Richcomm BMS Installation & Configuration
Richcomm BMS Installation & Configuration
,Ltd
Tel: +86 20 6685 4299
www.richcomm.com.cn
User Guide
1. Network Diagram
1.Connect the BDIT modules to ports group 1-6(RJ45 type) of Batt Manager Host
through network cable;
2.Connect Batt Manager host with computer through RS232 port (if the computer do
not with RS232 port, need prepare a USB-RS232 cable);
3. Long press the ESC button and press the AC-POWER In button at the same time,
the Batt Manager Host will display connecting and mean have enter configuration
status;
Note: BDIT module need to connect to 12V power supply(can directly connect to 12V
battery output, also can use other 12V power supply)
Run the program BDIT Config Tool, Choose a correct serial port and clickopen
com
Then read the voltage and modify BDIT module address.(read the address bit first,
then write a new address bit)
Choose a correct serial port and click the open com button
Note: the address bit of each BDIT module can not be the same, must start
from 1 and write by sequence.
and
cathode) connect to the No.1 single battery(anode and cathode), BDIT module should
stick close to single battery to capture data of high accuracy;
Note: pay attention to short circuit, for the connection, the terminal of BDIT module
should be removed first, when the terminal( anode and cathode) connect well with
battery( anode and cathode), finally install the terminal to BDIT module.
2) Connect the RJ45 port of the BDIT to the group 1~6 RJ45 port with a network wire
(568B type wire)
3) Connect the battery clamp of the second BDIT module to the second module;
connect the RJ45 port to the RJ45 port of the previous BDIT;
Showed as:
Note: Temperature sensor should be in serial connection to the last BDIT module,
temperature module no need to config address bit. One set of battery Manager only
need 1 temperature sensor.
The fire wire which connects battery with UPS should go across the current sensor,
then the terminals of the current sensor like GNDMV-V+
should be connected
to the Current port of the Batt manager like GINV-V+ r, the dial switch of Batt
Manager all should be off.
Note: Please pay attention to current direction when install current sensor, the arrow
direction of current sensor should be same with battery string discharge direction
Insert Netmate III adapter to the slot of Batt Manager Host, and connect to the
computer with UTP network cable
IP Address Setting
Open the web browser to input default IP address 192.168.0.100, User Name admin,
Password: admin, the home page will display as below:
7. Basic Configuration
Click Host Program, then click Connecting the Host; if connection succeed, it
will display as showed; if connection fails, please check the wiring connection;
Battery Type: if it is high discharging rate battery, please select High discharging
rate battery, if not, please select Conventional Battery
Battery Capacity Unit: Ah or Wh
If for old battery,
BDIT module amounts: Input real BDIT (single battery) amounts, if none, input 0
MODBUS AddressThe Batt manager use MODBUS address to access to the detector
through MODBUS protocol.
MODBUS Communication Type: Choose according to needs
MODBUS Baud rate: Choose according to needs
Other MODBUS Communication Serial Port Configuration: 8 bit data bits, no parity,
1 stop bit, no hardware flow control.
Discharging Depth: When discharging depth is higher than this value, the host will
give alarm
Backup Time: When discharging backup time is lower than this value, the host will
give alarm
Life Alarm: When battery capacity is lower than percentage of battery nominal
capacity,the host will give alarm
Periodical Maintenance: The intervals of battery periodic maintenance (at least 20%
discharging), generally it is 90days , and the host will give alarm if 20% discharge is
not occurred in this period.
Annual Inspection Alarm: The intervals of battery annual maintenance (at least 80%
discharge), generally it is 1 year. It alarms if 80% discharge is not occurred in this
period.
Upper Limit of Temperature, Voltage, Discharge Current: It alarms when
corresponding value surpass it.
Lower Limit of Temperature, Voltage, Discharge Current: It alarms when
corresponding value surpass it.
Version:
The parameters of the host hardware and software versions can be read on this
interface
Time Setting:
The Batt Manager time can be read or set.
pack life damage and the reliability declining of backup electric system c
Note: For newly installed host or the host have replace for monitoring battery string,
both need initialize self-learning data