SIHISuperNova Programme
Range: ULN
Self-primming volute casing pump to EN 733 / DIN 24255*
PUMP DESCRIPTION: ______________________________
SERIAL NUMBER: ____________________
Operating instructions
Safety issues
Chapter 1
Safety instructions and compliance
Intended application
Chapter 2
Application, description
Planning the installation
Chapter 3
Requirements, piping system, accessories
Unpacking, storage, transport
Chapter 4
Supply, interim storage, corrosion protection
Installing the pump
Chapter 5
Assembly at site, tools, checks
Start-up and shut-down
Chapter 6
Important requirements
Maintenance, dismantling, assembly
Chapter 7
Intervals, cleaning
Troubleshooting
Chapter 8
If something does not work
Technical data
Chapter 9
Dimensions, permissible values
Annex
Chapter 10
Technical data, dimensions table, sectional drawings
*
With certain exceptions see Technical Catalogue
Attention: Both the pump and/or the pump set must be installed and commissioned by qualified technical
personnel only and these installation, commissioning and operating instructions must be strictly observed.
Failure to do so could result in:
danger to you and your colleagues,
the pump or the pump unit may be damaged,
Note that the manufacturer is not liable for damages resulting from failure to observe these instructions.
Please be aware of your responsibility to your colleagues when working on the pump or the pump set!
Safety instructions marked with
included in this Operating Instructions and in the
Supplementary Operating Instructions, which must be attached to this Operating Instruction, have to
be considered in particular when operating this pump in potentially explosive atmospheres!
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Safety issues
Page 1 of 3
Chapter 1
1. Safety
the identification plate
This operating manual gives basic instructions,
and that these are kept legible.
which must be observed during installation,
operation and maintenance of the pump. It is
1.2
therefore imperative that this manual is read by
Qualification and training of
personnel
the responsible personnel / operator(s) prior to
The
assembly and commissioning. It must always be
maintenance, inspection and assembly must be
kept available at the site of pump installation.
adequately qualified. The scope of responsibility
It is not only the general safety instructions
and supervision of the personnel must be exactly
contained in this chapter Safety which must be
defined by plant management. If the staff do not
observed,
have the necessary knowledge, they must be
but
also
the
specific
information
provided in the other chapters.
trained
personnel
and
responsible
instructed.
This
for
task
operation,
may
be
performed by the machine manufacturer or
1.1
Identification of safety
symbols in the operating
instructions
supplier on behalf of the plant management.
Moreover, plant management must ensure that
the contents of the operation instructions are fully
Safety symbols are given in these operating
understood by plant operators and other relevant
instructions. Non compliance with these would
personnel such as maintenance staff.
affect safety and are identified by the following
1.3
symbol
Hazards in case of non
compliance with safety
instructions
Non compliance with the safety instructions may
result in risk to personnel as well as to the
Danger symbol as per DIN 4844-W9
(ISO 3864 - B.3.1)
environment and the pump/pump set and result in
the loss of any right to claim damages.
For example, non-compliance may result from, or
Or in case of danger of electric current with:
lead to, the following:
failure of important functions of the pump/pump
set/plant
failure of specified procedures of maintenance
and repair
Danger symbol as per DIN 4844 W-8
(ISO 3864 - B.3.6)
exposure of people to electrical, mechanical
and chemical hazards
danger to the environment owing to hazardous
The word
ATTENTION
substances being released.
identifies those safety regulations where noncompliance may pose a danger to the pump and
its function. It is imperative that the appropriate
safety information is attached to the pump/pump
set, for example:
an arrow indicating the direction of rotation
symbols indicating fluid connections
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Safety issues
1.4
Page 2 of 3
Compliance with regulations
relating to safety at work
Chapter 1
operative again. Prior to re-starting the machine,
the instructions listed under first commissioning
When operating the pump the safety instructions
are to be observed.
contained in this manual, the relevant national
accident prevention regulations and any other
1.7
service and safety instructions issued by plant
Safety instructions for the use in
areas with explosion hazard
management must be observed.
1.5
Safety instructions relating to
operation
If high or low temperature pump/pump set
components involve hazards, steps must be
taken to avoid accidental contact.
Guards for moving parts (e.g. couplings) must
In this section information is given for operation in
areas where an explosion hazard exists.
1.7.1 Complete pump sets
not be removed from the pump/pump set while
If the pump is combined with other mechanical or
in operation.
electrical components in one set, the category of
Any leakage of hazardous (e.g. explosive,
the complete unit will correspond, based upon the
toxic, hot) fluids (e.g. from the shaft seal) must
Directive 94/9/EC, only to that category with which
be drained safely so as to prevent any risk to
all of its components comply.
persons
or
the
environment.
Statutory
Note:
regulations are to be complied with.
Hazards from electricity are to be avoided by
These comments are of particular importance
VDE-
when pumps, which conform to a given category
specifications and the bye-laws of the local
of Directive 94/9/EC, are powered by a driver
power supply utilities).
which is not in the same category.
the
user
(see
for
example
the
Although the pump may bear the Ex sign, the set
1.6
Safety instructions relevant for
maintenance, inspection and
assembly work
should not be used in areas with an explosion
hazard when the motor is not classified for this
application.
It is the plant managements responsibility to
This means that plant management personnel
ensure that all maintenance, inspection and
should always check that all elements of the set
assembly
work
is
comply with the Directive 94/9/EC.
personnel
who
have
performed
by
adequately
authorized
familiarised
themselves with the subject matter by studying
1.7.2 Execution of coupling guards
this manual in detail.
Coupling guards that are to be used in areas with
Any work on the machine must only be performed
an explosion hazard, have to fulfil one of the
when it is at a standstill. It is imperative that the
following criteria:
procedure
for
shutting
down
the
machine
described in this manual is followed.
consist of non-sparking material, e.g. brass.
if they consist of sparking material, e.g. steel
Pumps and pump sets, which convey hazardous
sheet, they must be designed in such a way
media, must be decontaminated.
that the rotating parts will not come in contact
On completion of the work all safety and
with any part of the guard if errors, that could
protective guards must be re-installed and made
be foreseen, are committed by the user, e.g if
a person steps on the guard.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Safety issues
Page 3 of 3
Chapter 1
1.7.3 Monitoring technical
parameters
1.10 Warranty / guarantee
When using pumps in areas with an explosion
operation if:
risk, the operator must check the following
the
Sterling Fluid Systems guarantee satisfactory
pump
is
installed
and
operated
in
parameters regularly:
compliance with these instructions and in
leakage of shaft seals
operating conditions approved by Sterling Fluid
bearing temperature
Systems
that the pump is always filled with liquid during
operation
modifications are only undertaken with Sterling
Fluid Systems written agreement.
that the pump does not operate against a
closed valve for any length of time.
The operator must ensure that pumps, which
show evidence of abnormal operation, are
switched off and not started again until the cause
of the abnormal operation has been eliminated.
1.7.4 Avoiding external damage
In areas with a risk of explosion the operator must
ensure that the pumps and or pump set is not
subjected to external impacts e.g by heavy
objects.
1.8
Unauthorized alterations and
production of spare parts
Modifications may be made to the pump/pump set
only after consultation with,and written approval
from, the manufacturer. Using spare parts and
accessories authorized by the manufacturer are in
the interests of safety. Use of other parts may
exempt the manufacturer from any liability.
1.9
Unauthorized mode of operation
The reliability of the pump/pump set can only be
guaranteed if it is used in the manner intended
and in accordance with the instructions of this
manual. The specified limit values must under no
circumstances be exceeded.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Intended application
Page 1 of 3
2. Application
2.3
The pump is to be used only for the operating
Chapter 2
Construction and mode of
operation
conditions stated by the customer and confirmed
ULN pumps are horizontal, self-priming single
by the supplier. Guarantee is assumed within the
scope of the Sterling Fluid Systems conditions
stage volume casing pumps with dimensions and
of sale.
