GENERAL
SPECIFICATIONS
CENTRALIZED MODELS
ULTRA-700.0-TL
ULTRA-1050.0-TL
ULTRA-1400.0-TL
The largest solar power inverter in the Power-One
Aurora product range, the new UTLTRA-1400.0 unit is
designed with large utility-grade installations in mind.
This liquid-cooled, high-powered Aurora inverter
is the largest PV inverter available in the market.
The compact chassis gives maximum power for the
minimum footprint.
Industry-leading power conversion efficiencies of
up to 98.7%, combined with high-speed Maximum
Power Point Tracking (MPPT) channels, optimize
energy harvesting across a wide array of operating
conditions. Up to four independent MPPT input
channels oer maximum flexibility and energy
harvesting.
This large inverter system significantly reduces
the wiring requirements and on-site testing thanks
to the presence of separated and dedicated
compartments for DC and AC.
Features
High performance utility grade inverter for large utility PV installations with 98.7% efficiency
Outdoor enclosure for unrestricted use under any environmental conditions
Passive liquid cooling with total segregation of internal compartments assuring a 5-year maintenance cycle
Reduced susceptibility to a single fault. In case of a component failure, a maximum of 350kW will be lost
Extended MPPT input voltage range
Direct transformerless conversion to the 690 Vac output reduces AC distribution cost
Maximum input voltage up to 1100 Vdc, high design flexibility and reduced DC distribution losses for large scale PV
plants
Integrated DC and AC distribution and protection. Fully equipped for connection, additional accessories not required
Easy installation and maintenance procedure. Front extractible DC/AC converters and accessibility to all critical parts
Ethernet communication and two independent RS-485 communication interfaces for
inverter and intelligent string combiner monitoring
Compliant to BDEW and FERC 661
AURORA ULTRA
BLOCK DIAGRAM OF ULTRA-1400.0-TL
INVERTER MODULE 350kW
PV ARRAY 1(+)
PV ARRAY 2(+)
PV ARRAY 3(+)
OVR
DC LOAD
BREAK SWITCH
BULK
CAPS
MODULE
DC / AC
INVERTER
MODULE
LINE
FILTER
MODULE
AC
CONTACT
MODULE
AC
FUSE
PV ARRAY 4(+)
PV ARRAY 5(+)
EMI
FILTER
PV ARRAY 1(-)
PV ARRAY 2(-)
CONTROL CIRCUIT
PV ARRAY 3(-)
PV ARRAY 4(-)
PV ARRAY 5(-)
INVERTER MODULE 350kW
OVR
DC LOAD
BREAK SWITCH
BULK
CAPS
MODULE
DC / AC
INVERTER
MODULE
LINE
FILTER
MODULE
AC
CONTACT
MODULE
AC
FUSE
EMI
FILTER
CONTROL CIRCUIT
AC CIRCUIT
BREAKER
R
S MAIN AC POWER
CONNECTION
T
INVERTER MODULE 350kW
OVR
DC LOAD
BREAK SWITCH
BULK
CAPS
MODULE
DC / AC
INVERTER
MODULE
LINE
FILTER
MODULE
PE
AC
CONTACT
MODULE
AC
FUSE
EMI
FILTER
CONTROL CIRCUIT
OVR
PV ARRAY 17(+)
PV ARRAY 18(+)
PV ARRAY 19(+)
TO EACH
350.0 Kw MODULE
INVERTER MODULE 350kW
PV ARRAY 16(+)
DC LOAD
BREAK SWITCH
BULK
CAPS
MODULE
DC / AC
INVERTER
MODULE
LINE
FILTER
MODULE
AC
CONTACT
MODULE
AC
FUSE
PV ARRAY 20(+)
24 VDC
24 VDC
- 5 VDC
EMI
FILTER
PV ARRAY 16(-)
AC CIRCUIT
BREAKER
R
S
T
N
PE
PV ARRAY 17(-)
PV ARRAY 18(-)
LS1 LS2 LS3 N
CONTROL CIRCUIT
208 VAC
CONTROL CIRCUIT
PV ARRAY 19(-)
PV ARRAY 20(-)
Block Diagram and Efciency Curves
PVI-ULTRA
99,0%
98,0%
y, %
97,0%
96,0%
95,0%
94,0%
93,0%
585
680
800
92,0%
91,0%
90,0%
0,0%
10%
20%
30%
40%
50%
60%
% of Rated Output Power
AURORA ULTRA
70%
80%
90%
100%
AUX POWER
CONNECTION
PARAMETER
Input Side
Absolute Maximum DC Input Voltage (Vmax,abs)
