Overcurrent Protection
Overcurrent Protection
where, for a given PSM T is the desired relay operating time and Tm is the
corresponding operating time at TMS of 1.0. TMS is also referred to as TDS (Time Dial Setting).
Fig 15.4 illustrates an overcurrent protection scheme for radial distribution system of fig 15.2, with definite
time relays. Relay R 1 does not have any coordination responsibility and hence it can trip without any
intentional time delay. Relay R 2 has to coordinate with relay R 1 and hence its time of operation is delayed
by time equal to Coordination Time Interval (CTI). Relay R 3 has to back up R 2 . Hence its time of
operation is delayed by another CTI. Thus, we see that as we move along towards source, the relaying
action slows down. Typically, there is an upper limit on any fault clearing time in the system and it equals
approximately 1sec. This limit would be hit near the relay close to source.
Example: Consider a CTI of 0.3sec. Then what is the maximum length of a radial system of a feeder that
can be protected by overcurrent relay. Assume, that primary protection uses DT relays and primary
protection time should not be more than 1sec.
Answer: Let 'n' be the maximum number of feeder sections that can be protected by overcurrent relays
and let TOC max be the upper limit on the speed of primary protection. Then
. Thus
overcurrent relays should be used over a limited length in the 3 feeder sections.
to development of an inverse
characteristic for overcurrent relay.
This is probably the most widely used
characteristic. It is inverse in the
initial part and tends to approach a
definite minimum operating time
characteristic as the current becomes
very high.
Various inverse current operating
time characteristics of a relay are
shown in fig 15.7. They are normal
or standard inverse, very inverse and
extremely inverse characteristics.
As PSM approaches unity, it is clear from above equations that relay operating time increases to infinity.
With electromechanical relays, usually manufacturers do not guarantee accuracy of the relay operating
time in the PSM range 1 to 1.5. Hence, traditionally PSM of an overcurrent relay is set above 1.5.
However, in principle, such restrictions do not apply to numerical relays. Our next task would be to
understand the methodology of setting Is and TMS of overcurrent relays. Hence, we now discuss
guidelines for setting overcurrent relays. We begin with the classification of the faults.
US CO8 Inverse
(3)
(4)
For a fault on the feeder being backed up, the relay should provide sufficient time for the corresponding
primary relay to
act before it issues tripping command. This interval is called CTI (co-ordination time interval). Typically,
CTI is about 0.3 sec. It consists of
CB operating time+ Relay operating time+ Overtravel (time for electromechanical relay) + Factor of
safety.
Guidelines for earth fault protection would be discussed in a subsequent lecture.
(b)
The corresponding relays back up the leaf node relays. Store, the relays in row k + 1 of RSM.
(c)
(d)
Update k = k + 1.
For this particular example, there are 5 steps required in relay coordination. Identification of primary back
relay pairs begins at leaf nodes. There is no constraint involved in setting the relay at leaf node, as they
have no backup protection responsibility. Their sole role is to do primary protection, as quickly as possible.
Therefore, these relays can be set first (step 1 in fig 15.10). The reader should step through the
interactive example to obtain the feel of these steps. The relays to be coordinated at each step are
summarized in Table B.
Table B : Relative Sequence Matrix
Step
Set Relays
Step 1 R 1 , R 2 , R 3 , R 4 , R 5
Step 2 R 6 , R 7 , R 8 , R 9 , R 10
Step 4 R 14, R 15
Step 5 R
with R
and R
16
16
14
15
This table is also referred as Relative Sequence Matrix (RSM). The sequence for relay coordination is
recorded in the above table.
Identify the parents of leaf-nodes in step - 3. Compute their PSM and TMS for backup protection and
co-ordination.
Step 6 Delete the leaf nodes. Update the co-ordination tree and go back to step - 2.
Review Questions
1.
2.
3.
4.
5.
What are the various Time Current Characteristics available for an overcurrent relay?
Recap