Their back pull out construction allows the
Appropriate application and operating conditions
disassembly of the complete bearing unit towards
are contained in the attached data sheets.
the drive side without removing the pump casing
nominal outputs acc. to EN 733 / DIN 24255.
out of the pipe system.
The side channel suction stage is arranged at the
2.1
Warning of misuse
drive side of the volute casing. It is connected in
parallel to the liquid pumping stage and works
according to the sucking through principle.
ULN pumps are preferably used when it is
necessary to suck in and to handle without
problems and automatically, pure resp. turbid not
The pump may only be used for the
aggressive liquids which do not contain any
application(s) stated. Otherwise hazards for
solids.
people and environment may arise.
ATTENTION
Do not exceed fluid density stated.
Otherwise, there is a the danger of motor
overload.
The pump must not be operated beyond its
characteristic curve otherwise there is a
danger of cavitation and motor damage.
2.2
Accessories
The accessories included in the scope of supply
are indicated in the delivery note or in the order
confirmation. The corresponding operating and
installation instructions are also indicated in the
Annex relating to accessories.
If it is intended to mount other accessories on the
pump or on the pump set, please inform the
manufacturer in advance in order that appropriate
technical advice can be given.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Intended application
Page 2 of 3
Chapter 2
2.4 Description
Type
size
Hydraulic + Bearing
A speed = 1450 rpm
B speed = 2900 rpm
Shaft seal
AAE: Unbalanced standard mechanical seal. Orings: Perbunam
ULN
32125
to
125250
B Two greased
antifriction bearings
AA1: Unbalanced standard mechanical seal. Orings: Viton
Casing gasket
Material design
0A: Cast iron GG25
0C: Cast iron GG25,
Bronze G-CuSn10 impeller
2: flat gasket
without asbestos
3B: Bronze G-CuSn10
Alternatively
Alternatively
A, B
AAE, AA1
Alternatively
0A, 0C, 3B
B
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Intended application
Page 3 of 3
2.5
Example of a pump designation:
Chapter 2
Shaft sealing
Depending on the application, different shaft
1-3 4
sealing executions are offered (see 2.4)
5-7 8-10 11 12 13-15 16-17 18
ULNC 100 200 A B AAE OA 2
Casing gasket
Construction
utilised in the following cases:
if the pump draws from a suction line,
if the pump is fed by a feed line with a
pressure of less than 0.5 bar or
Shaft sealing
Bearings:B
Hydraulic: A/B
mechanical seals according to DIN 24960 are
if the pumped liquid is at or near its boiling
point.
Impeller size
Nominal discharge
Pump series
ATTENTION
Section 2.4 does not contain the codes for all
variations of mechanical seals. Where the code is
not included or replaced by QQQ, consult the
relevant data sheet of the mechanical seal
supplier (e.g. special execution of the mechanical
sealing in a back to back position).
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Planning the installation
Page 1 of 2
3. Planning the installation
Chapter 3
3.1.1 Suction line / inflow line
See the sketches below for the optimum layout of
3.1
Piping system
pump installation for flow and suction lift
operation.
ATTENTION
Note the arrows on the pump branches
indicating the direction of flow.
Choose nominal widths of the pipelines
according to the nominal widths of the pump
branches or larger ones with the
corresponding reductions.
Flange sealing must not protrude on the
inside.
Ensure that the pipework is clean before
installing of the pump.
positive suction head operation
suction lift operation
The suction line has to be laid acc. to fig. 1. The
lift of the suction line by the dimension "H" is
necessary to secure sufficient service liquid during
the priming phase of the pump.
H > nominal width suction side L > 400 mm
Support the pipework in order to avoid
distortions at the pump components (risk of
damage to pump components)
Avoid abrupt changes of cross section and
direction.
Where different diameter pipework is to be
used, connection should be by eccentric
fig. 1
transition pieces. This will avoid the formation
of air pockets in the pipework.
For difficult pumping on the suction side, to
stabilise the flow, a pipe length 15 times the
diameter of the suction branch should be
It is recommended that a filter is installed in front
of the pump with a filter surface of at least 3 times
the pipe cross section (approx. 100 meshes/cm).
installed before the suction branch.
When handling fuel the manometric suction
head must not exceed 3 m.
The flow rate in the suction line or inflow line,
must not exceed 2 - 3 m/s.
The suction opening of the suction line should be
well below the liquid level, and a strainer should
be used.
The strainer must be far enough from the bottom
to avoid excessive inlet losses, which could impair
pumping performance. It is advisable to check that
there is no leakage.
A shut-off valve should be installed in the feed
line. It must be closed for maintenance work.
It should be installed in order to avoid air pockets
forming in the spindle cap, i.e. with the spindle in
a horizontal position or pointing vertically
downward.
For local contact details:
www.sterlingfluidsystems.com
5
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Planning the installation
Page 2 of 2
Chapter 3
3.1.2 Discharge line
For flow regulation, a valve must be installed
behind the pump. If non-return valves are used,
they should close smoothly. Pressure shocks
must be avoided.
3.1.3 Inlet and outlet connections
The various connecting points are shown in the
drawings. (See Annex, Chapter 10, point 10.1).
The air venting tube has to be connected above
the shut-off gate at discharge side or at the non-
fig. 3
return trap (fig. 2).
3.1.4 Pressure control
For consistent control of pressure, it is advisable
to install in the pipework a measuring point in front
of, and behind the pump.
3.2 Electrical connections
For the drive motor a mains connection is required
which complies with the European Regulations
and Directives for the Standards in Industry and
with the instructions of the local power supply
utilities of the country concerned.
fig. 2
The air, sucked in by the venting stage, is ejected
on starting-up through the discharge line without
counter pressure or at a counter pressure up to
0,5 bar
In case of priming conditions with higher counter
pressures the air venting tube has to be returned
into the suction tank (fig. 3).
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Unpacking, storage, transport
Page 1 of 2
4. Unpacking, storage, handling
4.4
Chapter 4
Handling
The pump or pump set must be lifted and handled
4.1
Safety measures
as shown in the following sketches.
Never stay below the suspended load.
Keep a safe distance while the load is being
transported.
Use only approved lifting appliances, which
are in good condition.
Adjust the length of the lifting appliances in
such a way that the pump and/ or the pump
set, is suspended horizontally.
Do not use the eyebolts on the pump
components for lifting the assembled pump or
the complete set.
Do not remove documents, which are
Pump without motor
attached to the pump.
Do not remove the protection covers from the
pump suction/discharge. Otherwise, there
may be a risk of contamination.
4.2
Unpacking
Before unpacking, a visual check of the packing is
recommended. If transport damage is visible, the
extent should be noted on the receipt or on the
delivery note. Potential claims must be lodged
immediately with the carriers or the insurance
company.
Pump set
4.3
Interim storage
If the pump or the pump unit is not installed
4.5
immediately after delivery, it must be stored free
In general, a protective coating is only applied to
from vibration in a dry room.
the following executions: OA, OC.
For local contact details:
www.sterlingfluidsystems.com
Protection against corrosion
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Unpacking, storage, transport
Page 2 of 2
Chapter 4
4.5.1 Removal of protective coating
To remove the protective coating, the pump
should be filled and drained several times using
appropriate agents, e.g. solvent naphtha, diesel
oil or alkaline detergent. Flush with water, if
necessary.
The pump must be installed and started up
immediately afterwards.
4.5.2 Renewing corrosion protection
If the pump has been supplied with a protective
coating and has to be stored, a new protective
coating should be applied after six months.