MPPT Input DC Voltage Range (VMPPTmin ... VMPPTmax) at Vacr
ULTRA-700.0-TLOUTD-690
ULTRA-1050.0-TLOUTD-690
ULTRA-1400.0-TLOUTD-690
1000 V (1100 V opt.)
1000 V (1100 V opt.)
1000 V (1100 V opt.)
470...900 V
470...900 V
470...900 V
Linear Derating from MAX to 10kW Linear Derating from MAX to 15kW Linear Derating from MAX to 20kW
[850V<VMPPT<900V] 560 kW @ 470 V [850V<VMPPT<900V] 840 kW @ 470 V [850V<VMPPT<900V] 1120 kW @ 470 V
585...850 V @ 700 kW
585...850 V @ 1050 kW
585...850 V @ 1400 kW
645...850 V @ 780 kW
645...850 V @ 1170 kW
645...850 V @ 1560 kW
Number of Independent MPPT Multi-Master
2
3
4
Number of Independent MPPT Multi - Master/Slave
1
2
2
Maximum Combined DC Input Current (Idcmaxc)
1240 A
1240 A + 620 A
1240 A + 1240 A
Maximum DC Input Current for Each Module (Idcmax,m)
620 A
620 A
620 A
Number of DC Inputs Pairs
20
30
40
20 x 120mm2....300mm2 (max cable 30 x 120mm2....300mm2 (max cable 40 x 120mm2....300mm2 (max cable
DC Connection Type (both positive and negative polarity)
external diameter= 32,5 mm)
external diameter= 32,5 mm)
external diameter= 32,5 mm)
Input Protection
Reverse Polarity Protection
Yes, via input breaker
Yes, via input breaker
Yes, via input breaker
Input Over Voltage Protection - Varistor
1 for each module
1 for each module
1 for each module
Residual Current Protection, grounded Neutral,
Not included; recommended 10A ground fault protection with time and current adjustable
floating panels
Fuse Size for Each Input Pair
up to 400A /1100V
up to 400A /1100V
up to 400A /1100V
Output Side
AC Grid Connection Type
Three phases 3W+PE
Three phases 3W+PE
Three phases 3W+PE
Rated Apparent Power (Aac,r)
780 kVA (5)
1170 kVA (5)
1560 kVA (5)
Rated Active Power @cosphi=1/cosphi=0,9
780/700 kW (5)
1170/1050 kW (5)
1560/1400 kW (5)
Rated Grid Voltage (Vacr)
690 V
690 V
690 V
AC Voltage Range (Vacmin...Vacmax)
621...759 V (1)
621...759 V (1)
621...759 V (1)
Maximum Output Current (Iacmax)
650 A
975 A
1300 A
Rated Frequency (fr)
50/60 Hz
50/60 Hz
50/60 Hz
Frequency Range (fmin...fmax)
47...53 / 57...63 Hz (2)
47...53 / 57...63 Hz (2)
47...53 / 57...63 Hz (2)
Power Factor (Cosphiac,r)
> 0.995 (adj. 0.90)
> 0.995 (adj. 0.90)
> 0.995 (adj. 0.90)
Total Harmonic Distortion
< 3% (@ Pac,r)
< 3% (@ Pac,r)
< 3% (@ Pac,r)
AC Connection Type (for each phase)
2 x 240 mm2 (M12)
3 x 240 mm2 (M12)
4 x 240 mm2 (M12)
Output Protection
Anti-Islanding Protection
According to local standard
According to local standard
According to local standard
Output Overvoltage Protection (Varistor)
Yes
Yes
Yes
Night Time Disconnect
Yes
Yes
Yes
AC Switch
Yes
Yes
Yes
AC Fuse for each module
3x350A/200kA
3x350A/200kA
3x350A/200kA
Operating Performance
Maximum Efficiency (max)
98.7% (4)
98.7% (4)
98.7% (4)
Weithted Efficiency (EURO / CEC )
98.2% / 98.0% (4)
98.2% / 98.0% (4)
98.2% / 98.0% (4)
Stand-by Consumption/Night-time power loss
< 90 W
< 110 W
< 180 W
AC Auxiliary Supply
3 x 400 Vac +N, 50/60 Hz
3 x 400 Vac +N, 50/60 Hz
3 x 400 Vac +N, 50/60 Hz
Auxiliary Supply Consumption
< 0.50% of Pac,r
<0.53% of Pac,r
< 0.50% of Pac,r
Auxiliary Supply Consumption without Cooling
< 0.05% of Pac,r
< 0.04% of Pac,r
< 0.05% of Pac,r
Inverter Switching Frequency
9 kHz
9 kHz
9 kHz
Communication
Wired Local Monitoring
PVI-USB-RS232_485 (opt.)
