with remote display and operating terminal
85
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
7.3
7.4
86
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Alarm
8.1
General
Alarm must enable rapid intervention of fire-fighting forces. Basically the Cerberus
alarm concept (CAC) should be used.
See Planning guidelines, document e804, Manual ZH4.1 and document e1089, Manual
CS11.
87
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
9.1
General
Installations which form part of the fire protection concept can be actuated automatically
by the fire detection system.
This includes:
the switching off of air conditioning or ventilation systems
the closing of dampers
the closing of fire doors
the switching on of smoke and heat venting systems
the switching on of emergency lighting
the sending of lifts to the ground floor and blocking them there
the switching off of machines and equipment of all kinds
The actuation of such installations must not have a negative influence on the fire detection system.
9.1.1
9.1.2
External control
P
Ventilation
control voltage
88
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
9.1.3
9.1.4
External control
+
Performance check
Switch-off indicator
9.1.5
Safety precautions
Depending on the type of installation or device, actuation can have consequences which
question the advantages of automatic actuation.
If in doubt choose manual instead of automatic actuation.
89
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
10
10.1
General
Deceptive alarms can be largely avoided by choosing a suitable type of detector, response sensitivity, detector arrangement and by taking into account ambient conditions.
The fire detection systems immunity to deceptive alarms is more important than high response sensitivity.
The following possibilities are just a few examples of how deceptive alarms can be
avoided. Decide in each case on which measures are the most suitable.
10.2
Possible measures
10.2.1
Fire detectors
General information: Set all automatic detectors or detector zones to alarm intermediate data storage.
F-type detectors
a) In low rooms (room height 3m):
use integrating detectors (blue marker) or switch detector zone to alarm intermediate
data storage
install detectors outside ceiling areas above permanent work places (e.g. near the
door in small offices)
set detectors to sensitivity level 1
b) In dusty and low rooms:
use dust-resistant type of detector (e.g. F910 with small smoke entries or F930 with
drift inquiry)
shorter servicing interval (exchange of detectors)
set detectors to sensitivity level 1
c) In rooms with transient deceptive phenomena caused by work processes:
install detectors outside areas subject to deceptive phenomena
use integrated detectors (blue marker) or switch detector zone to alarm intermediate
data storage
use detectors with adjustable smoke entries
set detectors to sensitivity level 1
R-type detectors
As for F-type detectors, except:
use F-type detectors or linear smoke detectors in dusty rooms.
90
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
D/T-type detectors
Do not install detectors in places where, due to natural or operational sources of heat, the
ambient temperature can cause the detector to respond.
no direct solar radiation on the detector
install at a distance from equipment which radiates heat such as baking ovens, hot air
blowers, hot steam etc.
protect detectors from warm air currents with metal screening
Rate-of-rise heat detectors
Replace the rate-of-rise heat detector by a maximum temperature detector if the
above measures are not successful.
Flame detector S610 (single channel detector)
Keep detectors as far as possible from heat radiators
the detector may only look towards the open air through glass, therefore, screw tight
window to prevent it being opened
do not expose detector to vibrations (oscillations) so that deceptive phenomena are
not modulated
reduce detector sensitivity, e.g. use stages 3, 2 or 1
use flame detector S2406 (dual channel detector)
Flame detector S2406 (dual channel detector)
Keep detectors as far as possible from modulated heat radiators
when used in open air the detector axis must not be pointed directly at the sun (observe suns movement, it should shine from behind detector)
do not expose detector to vibration (oscillations), so that deceptive phenomena are
not modulated
reduce detector sensitivity, e.g. use stages 3, 2 or 1
if there are very hot and modulated heat radiators near where a detector must be
installed, protect using the polyethylene foil provided.
10.2.2
10.2.3
91
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
11
It is assumed that fire protection fire planning has been carried out according to Cerberus document 431 and that the fire
detection system has to be planned as part of the all-round fire protection measures.
7 Alarm
- Specify alarm concept (2-stage alarm/discreet alarm/possibly evacuation).
Explanation of abbreviations
<
>
a
b
d
d
h
h
l
s
sl
x
z
smaller than
greater than
smaller than or equal to
greater than or equal to
Lateral distance (S detectors)
Full building width (gable width)
Maximum detection distance (S detectors)
Reference measurement for maximum
detector spacing (s)
Height
Partial height
Length
Maximum detector spacing
Increased maximum detector spacing
Effective detector spacing parallel to ridge
Reference measurement to determine the
number of detector rows required for
gable roofs
A
AF
AU
AM
AMk
K
M
Mm
Mx
My
N
92
Fire & Security Products
Siemens Building Technologies Group
e432d
06.2002
Keyword index
C
Complete monitoring, 2
D
Deceptive phenomena, 5
E
Exchange of air, 28
Explanation of abbreviations, 92
F
Fire control installations, 88
Fire load, 3
Fire phenomena, 21
Fire resistance, 4
Fire risk reduction, 4
Fire spread, 6
Fixed extinguishing system, 4
O
Open incipient fire, 5
P
Partial monitoring, 2
Planning symbols, 23
Point-type detector, 14
S
Smoke distribution, 24, 25
Smouldering fire, 6
Smouldering incipient fire, 5
Sources of ignition, 3
93
Fire & Security Products
Siemens Building Technologies Group
06.2002
94
Fire & Security
Document
no. Products
e432d
Siemens Building Technologies Group
Edition 06.2002
Manual 06.2002
CRPB
Section 2