For suitable protective coatings, contact Sterling
Fluid Systems.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Installing the pump
Page 1 of 3
Chapter 5
5. Installing the pump
5.1
Requirements
5.4.3 Base, foundation
The pump and the pump set, must have been
The pump must be installed on a flat floor or
unpacked and handled as described in Chapter 4.
foundation free from vibration. In case of doubt
use vibration dampening feet.
5.2
Use of trained staff
The pump set must be correctly mounted on the
Only appropriately trained staff must undertake
foundations. To avoid distortion of the pump set
the work described in this chapter.
and/or the foundation, parallel shims must be
used between the base plate and foundation.
5.3
Safety measures
Prior to installing, checks should be made with
regard to:
- possible damage to the pump or the
pump set that may occur in transit
- ease of running ( check that the shaft is
free to rotate by hand )
Connect the pipework carefully to prevent the
- the foundation dimensions.
pumped liquid escaping during operation and
The following preparatory work must be carried
endangering operating personnel.
out before to placing the pump:
Ensure that the suction or inflow line, and the
- roughen and clean foundation surface
discharge line are closed by valves.
- remove shuttering/cores from the anchor
Ensure that all electrical connections are
holes
dead. Otherwise, there is a risk of electric
- blow the anchor holes clean
shock.
- check the position and dimensions of
Pay attention to relevant internal plant
the anchor holes against the arrangement
regulations.
drawing.
Avoid accidental contacts with hot
5.4.4 Installation of the set
components.
ATTENTION
Remove the protective coating by following
The complete set mounted on the base plate must
the instructions of Chapter 4. Otherwise there
be placed on the foundation with its foundation
is a danger of contamination .
(rag) bolts hanging below the baseplate.
5.4.5 Space required
5.4
General information
The space required for the pump set is set out in
the foundation plan or installation drawing.
5.4.1 Assembly tools
Ensure easy access to the shut-off and regulation
Special tools are not required for assembly and
valves as well as to any measuring instruments.
installation.
5.4.2 Permissible ambient conditions
The ambient temperature can be from -20 C to
+60 C. The atmospheric humidity should be as
low as possible in order to avoid corrosion.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Installing the pump
Page 2 of 3
Chapter 5
5.4.6 Position
In principle the ULN pumps are installed
half of the N-EUPEX B ( FLENDER ) coupling
horizontally.
must be 2 - 3 mm (see fig.).
If other manufacturers couplings are used, follow
the manufacturers instructions. After installation
on the foundation and connecting the pipework,
the coupling alignment must be checked and realigned, if necessary. Moreover, after reaching the
operating temperature the alignment of the
coupling must be checked again.
The coupling requires a guard that meets DIN
31001 in order to avoid accidental contact during
operation.
5.5
Motor
In any event, the operating instructions of the
Before assembly check the direction of rotation of
the motor (indicated by an arrow on the pump
coupling manufacturer must be followed, since the
coupling is a component incorporated by Sterling
casing). If this is not possible the direction of
Fluid Systems.
rotation of the complete unit can only be checked
ruler
only if the pump is filled.
In any event, the operating instructions of the
motor manufacturer must be followed, since the
motor is generally incorporated by STERLING
FLUID SYSTEMS into the pump set.
5.6
Alignment of the set
Place shims under the base plate on both sides of
The following is required a = a1 and b = b1
the foundation bolts, 10 mm from the base plate
edge. Use a spirit level to align the set.
If necessary, place shims between the foundation
bolts to prevent the base plate from sagging. Care
should be taken to minimize distortion of the base
plate during installation. The location of the driver
must not be higher than that of the pump. The
max. deviation from the shaft centre line is 0.1
mm.
The foundation bolts should be embedded in
concrete using quick-setting grout.
5.7
5.8
Checking before installation
Before installing the pump on the plant, the
following points must be checked:
1. is the electrical current to the drive motor
switched off?
2. are suction and discharge lines emptied and
closed by valves?
3. Is it possible to rotate the pump easily by
hand (for this purpose turn the fan of the
motor or the coupling)?
4. Have the latest internal/plant instructions been
Coupling
Instal the coupling avoiding hard blows, if
observed?.
necessary in warm condition. Arrange the pump
and motor on a level base. The shaft ends must
be aligned exactly. The distance between each
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Installing the pump
5.9
Page 3 of 3
Chapter 5
Mounting the pump and
installation into pipework
The following instructions must be carried out:
1. remove the protective covers from the pump
flanges and the auxiliary pipework
connections.
2. correctly insert the flange seals.
3. connect the suction or feed line.
4. connect the discharge line
The pump must be aligned with the pipework. The
pipework must be supported so that distortion
cannot occur when connecting the pump.
5.10 Final work
The following final steps must be undertaken:
1. check the tightness of the connecting flanges.
2. check for easy running of the pump (for that
purpose turn the motor fan or the coupling).
3. check the coupling alignment.
4. instal the coupling guard.
5.11 Hydrostatic pressure test
When subjecting the piping system to a
hydrostatic pressure test, exclude the pump from
the pressure test.
If it is not possible to test the pipework without the
pump, ensure that foreign material cannot enter
the pump.
The max. permmisible pressure for a
pressure test is 1.3 times the nominal
pump pressure.
The nominal pump pressure is indicated
in the tecnical data sheet.
Water should be used for testing
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Starp-up and shut-down
Page 1 of 3
6. Start-up and shut-down
operations
Chapter 6
If there is no bypass line, do not run the
pump with the control valve closed for any
6.1
Requirements
length of time.
The pump or the pump set, must be installed acc.
to the instructions of Chapter 5.
Safety measures should be taken by the
end user to ensure (for example by
means of a relief valve) that the
6.2
Use of trained staff
permissible pump casing pressure is not
Only appropriately trained staff must carry out the
exceeded during operation
work described in this chapter.
Repeat the alignment of the coupling at
operating temperature. Re-align the pump
6.3
Safety measures
or the motor, if necessary.
6.4
Electrical connection
The motor must be connected at set out in the
circuit diagram in the terminal box.
Electrical connections must be made
according to the European Regulations and
6.5
Directives for the Standards in Industry and in
Before switching on the pump unit, the following
compliance with the instructions of the local
points should be checked:
power supply utilities of the country
1. is all pipework connected and are the unions
concerned.
Checks before switching-on
tight?
Only appropriately authorized personnel may
carry out this work.
2. is the pump including the pipework filled
properly?
3. is the air ejector line connected properly?
ATTENTION
4. is the shut-off valve in the discharge line
closed?
Fill the pump correctly; otherwise the shaft
seal could be destroyed.
5. is the shut-off valve in the suction line
completely opened?
Fill the supply lines correctly.
6. is the motor ready for operation?
Check the direction of rotation only when the
7. is the direction of rotation of the motor
pump is filled.
correct?
Fill the pump slowly if hot media are being
(check by running the motor for a short time)
pumped in order to avoid distortions or heat
8. is the coupling aligned exactly?
shock.
9. has the shaft seal been installed?
When handling explosive, toxic, hot,
10. are the supply lines, if any, to the shaft seal
crystalline or corrosive media, ensure that
there is no risk to people or the environment.
Control the output at constant speed at the
open?
11. in the case of oil lubrication - has the bearing
housing been correctly filled with oil?
discharge side only. The valve at the suction
side must always be completely open during
operation to avoid the risk of cavitation.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems) 2001
Starp-up and shut-down
6.6
Page 2 of 3
Chapter 6
Start-up operation
ATTENTION
For starting proceed as follows:
1. Before the first start-up the pump has to be
filled with pumping liquid
Priming periods of more than 5 minutes are not
admissible, because of warming-up of the suction
2. open fully the valve on the suction side
stage.
