Electrical: Specifications
Electrical: Specifications
Page 1 of 4
Specifications
Cat Digital Voltage Regulator
Media Number -RENR7941-09
i05816864
Electrical
SMCS - 4467
Part Number - 361-8010
S/N - Part Number - 314-7755
S/N - Table 1
Specifications
Regulation
Regulator temperature
drift
Less than 1% for any 40 C (72 F) change over the ambient operating
temperature range.
Volts/Hz characteristic
that can be configured
Regulator stability
The regulator maintains stable output voltage within 0.25% for total
harmonic distortion of the generator output voltage waveform up to
30%. The regulator maintains stable output voltage within 0.50% for
total harmonic distortion of the generator output voltage waveform up
to 40%. Thee values are based on a typical 6-SCR bridge.
Telephone influence
factor (TIF)
Less than 50. Complies with MIL STD 461C Part 9 and VDE 0875
level N.
Harmonic tolerance
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 06/02/2015
Page 2 of 4
Over excitation
protection
Ambient operating
temperature
Storage temperature
range
40 C (40 F) to
+70 C (+ 158 F).
40 C (40 F) to
+85 C (+ 185 F).
Power dissipation
Shock
Vibration
Salt fog
Weight
1.47 kg (3.24 lb.).
Electromagnetic
compatibility
Power supply
CSA
CE
Conformity
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 06/02/2015
Page 3 of 4
View Image
Illustration 1
Regulation characteristic
g01040043
Table 2
Summary of Operating Parameters
Parameter
Specifications
Voltage Regulation
Rating
120 to 15000 V
PM
SE
Internal Excitation (IE)
Generator Type
Voltage (1)
Power Input
80 to 264 V
(3)
100 to 280 V
(1)
Frequency
50 to 400 Hz
Maximum Continuous
Output Rating
Burden (Continuous)
Voltage
Current
Voltage
Current
63 V or 125
V
12 or 10 A
125 V or 250 V
25 or 20 A
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 06/02/2015
Page 4 of 4
Voltage
Sensing
90 to 600 V
Maximum Current
1 VA
Maximum VA Burden
Reactive Droop
5A
Exciter Field
Resistance
(1)
Minimum Resistance
3 Ohms
1 VA
Maximum Resistance
39 Ohms
As the CDVR input voltage increases, the PWM duty cycle decreases. As PWM duty cycle decreases, system
stability may decrease as well. Powering the CDVR with a voltage closer to the low end of this range is preferred.
https://sis.cat.com/sisweb/sisweb/techdoc/content.jsp?calledpage=/sisweb/sisweb/med... 06/02/2015