Topic:

Technology and Solutions


Protection and Substation Automation

END FAULT
PROTECTION
APPLICATION

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 1

BASICS

Topic Objectives
Objectives
r Definition Protection Zone - Physical Zone
r Definition End- Fault Condition
r Fault clearance without EFP
r Fault evaluation
r EFP application
r Fault clearance with EFP
r End- Fault Condition in a bus- coupler
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 2

r CB auxiliary circuits
r Modern protection systems
r BBP - additional CB functionality on feeders
r Future standards

Definition Protection Zone - Physical Zone


protection
zone

2 CTs
(overlapped
protection zones)

protection
zone

1 CT

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 3

protection
zone

protection
zone
line zone

busbar zone

(physical)

(physical)

Definition End- Fault Condition


End - Zone

2 CTs
(overlapped
protection zones)

End - Fault

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 4

1 CT

End - Zone

Busbar Configurations

How will an End- Fault condition


be cleared in different busbar
configurations (without any EndFault Protection) ???
CT
line side

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 5

single or multiple
busbar

1 1/2 breaker
busbar

CT
bus side

CT
overlapped
Selectivity
Speed
Selectivity
Speed

Fault clearance (without EFP)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 6

Busbar

I. Multiple BB, CT line side

Fault clearance (without EFP)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 7

Line

I. Multiple BB, CT line side

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 8

Line

Busbar

Fault clearance (without EFP)


II. Multiple BB, CT bus side

Fault clearance (without EFP)


II. Multiple BB, CT bus side

Line Distance

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 9

OC Back- up

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 10

Line

Busbar

Fault clearance (without EFP)


III. Multiple BB, CT overlapped

Fault clearance (without EFP)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 11

III. Multiple BB, CT overlapped

Fault clearance (without EFP)


IV. 1 1/2 CB BB, CT line side

OC Back- up

OC Back- up
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 12

Line Distance

Fault clearance (without EFP)


V. 1 1/2 CB BB, CT bus side

OC Back- up
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 13

OC Back- up

Fault clearance (without EFP)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 14

VI. 1 1/2 CB BB, CT overlapped

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 15

Fault Evaluation
CT
line side

CT
bus side

CT
overlapped

single or multiple
busbar

++

++

Selectivity

++

Speed

1 1/2 breaker
busbar

++

Selectivity

++

Speed

++

very good

acceptable

critical

Fault Evaluation
Conclusion:

An additional protection function is


required in CT bus side and 1 1/2 circuit
breaker configuration without
overlapped CTs

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 16

!!!

End- Fault Protection Function

End- Fault Protection Function


logic depending on the
switchgear configuration
(CT bus side, Line side;
1 1/2 CB)
CB open

EFP

~120 ms

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 17

feeder
current

&

I>
remote
tripping

intertripping

t = EFP pick up time (higher than the highest possible


arc extinguish time + safety time

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 18

Fault clearance (with EFP)

How will an End- Fault


condition be cleared in
different busbar configurations
(with End- Fault Protection)
???

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 19

Line

Busbar

Fault clearance (with EFP)


II. Multiple BB, CT bus side

Fault clearance (with EFP)


II. Multiple BB, CT bus side

Fault cleared selectively


!!!(~250ms)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 20

Intertripping

EFP
G

Fault clearance (with EFP)


IV. 1 1/2 CB BB, CT line side

Intertripping
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 21

Remote trip

EFP
Fault cleared selectively
!!!(~250ms)

Fault clearance (with EFP)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 22

V. 1 1/2 CB BB, CT bus side

Intertripping

EFP
Fault cleared selectively
!!!(~250ms)

End- Fault Condition in a Bus- Coupler

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 23

How will an End- Fault


condition be cleared in a
bus- coupler (without any
EFP)
???

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 24

End- Fault Condition in a Bus- Coupler


BB2

BB1

~
~

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 25

End- Fault Condition in a Bus- Coupler

End- Fault Condition in a Bus- Coupler

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 26

by the coupler
function of the
BUSBAR protection

End Fault Protection application


Summery:
An EFP function in strictly required in:
r multiple BB configuration with CT bus side
r 1 1/2 circuit breaker configuration without
overlapped CTs
It is not required in:
r configuration with overlapped CTs
It will reduce the tripping time in:
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 27

r a bus- coupler
r multiple BB configuration with CT line side

CB auxiliary circuits

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 28

What problem will


occur in case on a switch
onto fault situation
???

CB auxiliary circuits

CT bus side

EFP will trip the BB wrongly

flash over before CB


indicates closed

CB open !!!
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 29

CB closing
command

I>
EFP enabled

CB auxiliary circuits
CT line side

flash over before CB


indicates closed

CB open !!!
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 30

CB closing
command

I>
EFP enabled

EFP will trip the line remote end wrongly

CB auxiliary circuits

in case on a switch onto fault


situation the EFP will generate a
tripping signal before the closed
indication appears

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 31

(flash- over in the circuit breaker)

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 32

CB auxiliary circuits

How can this be avoided


???

CB auxiliary circuits

the protection system must be


informed in advance that the CB is
going to be closed

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 33

by the (manual) close command


of the CB

End- Fault Protection Function


logic depending on the
switchgear configuration
(CT bus side, Line side;
1 1/2 CB)
CB open

EFP

~120 ms

CB (manual)
EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 34

feeder
current

close command

I>

&
remote
tripping

intertripping

t = EFP pick up time (higher than the highest possible


arc extinguish time + safety time

CB / isolator auxiliary circuits


Phase
+
CB closing

Phase
+
NC aux.

coil

contacts

S
CB closed
protection

system
CB open
NC aux.

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 35

contacts
CB (manual)
close command
CB close
order
+

EFP_basics / 2003-04-01 / RW

ABB Switzerland Ltd. - 36