3. close the valve on the discharge side
4. switch on the motor
5. check the pressure gauges at the pressure
measuring points
When pumping petrol or liquids with similar
If the pumping pressure does not increase
physical properties priming periods must be
consistently with increasing speed, switch off the
shorter than 3 minutes because of warming-up of
motor again and vent the pump one more.
the suction stage.
6. After reaching operating speed, regulate the
operating point of the pump by adjusting the
The alignment of the coupling should be repeated
valve in the discharge line (see technical data
at operational temperature. If necessary the pump
for permissible range of operation).
or the drive motor, respectively, is to be realigned.
Pumping against a closed valve in the discharge
line is permitted only if a minimum output via a
bypass line is guaranteed.
6.7
Switching frequency
Size
By means of safety measures at the plant (e.g.
overflow valve) it must be ensured that the
admissible casing pressure of the pump is not
exceeded by malfunction during operation.
Permissible number of
starts equally spaced
per hour
32-125, 32-160, 32-200, 32-250,
40-125, 40-315, 50-125, 50-160,
50-200, 50-250, 50-315,
65-125, 65-160, 65-200, 65-250,
65-315, 80-160, 80-200, 80-250,
80-315, 100-200, 100-250, 100-315
125-250
The suction stages of the ULN pumps are
constructed in such a way that the suction line is
6.8
Special instructions
evacuated and then the centrifugal stage gets
During operation the following points must be
liquid and will be able to pump. If penetration of
observed:
gas happens during pumping, the pumping flow
breaks down and the priming phase must begin
- control the speed and the delivery head
again and that partly under more unfavourable
- ensure that the pump runs without vibration
conditions than initially because the suction stage
- control the liquid level in the suction line and/or
is filled with liquid and must pump "free" itself.
inflow tank
- control the bearing temperature (max.
The capability of ULN pumps to handle gas is the
temperature 100 C)
same as of centrifugal pumps, i.e. max. 8 %
- shaft seal: As a rule leakage of some cm/h at
(referring to the output) can be handled during
mechanical seals occur as vapour or fog.
normal duty.
Additionally slight drop leakage may occur.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems) 2001
Starp-up and shut-down
Page 3 of 3
Chapter 6
ATTENTION
If the initial leakage does not disappear within 5
minutes of operation, stop the pump, dismantle
the seal and check for damage of the seal faces
and auxiliary sealing.
6.9
Shutting-down
Before shutting down close the valve on the
discharge side.
After shutting down, all valves may be closed.
If there is a risk of very low ambient temperatures,
remove the pump and then drain it using the
threaded plug 90.30.
When handling explosive, toxic, hot, crystalline or
corrosive media, ensure that people and the
environment are not endangered. Even if the
pump has been drained using the threaded plug
90.30, residues can remain in the pump. For
transport, the pump must be free from any
dangerous material. In case of extended periods
out of service, protect the pump against corrosion.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems) 2001
Maintenance, dismantling, assembly
Page 1 of 4
Chapter 7
7. Maintenance, dismantling,
assembly
7.1
lubricating nipple
Requirements
The pump or the pump set must have been shut
down in the manner described in Chapter 6.
7.2
Use of trained staff
Only appropriately trained and skilled staff should
undertake the work described in this chapter.
Only authorised personnel must undertake
electrical work associated with maintenance of the
pump/pump set.
7.3
Grease lubrication:
The roller bearings receive their first grease filling
in the factory.
Lubrication intervals:
-
Safety measures
at 2900 rpm approx. every 2500 operating
hours
at 1450 rpm approx. every 5000 operating
hours
Quantities:
Bearing support 25:
For explosive, toxic, hot, crystalline as well as
different pumping media ensure that people
(shaft diameter at drive journal 24 mm)
9 gr
and the environment are not endangered.
Flush the pump with clean liquid before
dismantling.
The working place for disassembly or
Bearing support 35:
(shaft diameter at drive journal 32 mm)
15 gr
assembly must be clean.
Before reinstallation, the pump must be free of
any dangerous material.
7.4
Maintenance and inspection
The pump needs only minimum maintenance after
the running-in phase.
The roller bearing on the pump side must be
removed, washed and filled with a new filling of
grease after approx. 10.000 operating hours, at
the latest after 2 years. The roller bearing on the
7.4.1 Bearing with grease lubrication
The pump is fitted with a roller bearing with
lifetime lubrication on the drive side, and a roller
bearing with a lubricating nipple (DIN 71412 Form
A) on the pump side.
Bearing support 45:
(shaft diameter at drive journal 42 mm)
22 gr
drive side (suffix 2RS) must be replaced.
In extreme operating conditions (wet and dusty
operation or high ambient temperatures), the
lubricating intervals must be shortened.
Only high grade lithium-based roller bearing
grease may be used for replacement or topping
up (e.g. Mobilux 2, Shell Aero Grease 16, Esso
Unirex N3).
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Maintenance, dismantling, assembly
7.4.2 Drive motor
Page 2 of 4
Chapter 7
7.5.3 Dismantling the pump
The drive motor is to be maintained according to
the manufacturer's instructions
7.4.3 Mechanical seal
The mechanical seal should have little or no
visible leakage. Where there is considerable
leakage, check the mechanical seal. To do this, it
is necessary to dismantle the rotating part(s).
7.5
Fig. 1
Dismantling
7.5.1 Preparation for the dismantling
Proceed as follows:
1.
The respective positions of the parts are to be
marked with a coloured pen or scribing iron.
2.
Unscrew vent pipe 71.10 complete with union
drain the plant, at least within the pump area,
3.
Unscrew hex. screws 90.10.
i.e. between the valves on the suction- and
4.
Lift module out of pump housing 10.20.
disconnect power to the motor
73.10, stop plug 75.70 and sleeve 73.11.
discharge side
if necessary, disconnect any measuring
probes or control devices and remove them
drain liquid from the pump by means of the
drain plug
Take precautions to support the complete module
the pump casing must not be detached from
and possibly to catch any leaking pumping
the pipe union
medium.
remove motor mounting bolts and move the
motor so that there is sufficient space to
remove the back pull out unit. When using a
spacer coupling repositioning of the motor is
not necessary.
dismantle guard coupling, pump feet and
coupling.
Fig. 2
7.5.2 Replacement parts
The item numbers necessary for ordering spare
5.
Unscrew shaft nut 92.20. Remove lock
parts are provided in the component parts list in
washer 93.10, impeller 23.00 and feather key
the Annex.
94.01.
6.
Unscrew hex. nut 92.02 and dismantle cover
16.10, spacer 10.90, impeller 23.50 and
feather key 94.02 and spacer 11.40 .
7.
Mark position of set collar 48.50 on shaft.
8.
Unscrew set collar 48.50, carefully remove
axial seal 43.30 and shaft seal housing 47.10.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Maintenance, dismantling, assembly
Page 3 of 4
Chapter 7
7.6.2 Points to be checked
The
ATTENTION
following
pump
components
must
be
checked:
The mating surfaces of the axial seal are
1. Check the axial seal for damage and wear. If
particularly vulnerable to damage and scratches.
the mating surfaces are damaged or worn, the
It is advisable to place these parts on a felt
surface.
axial seal must be replaced.
2. Check the split ring surfaces for damage and
wear. The difference in diameter between split
ring on impeller and the housing components
should be between 0.3 mm and 0.5 mm. If the
split rings are too
worn, they must be
replaced.
3. Check the suction stage and impeller for wear
and replace if necessary.
4. Bearing bushing 54.50 is to be replaced when
worn. It must be glued in with a special glue
(e.g.. Loctite 648).
Fig. 3
9.
Loosen bearing cover 36.00 by unscrewing
hex. screws 90.11.
