Static Analysis of Slug Flow
Static Analysis of Slug Flow
Introduction
Calculation of Slug Force
Static Analysis
Inputs Required
Assumptions
INTRODUCTION
Slug Flow is typical two phase flow where a wave is picked up periodically by the
rapidly moving gas to form a frothy slug, which passes along the pipe at a greater
velocity than the average liquid velocity.
In this type of flow, slugs can cause severe and, in some cases, dangerous vibrations in
piping systems because of the impact of the high-velocity slugs against fittings such as
bend, Tee etc.
Slug flows generate dynamic fluid forces, which may induce structural vibration.
Slug Flow
SLUG FORCE
Slug force is equal to the change in momentum with respect to time. Refer the below
attached figure:
STATIC ANALYSIS
INPUTS REQUIRED FOR ANALYSIS:
Parameters required for Slug force calculation like slug density or liquid density, two
phase velocity etc.
It is assumed that the slug is formed across the full cross section of the pipe for the
maximum impact. This configuration is least probable for vertically down word flow
as no hold up is possible for accumulation of liquid and eventual formation of slug.
Hence slug force at elbows for vertically downward flow lines are not considered.
It is assumed that the reader knows normal static analysis of piping system using
Caesar II.
T1=100 degree C
T2=75 degree C
P1=15 bar
So if we use a DLF of 2 then each of axial and orthogonal force will be 4240N. We have to
incorporate this force in Caesar II input spreadsheet. Check the below mentioned figure for
direction of forces.
Now we will input the axial and orthogonal forces at all changes in direction as shown in
attached figure.
Similarly input forces in all bends (other than vertically downward bends).
Next step is to prepare the required load cases. Few additional load cases need to be prepared
for static analysis of slug force. The same has been shown in the below mentioned figure.
OUTPUT REPORT
Additionally We have to check code compliance for load cases L14 to L17 and ensure
that the values are well within code allowable values.
We have to check forces and displacements for load cases L1 to L9.