Remote Monitoring
PVI-AEC-EVO (opt.), AURORA-UNIVERSAL (opt.)
AURORA String Combiner
PVI-STRINGCOMB (opt.)
User Interface
TFT LCD 5.7
Environmental
-20...+ 60C/-4...140F with derating above 50C/122F
Ambient Temperature Range
-40...+ 60C/-40...140F with derating above 50C/122F (opt.)
Relative Humidity
0...100% condensing
0...100% condensing
0...100% condensing
Noise Emission
< 78 dB(A) @ 1 m
< 78 dB(A) @ 1 m
< 78 dB(A) @ 1 m
Maximum Operating Altitude without Derating
2000 m / 6560 ft
2000 m / 6560 ft
2000 m / 6560 ft
Physical
Environmental Protection Rating
IP 65
IP 65
IP 65
Cooling
Passive liquid and air forced
Passive liquid and air forced
Passive liquid and air forced
Required Air Cooling Flow
Not applicable
Not applicable
Not applicable
2920mm x 3020mm x 1520mm /
2920mm x 3720mm x 1520mm /
2920mm x 4420mm x 1520mm /
Dimension (H x W x D)
114,9 x 118.9 x 59.9
114,9 x 146,5 x 59.9
114,9 x 174,0 x 59.9
Weight
< 3000 kg / 6613 lb
< 3800 kg / 8377 lb
< 4600 kg / 10141 lb
Weight of the module
< 55 kg / 121 lb
< 55 kg / 121 lb
< 55 kg / 121 lb
Safety
Transformer
No
No
No
Marking
CE
CE
CE
EN 50178, EN61000-6-2, EN61000-6- EN 50178, EN61000-6-2, EN61000-6- EN 50178, EN61000-6-2, EN61000-6Safety and EMC Standard
4, EN61000-3-11, EN61000-3-12
4, EN61000-3-11, EN61000-3-12
4, EN61000-3-11, EN61000-3-12
MPPT Input DC Range (VMPPTmin ... VMPPTmax) at Pacr and Vacr
Grid Standard
Attachment A70 Terna(3), CEI-0-16(3),
BDEW, FERC661
1. The AC voltage range may vary depending on specific country grid standard
2. The Frequency range may vary depending on specific country grid standard
3. Since their applicability dates
4. Power consumption of the auxiliary services not included
5. Linear derating when ac voltage fall below 690Vac; maximum output power available at or above 690Vac.
Remark. Features not specifically listed in the present data sheet are not included in the product
Attachment A70 Terna(3), CEI-0-16(3),
BDEW, FERC661
Attachment A70 Terna(3), CEI-0-16(3),
BDEW, FERC661
AURORA ULTRA
Ver. 2012-03.1-EN - All products are subject to technical improvements without notice.
www.power-one.com
Power-One Renewable Energy Worldwide Sales Offices
Country
Name/Region
Telephone
Email
Australia
China (Shenzhen)
China (Shanghai)
India
Singapore
Asia Pacific
Asia Pacific
Asia Pacific
Asia Pacific
Asia Pacific
+61 2 9735 3111
+86 755 2988 5888
+86 21 5505 6907
+65 6896 3363
+65 6896 3363
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
Belgium / The Netherlands / Luxembourg
France
Germany
Italy
Spain
United Kingdom
Europe
Europe
Europe
Europe
Europe
Europe
+32 2 206 0338
+33 (0) 141 796 140
+49 7641 955 2020
00 800 00287672 Opt. n5
+34 91 879 88 54
+44 1903 823 323
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
[email protected]
Dubai
Middle East
+971 50 100 4142
[email protected]
Canada
USA East
USA Central
USA West
North America
North America
North America
North America
+1 877 261-1374
+1 877 261-1374
+1 877 261-1374
+1 877 261-1374
[email protected]
[email protected]
[email protected]
[email protected]
AURORA ULTRA