10. Pull the shaft completely out of bearing
7.7
Assembly
7.7.1 Tightening torque
When tightening the bolts the following torques
must be used:
support 33.00.
11. Dismantle support foot 18.30 by unscrewing
hex. screw 90.12 and hex. nut 92.01.
Thread
Torque
M8
M10
M12
M16
M20
12Nm 25Nm 40Nm 90Nm 175Nm
7.7.2 Pump assembly
Proceed as follows:
1. as per fig. 4, assembly of shaft unit
Fig. 4
ATTENTION
12. Remove bearing 32.00 and 32.10 and spacer
tube 52.50 from shaft 21.00.
In roller bearing 32.00, the refill groove of the balls
must point in the direction of the impeller which is
still to be assembled.
7.6
Post dismantling activities
7.6.1 Hints for cleaning.
2. Slide pre-assembled shaft unit in bearing
Clean all parts.
support 33.00 and mount bearing cover 26.00
Clean the clearances and sealing surfaces
as per fig. 3. Screw on support foot 18.30.
with an appropriate liquid.
3.
Slide shaft sealing housing 47.10 complete
with axial seal counter ring over the shaft as
per fig. 2. Ensure that the connection for vent
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Maintenance, dismantling, assembly
tube 71.10 is flush with the corresponding
4.
Page 4 of 4
9.
Chapter 7
Insert seal 40.00 in spiral housing 10.20 and
bore in the bearing support.
slide the complete module in spiral housing
Slide axial seal 43.30 carefully onto the shaft
10.20. Insert hex. screws 90.10 and screw
using the assembly tool and then fix set collar
tight.
48.50 in the previously marked position.
ATTENTION
The sealing surfaces of the suction stage (i.e.
sealing surfaces between items 16.10, 10.90,
11.40, 47.10) are to be coated with liquid
sealant (e.g. Epple 33) before assembly.
The spacers are to be aligned on the basis of
the marks (fig. 5).
Rub Molykote Paste G into the mating surfaces
of spacer 10.90 and spacer 11.40.
Take into
account the
groove
position
Take into
account the
groove
position
Fig. 5
5.
Mount spacer 11.40, insert feather key 94.02,
mount impeller 23.50 and spacer 10.90.
6.
Screw set screws 90.21 in cover 16.10. Fit
cover and fasten to shaft seal housing 47.10
using nuts 92.02 and washers 55.02.
7.
Insert feather key 94.01, mount impeller
23.00 and hold in position with lock washer
93.10 and nut 92.20.
8.
Screw vent tube 71.10 complete with union
73.10, stop plug 75.70 and sleeve 73.11 in
the shaft seal housing.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Troubleshooting
Page 1 of 1
Chapter 8
8. Help in case of trouble
8.1
Use of trained staff
Trouble shooting must be undertaken only by appropriately trained personnel.
8.2
Symptoms, causes and remedies
Symptom
Cause
Output too low
- Counter pressure too high.
- Pump or pipeline, resp., not completely
filled.
- Suction lift too high or positive suction
head too low.
- Sealing gap too large beause of wear.
- Wrong sense of rotation.
- Casing or suction line leaky.
Pump loses its prime or does
not prime
- Pump casing, shaft seal, foot valve or
suction line leaky..
- Suction lift too high or positive suction
head too low.
- Loose or jammed particles in the
pump.
- Lliquid quantity in the pump not sufficient
- Air venting tube clogged
- Counter pressure too high for air ejection
- Casing screws not correctly
tightened.
Leakage of the pump
- Mechanical seal leaky
- Joints defective
Temperature rise in the pump
- Pump or pipeline not completely filled.
- Suction lift too high or positive suction
head too low.
- Pump is running against closed gate.
Pump runs unquiet or noisy
- Pump or pipeline not completely filled.
- Suction lift too high or positive suction
head too low..
- Pump is not properly leveled on the floor
or is
distorted
- Foreign matters in the pump.
Motor protection switch
switches off.
For local contact details:
www.sterlingfluidsystems.com
Remedy
Check the plant for contamination. Re-set
the operating point.
Vent and fill the pump as well as the
suction or inflow line, resp.
Check the liquid levels, open the shut-off
elements at suction side.
Clean the filters and dirt traps installed at
suction side.
Replace the worn out parts.
Modify the motor connection.
Replace the casing seal.
Check the flange connections
Replace the casing seal.
Check the shaft seal.
Check the flange connections..
Check the liquid levels, open the shut-off
elements at suction side.
Clean the filters and dirt traps installed at
suction side.
Open and clean the pump.
Fill the pump properly
Clean the air venting tube
Check the operating conditions of the
installation
Check the tightening torque of the casing
screws.
Check the condition of the mechanical
seal. If necessary, replace it.
Replace the joints.
Vent and fill the pump as well as the
suction line or inflow line, resp.
Check the liquid levels, open the shut-off
elements at suction side.
Clean the filters and dirt traps installed at
suction side.
Open the shut-off element at discharge
side.
Vent and fill the pump as well as the
suction line or inflow line, resp.
Check the liquid levels, open the shut-off
elements at suction side.
Clean the filters and dirt traps installed at
suction side.
Check the pump installation
Disassemble and clean the pump.
- Pump is not properly leveled or is
distorted.
Check the pump installation.
- The admissible operating conditions were
not complied with.
- Loose or jammed parts in the pump.
Observe the operating conditions stated in
the data sheet.
Open and clean the pump.
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV 2001)
Technical data
Page 1 of 4
Chapter 9
9. Technical Data
For technical information about the pump or pump
Direction of rotation:
set, which is not described in this chapter, see the
Clockwise seen from the drive end of the pump.
specific data sheet. Note that data relating to a
specific order may conflict with information
Materials of construction, and of shaft seals:
provided here. In any such case, the order
See Chapter 2.4.
specific information will override data provided in
the general technical documentation.
Vibrations:
Pressure component operating limits:
ULN range pumps comply with VDI 2056 and ISO
5199 Class K for pumps with a driving power of up
Material
Temperature
OA/OC/3B
-40C to 120C
Pressure
16 bar
10 bar
Sizes
32125 to 80315
100200 to 125250
to 15 kW and Class M with a driving power of
more than 15 kW
Noise levels:
Shaft sealing operating limits:
The noise levels of the pump comply with the
Shaft sealing execution
AAE
AA1
Temperature range
-40C to + 120C
-40C to + 140C
Directive 001/30 - 1992 of the EUROPUMP
Commission.
The following table provides approximate values:
LWA (dB)
ATTENTION
All indicated operating limits are not valid
for all liquids which can be pumped. See
technical data or delivery note.
Flange locations:
Axial suction flange, discharge flange radially
P (kW)
upwards.
pump without motor
Flanges:
Note that additional noise can be generated by:
Material design 0A, 0C, 3B : DIN 2533 PN16 /
2532 PN10
1)
Flanges drilled according to ANSI 150 can be
supplied.
1)
the driver.
a possible misalignment of the coupling.
pipework (note: the larger the pipe diameter,
the lower the pipe noise).
100200 to125250
For local contact details:
www. sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Techical Data
Page 2 of 4
Chapter 9
Permissible branch forces and moments:
Values according to ISO/DIN 5199 Class II (1997) Annex B, Family N 2 for mounting on sheet metal
baseplates and frames without grouting for pumping temperatures up to 110 C and up to 120 C for
grouted baseplates / frames.
Material execution 0A / 0C / 3B:
End branch x-Axis
Top branch z-Axis
DN
Fy
Fz
Fx
My
Mz
Mx
flanges
(N)
(N)
(N)
(N)
(Nm)
(Nm)
(Nm)
(Nm)
32
500
625
550
975
450
525
650
950
40
500
625
550
975
450
525
650
950
50
675
825
750
1300
500
575
700
1025
65
1025
1250
1125
1975
575
650
800
1175
80
1025
1250
1125
1975
575
650
800
1175
100
1350
1675
1500
2625
625
725
875
1300
125
2025
2500
2250
3925
875
1025
1250
1825
50
750
675
825
1300
500
575
700
1025
65
1125
1025
1250
1975
575
650
800
1175
80
1125
1025
1250
1975
575
650
800
1175
100
1500
1350
1675
2625
625
725
875
1300
125
2250
2025
2500
3925
875
1025
1250
1825
150
2250
2025
2500
3925
875
1025
1250
1825
For local contact details:
www. sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Techical Data
Page 3 of 4
Chapter 9
Maximum permissible speeds at 50 Hz:
Size
Characteristic Nominal speed
Maximum permissible speed
rpm
design
rpm
2900
2900
1450
1450
2900
2900
40250
1450
1800
40250
2900
2900
40315
1450
1800
2900
2900
50250
1450
1800
50250
2900
2900
50315
1450
1800
2900
2900
1450
1800
2900
2900
80200
1450
1800
80250
2900
2900
1450
1800
100200
2900
2900
100200
1450
1800
100250
2900
2900
1450
1800
0A, 0C, 3B
32125
32160
32200
32250
32250
40125
40160
40200
50125
50160
50200
65125
65160
65250
65250
65315
80160
80200
80250
80315
100250
100315
125250
For local contact details:
www. sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Techical Data
Page 4 of 4
Chapter 9
Operating range:
(Continuous operation)
0,3 Qopt < Q < 1,1 Qopt
0,5 Qopt < Q < 1,1 Qopt
Sizes
32125 to 80315
100315
100200 to 100250
125250
This operating range is applicable if waterlike liquids are pumped. If liquids having distinctly different physical
properties are handled, it may be necessary to narrow the permissible operating range.
See the specific performance curve for more details.
For local contact details:
www. sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice.
(Sterling Fluid Systems BV) 2001
Annex
Page 1 of 5
Chapter 10
10. Annex
10.1
Connections
III : air vent pipe connection
UAL : leakage connection
Size
32125
32160
32200
32250
40125
40160
40200
40250
40315
50125
50160
50200
50250
50315
65125
65160
65200
65250
65315
III
Ue
Ue : drainage
UAL
G1/4
G3/8
G1/4
80160
80200
80250
80315
G3/8
100200
100250
100315
125250
Drawings are indicative only.
10.2
Table of Dimensions
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Annex
Page 2 of 5
Chapter 10
All dimensions in mm
Size
DNA
DNE
32125
50
32160
32200
50
50
80
50
50
100
65
32
32250
15
80
40160
40
360
50
100
40250
65
40315
65
125
50125
18
470
32,5
50
50160
50200
25
40125
40200
100
50
15
360
125
140
132
160
160
180
180
225
112
140
132
160
160
180
180
225
225
250
132
160
65
18
80
100
65250
15
80
470
225
225
280
160
180
200
180
225
200
250
225
280
360
40
470
65315
18
80160
360
65
80
100
m2
100
70
125
95
100
87
73
125
100
100
180
125
50
80
125
18
470
62,5
75
150
87
125
70
95
n1
n2
190
140
240
190
320
250
210
160
240
190
265
212
320
250
345
280
240
190
265
212
320
250
345
280
280
212
320
250
15
d1
267
80
24
50
27
342
100
32
80
35
10
267
80
24
50
27
340
100
32
80
35
10
267
80
24
50
27
340
100
32
80
35
10
24
50
27
32
80
35
10
24
50
27
32
80
35
10
70
200
250
200
225
250
95
73
87
225
15
140
125
m1
73
180
180
65
65125
65160
80250
80315
100200
100250
100315
125250
112
h3
200
50315
80200
h2
160
50250
65200
h1
160
120
125
95
160
120
73
250
360
280
400
315
320
250
345
280
400
315
267
19
15
80
340
267
100
280
315
87
280
19
340
120
315
355
Flange connections acc. to DIN 2501 PN 16 and PN 10
DNA/DNE
32
40
50
65
80
100
125
150
D
k
d2 x number
140
100
18x4
150
110
18x4
165
125
18x4
185
145
18x4
200
160
18x8
220
180
18x8
250
210
18x8
285
240
22x8
10.3 Parts list
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Annex
Page 3 of 5
Chapter 10
When ordering spare parts give the following information: position number, the complete pump designation
and the serial number, which can be found on the nameplate fixed to the pump.
Pos. Nr.
10.20
10.90*
11.40*
16.10
18.30
21.00*
23.00*
23.50*
32.00*
32.10*
33.00
36.00
40.00*
42.10*
43.30*
47.10
48.50
52.50*
54.50*
55.00
55.01
55.02
63.60
71.10
73.10
73.11
75.70
90.10
90.11
90.12
90.21
90.40
90.42
90.30
90.31
92.01
92.02
92.20*
93.10*
94.00*
94.01*
94.02*
Description
Volute casing
Intermediate piece
Intermediate piece
Cover
Support foot
Shaft
Impeller
Vane wheel impeller
Inclined ball bearing
Grooved ball bearing
Bearing bracket
Bearing cover
Joint
Radial shaft seal ring
Mechanical seal
Shaft seal casing
Locating ring
Spacer
Bearing bush
Disc
Disc
Disc
Grease nipple
Pipe
Pipe union
Socket
Orifice plate
Hexagon screw
Hexagon screw
Hexagon screw
Stud
Grub screw
Orifice plate
Screwed plug
Screwed plug
Hexagon nut
Hexagon nut
Hexagon nut
Lock washer
Key
Key
Key
*Recommended spare parts
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Annex
Page 4 of 5
Chapter 10
ULN 32125 to 125250
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
Annex
Page 5 of 5
Chapter 10
COPYRIGHT WARNING
Please read this notice
The material you are viewing in this document is protected
by Copyright and may only be used in accordance with
Copyright, Designs and Patent legislation.
You are not permitted to copy - either in full or in
part - nor substantially extract, reproduce or re-use any
of the contents of this document in any material form or in
any medium without permission from the Copyright
holders or their assignees. Any unlawful use of the
material in this document may result in claims for civil
remedies, including an injunction to restrain further use
and a claim for damages; or may result in criminal penalties.
For local contact details:
www.sterlingfluidsystems.com
In the search to improve continuously its products,
Sterling Fluid Systems reserves the right to modify its
products at any time without prior notice
(Sterling Fluid Systems BV) 2001
SIHI SuperNova Program
Supplementary operating instructions in accordance to EC directive
94/9/EC (ATEX) for the intended use in potentially explosive
atmospheres of the following pumps types, manufactured by
Sterling Fluid Systems (Spain), S.A.:
ZLN, ZLK and ZLI (Industrial Pumps)
ULN (Self Priming Pumps)
ZTN, ZTK and ZTI (Thermal Oil Pumps)
ZHN, ZDN, ZEN and ZLI (Hot Water Pumps)
These supplementary operating instructions give only general instructions for the
use of pumps in conditions that need explosion protection. The operating
instructions of the specific pump must be taken into consideration as well.
Contents
Page
General objective
2
2.1
2.2
2.3
2.4
Safety issues
Identification of safety symbols in the supplementary operating instructions
Compliance with regulations
Qualification and training of personnel
Safety instructions for maintenance, inspection and installation work
2
2
2
2
3
3
3.1
3.2
3.2
3.4
Instructions referring to design of pump and accessories
General
Pump pressure containment components
Coupling, coupling guard
Belt drive
3
3
3
3
3
4
4.1
4.2
4.3
4.4
Instructions referring to installation and start-up of pump sets
Coupling
Connection to power supply
Earthing
Belt drive
3
3
3
3
3
5
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
Instructions concerning operation and servicing
Unauthorised modes of operation
Explosion protection
Pump filled and vented
Marking
Fluid pumped
Checking of direction of rotation (see also pump-specific operating manual)
Pump operating mode
Temperature limits
Maintenance
3
3
3
4
4
4
4
5
5
6
General Objective
Pumping systems can be operated in hazardous areas. It is the obligation of the operator to define the zone and to
select the pump with the correct category for this zone.
The pump installation and operation must take the Operating Instructions into accounts that are described in these
supplementary operating instructions. They contain important information for safe and reliable pump operation in
hazardous areas. This information plus all information given for all components of the system (e.g. the operating
instructions for the pump) are of vital importance to avoid risks.
These supplementary operating instructions do not take into account national nor local regulations; the operator must
ensure that such regulations are strictly observed by all, including the personnel in charge of the installation.
For any further information or instructions exceeding the scope of this manual or in case of damage please contact
Sterling Fluid Systems nearest customers service.
Safety issues
These supplementary operating instructions contain fundamental information concerning all actions with pumping
systems, when operated in hazardous areas like: installation, inspection, operation, monitoring and maintenance.
Therefore these and all other instructions with related to safety must be known and available with easy access to all
personnel, which is involved in the above stated actions.
Not only must the general safety instructions established in this chapter on Safety issues be complied with, but also
the safety instructions outlined under specific headings as well as the safety instructions contained in the specific
operating manual of the specific pump.
2.1 Identification of safety symbols in the supplementary operating instructions
In these supplementary operating instructions the safety instructions related to explosion protection are marked with:
The sign
is used to highlight safety instructions where non-compliance may pose a damage to the pump and its functions.
2.2 Compliance with regulations
It is imperative to comply with the safety instructions contained in these supplementary operating instructions, the
operating instructions of the pump type concerned, the relevant national and international explosion protection
regulations, health and safety regulations and the operators own internal work, operation and safety regulations.
Ex symbol relates to additional requirements, which must be complied with when the pump is operated in
hazardous areas.
In addition the following must be observed:
If the pumps / units are located in hazardous areas, it is imperative to make sure that the correct category of
pump and equipment is selected and that unauthorised modes of operation are prevented. Non-compliance may
result in first: increased risk of explosion and second: the specified temperature limits might be exceeded.
Non-compliance with these safety instructions may also result in the loss of any rights to claim damages.
In addition to the hazards indicated in the operating manual of the relevant pump type,
Non-compliance may also result in hazards to persons by explosion.
2.3 Qualification and training of personnel
The personnel responsible for or involved in the installation, the operation, maintenance and inspection of the pump
and the unit must be adequately qualified to carry out these works in hazardous areas.
The scope of responsibility and supervision of the personnel must be exactly defined by plant management. If the
staff does not have the necessary knowledge, they must be trained and instructed. The pump manufacturer or
supplier on behalf of the plant management may perform this task. Moreover, plant management must ensure that
the contents of the operation instructions are fully understood by plant operators and other relevant personnel such
as maintenance staff.
Page 2
2.4 Safety instructions for installation work, inspection operation and maintenance
The operator is responsible to assure that all installation work, inspection, operation and maintenance must be
carried out by authorised and qualified specialist personnel, which is thoroughly familiarised with the pump operating
instructions and these supplementary operating instructions.
If necessary, additional explosion protection regulations must be considered.
Instructions concerning design of pump and accessories
3.1 General
The pumps and the accessories for installations in hazardous areas must comply with the relevant category of
mechanical and electrical equipment.
Some details are pointed out below:
3.2 Pump pressure containment components
For handling inflammable fluids, the pump pressure containment components must be made of ductile
material.
3.3 Coupling, coupling guard
The accident prevention regulations require, that pump drives must not be operated without a coupling guard. If a
customer specifically decides, not to include a coupling guard in our delivery, then the operator must provide such
coupling guard himself. The coupling must be selected and sized in accordance with the instructions of the coupling
manufacturer. It is important to make sure that the materials selected for coupling and coupling guard are nonsparking in the event of mechanical contact. Sterling Fluid Systems scope of supply meets this requirement.
In hazardous areas coupling guards must be of non-sparking material, whereby the coupling material must be
considered.
3.4 Belt drives
Belts must include some electrically conductive material.
Instructions concerning installation and start-up of pump sets
In addition to the normal installation instructions, the specific criteria for explosion proof are listed below:
4.1 Coupling
The coupling must be installed, started-up and operated in accordance with the operating instructions of the
coupling manufacturer. Misalignment of the coupling may result in inadmissible temperatures at the coupling and
pump and motor bearings. It has to be ensured, that the half couplings are correctly aligned at all times.
4.2 Connection to power supply
Only a properly trained electrician must effect connection to the power supply. The available main voltage
must be checked against the data on the motor rating plate and an appropriate start-up method must be selected.
It is strongly recommend to use a motor protection device (motor protection switch).
In hazardous areas, compliance with national and local regulations form an additional requirement for
electrical connections.
4.3 Earthing
To eliminate risks due to electrostatic charging, the pump set must be earthed directly or through an earthing
line.
4.4 Belt drive
Belt-driven pump sets must always be earthed. The condition of the belts must be checked regularly.
Page 3
Instructions concerning operation and maintenance
5.1 Unauthorised modes of operation
The warranty relating to the operating reliability and safety of the unit supplied is only valid if the equipment is used in
accordance with its designated use as described in the following sections of this supplementary operating manual
and the pump-specific operating manual. The limits stated in the data sheet must not be exceeded under any
circumstances.
Any operation of the pump outside the permissible operating range and any unauthorised modes of operation
may result in the specified temperature limits being exceeded (see section 5.8).
5.2 Explosion protection
If the pumps / units are installed in hazardous areas where compliance with EC directive 94/9/EC is required,
the measures and instructions given in the following sections 5.3 to 5.9 must be carried out with no excuse, to ensure
explosion protection.
5.3 Pump filled and vented
Especially dry running of a pump results in friction and non-allowed temperature rise. Therefore precautions have to
be taken to prevent dry running.
It is necessary that the system of suction and discharge lines and thus the wetted pump internals including
seal chamber and auxiliary systems are completely filled with the fluid to be handled at all times during pump
operation, so that an explosive atmosphere is prevented.
If the operator cannot warrant this condition, appropriate monitoring devices must be used.
Improper installation (e.g. vertical installation) may impair the self-venting properties of the seal chamber, so that gas
bubbles may be collected in the pump and cause the mechanical seal to run dry.
High negative pressure on the suction side (e.g. due to clogged suction-side strainers or low system pressure)
may result in air intake at the shaft seal forming gas bubbles in the pump. This may also cause the mechanical seal
to run dry. Suitable monitoring facilities shall be installed, if necessary.
For design-inherent reasons, however, it is not always possible to exclude the existence of a certain residual
volume not filled with liquid after the pump has been filled prior to start of operation. However, once the motor is
started up the pumping effect will immediately fill this volume with pumped fluid.
It is imperative to make sure that the seal chambers and auxiliary seal systems are properly vented from air and filled
with liquid.
5.4 Marking
The Ex marking on the pump only refers to the pump part, i.e. the coupling and motor must be considered
separately. The coupling must have an EC Declaration of Manufacturer and the EC marking. The driver must be
treated separately.
Example of marking on the pump part:
CE Ex II 2 G c T1 - T5
The safety instructions published in section 5.8 must be complied with.
5.5 Fluid handled
Abrasive particles in the fluid handled may erode the casing walls to such an extent that fluid may escape.
When handling inflammable media, it has to be ensured that the fluid does not contain any abrasive particles, or that
the pump is regularly checked with respect to erosion.
5.6 Checking the direction of rotation (see also pump-specific operating manual)
If the explosion hazard also exists during the installation phase, the direction of rotation must never be
checked by starting up the unfilled pump unit, even for a short period, to prevent temperature increases resulting from
contact between rotating and stationary components. If it is not possible to fill the pump, the direction of rotation must
be checked with the pump / motor coupling removed.
Page 4
5.7 Pump operating mode
Make sure that the pump is always started up with the suction-side shut-off valve fully open and the discharge-side
shut-off valve slightly open. However, the pump can also be started up against a closed swing check valve. Only after
the pump has reached full rotational speed shall the discharge-side shut-off valve be adjusted to comply with the duty
point.
Pump operation with closed shut-off valves in the suction and / or discharge pipes is not permitted. In this
case, there is a risk of the pump casing reaching a high surface temperatures after a very short time, due to a rapid
temperature rise in the pumped fluid inside the pump.
Additionally, the resulting rapid pressure build-up inside the pump may cause excessive stresses on the pump
materials and even cause it to burst.
The minimum flows indicated in the relevant pump operating manuals refer to water and water-like liquids. Longer
operating periods with these liquids and at the flow rates indicated will not cause an additional increase in the
temperatures on the pump surface. However, if the physical properties of the fluids handled are different from water,
it is essential to check if an additional heat build-up may occur and if the minimum flow rate must therefore be
increased.
The calculation formula below can be used to check if an additional heat build-up may lead to a dangerous
temperature increase at the pump surface.
To = Tf +
= ((g * H) / (c * ))*(1 - )
c
g
H
Tf
To
Specific heat of liquid [J / kg K]
2
Acceleration due to gravity [m /s]
Pump head [m]
Temperature of fluid handled [ C]
Temperature of casing surface [ C]
Pump efficiency [-]
Temperature difference [ C]
5.8 Temperature limits
In normal pump operation, the highest temperatures are to be expected on the surface of the pump casing, at
the shaft seal, at the bearing areas and at the pump shaft end in close coupled executions.
Unless the pump is equipped with an additional heating facility, the surface temperature at the pump casing will
correspond to the temperature of the fluid handled, assuming that the pump surface is freely exposed to the
atmosphere.
In any case, responsibility for compliance with the specified fluid temperature (operating temperature) lies with the
plant operator. The maximum permissible fluid temperature depends on the temperature class to be complied with.
The following limits for the maximum permissible fluid temperature must be observed for the individual temperature
classes as per EN13463-1 given below (temperature increase in the shaft seal area, if any, has been taken into
consideration):
Temperature classes
as per EN 13463-1:
Permissible
surface
temperature
Max. permissible fluid
temperature for compliance
with temperature class
T5
T4
T3
T2
T1
100 C
135 C
200 C
300 C
450 C
80 C
115 C
180 C
280 C
Temperature limit of pump
Safety note:
The permissible operating temperature of the pump in question is indicated in the technical data. If the pump is to be
operated at a higher temperature, the technical data are missing or if the pump is part of a pool of pumps, the
maximum permissible operating temperature must be requested from the pump manufacturer.
Page 5
Because of the very close contact between pumps and motors in close coupled design (ZLK and ZLI,
Industrial Pumps; ZTK and ZTI, Thermal Oil Pumps; and ZLI, Hot Water Pumps), there is a thermal influence
between pump and motor.
Especially for motors with protection type EExe (increased safety) the possibility exists that the declaration of
conformity looses its validity, as for the EC type examination an ambient temperature of 40C is taken as a basis.
This admissible ambient temperature could be exceeded in the area of the motor flange when pumping hot liquids.
In the event of fluid temperature above 80C, the temperature category of the unit / set is determined by the pump not
by the motor.
The motor is usually rated for continuous operation at the data indicated in the technical data. Frequent motor
start-ups may result in increased surface temperatures at the motor. Contact the motor manufacturer, if necessary.
Based on ambient temperatures of max. 40 C and assuming that the pump unit is properly serviced and operated
and that the surfaces in the bearing area are freely exposed to the atmosphere, compliance with temperature class
T4 is warranted for surfaces in the area of the rolling element bearings.
If temperature classes T5 (100C) and T6 (85C) have to be complied with, special measures may have to taken with
regard to bearing temperature. In such cases, and if ambient temperatures are higher, contact the manufacturer.
Operators errors or malfunctions may result in substantially higher temperatures. Please refer to section 5.1 in this
context.
Mechanical seals may exceed the specified temperature limits if run dry. Dry running may not only result from
an inadequately filled seal chamber, but also from excessive gas content in the fluid pumped.
Pump operation outside the specified operating range may also result in dry running.
Shaft seals shall be regularly checked for leakage.
The above stated and also stated in other paragraphs related to the mechanical seal, is also applicable for
any shaft sealing execution (i.e. packing rings, lip seal rings, etc.)
In any case the operator has the responsibility to check the real compatibility between the normal leakage of the fluid
and the atmosphere in the case of shaft sealing made by packing rings.
It has to be verified, that V-rings are properly fitted to the shaft. Only proper contact should be exist between
the sealing lip and the shaft.
5.9 Maintenance
Only a pump set, which is properly operated and maintained in perfect technical condition, will give safe and
reliable operation.
This also applies to the reliable function of the rolling element bearings whose actual lifetime largely depends on the
operating mode and operating conditions.
Regular checks of the lubricant and the running noises will prevent the risk of excessive temperatures as a result of
bearings running hot or defective bearing seals.
The correct function of the shaft seal must be checked regularly.
Any auxiliary systems installed must be monitored, if necessary, to make sure they function correctly.
Static sealing elements shall be regularly checked for leakage.
The coupling guard and any other guards of fast rotating components must be regularly checked for deformation and
sufficient distance from rotating elements.
Regularly verify the correct position and the status of plastic components exposed to the atmosphere.
It is strongly recommended to draw up a maintenance schedule, which includes the above-mentioned points.
In case of repair only original Sterling Fluid Systems spare parts must be used, which comply with the
corresponding EC Directives.
Sterling Fluid Systems
In the search to improve continuously its products, Sterling Fluid Systems
reserves the right to modify its products at any time without prior notice
For local contact details: www. sterlingfluidsystems.com
Page 6
Sterling Fluid Systems (Spain), S.A.
Vereda de los Zapateros, s/n
28223 Pozuelo de Alarcon (Madrid) Espaa
Phone: 0034 91 7091310, Fax: 0034 91 7159700
Declaration of Conformity
In the sense of the EU Directive 98/37/EC, Appendix II B
Herewith we declare that the pump type:
In the version supplied by us complies with the following relevant regulations:
EU Machine Directive 98/37/EC, Appendix I No. 1
EU Directive 94/9/EC, Group II, category 2, atmosphere G (Ex II 2 G c T1-T5)
And that is destined for installation in a machine / assembly with other machines to form a
single machine and that it may not be commissioned until it has been determined that the
machine in which this pump is to be installed or with which this pump is to be assembled
complies with the clauses of the EU Machine Directive in the version of 98/37/EC and
94/9/EC.
Harmonised standards used, in particular:
EN 809
EN 292 part 1
EN 292 part 2
EN 733
EN 1127 - 1
EN 13463 - 1
prEN 13463 - 5
In the actual version.
National technical standards and specifications used, in particular:
UNE-EN 809
UNE-EN 292-1
UNE-EN 292-2
UNE-EN 1127-1
UNE-EN 13463 - 1
Unauthorised alterations of the pump unit and any use not in accordance with valid
regulations and / or intended use result in a loss of validity of this declaration.
Sterling Fluid Systems, (Spain), S.A.
Business Unit Manager
J. A. Cobo
June 10, 2003